Introduction ................................................................................................................. 2
2
Part 1 General Information ............................................... 1 ................................ 3
Ceiling Mounted Cassette (Round Flow with Sensing) Type ... 2 FXFQ-S ................29 4
Ceiling Mounted Cassette (Round Flow) Type......................... 3 FXFQ-LU ................45 5
Ceiling Mounted Cassette (Compact Multi Flow) Type........... 4 FXZQ-M ................61
6
4-Way Flow Ceiling Suspended Type..................................... 5 FXUQ-A ................79
7
Ceiling Mounted Cassette (Double Flow) Type ...................... 6 FXCQ-M ................89
8
Ceiling Mounted Cassette Corner Type.................................. 7 FXKQ-MA ..............107
9
Slim Ceiling Mounted Duct Type ............................................ 8 FXDQ-PB / FXDQ-NB ..............121
Table of Contents 1
Introduction EDIN341424
1. Introduction
1.1 Publication List of Engineering Data for VRV Products
Refrigerant Type Product Series Book No. Type, Hz Model name Area Note Published
in
High-COP type New lineup of outdoor
RXYQ12-50THRY6(E) units RXYQ-TRY6
Addition of
Inverter Standard type FXFQ-S, FXVQ Dec. 2014
EDIN341324 H/P 50Hz India
T RXYQ6-60T(N)RY6(E) Model change of
FXFQ from P to LU,
Space saving type FXUQ from MA to A
RXYQ18-50T(S)RY6(E) Deletion of BEVQ
Revision of
Normal type Duct series of
Air RXYQ5PAY6(E)
indoor units to
cooled EDIN341106 H/P 50Hz RXYQ8-54PRY6 India EDIN341011 Apr. 2011
R410A High COP type Addition of
RXYQ5PAY6(E)
RXYQ16-50PRHY6 to EDIN341011
Inverter New lineup of
P(A) EDIN341305 H/P 50Hz RXYQ6PAY16 India 6HP outdoor Apr. 2013
unit for India
Model change
H/P 50/60Hz
EDMT34-635A C/O 50/60Hz RX(Y)MQ4-6PVE General of FXAQ from Dec. 2012
MA to P series
Water RWEYQ8-30PY1 New lineup of
ED30-942 H/P,H/R 50Hz
H/P,H/R 60Hz RWEYQ10-30PYL General Centralized BS Dec. 2009
cooled RWEYQ10-30PTL units
For indoor and outdoor Option
Option for all type OH14-01 50/60Hz units General handbook Apr. 2014
New lineup
Heat Reclaim Ventilator (VAM) GJ ED71-613 50/60Hz VAM150-2000GJVE General from FA to GA Feb. 2006
series
With DX coil
and humidifier
VKM50-100GAMV1
Heat Reclaim Ventilator (VKM) GA(M) ED71-440B 50Hz VKM50-100GAV1 General (VKM-GAM) Mar. 2012
With DX coil
(VKM-GA)
2 Introduction
EDIN341424
1
Part 1
General Information
1. Model Names of Indoor/Outdoor Units....................................................4
1.1 Indoor Units ..............................................................................................4
1.2 Outdoor Units ...........................................................................................5
1.3 Air Treatment Equipment .........................................................................7
2. External Appearance...............................................................................8
2.1 Indoor Units ..............................................................................................8
2.2 Outdoor Units ...........................................................................................9
2.3 Air Treatment Equipment .......................................................................11
3. Combination of Outdoor Units...............................................................12
4. Nomenclature........................................................................................14
5. Capacity Range.....................................................................................16
5.1 Capacity Range for VRV Indoor Units Only ...........................................16
6. Selection Procedure..............................................................................22
6.1 Selection Procedure for VRV Indoor Units Only.....................................22
General Information 3
Model Names of Indoor/Outdoor Units EDIN341424
4 General Information
EDIN341424 Model Names of Indoor/Outdoor Units
1
1.2 Outdoor Units
High-COP Type
Series Model Name Power Supply
12THR 14THR 16THR 18THR 20THR 22THR 24THR 26THR 28THR 30THR
Heat Pump RXYQ Y6(E)
32THR 34THR 36THR 38THR 40THR 42THR 44THR 46THR 48THR 50THR
Standard Type
Series Model Name Power Supply
6TR 8TR 10TR 12TR 14TR 16TR 18TNR 20TNR 22TNR 24TNR
Heat Pump RXYQ 26TNR 28TNR 30TNR 32TNR 34TNR 36TNR 38TNR 40TNR 42TNR 44TNR Y6(E)
46TNR 48TNR 50TNR 52TNR 54TNR 56TNR 58TNR 60TNR — —
General Information 5
Model Names of Indoor/Outdoor Units EDIN341424
Capacity range 28HP 30HP 32HP 34HP 36HP 38HP 40HP 42HP
Model name RXYQ28THR RXYQ30THR RXYQ32THR RXYQ34THR RXYQ36THR RXYQ38THR RXYQ40THR RXYQ42THR
Outdoor unit 1 RXYQ8TR RXYQ8TR RXYQ8TR RXYQ8TR RXYQ8TR RXYQ12TR RXYQ12TR RXYQ14TR
Outdoor unit 2 RXYQ8TR RXYQ10TR RXYQ12TR RXYQ12TR RXYQ14TR RXYQ12TR RXYQ14TR RXYQ14TR
Outdoor unit 3 RXYQ12TR RXYQ12TR RXYQ12TR RXYQ14TR RXYQ14TR RXYQ14TR RXYQ14TR RXYQ14TR
Capacity range 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
Model name RXYQ18TNR RXYQ20TNR RXYQ22TNR RXYQ24TNR RXYQ26TNR RXYQ28TNR RXYQ30TNR RXYQ32TNR
Outdoor unit 1 RXYQ8TR RXYQ8TR RXYQ8TR RXYQ10TR RXYQ12TR RXYQ14TR RXYQ14TR RXYQ14TR
Outdoor unit 2 RXYQ10TR RXYQ12TR RXYQ14TR RXYQ14TR RXYQ14TR RXYQ14TR RXYQ16TR RXYQ18TR
Outdoor unit 3 – – – – – – – –
Capacity range 34HP 36HP 38HP 40HP 42HP 44HP 46HP 48HP
Model name RXYQ34TNR RXYQ36TNR RXYQ38TNR RXYQ40TNR RXYQ42TNR RXYQ44TNR RXYQ46TNR RXYQ48TNR
Outdoor unit 1 RXYQ10TR RXYQ12TR RXYQ8TR RXYQ12TR RXYQ12TR RXYQ12TR RXYQ14TR RXYQ14TR
Outdoor unit 2 RXYQ12TR RXYQ12TR RXYQ12TR RXYQ12TR RXYQ14TR RXYQ16TR RXYQ14TR RXYQ16TR
Outdoor unit 3 RXYQ12TR RXYQ12TR RXYQ18TR RXYQ16TR RXYQ16TR RXYQ16TR RXYQ18TR RXYQ18TR
Capacity range 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP
Model name RXYQ22TSR RXYQ24TSR RXYQ26TSR RXYQ28TSR RXYQ30TSR RXYQ32TSR RXYQ34TSR RXYQ36TSR
Outdoor unit 1 RXYQ10TR RXYQ12TR RXYQ8TR RXYQ12TR RXYQ12TR RXYQ12TR RXYQ16TR RXYQ18TR
Outdoor unit 2 RXYQ12TR RXYQ12TR RXYQ18TR RXYQ16TR RXYQ18TR RXYQ20TR RXYQ18TR RXYQ18TR
Outdoor unit 3 – – – – – – – –
6 General Information
EDIN341424 Model Names of Indoor/Outdoor Units
1
1.3 Air Treatment Equipment
General Information 7
External Appearance EDIN341424
2. External Appearance
2.1 Indoor Units
VRV indoor units
Ceiling mounted cassette (Round flow with sensing) type Ceiling mounted duct type
FXFQ-S FXMQ-P
Ceiling mounted cassette (Round flow) type Ceiling mounted duct type
FXFQ-LU FXMQ-M
Ceiling mounted cassette (Compact multi flow) type Ceiling suspended type
FXZQ-M FXHQ-MA
FXUQ-A FXAQ-P
8 General Information
EDIN341424 External Appearance
1
2.2 Outdoor Units
High-COP Type
RXYQ12 / 14 / 16THR RXYQ18 / 20 / 22 / 24 / 26 / 28 / 30 / 32THR
General Information 9
External Appearance EDIN341424
Standard Type
RXYQ6 / 8 / 10 / 12TR RXYQ14 / 16TR RXYQ18 / 20TNR
10 General Information
EDIN341424 External Appearance
1
Space Saving Type
RXYQ18 / 20TR RXYQ22 / 24TSR
General Information 11
Combination of Outdoor Units EDIN341424
Note: 1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
12 General Information
EDIN341424 Combination of Outdoor Units
1
Standard Type
System capacity Number Module Outdoor Unit Multi Connection
kW HP of units 6 8 10 12 14 16 18 20 Piping Kit 1
16.0 6 1
22.4 8 1
28.0 10 1
—
33.5 12 1
40.0 14 1
45.0 16 1
50.4 18 2
55.9 20 2
62.4 22 2
68.0 24 2
BHFP22P100
73.5 26 2
80.0 28 2
85.0 30 2
90.0 32 2
95.0 34 3
101 36 3
106 38 3
112 40 3
119 42 3
124 44 3
130 46 3
BHFP22P151
135 48 3
140 50 3
145 52 3
150 54 3
156 56 3
162 58 3
168 60 3
Note: 1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
General Information 13
Nomenclature EDIN341424
4. Nomenclature
VRV Indoor Unit
F X F Q 25 S VM
Power Supply Symbol
VE: 1 phase, 220-240/220V, 50/60Hz
V1 : 1 phase, 220-240V, 50Hz
VM: 1 phase, 220-240/220-230V, 50/60Hz
Y1: 3 phase, 380-415V, 50Hz
VE6: 1 phase, 220-240/220V, 50/60Hz (for India)
Capacity indication
Conversion to kW (Horsepower)
25: 2.8 kW (1 HP)
125: 14.0 kW (5 HP)
250: 28.0 kW (10 HP)
Refrigerant
Q: R410A
Type
F : Ceiling Mounted Cassette (Round Flow with Sensing / Round Flow)
Z : Ceiling Mounted Cassette (Compact Multi Flow)
U : 4-Way Flow Ceiling Suspended
C : Ceiling Mounted Cassette (Double Flow)
K : Ceiling Mounted Cassette Corner
D : Slim Ceiling Mounted Duct
M: Ceiling Mounted Duct
H : Ceiling Suspended
A : Wall Mounted
L : Floor Standing
N : Concealed Floor Standing
V: Floor Standing Duct
Series category
X: Inverter
Unit category
F: Indoor unit for air cooled type
14 General Information
EDIN341424 Nomenclature
1
Outdoor Unit
R X Y Q 54 TNR Y6 E
E: The unit with anti corrosion treatment
Power Supply Symbol
Y6: 3 phase, 380-415V, 50Hz (for india)
Indicates Major Design Category
THR: High-COP Type
TR, TNR: Standard Type (Only T: Single Unit)
TR, TSR: Space Saving Type (Only T: Single Unit)
Capacity indication
Conversion to kW (Horsepower)
6: 16.0 kW (6 HP)
10: 28.0 kW (10 HP)
60: 168 kW (60 HP)
Refrigerant
Q: R410A
Type
Y: Heat pump
Blank: Cooling only
Series category
X: Inverter
Unit category
R: Outdoor unit for air cooled type
V K M 50 GA M V1
V A M 500 GJ VE
Power supply symbol
VE: 1 phase, 220-240/220V, 50/60Hz
Indicates major design category
Airflow rate (H) (m3/h)
Mounted type
Air
Ventilation
General Information 15
Capacity Range EDIN341424
5. Capacity Range
5.1 Capacity Range for VRV Indoor Units Only
5.1.1 Combination Ratio
Note: When outdoor-air processing mode of FXVQ is selected, be sure to connect as follows:
Outdoor Unit
HP Indoor Unit
India
5HP FXVQ125MY1×1 RXYQ6TRY6×1
8HP FXVQ200MY1×1 RXYQ8TRY6×1
10HP FXVQ250MY1×1 RXYQ10TRY6×1
16HP FXVQ400MY1×1 RXYQ16TRY6×1
20HP FXVQ500MY16×1 RXYQ20TNRY6×1
16 General Information
EDIN341424 Capacity Range
1
5.1.2 Outdoor Unit Combinations
High-COP Type
kW HP Capacity Model name Combination Outdoor unit multi Total capacity index of Maximum number of
index connection piping kit *1 connectable indoor units *2 *3 connectable indoor units *2
32.0 12HP 300 RXYQ12THR RXYQ6TR × 2 150 to 390 (480) 19 (24)
38.4 14HP 350 RXYQ14THR RXYQ6TR + RXYQ8TR BHFP22P100 175 to 455 (560) 22 (28)
44.8 16HP 400 RXYQ16THR RXYQ8TR × 2 200 to 520 (640) 26 (32)
48.0 18HP 450 RXYQ18THR RXYQ6TR × 3 225 to 585 (585) 29 (29)
54.4 20HP 500 RXYQ20THR RXYQ6TR × 2 + RXYQ8TR 250 to 650 (650) 32 (32)
60.8 22HP 550 RXYQ22THR RXYQ6TR + RXYQ8TR × 2 275 to 715 (715) 35 (35)
67.2 24HP 600 RXYQ24THR RXYQ8TR × 3 300 to 780 (780) 39 (39)
72.8 26HP 650 RXYQ26THR RXYQ8TR × 2 + RXYQ10TR 325 to 845 (845) 42 (42)
78.3 28HP 700 RXYQ28THR RXYQ8TR × 2 + RXYQ12TR 350 to 910 (910) 45 (45)
83.9 30HP 750 RXYQ30THR RXYQ8TR + RXYQ10TR + RXYQ12TR 375 to 975 (975) 48 (48)
89.4 32HP 800 RXYQ32THR RXYQ8TR + RXYQ12TR × 2 400 to 1,040 (1,040) 52 (52)
95.9 34HP 850 RXYQ34THR RXYQ8TR + RXYQ12TR + RXYQ14TR BHFP22P151 425 to 1,105 (1,105) 55 (55)
102 36HP 900 RXYQ36THR RXYQ8TR + RXYQ14TR × 2 450 to 1,170 (1,170) 58 (58)
107 38HP 950 RXYQ38THR RXYQ12TR × 2 + RXYQ14TR 475 to 1,235 (1,235) 61 (61)
114 40HP 1,000 RXYQ40THR RXYQ12TR + RXYQ14TR × 2 500 to 1,300 (1,300)
120 42HP 1,050 RXYQ42THR RXYQ14TR × 3 525 to 1,365 (1,365)
125 44HP 1,100 RXYQ44THR RXYQ14TR × 2 + RXYQ16TR 550 to 1,430 (1,430)
64 (64)
130 46HP 1,150 RXYQ46THR RXYQ14TR + RXYQ16TR × 2 575 to 1,495 (1,495)
135 48HP 1,200 RXYQ48THR RXYQ16TR × 3 600 to 1,560 (1,560)
140 50HP 1,250 RXYQ50THR RXYQ16TR × 2 + RXYQ18TR 625 to 1,625 (1,625)
Notes: *1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
*3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity
index of the outdoor units. And the connection ratio must not exceed 100%.
General Information 17
Capacity Range EDIN341424
Standard Type
kW HP Capacity Model name Combination Outdoor unit multi Total capacity index of Maximum number of
index connection piping kit *1 connectable indoor units *2 *3 connectable indoor units *2
16.0 6HP 150 RXYQ6TR RXYQ6TR — 75 to 195 (300) 9 (15)
22.4 8HP 200 RXYQ8TR RXYQ8TR — 100 to 260 (400) 13 (20)
28.0 10HP 250 RXYQ10TR RXYQ10TR — 125 to 325 (500) 16 (25)
33.5 12HP 300 RXYQ12TR RXYQ12TR — 150 to 390 (600) 19 (30)
40.0 14HP 350 RXYQ14TR RXYQ14TR — 175 to 455 (700) 22 (35)
45.0 16HP 400 RXYQ16TR RXYQ16TR — 200 to 520 (800) 26 (40)
50.4 18HP 450 RXYQ18TNR RXYQ8TR + RXYQ10TR 225 to 585 (720) 29 (36)
55.9 20HP 500 RXYQ20TNR RXYQ8TR + RXYQ12TR 250 to 650 (800) 32 (40)
62.4 22HP 550 RXYQ22TNR RXYQ8TR + RXYQ14TR 275 to 715 (880) 35 (44)
68.0 24HP 600 RXYQ24TNR RXYQ10TR + RXYQ14TR 300 to 780 (960) 39 (48)
BHFP22P100
73.5 26HP 650 RXYQ26TNR RXYQ12TR + RXYQ14TR 325 to 845 (1,040) 42 (52)
80.0 28HP 700 RXYQ28TNR RXYQ14TR × 2 350 to 910 (1,120) 45 (56)
85.0 30HP 750 RXYQ30TNR RXYQ14TR + RXYQ16TR 375 to 975 (1,200) 48 (60)
90.0 32HP 800 RXYQ32TNR RXYQ14TR + RXYQ18TR 400 to 1,040 (1,280) 52 (64)
95.0 34HP 850 RXYQ34TNR RXYQ10TR + RXYQ12TR × 2 425 to 1,105 (1,105) 55 (55)
101 36HP 900 RXYQ36TNR RXYQ12TR × 3 450 to 1,170 (1,170) 58 (58)
106 38HP 950 RXYQ38TNR RXYQ8TR + RXYQ12TR + RXYQ18TR 475 to 1,235 (1,235) 61 (61)
112 40HP 1,000 RXYQ40TNR RXYQ12TR × 2 + RXYQ16TR 500 to 1,300 (1,300)
119 42HP 1,050 RXYQ42TNR RXYQ12TR + RXYQ14TR + RXYQ16TR 525 to 1,365 (1,365)
124 44HP 1,100 RXYQ44TNR RXYQ12TR + RXYQ16TR × 2 550 to 1,430 (1,430)
130 46HP 1,150 RXYQ46TNR RXYQ14TR × 2 + RXYQ18TR 575 to 1,495 (1,495)
BHFP22P151
135 48HP 1,200 RXYQ48TNR RXYQ14TR + RXYQ16TR + RXYQ18TR 600 to 1,560 (1,560)
140 50HP 1,250 RXYQ50TNR RXYQ14TR + RXYQ18TR × 2 625 to 1,625 (1,625) 64 (64)
145 52HP 1,300 RXYQ52TNR RXYQ16TR + RXYQ18TR × 2 650 to 1,690 (1,690)
150 54HP 1,350 RXYQ54TNR RXYQ18TR × 3 675 to 1,755 (1,755)
156 56HP 1,400 RXYQ56TNR RXYQ18TR × 2 + RXYQ20TR 700 to 1,820 (1,820)
162 58HP 1,450 RXYQ58TNR RXYQ18TR + RXYQ20TR × 2 725 to 1,885 (1,885)
168 60HP 1,500 RXYQ60TNR RXYQ20TR × 3 750 to 1,950 (1,950)
Notes: *1 For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.
*2 Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for
single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
*3 When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity
index of the outdoor units. And the connection ratio must not exceed 100%.
18 General Information
EDIN341424 Capacity Range
1
5.1.3 Indoor Unit Connection Capacity
High-COP Type
Types of connected indoor units
Including FXFQ25LU,
Capacity Model FXDQ, FXMQ-P, FXAQ FXFQ-S and FXVQ at Other indoor unit models
Type HP Min. least one unit
index name combination
ratio Max. Max. number Max. Max. number Max. Max. number
combination of connectable combination of connectable combination of connectable
ratio indoor units ratio indoor units ratio indoor units
Double 12 300 RXYQ12THR 30 19 24
outdoor 14 350 RXYQ14THR 35 22 160% 28
units
16 400 RXYQ16THR 40 26 32
18 450 RXYQ18THR 45 29 29
20 500 RXYQ20THR 50 32 32
22 550 RXYQ22THR 55 35 35
24 600 RXYQ24THR 60 39 39
26 650 RXYQ26THR 42 42
28 700 RXYQ28THR 45 45
30 750 RXYQ30THR 48 48
50% 200% 130%
Triple 32 800 RXYQ32THR 52 52
outdoor 34 850 RXYQ34THR 55 130% 55
units 36 900 RXYQ36THR 58 58
38 950 RXYQ38THR 64 61 61
40 1,000 RXYQ40THR
42 1,050 RXYQ42THR
44 1,100 RXYQ44THR
64 64
46 1,150 RXYQ46THR
48 1,200 RXYQ48THR
50 1,250 RXYQ50THR
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor
units.
General Information 19
Capacity Range EDIN341424
Standard Type
Types of connected indoor units
Including FXFQ25LU,
Capacity Model FXDQ, FXMQ-P, FXAQ FXFQ-S and FXVQ at Other indoor unit models
Type HP Min. least one unit
index name combination
ratio Max. Max. number Max. Max. number Max. Max. number
combination of connectable combination of connectable combination of connectable
ratio indoor units ratio indoor units ratio indoor units
6 150 RXYQ6TR 15 9 15
8 200 RXYQ8TR 20 13 20
Single 10 250 RXYQ10TR 25 16 25
outdoor 200%
units 12 300 RXYQ12TR 30 19 30
14 350 RXYQ14TR 35 22 35
16 400 RXYQ16TR 40 26 40
18 450 RXYQ18TNR 45 29 36
20 500 RXYQ20TNR 50 32 40
22 550 RXYQ22TNR 55 35 44
Double 24 600 RXYQ24TNR 60 39 48
outdoor 160%
units 26 650 RXYQ26TNR 42 52
28 700 RXYQ28TNR 45 56
30 750 RXYQ30TNR 48 60
32 800 RXYQ32TNR 52 64
50% 200% 130%
34 850 RXYQ34TNR 55 55
36 900 RXYQ36TNR 58 58
38 950 RXYQ38TNR 61 61
40 1,000 RXYQ40TNR
42 1,050 RXYQ42TNR
64
44 1,100 RXYQ44TNR
Triple 46 1,150 RXYQ46TNR
outdoor 130%
units 48 1,200 RXYQ48TNR
50 1,250 RXYQ50TNR 64 64
52 1,300 RXYQ52TNR
54 1,350 RXYQ54TNR
56 1,400 RXYQ56TNR
58 1,450 RXYQ58TNR
60 1,500 RXYQ60TNR
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor
units.
20 General Information
EDIN341424 Capacity Range
1
Space Saving Type
Types of connected indoor units
Including FXFQ25LU,
Capacity Model FXDQ, FXMQ-P, FXAQ FXFQ-S and FXVQ at Other indoor unit models
Type HP Min. least one unit
index name combination
ratio Max. Max. number Max. Max. number Max. Max. number
combination of connectable combination of connectable combination of connectable
ratio indoor units ratio indoor units ratio indoor units
Single 18 450 RXYQ18TR 45 29 45
outdoor 200%
units 20 500 RXYQ20TR 50 32 50
22 550 RXYQ22TSR 55 35 44
24 600 RXYQ24TSR 60 39 48
26 650 RXYQ26TSR 42 52
28 700 RXYQ28TSR 45 56
Double 30 750 RXYQ30TSR 48 60
outdoor 160%
units 32 800 RXYQ32TSR 52
34 850 RXYQ34TSR 50% 200% 130% 55
36 900 RXYQ36TSR 58
38 950 RXYQ38TSR 64 61
40 1,000 RXYQ40TSR
64
42 1,050 RXYQ42TSR
44 1,100 RXYQ44TSR
Triple 64
outdoor 46 1,150 RXYQ46TSR 130%
units 48 1,200 RXYQ48TSR
50 1,250 RXYQ50TSR
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the indoor
units.
General Information 21
Selection Procedure EDIN341424
6. Selection Procedure
6.1 Selection Procedure for VRV Indoor Units Only
6.1.1 Flowchart
Given Conditions:
· Design temperature and humidity (indoor & outdoor)
[1]] Given conditions · Required heat load of each room
· System peak load ( if necessary)
· Piping length, level difference
· Specifications of indoor units (type and number)
Define safety factor for the indoor units and outdoor unit
[2]] Selection of indoor units
Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units
1) Use the sum of the peak load of each room 2) Use the system peak load
Provisionally select outdoor unit type and size based on limitation of combination ratio
Confirm that the number of indoor units connected to the outdoor unit is within limitation.
Correct for cooling & heating capacity of the outdoor unit by the following items
-Outdoor air temperature -Piping length, level difference
-Indoor air temperature -Piping heat loss
-Combination ratio -Safety factor for the outdoor unit
-Defrost (only for heating capacity)
No
Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit
Yes
Room B Room E
Room C Room D
Floor plan
-Determine peak load of each room (and system peak load if necessary)
22 General Information
EDIN341424 Selection Procedure
-Safety factor
In this example, safety factor is not used. (i. e., safety factor = 1.0)
Selected IDU FXMQ125PVE6 FXMQ125PVE6 FXMQ50PVE6 FXMQ50PVE6 FXMQ100PVE6 FXMQ100PVE6 FXMQ40PVE6 FXMQ40PVE6
Corrected TC
13.1 13.1 5.2 5.2 10.5 10.5 4.2 4.2
(kW)
∗In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not
only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of
indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls
between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated
by interpolation for each indoor air temperature.
General Information 23
Selection Procedure EDIN341424
CI of FXMQ40PVE6 = 40
-Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for Outdoor air temperature, Indoor
air temperature, and Combination ratio.
∗ In case the outdoor air temperature, the indoor RXYQ20TRY6 Cooling capacity (Te: 6˚C)
air temperature, or the combination ratio falls
between temperatures listed in the table,
calculate the capacity by interpolation.
24 General Information
EDIN341424 Selection Procedure
1
-Confirm capacity correction factor by piping length and level difference (K1)
(K1) = 0.898
0.898
In cooling mode, heat loss factor per meter at 33°C is calculated as below.
Heat loss factor per meter = 0.022 + (0.030 – 0.022) × (33 – 30) / (35 – 30) = 0.0268
Using “Equivalent piping length = 60m” and “Heat loss factor per meter = 0.0268”,
(K2) = 1 + (0.0268 × (60 – 7.5)) / 100 = 1.014
Cooling Ambient temperature
Heat loss factor per 5°C 10°C 15°C 20°C 25°C 30°C 35°C 40°C
meter of piping (%) 0.000 0.000 0.004 0.009 0.014 0.022 0.030 0.038
-Calculate the corrected capacity of RXYQ20TRY6 (C) by using (K1) and (K2).
Corrected capacity of RXYQ20TRY6 (C) = (B) × (K1) / (K2) (add defrost correction factor for heating capacity)
58.8 × 0.898 / 1.014 = 52.1 (kW)
If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.
If (C) < (A), return to Procedure [3]–2 and provisionally select a larger outdoor unit.
General Information 25
Selection Procedure EDIN341424
26 General Information
EDIN341424
Part 2
Indoor Units
FXFQ-S
Ceiling Mounted Cassette
(Round Flow with Sensing) Type . . . . . . . . . . . . . . 29
FXFQ-LU
Ceiling Mounted Cassette
(Round Flow) Type . . . . . . . . . . . . . . . . . . . . . . . . . 45
FXZQ-M
Ceiling Mounted Cassette
(Compact Multi Flow) Type . . . . . . . . . . . . . . . . . . . 61
FXUQ-A
4-Way Flow Ceiling Suspended Type . . . . . . . . . . . 79
FXCQ-M
Ceiling Mounted Cassette
(Double Flow) Type . . . . . . . . . . . . . . . . . . . . . . . . . 89
FXKQ-MA
Ceiling Mounted Cassette
Corner Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
FXDQ-PB / FXDQ-NB
Slim Ceiling Mounted Duct Type . . . . . . . . . . . . . 121
FXMQ-P
Ceiling Mounted Duct Type. . . . . . . . . . . . . . . . . . 143
FXMQ-M
Ceiling Mounted Duct Type. . . . . . . . . . . . . . . . . . 171
FXHQ-MA
Ceiling Suspended Type . . . . . . . . . . . . . . . . . . . . 183
FXAQ-P
Wall Mounted Type . . . . . . . . . . . . . . . . . . . . . . . . 197
Indoor Units 27
EDIN341424
FXLQ-MA / FXNQ-MA
Floor Standing Type /
Concealed Floor Standing Type . . . . . . . . . . . . . . 211
FXVQ-M
Floor Standing Duct Type . . . . . . . . . . . . . . . . . . . 231
28 Indoor Units
EDIN341424
FXFQ-S
2
Ceiling Mounted Cassette
(Round Flow with Sensing) Type
1. Specifications ........................................................................................30
2. Dimensions ...........................................................................................32
3. Piping Diagrams....................................................................................35
4. Wiring Diagrams....................................................................................36
5. Electric Characteristics..........................................................................37
6. Safety Devices Setting ..........................................................................38
7. Capacity Tables ....................................................................................39
7.1 Cooling Capacity ....................................................................................39
7.2 Heating Capacity ....................................................................................39
8. Sound Levels ........................................................................................40
9. Centre of Gravity ...................................................................................42
10.Accessories...........................................................................................43
10.1 Optional Accessories (for Unit)...............................................................43
10.2 Optional Accessories (for Controls)........................................................43
FXFQ-S 29
Specifications EDIN341424
1. Specifications
Ceiling mounted cassette (Round flow with sensing) type
Model FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM
1 phase, 1 phase, 1 phase, 1 phase,
Power supply 220-240/220 · 230V, 220-240/220 · 230V, 220-240/220 · 230V, 220-240/220 · 230V,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 2,400 3,100 3,900 4,800
1 3 Cooling capacity Btu/h 9,600 12,300 15,400 19,100
kW 2.8 3.6 4.5 5.6
kcal/h 2,800 3,400 4,300 5,400
2 3 Heating capacity Btu/h 10,900 13,600 17,100 21,500
kW 3.2 4.0 5.0 6.3
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 246×840×840 246×840×840
Coil (Cross Rows×Stages×Fin pitch mm 2×8×1.20 2×8×1.20 2×8×1.20 3×(12+15×2)×(1.25+1.20×2)
fin coil) Face area m² 0.244 0.244 0.244 0.427
Model QTS48C15M QTS48C15M QTS48C15M QTS48C15M
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × W 48×1 48×1 48×1 48×1
Number of units
Fan m³/min 12.5/11.5/10.0 12.5/11.5/10.0 14.5/13.0/11.0 22.0/17.5/13.5
Airflow rate (H/M/L) l/s 208/192/167 208/192/167 242/217/183 367/292/225
cfm 441/406/353 441/406/353 512/459/388 777/618/477
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections Gas pipes mm
Drain pipe mm VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32) VP25 (External dia. 32)
Mass kg 19 19 19 23
4 Sound pressure level (H/M/L) dB(A) 30.0/28.5/27.0 30.0/28.5/27.0 31.0/29.0/27.0 36.0/32.0/28.0
Sound power level (H/M/L) dB(A) 47.0/45.5/44.0 47.0/45.5/44.0 48.0/46.0/44.0 53.0/49.0/45.0
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYCQ125B-W1 BYCQ125B-W1 BYCQ125B-W1 BYCQ125B-W1
Colour Fresh white Fresh white Fresh white Fresh white
Decoration
panels Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 5.5 5.5 5.5 5.5
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Installation manual. Installation manual. Installation manual.
Installation pattern paper. Installation pattern paper. Installation pattern paper. Installation pattern paper.
Drain hose. Metal clamp. Drain hose. Metal clamp. Drain hose. Metal clamp. Drain hose. Metal clamp.
Standard accessories Washer clamp. Sealing Washer clamp. Sealing Washer clamp. Sealing Washer clamp. Sealing
material. Clamp. Screw. material. Clamp. Screw. material. Clamp. Screw. material. Clamp. Screw.
Washer for hanger. Joint Washer for hanger. Joint Washer for hanger. Joint Washer for hanger. Joint
insulating material. insulating material. insulating material. insulating material.
Installation guide. Installation guide. Installation guide. Installation guide.
Drawing No. C: 3D084443A
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
30 FXFQ-S
EDIN341424 Specifications
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXFQ-S 31
Dimensions EDIN341424
2. Dimensions
FXFQ25SVM / FXFQ32SVM / FXFQ40SVM / FXFQ50SVM
Unit (mm)
3D084388
32 FXFQ-S
EDIN341424 Dimensions
FXFQ63SVM / FXFQ80SVM
Unit (mm) 2
3D084389
FXFQ-S 33
Dimensions EDIN341424
FXFQ100SVM / FXFQ125SVM
Unit (mm)
3D084390
34 FXFQ-S
EDIN341424 Piping Diagrams
3. Piping Diagrams
2
4D024460K
FXFQ-S 35
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXFQ25SVM / FXFQ32SVM / FXFQ40SVM / FXFQ50SVM / FXFQ63SVM / FXFQ80SVM /
FXFQ100SVM / FXFQ125SVM
3D084349
36 FXFQ-S
EDIN341424 Electric Characteristics
5. Electric Characteristics
2
FXFQ25SVM / FXFQ32SVM / FXFQ40SVM / FXFQ50SVM / FXFQ63SVM / FXFQ80SVM /
FXFQ100SVM / FXFQ125SVM
4D084422
FXFQ-S 37
Safety Devices Setting EDIN341424
38 FXFQ-S
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity 2
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
25 1.9 2.0 2.3 2.3 2.6 2.5 2.8 2.5 2.8 2.5 2.9 2.4 3.0 2.4
32 2.4 2.2 2.9 2.5 3.4 2.8 3.6 2.9 3.6 2.8 3.7 2.7 3.8 2.6
40 3.0 2.6 3.6 3.0 4.2 3.3 4.5 3.4 4.6 3.4 4.7 3.3 4.8 3.2
50 3.8 3.9 4.5 4.4 5.2 5.0 5.6 5.0 5.7 5.0 5.8 4.8 5.9 4.7
FXFQ-S
63 4.8 4.5 5.7 5.2 6.6 5.8 7.1 5.9 7.2 5.8 7.4 5.6 7.5 5.5
80 6.1 5.2 7.2 5.9 8.4 6.6 9.0 6.7 9.1 6.6 9.3 6.4 9.5 6.2
100 7.6 6.8 9.0 7.7 10.5 8.7 11.2 8.8 11.3 8.6 11.6 8.4 11.9 8.2
125 9.4 7.9 11.3 9.0 13.1 10.1 14.0 10.2 14.2 10.1 14.5 9.7 14.9 9.4
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXFQ-S 39
Sound Levels EDIN341424
8. Sound Levels
Overall
dB(A)
Sound pressure level
Model 220-240/220 · 230V, 50/60Hz
High Middle Low
FXFQ25SVM 30.0 28.5 27.0
FXFQ32SVM
FXFQ40SVM 31.0 29.0 27.0
FXFQ50SVM 36.0 32.0 28.0
FXFQ63SVM 38.0 33.0 28.0
FXFQ80SVM 38.0 35.0 31.0
FXFQ100SVM 44.0 38.0 32.0
FXFQ125SVM 45.0 40.0 35.0
40 FXFQ-S
EDIN341424 Sound Levels
FXFQ125SVM
4D084365
FXFQ-S 41
Centre of Gravity EDIN341424
9. Centre of Gravity
FXFQ25SVM / FXFQ32SVM / FXFQ40SVM / FXFQ50SVM / FXFQ63SVM / FXFQ80SVM /
FXFQ100SVM / FXFQ125SVM
Unit (mm)
C: 4D052237L
42 FXFQ-S
EDIN341424 Accessories
10. Accessories
10.1 Optional Accessories (for Unit) 2
Model
Item Note
FXFQ25SVM FXFQ32SVM FXFQ40SVM FXFQ50SVM FXFQ63SVM FXFQ80SVM FXFQ100SVM FXFQ125SVM
Decoration panel BYCQ125B-W1
Sealing member of air discharge
KDBHQ55B140
outlet
Panel spacer KDBP55H160FA
High 65% KAFP556B80 KAFP556B160
efficiency
filter unit 90% KAFP557B80 KAFP557B160
Replacement 65% KAFP552B80 KAFP552B160
high efficiency
filter 90% KAFP553B80 KAFP553B160
Filter
related Filter chamber KDDFP55B160
Replacement long life filter KAFP551K160
Ultra long-life filter KAFP55B160
Replacement ultra long life
KAFP55H160H
filter
Without T-
joint pipe 1 KDDQ55B140
Chamber and fan
Fresh air type
intake kit With T-joint
pipe 1 KDDP55B160K
without fan
Direct installation type KDDP55X160
Branch duct chamber KDJP55B80 KDJP55B160
Insulation kit for high humidity KDTP55K80 KDTP55K160
C: 3D084501B
Note:
1. Two of four corner air outlets are closed Without T-joint pipe. Fresh air intake volume is 10% or less of airflow rate.
FXFQ-S 43
Accessories EDIN341424
44 FXFQ-S
EDIN341424
FXFQ-LU
Ceiling Mounted Cassette
(Round Flow) Type 3
1. Specifications ........................................................................................46
2. Dimensions ...........................................................................................48
3. Piping Diagrams....................................................................................51
4. Wiring Diagrams....................................................................................52
5. Electric Characteristics..........................................................................53
6. Safety Devices Setting ..........................................................................54
7. Capacity Tables ....................................................................................55
7.1 Cooling Capacity ....................................................................................55
7.2 Heating Capacity ....................................................................................55
8. Sound Levels ........................................................................................56
9. Centre of Gravity ...................................................................................58
10.Accessories...........................................................................................59
10.1 Optional Accessories (for Unit)...............................................................59
10.2 Optional Accessories (for Controls)........................................................59
FXFQ-LU 45
Specifications EDIN341424
1. Specifications
Ceiling mounted cassette (Round flow) type
Model FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1
Power supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
kcal/h 2,400 3,100 3,900 4,800
1 3 Cooling capacity Btu/h 9,600 12,300 15,400 19,100
kW 2.8 3.6 4.5 5.6
kcal/h 2,800 3,400 4,300 5,400
2 3 Heating capacity Btu/h 10,900 13,600 17,100 21,500
kW 3.2 4.0 5.0 6.3
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 246×840×840 246×840×840
Coil (Cross Rows×Stages×Fin pitch mm 2×6×1.2 2×6×1.2 2×6×1.2 2×6×1.2
fin coil) Face area m² 0.267 0.267 0.267 0.267
Model QTS48C15M QTS48C15M QTS48C15M QTS48C15M
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × W 56×1 56×1 56×1 56×1
Fan Number of units
m³/min 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11
Airflow rate (HH/H/L)
cfm 459/406/353 459/406/353 530/459/388 565/477/388
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32 External dia. 32 External dia. 32
(Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 )
Mass kg 19.5 19.5 19.5 19.5
4 Sound pressure level (HH/H/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYCP125K-W1 BYCP125K-W1 BYCP125K-W1 BYCP125K-W1
Panel colour Fresh white Fresh white Fresh white Fresh white
Decoration
panels Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 5.5 5.5 5.5 5.5
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Paper Installation manual. Paper Installation manual. Paper Installation manual. Paper
pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain
hose. Clamp metal. Washer hose. Clamp metal. Washer hose. Clamp metal. Washer hose. Clamp metal. Washer
Standard accessories fixing plate. Sealing pads. fixing plate. Sealing pads. fixing plate. Sealing pads. fixing plate. Sealing pads.
Clamps. Screws. Washer for Clamps. Screws. Washer for Clamps. Screws. Washer for Clamps. Screws. Washer for
hanging bracket. Insulation hanging bracket. Insulation hanging bracket. Insulation hanging bracket. Insulation
for fitting. Installation guide. for fitting. Installation guide. for fitting. Installation guide. for fitting. Installation guide.
Drawing No. C: 3D081322
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
46 FXFQ-LU
EDIN341424 Specifications
1 3 Cooling capacity
kcal/h
Btu/h
6,100
24,200
7,700
30,700
9,600
38,200
12,000
47,800 3
kW 7.1 9.0 11.2 14.0
kcal/h 6,900 8,600 10,800 13,800
2 3 Heating capacity Btu/h 27,300 34,100 42,700 54,600
kW 8.0 10.0 12.5 16.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 246×840×840 246×840×840 288×840×840 288×840×840
Coil (Cross Rows×Stages×Fin pitch mm 2×10×1.2 2×10×1.2 2×12×1.2 2×12×1.2
fin coil) Face area m² 0.446 0.446 0.535 0.535
Model QTS48C15M QTS48C15M QTS48C15M QTS48C15M
Type Turbo fan Turbo fan Turbo fan Turbo fan
Motor output × W 56×1 56×1 120×1 120×1
Fan Number of units
m³/min 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5
Airflow rate (HH/H/L)
cfm 671/583/477 742/636/530 1,130/918/706 1,165/989/794
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyurethane form Polyurethane form Polyurethane form Polyurethane form
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32 External dia. 32 External dia. 32
(Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 )
Mass kg 22 22 25 25
4 Sound pressure level (HH/H/L) dB(A) 34/31/28 36/33.5/31 43/37.5/32 44/39/34
Safety devices Fuse Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYCP125K-W1 BYCP125K-W1 BYCP125K-W1 BYCP125K-W1
Panel colour Fresh white Fresh white Fresh white Fresh white
Decoration
panels Dimensions: (H×W×D) mm 50×950×950 50×950×950 50×950×950 50×950×950
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 5.5 5.5 5.5 5.5
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Paper Installation manual. Paper Installation manual. Paper Installation manual. Paper
pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain
hose. Clamp metal. Washer hose. Clamp metal. Washer hose. Clamp metal. Washer hose. Clamp metal. Washer
Standard accessories fixing plate. Sealing pads. fixing plate. Sealing pads. fixing plate. Sealing pads. fixing plate. Sealing pads.
Clamps. Screws. Washer for Clamps. Screws. Washer for Clamps. Screws. Washer for Clamps. Screws. Washer for
hanging bracket. Insulation hanging bracket. Insulation hanging bracket. Insulation hanging bracket. Insulation
for fitting. Installation guide. for fitting. Installation guide. for fitting. Installation guide. for fitting. Installation guide.
Drawing No. C: 3D081322
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXFQ-LU 47
Dimensions EDIN341424
2. Dimensions
FXFQ25LUV1 / FXFQ32LUV1 / FXFQ40LUV1 / FXFQ50LUV1
Unit (mm)
3D081556A
48 FXFQ-LU
EDIN341424 Dimensions
FXFQ63LUV1 / FXFQ80LUV1
Unit (mm)
3D078813E
3
FXFQ-LU 49
Dimensions EDIN341424
FXFQ100LUV1 / FXFQ125LUV1
Unit (mm)
3D078815E
50 FXFQ-LU
EDIN341424 Piping Diagrams
3. Piping Diagrams
4D024460K
FXFQ-LU 51
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXFQ25LUV1 / FXFQ32LUV1 / FXFQ40LUV1 / FXFQ50LUV1 / FXFQ63LUV1 / FXFQ80LUV1 /
FXFQ100LUV1 / FXFQ125LUV1
3D080879
52 FXFQ-LU
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXFQ25LUV1 / FXFQ32LUV1 / FXFQ40LUV1 / FXFQ50LUV1 / FXFQ63LUV1 / FXFQ80LUV1 /
FXFQ100LUV1 / FXFQ125LUV1
3
C: 4D060238F
FXFQ-LU 53
Safety Devices Setting EDIN341424
54 FXFQ-LU
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Model
Capacity
indication
14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB 3
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
25 1.9 1.9 2.3 2.3 2.6 2.6 2.8 2.8 2.8 2.8 2.9 2.7 3.0 2.6
32 2.4 2.4 2.9 2.8 3.4 3.1 3.6 3.1 3.6 3.1 3.7 3.1 3.8 3.0
40 3.0 2.9 3.6 3.4 4.2 3.7 4.5 3.8 4.6 3.7 4.7 3.6 4.8 3.5
50 3.8 3.4 4.5 3.9 5.2 4.3 5.6 4.4 5.7 4.4 5.8 4.2 5.9 4.1
FXFQ-LU
63 4.8 4.3 5.7 4.9 6.6 5.5 7.1 5.6 7.2 5.5 7.4 5.4 7.5 5.2
80 6.1 5.1 7.2 5.8 8.4 6.5 9.0 6.6 9.1 6.6 9.3 6.4 9.5 6.2
100 7.6 6.8 9.0 7.8 10.5 8.7 11.2 8.9 11.3 8.8 11.6 8.5 11.9 8.3
125 9.4 7.9 11.3 9.0 13.1 10.1 14.0 10.3 14.2 10.2 14.5 9.9 14.9 9.6
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXFQ-LU 55
Sound Levels EDIN341424
8. Sound Levels
Overall
dB(A)
Sound pressure level
Model 220-240V, 50Hz
HH H L
FXFQ25LUV1 30 28.5 27
FXFQ32LUV1
FXFQ40LUV1 31 29 27
FXFQ50LUV1 32 29.5 27
FXFQ63LUV1 34 31 28
FXFQ80LUV1 36 33.5 31
FXFQ100LUV1 43 37.5 32
FXFQ125LUV1 44 39 34
56 FXFQ-LU
EDIN341424 Sound Levels
FXFQ125LUV1
4D060237C
FXFQ-LU 57
Centre of Gravity EDIN341424
9. Centre of Gravity
FXFQ25LUV1 / FXFQ32LUV1 / FXFQ40LUV1 / FXFQ50LUV1 / FXFQ63LUV1 / FXFQ80LUV1 /
FXFQ100LUV1 / FXFQ125LUV1
Unit (mm)
C: 4D052237L
58 FXFQ-LU
EDIN341424 Accessories
10. Accessories
10.1 Optional Accessories (for Unit)
Model
Item
FXFQ25LUV1 FXFQ32LUV1 FXFQ40LUV1 FXFQ50LUV1 FXFQ63LUV1 FXFQ80LUV1 FXFQ100LUV1 FXFQ125LUV1 3
Decoration panel BYCP125K-W1
Sealing member of air discharge
KDBH55K160F
outlet
Panel spacer KDBP55H160FA
High 65% KAFP556B80 KAFP556B160
efficiency
filter unit 90% KAFP557B80 KAFP557B160
Replacement 65% KAFP552B80 KAFP552B160
high efficiency
filter 90% KAFP553B80 KAFP553B160
Filter Filter chamber KDDFP55B160
related
Replacement Non-
KAFP551K160
long life filter woven type
Ultra long-life filter KAFP55B160
Replacement ultra long life
filter KAFP55H160H
Without T-
joint pipe KDDP55B160
Chamber and fan
Fresh air type With T-joint
intake kit pipe KDDP55B160K
without fan
Direct installation type KDDP55X160
Branch duct chamber KDJP55B80 KDJP55B160
Chamber connection kit KKSJ55KA160
Insulation kit for high humidity KDTP55K80 KDTP55K160
C: 3D081321A
FXFQ-LU 59
Accessories EDIN341424
60 FXFQ-LU
EDIN341424
FXZQ-M
Ceiling Mounted Cassette
(Compact Multi Flow) Type
4
1. Specifications ........................................................................................62
2. Dimensions ...........................................................................................64
3. Piping Diagrams....................................................................................65
4. Wiring Diagrams....................................................................................66
5. Electric Characteristics..........................................................................67
6. Safety Devices Setting ..........................................................................68
7. Capacity Tables ....................................................................................69
7.1 Cooling Capacity ....................................................................................69
7.2 Heating Capacity ....................................................................................69
8. Air Velocity and Temperature Distributions (Reference Data) ..............70
9. Sound Levels ........................................................................................74
10.Centre of Gravity ...................................................................................76
11.Accessories...........................................................................................77
11.1 Optional Accessories (for Unit)...............................................................77
11.2 Optional Accessories (for Controls)........................................................77
FXZQ-M 61
Specifications EDIN341424
1. Specifications
Ceiling mounted cassette (Compact multi flow) type
Model FXZQ20MVE FXZQ25MVE FXZQ32MVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 1,900 2,400 3,100
1 3 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
kcal/h 2,200 2,800 3,400
2 3 Heating capacity Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 286×575×575 286×575×575 286×575×575
Coil (Cross Rows×Stages×Fin pitch mm 2×10×1.5 2×10×1.5 2×10×1.5
fin coil) Face area m² 0.269 0.269 0.269
Model QTS32C15M QTS32C15M QTS32C15M
Type Turbo fan Turbo fan Turbo fan
Motor output × W 55×1 55×1 55×1
Number of units
Fan m³/min 9.0/7.0 9.0/7.0 9.5/7.5
Airflow rate (H/L) l/s 150/116 150/116 158/125
cfm 318/247 318/247 335/265
Drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for Microprocessor thermostat for Microprocessor thermostat for
cooling and heating cooling and heating cooling and heating
Sound absorbing thermal insulation material Foamed polystyrene/ Foamed polystyrene/ Foamed polystyrene/
Foamed polyethylene Foamed polyethylene Foamed polyethylene
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP20 VP20 VP20
Drain pipe mm External dia. 26 External dia. 26 External dia. 26
( Internal dia. 20 ) ( Internal dia. 20 ) ( Internal dia. 20 )
Mass kg 18 18 18
4 Sound pressure level 230V, 50Hz 30/25 30/25 32/26
(H/L) dB(A)
240V, 50Hz 32/26 32/26 34/28
230V, 50Hz 47 47 49
Sound power level (H) dB(A)
240V, 50Hz 49 49 51
Safety devices Printed circuit board fuse. Printed circuit board fuse. Printed circuit board fuse.
Fan motor thermal protector. Fan motor thermal protector. Fan motor thermal protector.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYFQ60B3W1 BYFQ60B3W1 BYFQ60B3W1
Panel colour White (6.5Y9.5/0.5) White (6.5Y9.5/0.5) White (6.5Y9.5/0.5)
Decoration Dimensions: (H×W×D) mm 55×700×700 55×700×700 55×700×700
panels
(Option) Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 2.7 2.7 2.7
Operation manual. Installation manual. Operation manual. Installation manual. Operation manual. Installation manual.
Paper pattern for installation. Drain Paper pattern for installation. Drain Paper pattern for installation. Drain
Standard accessories hose. Clamp metal. Washer fixing hose. Clamp metal. Washer fixing hose. Clamp metal. Washer fixing
plate. Sealing pads. Clamps. Screws. plate. Sealing pads. Clamps. Screws. plate. Sealing pads. Clamps. Screws.
Washer for hanging bracket. Insulation Washer for hanging bracket. Insulation Washer for hanging bracket. Insulation
for fitting. for fitting. for fitting.
Drawing No. C: 3D038929C
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
62 FXZQ-M
EDIN341424 Specifications
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXZQ-M 63
Dimensions EDIN341424
2. Dimensions
FXZQ20MVE / FXZQ25MVE / FXZQ32MVE / FXZQ40MVE / FXZQ50MVE
Unit (mm)
C: 3D039005E
64 FXZQ-M
EDIN341424 Piping Diagrams
3. Piping Diagrams
4D040157B
FXZQ-M 65
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXZQ20MVE / FXZQ25MVE / FXZQ32MVE / FXZQ40MVE / FXZQ50MVE
C: 3D064843
66 FXZQ-M
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXZQ20MVE / FXZQ25MVE / FXZQ32MVE / FXZQ40MVE / FXZQ50MVE
C: 4D040159B
FXZQ-M 67
Safety Devices Setting EDIN341424
68 FXZQ-M
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.3 1.8 1.5 2.1 1.7 2.2 1.7 2.2 1.6 2.3 1.5 2.3 1.4 4
25 1.9 1.5 2.3 1.8 2.6 2.0 2.8 2.0 2.8 1.9 2.9 1.8 3.0 1.7
FXZQ-M 32 2.4 1.9 2.9 2.1 3.4 2.4 3.6 2.4 3.6 2.2 3.7 2.2 3.8 2.1
40 3.0 2.5 3.6 2.9 4.2 3.2 4.5 3.3 4.6 3.2 4.7 3.1 4.8 2.9
50 3.8 3.1 4.5 3.6 5.2 4.0 5.6 4.1 5.7 4.1 5.8 3.9 5.9 3.7
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXZQ-M 69
Air Velocity and Temperature Distributions (Reference Data) EDIN341424
4D039738D
4D039820D
70 FXZQ-M
EDIN341424 Air Velocity and Temperature Distributions (Reference Data)
FXZQ32MVE (Cooling)
4D040188A
FXZQ32MVE (Heating)
4D040191A
FXZQ-M 71
Air Velocity and Temperature Distributions (Reference Data) EDIN341424
FXZQ40MVE (Cooling)
4D040189A
FXZQ40MVE (Heating)
4D040192A
72 FXZQ-M
EDIN341424 Air Velocity and Temperature Distributions (Reference Data)
FXZQ50MVE (Cooling)
4D040190A
FXZQ50MVE (Heating)
4D040193A
FXZQ-M 73
Sound Levels EDIN341424
9. Sound Levels
Overall
Location of microphone (for sound pressure level) Notes:
1. The operating conditions are assumed to be standard (JIS
conditions)
2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors such
as the construction (acoustic absorption coefficient) of the
particular room in which the equipment installed.
dB(A)
Sound pressure level Sound power level
Model 230V, 50Hz 240V, 50Hz 230V, 50Hz 240V, 50Hz
H L H L H H
FXZQ20MVE 30 25 32 26 47 49
FXZQ25MVE
FXZQ32MVE 32 26 34 28 49 51
FXZQ40MVE 36 28 37 29 53 54
FXZQ50MVE 41 33 42 35 58 59
4D040274A 4D040285A
FXZQ40MVE FXZQ50MVE
4D040286A 4D040287A
74 FXZQ-M
EDIN341424 Sound Levels
4D040492A 4D040491A
FXZQ40MVE FXZQ50MVE
4D040490A 4D040293A
FXZQ-M 75
Centre of Gravity EDIN341424
4D040158A
76 FXZQ-M
EDIN341424 Accessories
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item
FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
Decoration panel BYFQ60B3W1
Sealing material of air discharge outlet KDBH44BA60
Panel spacer KDBQ44BA60A 4
Replacement long-life filter KAFQ441BA60
Fresh air
Direct installation type KDDQ44XA60
intake kit
C: 3D038933B
FXZQ-M 77
Accessories EDIN341424
78 FXZQ-M
EDIN341424
FXUQ-A
4-Way Flow Ceiling Suspended Type
1. Specifications ........................................................................................80
2. Dimensions ...........................................................................................81
3. Piping Diagrams....................................................................................82
5
4. Wiring Diagrams....................................................................................83
5. Electric Characteristics..........................................................................84
6. Safety Devices Setting ..........................................................................85
7. Capacity Tables ....................................................................................86
7.1 Cooling Capacity ....................................................................................86
7.2 Heating Capacity ....................................................................................86
8. Sound Levels ........................................................................................87
9. Accessories...........................................................................................88
9.1 Optional Accessories (for Unit)...............................................................88
9.2 Optional Accessories (for Control) .........................................................88
FXUQ-A 79
Specifications EDIN341424
1. Specifications
4-way flow ceiling suspended type
Model FXUQ71AVEB FXUQ100AVEB
Power supply 1 phase, 220-240/220-230V, 50/60Hz 1 phase, 220-240/220-230V, 50/60Hz
kcal/h 6,900 9,600
1 3 Cooling capacity Btu/h 27,300 38,200
kW 8.0 11.2
kcal/h 7,700 10,800
2 3 Heating capacity Btu/h 30,700 42,700
kW 9.0 12.5
Casing colour Fresh white Fresh white
Dimensions: (H×W×D) mm 198×950×950 198×950×950
Coil (Cross Rows×Stages×Fin pitch mm 3×10×1.2 3×10×1.2
fin coil) Face area m² 0.330 0.330
Model QTS48D11M QTS48D11M
Type Turbo fan Turbo fan
Motor output × W 46×1 106×1
Number of units
Fan m³/min 22.5/19.5/16 31/26/21
Airflow rate (H/M/L) l/s 375/325/267 517/433/350
cfm 794/688/565 1,094/918/741
Drive Direct drive Direct drive
Temperature control Microprocessor thermostat for Microprocessor thermostat for
cooling and heating cooling and heating
Heat resistant foamed polyethylene / Regular foamed Heat resistant foamed polyethylene / Regular foamed
Insulation Heat insulation
polyethylene polyethylene
Air filter Resin net (with mould resistance) Resin net (with mould resistance)
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ15.9 (Flare connection) φ15.9 (Flare connection)
connections
Drain pipe mm VP20 VP20
(External dia. 26 Internal dia. 20) (External dia. 26 Internal dia. 20)
Mass kg 26 27
4 Sound pressure level (H/M/L) dB(A) 40/38/36 47/44/40
Sound power level (H/M/L) dB(A) 58/56/54 65/62/58
Safety devices Fuse Fuse
Operation manual. Installation manual. Declaration of Operation manual. Installation manual. Declaration of
conformity. Drain hose. Metal clamp. Washer for hanger. conformity. Drain hose. Metal clamp. Washer for hanger.
Standard accessories Clamp. Washer clamp. Joint insulating material. Sealing Clamp. Washer clamp. Joint insulating material. Sealing
material. Elbow. Installation pattern paper. Blocking material. Elbow. Installation pattern paper. Blocking
material. L-bent piping. Screw. Non woven fabric. material. L-bent piping. Screw. Non woven fabric.
Drawing No. C: 4D080137
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
3. The capacity of the indoor unit is only for reference. The actual capacity of the indoor unit is based on the total capacity index. Btu/h=kW×3412
4. Anechoic chamber conversion value, measured at a point 1m in front of the unit and 1m downward. During actual operation, these values cfm=m³/min×35.3
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
80 FXUQ-A
EDIN341424 Dimensions
2. Dimensions
FXUQ71AVEB / FXUQ100AVEB
Unit (mm)
3D080135
5
FXUQ-A 81
Piping Diagrams EDIN341424
3. Piping Diagrams
FXUQ71AVEB / FXUQ100AVEB
4D034245H
82 FXUQ-A
EDIN341424 Wiring Diagrams
4. Wiring Diagrams
FXUQ71AVEB / FXUQ100AVEB
3D079580
5
FXUQ-A 83
Electric Characteristics EDIN341424
5. Electric Characteristics
FXUQ71AVEB / FXUQ100AVEB
4D080216A
84 FXUQ-A
EDIN341424 Safety Devices Setting
FXUQ-A 85
Capacity Tables EDIN341424
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
71 5.4 4.6 6.4 5.2 7.5 5.9 8.0 6.0 8.4 6.1 8.6 5.9 8.8 5.8
FXUQ-A
100 7.6 6.1 9.0 7.0 10.5 7.9 11.2 8.1 11.3 7.9 11.6 7.7 11.9 7.4
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
86 FXUQ-A
EDIN341424 Sound Levels
8. Sound Levels
Overall
Location of microphone (for sound pressure level) Notes:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in anechoic
chamber (conversion values).
Sound level will vary depending on a range of factors
such as the construction (acoustic absorption
coefficient) of the particular room in which the
5
dB(A) equipments installed.
Sound pressure level
Model 220-240/220-230V, 50/60Hz
H M L
FXUQ71AVEB 40 38 36
FXUQ100AVEB 47 44 40
FXUQ71AVEB FXUQ100AVEB
4D080130 4D080131
FXUQ-A 87
Accessories EDIN341424
9. Accessories
9.1 Optional Accessories (for Unit)
Model
Item
FXUQ71AVEB FXUQ100AVEB
Sealing member of air discharge outlet KDBHP49B140
Decoration panel for air discharge KDBTP49B140
Replacement long-life filter KAFP551K160
C: 3D080116A
88 FXUQ-A
EDIN341424
FXCQ-M
Ceiling Mounted Cassette
(Double Flow) Type
1. Specifications ........................................................................................90
2. Dimensions ...........................................................................................92
3. Piping Diagrams....................................................................................96 6
4. Wiring Diagrams....................................................................................97
5. Electric Characteristics..........................................................................99
6. Safety Devices Setting ........................................................................100
7. Capacity Tables ..................................................................................101
7.1 Cooling Capacity ..................................................................................101
7.2 Heating Capacity ..................................................................................101
8. Air Velocity and Temperature Distributions (Reference Data) ............102
9. Sound Levels ......................................................................................104
10.Centre of Gravity .................................................................................105
11.Accessories.........................................................................................106
11.1 Optional Accessories (for Unit).............................................................106
11.2 Optional Accessories (for Controls)......................................................106
FXCQ-M 89
Specifications EDIN341424
1. Specifications
Ceiling mounted cassette (Double flow) type
Model FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE
Power supply 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 1,900 2,400 3,100 3,900
1 3 Cooling capacity Btu/h 7,500 9,600 12,300 15,400
kW 2.2 2.8 3.6 4.5
kcal/h 2,200 2,800 3,400 4,300
2 3 Heating capacity Btu/h 8,500 10,900 13,600 17,100
kW 2.5 3.2 4.0 5.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 305×775×600 305×775×600 305×775×600 305×990×600
Coil (Cross Rows×Stages×Fin pitch mm 2×10×1.5 2×10×1.5 2×10×1.5 2×10×1.5
fin coil) Face area m² 2×0.100 2×0.100 2×0.100 2×0.145
Model D17K2AA1 D17K2AB1 D17K2AB1 2D17K1AA1
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output × W 10×1 15×1 15×1 20×1
Number of units
Fan m³/min 7/5 9/6.5 9/6.5 12/9
Airflow rate (H/L) l/s 116/83 150/108 150/108 200/150
cfm 247/177 318/230 318/230 424/318
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Glass wool/Urethane foam Glass wool/Urethane foam Glass wool/Urethane foam Glass wool/Urethane foam
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32 External dia. 32 External dia. 32
(Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 )
Mass kg 26 26 26 31
4 Sound pressure 220V, 50/60Hz 32/27 34/28 34/28 34/29
level (H/L) dB(A)
240V, 50Hz 34/29 36/30 36/30 37/32
Safety devices Fuse. Thermal protector for Fuse. Thermal protector for Fuse. Thermal protector for Fuse. Thermal protector for
fan motor. fan motor. fan motor. fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYBC32G-W1 BYBC32G-W1 BYBC32G-W1 BYBC50G-W1
Panel colour White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Decoration Dimensions: (H×W×D) mm 53×1,030×680 53×1,030×680 53×1,030×680 53×1,245×680
panels
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 8 8 8 8.5
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Paper Installation manual. Paper Installation manual. Paper Installation manual. Paper
pattern for installation. pattern for installation. pattern for installation. pattern for installation.
Washer for hanging Washer for hanging Washer for hanging Washer for hanging
Standard accessories brackets. Clamp metal. brackets. Clamp metal. brackets. Clamp metal. brackets. Clamp metal.
Drain hose. Insulation for Drain hose. Insulation for Drain hose. Insulation for Drain hose. Insulation for
fitting. Washer fixing plates. fitting. Washer fixing plates. fitting. Washer fixing plates. fitting. Washer fixing plates.
Sealing pads. Clamps. Sealing pads. Clamps. Sealing pads. Clamps. Sealing pads. Clamps.
Screws. Washers. Screws. Washers. Screws. Washers. Screws. Washers.
Drawing No. C: 3D039413
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
90 FXCQ-M
EDIN341424 Specifications
Power supply 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 4,800 6,100 7,700 12,000
1 3 Cooling capacity Btu/h 19,100 24,200 30,700 47,800
kW 5.6 7.1 9.0 14.0
kcal/h 5,400 6,900 8,600 13,800
2 3 Heating capacity Btu/h 21,500 27,300 34,100 54,600
kW 6.3 8.0 10.0 16.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 305×990×600 305×1,175×600 305×1,665×600 305×1,665×600
Coil (Cross Rows×Stages×Fin pitch mm 2×10×1.5 2×10×1.5 2×10×1.5 2×10×1.5
fin coil) Face area
Model
m² 2×0.145
2D17K1AA1
2×0.184
2D17K2AA1VE
2×0.287
3D17K2AA1
2×0.287
3D17K2AB1 6
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output × W 20×1 30×1 50×1 85×1
Number of units
Fan m³/min 12/9 16.5/13 26/21 33/25
Airflow rate (H/L) l/s 200/150 275/216 433/350 550/416
cfm 424/318 582/459 918/741 1,165/883
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Glass wool/Urethane foam Glass wool/Urethane foam Glass wool/Urethane foam Glass wool/Urethane foam
Liquid pipes mm φ6.4 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 32 35 47 48
4 Sound pressure 220V, 50/60Hz 34/29 37/32 39/34 44/38
level (H/L) dB(A)
240V, 50Hz 37/32 39/34 41/36 46/40
Safety devices Fuse. Thermal protector for Fuse. Thermal protector for Fuse. Thermal protector for Fuse. Thermal protector for
fan motor. fan motor. fan motor. fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYBC50G-W1 BYBC63G-W1 BYBC125G-W1 BYBC125G-W1
Panel colour White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Decoration Dimensions: (H×W×D) mm 53×1,245×680 53×1,430×680 53×1,920×680 53×1,920×680
panels
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 8.5 9.5 12 12
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Paper Installation manual. Paper Installation manual. Paper Installation manual. Paper
pattern for installation. pattern for installation. pattern for installation. pattern for installation.
Washer for hanging Washer for hanging Washer for hanging Washer for hanging
Standard accessories brackets. Clamp metal. brackets. Clamp metal. brackets. Clamp metal. brackets. Clamp metal.
Drain hose. Insulation for Drain hose. Insulation for Drain hose. Insulation for Drain hose. Insulation for
fitting. Washer fixing plates. fitting. Washer fixing plates. fitting. Washer fixing plates. fitting. Washer fixing plates.
Sealing pads. Clamps. Sealing pads. Clamps. Sealing pads. Clamps. Sealing pads. Clamps.
Screws. Washers. Screws. Washers. Screws. Washers. Screws. Washers.
Standard accessories C: 3D039413
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXCQ-M 91
Dimensions EDIN341424
2. Dimensions
FXCQ20MVE + BYBC32G-W1 (Decoration panel)
FXCQ25MVE + BYBC32G-W1 (Decoration panel)
FXCQ32MVE + BYBC32G-W1 (Decoration panel) Unit (mm)
3D039405B
92 FXCQ-M
EDIN341424 Dimensions
3D039406B
6
FXCQ-M 93
Dimensions EDIN341424
3D039407B
94 FXCQ-M
EDIN341424 Dimensions
3D039409B
6
FXCQ-M 95
Piping Diagrams EDIN341424
3. Piping Diagrams
4D034245H
96 FXCQ-M
EDIN341424 Wiring Diagrams
4. Wiring Diagrams
FXCQ20MVE / FXCQ25MVE / FXCQ32MVE / FXCQ63MVE
C: 3D039558A
6
FXCQ-M 97
Wiring Diagrams EDIN341424
C: 3D039559A
98 FXCQ-M
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXCQ20MVE / FXCQ25MVE / FXCQ32MVE / FXCQ40MVE / FXCQ50MVE / FXCQ63MVE / FXCQ80MVE /
FXCQ125MVE
C: 4D034243B
FXCQ-M 99
Safety Devices Setting EDIN341424
100 FXCQ-M
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.4 1.8 1.5 2.1 1.7 2.2 1.7 2.2 1.6 2.3 1.5 2.3 1.4
25 1.9 1.7 2.3 1.9 2.6 2.1 2.8 2.2 2.8 2.1 2.9 2.0 3.0 1.8
32 2.4 2.1 2.9 2.3 3.4 2.5 3.6 2.6 3.6 2.4 3.7 2.4 3.8 2.3
40 3.0 2.5 3.6 2.8 4.2 3.1 4.5 3.2 4.6 3.2 4.7 3.0 4.8 2.8
FXCQ-M
50 3.8 3.0 4.5 3.4 5.2 3.8 5.6 3.9 5.7 3.9 5.8 3.7 5.9 3.3
63 4.8 3.8 5.7 4.2 6.6 4.7 7.1 4.9 7.2 4.6 7.4 4.4 7.5 4.2
80 6.1 5.2 7.2 5.7 8.4 6.2 9.0 6.3 9.1 6.1 9.3 6.0 9.5 5.6 6
125 9.5 7.8 11.3 8.6 13.1 9.5 14.0 9.7 14.2 9.5 14.5 9.0 14.9 8.7
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXCQ-M 101
Air Velocity and Temperature Distributions (Reference Data) EDIN341424
FXCQ63MVE
(Heating · Temperature distribution)
Discharge angle : 60°
Note:
The standard setup height of the double flow type is 3 m maximum. Shown here is the measurement distribution at
the ceiling height of 3 m.
102 FXCQ-M
EDIN341424 Air Velocity and Temperature Distributions (Reference Data)
FXCQ125MVE
(Heating · Air velocity distribution)
Discharge angle : 60°
FXCQ125MVE
(Heating · Temperature distribution)
Discharge angle : 60°
Note:
The standard setup height of the double flow type is 3 m maximum. Shown here is the measurement distribution at
the ceiling height of 3 m.
FXCQ-M 103
Sound Levels EDIN341424
9. Sound Levels
Overall
dB(A)
Sound pressure level
Model 220V, 50/60Hz 240V, 50Hz
H L H L
FXCQ20MVE 32 27 34 29
FXCQ25MVE 34 28 36 30
FXCQ32MVE
FXCQ40MVE 34 29 37 32
FXCQ50MVE
FXCQ63MVE 37 32 39 34
FXCQ80MVE 39 34 41 36
FXCQ125MVE 44 38 46 40
104 FXCQ-M
EDIN341424 Centre of Gravity
C: 4D034788C
FXCQ-M 105
Accessories EDIN341424
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item FXCQ20MVE FXCQ40MVE FXCQ80MVE
FXCQ25MVE FXCQ63MVE
FXCQ50MVE FXCQ125MVE
FXCQ32MVE
Decoration panel BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
High efficiency filter 65%
1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160
106 FXCQ-M
EDIN341424
FXKQ-MA
Ceiling Mounted Cassette
Corner Type
1. Specifications ......................................................................................108
2. Dimensions .........................................................................................109
3. Piping Diagrams..................................................................................111
4. Wiring Diagrams..................................................................................112
5. Electric Characteristics........................................................................113 7
6. Safety Devices Setting ........................................................................114
7. Capacity Tables ..................................................................................115
7.1 Cooling Capacity ..................................................................................115
7.2 Heating Capacity ..................................................................................115
8. Air Velocity and Temperature Distributions (Reference Data) ............116
9. Sound Levels ......................................................................................117
10.Centre of Gravity .................................................................................118
11.Accessories.........................................................................................119
11.1 Optional Accessories (for Unit).............................................................119
11.2 Optional Accessories (for Controls)......................................................119
FXKQ-MA 107
Specifications EDIN341424
1. Specifications
Ceiling mounted cassette corner type
Model FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Power supply 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 2,400 3,100 3,900 6,100
1 3 Cooling capacity Btu/h 9,600 12,300 15,400 24,200
kW 2.8 3.6 4.5 7.1
kcal/h 2,800 3,400 4,300 6,900
2 3 Heating capacity Btu/h 10,900 13,600 17,100 27,300
kW 3.2 4.0 5.0 8.0
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 215×1,110×710 215×1,110×710 215×1,110×710 215×1,310×710
Coil (Cross Rows×Stages×Fin pitch mm 2×11×1.75 2×11×1.75 2×11×1.75 3×11×1.75
fin coil) Face area m² 0.180 0.180 0.180 0.226
Model 3D12H1AN1V1 3D12H1AN1V1 3D12H1AP1V1 4D12H1AJ1V1
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output × W 15×1 15×1 20×1 45×1
Number of units
Fan m³/min 11/9 11/9 13/10 18/15
Airflow rate 50Hz l/s 183/150 183/150 216/166 300/250
(H/L)
cfm 388/318 388/318 459/353 635/530
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Sound absorbing thermal insulation material Polyethylene foam Polyethylene foam Polyethylene foam Polyethylene foam
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm External dia. 32 External dia. 32 External dia. 32 External dia. 32
(Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 ) (Internal dia. 25 )
Mass kg 31 31 31 34
4 Sound pressure 220V, 50/60Hz 38/33 38/33 40/34 42/37
level (H/L) dB(A)
240V, 50Hz 40/35 40/35 42/36 44/39
Safety devices Fuse. Fuse. Fuse. Fuse.
Thermal fuse for fan motor. Thermal fuse for fan motor. Thermal fuse for fan motor. Thermal fuse for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Model BYK45FJW1 BYK45FJW1 BYK45FJW1 BYK71FJW1
Panel colour White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Decoration Dimensions: (H×W×D) mm 70×1,240×800 70×1,240×800 70×1,240×800 70×1,440×800
panels
(Option) Resin net Resin net Resin net Resin net
Air filter (with mould resistance) (with mould resistance) (with mould resistance) (with mould resistance)
Mass kg 8.5 8.5 8.5 9.5
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Paper Installation manual. Paper Installation manual. Paper Installation manual. Paper
pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain pattern for installation. Drain
hose. Clamp metal. hose. Clamp metal. hose. Clamp metal. hose. Clamp metal.
Standard accessories Insulation for fitting. Sealing Insulation for fitting. Sealing Insulation for fitting. Sealing Insulation for fitting. Sealing
pads. Clamps. Screws. pads. Clamps. Screws. pads. Clamps. Screws. pads. Clamps. Screws.
Washers. Positioning jig for Washers. Positioning jig for Washers. Positioning jig for Washers. Positioning jig for
installation. Insulation for installation. Insulation for installation. Insulation for installation. Insulation for
hanger bracket. Air outlet hanger bracket. Air outlet hanger bracket. Air outlet hanger bracket. Air outlet
blocking pad. blocking pad. blocking pad. blocking pad.
Drawing No. C: 3D038813A
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
108 FXKQ-MA
FXKQ-MA
EDIN341424
140
170
20mm or more
67
2. Dimensions
148
9
215 4
6 8
250 1240
45
125
190
233
280
800
710
FXKQ40MAVE + BYK45FJW1 (Decoration panel)
FXKQ32MAVE + BYK45FJW1 (Decoration panel)
FXKQ25MAVE + BYK45FJW1 (Decoration panel)
120
100
Number Name Description
1 Liquid pipe connection φ6.4 flare connection
215
170
2 Gas pipe connection
140
φ12.7 flare connection
3 Drain pipe connection VP25 (O.D. φ32)
20
4 Wire intake
520 5 Interunit wiring connection
6 Grounding terminal Inside switch box (M4)
7 Discharge
8 Air suction grille
1000 or more
Required
installation space
9 Long life filter
10 Suspension bolt
C: 3D038840
109
Dimensions
Unit (mm)
7
110
Dimensions
200mm or more
1500mm or more 200mm or more
140
170
20mm or more
67
148
215
6 4 8 9
250 1440
45
125
190
233
280
FXKQ63MAVE + BYK71FJW1 (Decoration panel)
800
710
120
100
1 Liquid pipe connection φ9.5 flare connection
2 Gas pipe connection φ15.9 flare connection
215
3 Drain pipe connection VP25 (O.D. φ32)
140
4 Wire intake
5 Interunit wiring connection
20
6 Grounding terminal Inside switch box (M4)
720 7 Discharge
8 Air suction grille
Required
installation
space
C: 3D038841
Unit (mm)
EDIN341424
FXKQ-MA
EDIN341424 Piping Diagrams
3. Piping Diagrams
4D034245H
FXKQ-MA 111
112
INDOOR UNIT
A1P PRINTED CIRCUIT BOARD
A2P TERMINAL BOARD
Wiring Diagrams
C1 CAPACITOR (M1F)
POWER SUPPLY
F1U FUSE ( B , 5A, 250V) ELECTRIC PARTS BOX
220-240V 220V
HAP LIGHT EMITTING DIODE ~ ~ X18A X16A
(SERVICE MONITOR-GREEN) 50Hz 60Hz
S1Q
K1R-K3R
MAGNETIC RELAY (M1F) C1
KAR MAGNETIC RELAY (M1S) R1T R2T R3T S1L A2P
X1M A1P T1R X1M
L N X2M
KPR MAGNETIC RELAY (M1P) GRN/ t˚ t˚
A1P RED WHT YLW t˚ BLK
M1F MOTOR (INDOOR FAN) FC FH FL FLL
X4A
4. Wiring Diagrams
C: 3D039564C
EDIN341424
FXKQ-MA
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXKQ25MAVE / FXKQ32MAVE / FXKQ40MAVE / FXKQ63MAVE
4D037076C
FXKQ-MA 113
Safety Devices Setting EDIN341424
114 FXKQ-MA
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
25 1.9 1.9 2.3 2.2 2.6 2.3 2.8 2.4 2.8 2.3 2.9 2.3 3.0 2.2
32 2.4 2.2 2.9 2.5 3.4 2.6 3.6 2.7 3.6 2.6 3.7 2.6 3.8 2.5
FXKQ-MA
40 3.0 2.6 3.6 2.8 4.2 3.2 4.5 3.2 4.6 3.2 4.7 3.1 4.8 2.9
63 4.8 4.0 5.7 4.5 6.6 5.0 7.1 5.1 7.2 5.0 7.4 4.8 7.5 4.6
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXKQ-MA 115
Air Velocity and Temperature Distributions (Reference Data) EDIN341424
FXKQ63MAVE
(Heating · Temperature distribution)
Lower airflow
Note:
The corner type is applicable on a high ceiling. The standard setup height is 3 m. Shown here is the measurement
distribution at the ceiling height of 3 m.
116 FXKQ-MA
EDIN341424 Sound Levels
9. Sound Levels
Overall
FXKQ-MA 117
Centre of Gravity EDIN341424
C: 4D037079A
118 FXKQ-MA
EDIN341424 Accessories
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item FXKQ25MAVE
FXKQ32MAVE FXKQ63MAVE
FXKQ40MAVE
Decoration panel BYK45FJW1 BYK71FJW1
Panel
related Long life replacement
KAFJ521F56 KAFJ521F80
filter
Air discharge grill K-HV7AW K-HV9AW
Air inlet Air discharge blind
and air panel KDBJ52F56W KDBJ52F80W
discharge
outlet Panel spacer KPBJ52F56W KPBJ52F80W
related Flexible duct
KFDJ52FA56 KFDJ52FA80
(with shutter)
C: 3D037081A
7
11.2 Optional Accessories (for Controls)
Refer to page 698.
FXKQ-MA 119
Accessories EDIN341424
120 FXKQ-MA
EDIN341424
FXDQ-PB / FXDQ-NB
Slim Ceiling Mounted Duct Type
1. Specifications ......................................................................................122
1.1 FXDQ-PB .............................................................................................122
1.2 FXDQ-NB .............................................................................................123
2. Dimensions .........................................................................................124
2.1 FXDQ-PB .............................................................................................124
2.2 FXDQ-NB .............................................................................................126
3. Piping Diagrams..................................................................................130
4. Wiring Diagrams..................................................................................131
5. Electric Characteristics........................................................................133
8
6. Safety Devices Setting ........................................................................134
7. Capacity Tables ..................................................................................135
7.1 Cooling Capacity ..................................................................................135
7.2 Heating Capacity ..................................................................................135
8. Fan Performances...............................................................................136
8.1 FXDQ-PB .............................................................................................136
8.2 FXDQ-NB .............................................................................................137
9. Sound Levels ......................................................................................138
9.1 FXDQ-PB .............................................................................................138
9.2 FXDQ-NB .............................................................................................139
10.Centre of Gravity .................................................................................140
10.1 FXDQ-PB .............................................................................................140
10.2 FXDQ-NB .............................................................................................141
11.Accessories.........................................................................................142
11.1 Optional Accessories (for Unit).............................................................142
11.2 Optional Accessories (for Controls)......................................................142
1. Specifications
1.1 FXDQ-PB
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”.
(Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
6. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
7. Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
8. Refer to Electric Characteristics for the power input.
1.2 FXDQ-NB
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. External static pressure is changeable to set by the remote controller. This pressure means “High static pressure - Standard static pressure”.
(Factory setting is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
6. The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
7. Values are based on the following conditions: FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.
8. Refer to Electric Characteristics for the power input.
2. Dimensions
2.1 FXDQ-PB
3D049799C
3D050732B
8
2.2 FXDQ-NB
3D045494C
3D045496D
8
3D049701B
3D049702B
8
3. Piping Diagrams
4D060927B
4. Wiring Diagrams
FXDQ20PBVE6 / FXDQ25PBVE6 / FXDQ32PBVE6 / FXDQ40NBVE6 / FXDQ50NBVE6 / FXDQ63NBVE6
(with a drain pump)
3D060547B
8
Y1E
V1TR
YLW
WHT
X7A
X18A X16A RED M
~
BLK Q1M
X4A M1F
A1P HAP
X1M C1 X2M
Z1C
T1R
Z2C
NOTES) CONTROL BOX
1. : TERMINAL
, : CONNECTOR
2. : FIELD WIRING
3. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL.
4. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING MATERIALS AND CATALOGS, ETC. BEFORE CONNECTING.
5. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER.
IN DETAILS, REFER TO THE INSTALLATION MANUAL ATTACHED THE UNIT.
6. SYMBOLS SHOW AS FOLLOWS: RED : RED BLK : BLACK WHT : WHITE YLW : YELLOW PRP : PURPLE GRY : GRAY BLU : BLUE PNK : PINK ORG : ORANGE GRN : GREEN
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET / FXDQ63NBVET
C: 3D060548
FXDQ-PB / FXDQ-NB
EDIN341424
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXDQ20PBVE6 / FXDQ25PBVE6 / FXDQ32PBVE6 / FXDQ40NBVE6 / FXDQ50NBVE6 / FXDQ63NBVE6 /
FXDQ20PBVET / FXDQ25PBVET / FXDQ32PBVET / FXDQ40NBVET / FXDQ50NBVET / FXDQ63NBVET
4D060922
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.2 1.8 2.3 1.6 2.3 1.7
FXDQ-PB 25 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 2.8 2.1 2.9 2.0 3.0 1.9
32 2.4 1.9 2.9 2.2 3.4 2.4 3.6 2.6 3.6 2.4 3.7 2.4 3.8 2.4
40 3.0 2.5 3.6 2.8 4.2 3.2 4.5 3.3 4.6 3.1 4.7 3.0 4.8 3.1
FXDQ-NB 50 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.7 3.9 5.8 3.8 5.9 3.5
63 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.2 4.6 7.4 4.6 7.5 4.6
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
8. Fan Performances
8.1 FXDQ-PB
FXDQ20PBVE6 / FXDQ25PBVE6 FXDQ32PBVE6
FXDQ20PBVET / FXDQ25PBVET FXDQ32PBVET
3D052156D 3D052157D
Notes:
1. The remote controller can be used to switch between “HH”, “H” and “L”.
2. The airflow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” by the remote controller.
8.2 FXDQ-NB
FXDQ40NBVE6 FXDQ50NBVE6
FXDQ40NBVET FXDQ50NBVET
3D046299F
3D046300F
FXDQ63NBVE6
FXDQ63NBVET
3D046301F
Notes:
1. The remote controller can be used to switch between “HH”, “H” and “L”.
2. The airflow is set to “standard” before leaving the factory.
It is possible to switch between “standard ESP” and “high ESP” by the remote controller.
9. Sound Levels
9.1 FXDQ-PB
Overall
dB(A)
Sound pressure level
Model 220-240/220V, 50/60Hz
HH H L
FXDQ20PBVE6 33 31 29
FXDQ20PBVET
FXDQ25PBVE6
FXDQ25PBVET 33 31 29
FXDQ32PBVE6
FXDQ32PBVET 33 31 29
9.2 FXDQ-NB
Overall
4D049300L
10.2 FXDQ-NB
FXDQ40NBVE6 / FXDQ50NBVE6
FXDQ40NBVET / FXDQ50NBVET
Unit (mm)
4D043886Q
FXDQ63NBVE6
FXDQ63NBVET
Unit (mm)
4D043887P
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item FXDQ20PBVE6 FXDQ20PBVET FXDQ40NBVE6 FXDQ40NBVET
FXDQ25PBVE6 FXDQ25PBVET FXDQ63NBVE6 FXDQ63NBVET
FXDQ50NBVE6 FXDQ50NBVET
FXDQ32PBVE6 FXDQ32PBVET
Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63
C: 4D060939C
FXMQ-P
Ceiling Mounted Duct Type
1. Specifications ......................................................................................144
2. Dimensions .........................................................................................147
3. Piping Diagrams..................................................................................152
4. Wiring Diagrams..................................................................................153
5. Electric Characteristics........................................................................155
6. Safety Devices Setting ........................................................................156
7. Capacity Tables ..................................................................................157
7.1 Cooling Capacity ..................................................................................157
7.2 Heating Capacity ..................................................................................157
8. Fan Performances...............................................................................158
9. Airflow Auto Adjustment Characteristics .............................................163 9
10.Sound Levels ......................................................................................167
11.Centre of Gravity .................................................................................169
12.Accessories.........................................................................................170
12.1 Optional Accessories (for Unit).............................................................170
12.2 Optional Accessories (for Controls)......................................................170
FXMQ-P 143
Specifications EDIN341424
1. Specifications
Ceiling mounted duct type
Model FXMQ20PVE FXMQ25PVE FXMQ32PVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 1,900 2,400 3,100
1 3 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
kcal/h 2,200 2,800 3,400
2 3 Heating capacity Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
50Hz kW 0.056 0.056 0.060
Cooling
7 Power 60Hz kW 0.056 0.056 0.059
input 50Hz kW 0.044 0.044 0.048
Heating
60Hz kW 0.044 0.044 0.048
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×550×700 300×550×700 300×550×700
Coil (Cross Rows×Stages×Fin pitch mm 3×16×1.75 3×16×1.75 3×16×1.75
fin coil) Face area m² 0.098 0.098 0.098
Model — — —
Type Sirocco fan Sirocco fan Sirocco fan
Motor output × W 90×1 90×1 90×1
Number of units
m³/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7
Fan
Airflow rate (HH/H/L) l/s 150/125/108 150/125/108 158/133/116
cfm 318/265/230 318/265/230 335/282/247
4 External static Pa 30-100 (50) 30-100 (50) 30-100 (50)
pressure
Drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for Microprocessor thermostat for Microprocessor thermostat for
cooling and heating cooling and heating cooling and heating
Air filter 5 5 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 25 25 25
6 Sound pressure level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30
Sound power level (H) dB(A) 51 51 52
Safety devices Fuse. Fuse. Fuse.
Fan driver overload protector. Fan driver overload protector. Fan driver overload protector.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Installation manual. Operation manual. Installation manual. Operation manual. Installation manual.
Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps. Drain hose. Sealing pads. Clamps.
Standard accessories Washers. Screws. Insulation for fitting. Washers. Screws. Insulation for fitting. Washers. Screws. Insulation for fitting.
Clamp metal. Air discharge flange. Air Clamp metal. Air discharge flange. Air Clamp metal. Air discharge flange. Air
suction flange. suction flange. suction flange.
Drawing No. C: 3D060388E
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen cfm=m³/min×35.3
(FXMQ50-125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The rated
static pressure is shown with ( ). The factory setting is the rated value.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input.
144 FXMQ-P
EDIN341424 Specifications
Power supply 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V, 1 phase, 220-240/220V,
50/60Hz 50/60Hz 50/60Hz 50/60Hz
kcal/h 3,900 4,800 6,100 7,700
1 3 Cooling capacity Btu/h 15,400 19,100 24,200 30,700
kW 4.5 5.6 7.1 9.0
kcal/h 4,300 5,400 6,900 8,600
2 3 Heating capacity Btu/h 17,100 21,500 27,300 34,100
kW 5.0 6.3 8.0 10.0
50 Hz kW 0.151 0.128 0.138 0.185
Cooling
7 Power 60 Hz kW 0.150 0.127 0.138 0.184
input 50 Hz kW 0.139 0.116 0.127 0.173
Heating
60 Hz kW 0.139 0.116 0.127 0.173
Casing / Colour Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 300×700×700 300×1,000×700 300×1,000×700 300×1,000×700
Coil (Cross Rows×Stages×Fin pitch mm 3×16×1.75 3×16×1.75 3×16×1.75 3×16×1.75
fin coil) Face area m² 0.148 0.249 0.249 0.249
Model — — — —
Type Sirocco fan Sirocco fan Sirocco fan Sirocco fan
Motor output × W 140×1 350×1 350×1 350×1
Number of units
m³/min 16/13/11 18/16.5/15 19.5/17.5/16 25/22.5/20
Fan
Airflow rate (HH/H/L) l/s
cfm
267/216/183
565/459/388
300/275/250
635/582/530
325/292/267
688/618/565
417/375/333
883/794/706
9
4 External static Pa 30-160 (100) 50-200 (100) 50-200 (100) 50-200 (100)
pressure
Drive Direct drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat Microprocessor thermostat
for cooling and heating for cooling and heating for cooling and heating for cooling and heating
Air filter 5 5 5 5
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
connections VP25 VP25 VP25 VP25
Drain pipe mm
( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 ) ( External dia. 32
Internal dia. 25 )
Mass kg 28 36 36 36
6 Sound pressure level (HH/H/L) dB(A) 39/37/35 41/39/37 42/40/38 43/41/39
Sound power level (H) dB(A) 57 59 60 61
Fuse. Fuse. Fuse. Fuse.
Safety devices Fan driver overload Fan driver overload Fan driver overload Fan driver overload
protector. protector. protector. protector.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Operation manual. Operation manual. Operation manual.
Installation manual. Drain Installation manual. Drain Installation manual. Drain Installation manual. Drain
hose. Sealing pads. hose. Sealing pads. hose. Sealing pads. hose. Sealing pads.
Standard accessories Clamps. Washers. Screws. Clamps. Washers. Screws. Clamps. Washers. Screws. Clamps. Washers. Screws.
Insulation for fitting. Clamp Insulation for fitting. Clamp Insulation for fitting. Clamp Insulation for fitting. Clamp
metal. Air discharge flange. metal. Air discharge flange. metal. Air discharge flange. metal. Air discharge flange.
Air suction flange. Air suction flange. Air suction flange. Air suction flange.
Drawing No. C: 3D073012B
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen cfm=m³/min×35.3
(FXMQ50-125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The rated
static pressure is shown with ( ). The factory setting is the rated value.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input.
FXMQ-P 145
Specifications EDIN341424
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen cfm=m³/min×35.3
(FXMQ50-125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The rated
static pressure is shown with ( ). The factory setting is the rated value.
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are
normally somewhat higher as a result of ambient conditions.
7. Power input values are based on conditions of rated external static pressure.
8. Refer to Electric Characteristics for the power input.
146 FXMQ-P
EDIN341424 Dimensions
2. Dimensions
FXMQ20PVE / FXMQ25PVE / FXMQ32PVE
Unit (mm)
3D062541B
9
FXMQ-P 147
Dimensions EDIN341424
FXMQ40PVE6
Unit (mm)
3D060160G
148 FXMQ-P
EDIN341424 Dimensions
FXMQ50PVE6
Unit (mm)
3D060159F
9
FXMQ-P 149
Dimensions EDIN341424
FXMQ63PVE6 / FXMQ80PVE6
Unit (mm)
3D060161G
150 FXMQ-P
EDIN341424 Dimensions
3D060162G
9
FXMQ-P 151
Piping Diagrams EDIN341424
3. Piping Diagrams
4D034245H
152 FXMQ-P
EDIN341424 Wiring Diagrams
4. Wiring Diagrams
FXMQ20PVE / FXMQ25PVE / FXMQ32PVE
C: 3D058783F
9
FXMQ-P 153
Wiring Diagrams EDIN341424
3D074860A
154 FXMQ-P
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXMQ20PVE / FXMQ25PVE / FXMQ32PVE / FXMQ40PVE6 / FXMQ50PVE6 / FXMQ63PVE6 / FXMQ80PVE6 /
FXMQ100PVE6 / FXMQ125PVE6 / FXMQ140PVE6
C: 4D060439D
FXMQ-P 155
Safety Devices Setting EDIN341424
Model FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE6 FXMQ50PVE6 FXMQ63PVE6 FXMQ80PVE6 FXMQ100PVE6 FXMQ125PVE6 FXMQ140PVE6
Printed circuit board fuse 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A 250V 3.15A
Printed circuit board fuse
250V 5A 250V 5A 250V 5A 250V 5A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A 250V 6.3A
(Fan driver)
Drain pump thermal fuse °C 145 145 145 145 145 145 145 145 145 145
C: 3D034597J
156 FXMQ-P
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.5 1.8 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.3 1.8 2.3 1.8
25 1.9 1.8 2.3 2.0 2.6 2.3 2.8 2.3 2.8 2.2 2.9 2.1 3.0 2.2
32 2.4 2.1 2.9 2.4 3.4 2.7 3.6 2.8 3.6 2.7 3.7 2.7 3.8 2.6
40 3.0 2.9 3.6 3.4 4.2 3.8 4.5 3.8 4.6 3.7 4.7 3.5 4.8 3.6
50 3.8 3.6 4.5 4.1 5.2 4.5 5.6 4.6 5.7 4.5 5.8 4.3 5.9 3.6
FXMQ-P
63 4.8 4.2 5.7 4.9 6.6 5.4 7.1 5.5 7.2 5.4 7.4 5.3 7.5 5.2
80 6.1 5.3 7.2 6.1 8.4 6.9 9.0 7.0 9.1 6.9 9.3 6.6 9.5 6.6
100 7.6 6.4 9.0 7.3 10.5 8.3 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.8
125 9.4 8.0 11.3 9.2 13.1 10.3 14.0 10.5 14.2 10.4 14.5 10.1 14.9 9.7
140 10.8 9.0 12.9 10.4 15.0 11.7 16.0 12.0 16.2 11.9 16.6 11.5 17.0 11.3
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
FXMQ-P 157
Fan Performances EDIN341424
8. Fan Performances
FXMQ20PVE / FXMQ25PVE
3D062537A
FXMQ32PVE
3D062538A
158 FXMQ-P
EDIN341424 Fan Performances
FXMQ40PVE6
3D060456C
FXMQ50PVE6
3D060457D
FXMQ-P 159
Fan Performances EDIN341424
FXMQ63PVE6
3D060458C
FXMQ80PVE6
3D060459C
160 FXMQ-P
EDIN341424 Fan Performances
FXMQ100PVE6
3D060460C
FXMQ125PVE6
3D060461C
FXMQ-P 161
Fan Performances EDIN341424
FXMQ140PVE6
3D063787
162 FXMQ-P
EDIN341424 Airflow Auto Adjustment Characteristics
3D062539A
FXMQ32PVE
3D062540A
FXMQ-P 163
Airflow Auto Adjustment Characteristics EDIN341424
FXMQ40PVE6
3D060577D
FXMQ50PVE6
3D060578D
164 FXMQ-P
EDIN341424 Airflow Auto Adjustment Characteristics
FXMQ63PVE6
3D060579D
FXMQ80PVE6
3D060580D
FXMQ-P 165
Airflow Auto Adjustment Characteristics EDIN341424
FXMQ100PVE6
3D060581D
FXMQ125PVE6
3D060582D
166 FXMQ-P
EDIN341424 Sound Levels
dB(A)
Sound pressure level
Model 220-240/220V, 50/60Hz
HH H L
FXMQ20PVE / FXMQ25PVE 33 31 29
FXMQ32PVE 34 32 30
FXMQ40PVE6 39 37 35
FXMQ50PVE6 41 39 37 9
FXMQ63PVE6 42 40 38
FXMQ80PVE6 43 41 39
FXMQ100PVE6 43 41 39
FXMQ125PVE6 44 42 40
FXMQ140PVE6 46 45 43
FXMQ-P 167
Sound Levels EDIN341424
168 FXMQ-P
EDIN341424 Centre of Gravity
C: 4D060438C
FXMQ-P 169
Accessories EDIN341424
12. Accessories
12.1 Optional Accessories (for Unit)
Model
Item
FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE6 FXMQ50PVE6 FXMQ63PVE6 FXMQ80PVE6 FXMQ100PVE6 FXMQ125PVE6 FXMQ140PVE6
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160
High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160
Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160
Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160
Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
Service panel KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F
KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
C: 3D060443D
170 FXMQ-P
EDIN341424
FXMQ-M
Ceiling Mounted Duct Type
1. Specifications ......................................................................................172
2. Dimensions .........................................................................................173
3. Piping Diagrams..................................................................................174
4. Wiring Diagrams..................................................................................175
5. Electric Characteristics........................................................................176
6. Safety Devices Setting ........................................................................177
7. Capacity Tables ..................................................................................178
7.1 Cooling Capacity ..................................................................................178
7.2 Heating Capacity ..................................................................................178
8. Fan Performances...............................................................................179
9. Sound Levels ......................................................................................180
10.Centre of Gravity .................................................................................181
11.Accessories.........................................................................................182
11.1 Optional Accessories (for Unit).............................................................182
10
11.2 Optional Accessories (for Controls)......................................................182
FXMQ-M 171
Specifications EDIN341424
1. Specifications
Ceiling mounted duct type
Model FXMQ200MVE6 FXMQ250MVE6
Power supply 1 phase, 230V, 50Hz 1 phase, 230V, 50Hz
kcal/h 19,300 24,100
1 3 Cooling capacity Btu/h 76,400 95,500
kW 22.4 28.0
kcal/h 21,500 27,100
2 3 Heating capacity Btu/h 85,300 107,500
kW 25.0 31.5
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 470×1,380×1,100 470×1,380×1,100
Coil (Cross Rows×Stages×Fin pitch mm 3×26×2.0 3×26×2.0
fin coil) Face area m² 0.68 0.68
Type Sirocco fan Sirocco fan
Motor output × W 380×2 380×2
Number of units
m³/min 58/50 72/62
Fan Airflow rate (H/L) l/s 966/833 1,200/1,033
cfm 2,047/1,765 2,542/2,189
External static pressure Pa 221-132 4 270-191 4
Drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating
Air filter 5 5
Liquid pipes mm φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ19.1(Brazing connection) φ22.2 (Brazing connection)
connections
Drain pipe mm PS1B PS1B
Mass kg 137 137
6 Sound pressure level (H/L) dB(A) 49/47 49/47
Safety devices Fuse. Thermal protector for fan motor. Fuse. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve
Standard accessories Operation manual. Installation manual. Sealing pads. Operation manual. Installation manual. Sealing pads.
Connection pipes. Screws. Clamps. Connection pipes. Screws. Clamps.
Drawing No. C: 4D078696A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. External static pressure is changeable to change over the connectors inside electrical box, this pressure means cfm=m³/min×35.3
"High static pressure-Standard".
5. Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity
method) 50% or more.
6. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. These values are normally somewhat higher
during actual operation as a result of ambient conditions.
7. Refer to Electric Characteristics for the power input.
172 FXMQ-M
EDIN341424 Dimensions
2. Dimensions
FXMQ200MVE6 / FXMQ250MVE6
Unit (mm)
C: 3D038851A
10
FXMQ-M 173
Piping Diagrams EDIN341424
3. Piping Diagrams
4D034245H
174 FXMQ-M
EDIN341424 Wiring Diagrams
4. Wiring Diagrams
FXMQ200MVE6 / FXMQ250MVE6
3D078695A
10
FXMQ-M 175
Electric Characteristics EDIN341424
5. Electric Characteristics
FXMQ200MVE6 / FXMQ250MVE6
4D078599
176 FXMQ-M
EDIN341424 Safety Devices Setting
10
FXMQ-M 177
Capacity Tables EDIN341424
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
200 15.1 13.3 18.0 14.9 21.0 16.3 22.4 16.8 23.6 17.0 24.2 16.1 24.6 15.4
FXMQ-M
250 18.9 16.6 22.5 18.5 26.2 20.4 28.0 20.9 29.5 21.1 30.2 20.2 30.8 19.4
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
178 FXMQ-M
EDIN341424 Fan Performances
8. Fan Performances
FXMQ200MVE6
10
4D078610
FXMQ250MVE6
4D078616
FXMQ-M 179
Sound Levels EDIN341424
9. Sound Levels
Overall
FXMQ200MVE6 / FXMQ250MVE6
4D078620
180 FXMQ-M
EDIN341424 Centre of Gravity
4D035171
10
FXMQ-M 181
Accessories EDIN341424
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item
FXMQ200MVE6 FXMQ250MVE6
Drain pump kit KDU30L250VE
65% KAFJ372L280
High efficiency filter
90% KAFJ373L280
Filter chamber KDJ3705L280
Long life replacement filter KAFJ371L280
C: 3D040334C
182 FXMQ-M
EDIN341424
FXHQ-MA
Ceiling Suspended Type
1. Specifications ......................................................................................184
2. Dimensions .........................................................................................185
3. Piping Diagrams..................................................................................188
4. Wiring Diagrams..................................................................................189
5. Electric Characteristics........................................................................190
6. Safety Devices Setting ........................................................................191
7. Capacity Tables ..................................................................................192
7.1 Cooling Capacity ..................................................................................192
7.2 Heating Capacity ..................................................................................192
8. Air Velocity and Temperature Distributions (Reference Data) ............193
9. Sound Levels ......................................................................................194
10.Accessories.........................................................................................195
10.1 Optional Accessories (for Unit).............................................................195
10.2 Optional Accessories (for Controls)......................................................195
11
FXHQ-MA 183
Specifications EDIN341424
1. Specifications
Ceiling suspended type
Model FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 3,100 6,100 9,600
1 3 Cooling capacity Btu/h 12,300 24,200 38,200
kW 3.6 7.1 11.2
kcal/h 3,400 6,900 10,800
2 3 Heating capacity Btu/h 13,600 27,300 42,700
kW 4.0 8.0 12.5
Casing colour White (10Y9/0.5) White (10Y9/0.5) White (10Y9/0.5)
Dimensions: (H×W×D) mm 195×960×680 195×1,160×680 195×1,400×680
Coil (Cross Rows×Stages×Fin pitch mm 2×12×1.75 3×12×1.75 3×12×1.75
fin coil) Face area m² 0.182 0.233 0.293
Model 3D12K1AA1 4D12K1AA1 3D12K2AA1
Type Sirocco fan Sirocco fan Sirocco fan
Motor output × W 62×1 62×1 130×1
Number of units
Fan m³/min 12/10 17.5/14 25/19.5
Airflow rate (H/L) l/s 200/166 291/233 416/325
cfm 424/353 618/494 883/688
Drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling Microprocessor thermostat for cooling Microprocessor thermostat for cooling
and heating and heating and heating
Sound absorbing thermal insulation material Glass wool Glass wool Glass wool
Air filter Resin net (with mold resistant) Resin net (with mold resistant) Resin net (with mold resistant)
Liquid pipes mm φ6.4 (Flare connection) φ9.5 (Flare connection) φ9.5 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ15.9 (Flare connection) φ15.9 (Flare connection)
Connections
Drain pipe mm VP20 VP20 VP20
(External dia. 26 Internal dia. 20) (External dia. 26 Internal dia. 20) (External dia. 26 Internal dia. 20)
Mass kg 24 28 33
4 Sound pressure level (H/L) dB(A) 36/31 39/34 45/37
Safety devices Fuse. Fuse. Fuse.
Thermal protector for fan motor. Thermal protector for fan motor. Thermal protector for fan motor.
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Installation Operation manual. Installation Operation manual. Installation
Standard accessories manual. Drain hose. Paper pattern for manual. Drain hose. Paper pattern for manual. Drain hose. Paper pattern for
installation. Clamp metal. Insulation installation. Clamp metal. Insulation installation. Clamp metal. Insulation
for fitting. Clamps. Washers. for fitting. Clamps. Washers. for fitting. Clamps. Washers.
Drawing No. C: 3D038815A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values cfm=m³/min×35.3
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
184 FXHQ-MA
EDIN341424 Dimensions
2. Dimensions
FXHQ32MAVE
Unit (mm)
3D038855A
11
FXHQ-MA 185
Dimensions EDIN341424
FXHQ63MAVE
Unit (mm)
3D038856A
186 FXHQ-MA
EDIN341424 Dimensions
FXHQ100MAVE
Unit (mm)
3D038857C
11
FXHQ-MA 187
Piping Diagrams EDIN341424
3. Piping Diagrams
4D034245H
188 FXHQ-MA
FXHQ-MA
EDIN341424
C: 3D039801D
189
Wiring Diagrams
11
Electric Characteristics EDIN341424
5. Electric Characteristics
FXHQ32MAVE / FXHQ63MAVE / FXHQ100MAVE
C: 4D035304C
190 FXHQ-MA
EDIN341424 Safety Devices Setting
11
FXHQ-MA 191
Capacity Tables EDIN341424
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
32 2.4 2.3 2.9 2.6 3.4 2.8 3.6 2.9 3.6 2.6 3.7 2.7 3.8 2.6
FXHQ-MA 63 4.8 4.1 5.7 4.6 6.6 5.1 7.1 5.2 7.2 5.1 7.4 4.9 7.5 4.6
100 7.6 6.2 9.0 6.9 10.5 7.8 11.2 8.0 11.3 7.8 11.6 7.4 11.9 7.2
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
192 FXHQ-MA
EDIN341424 Air Velocity and Temperature Distributions (Reference Data)
11
FXHQ100MAVE
(Heating · Temperature distribution)
Centre airflow
FXHQ-MA 193
Sound Levels EDIN341424
9. Sound Levels
Overall
Location of microphone (for sound pressure level) Notes:
1. The operating conditions are assumed to be standard
(JIS conditions).
2. These operating values were obtained in anechoic
Microphone
chamber (conversion values).
Sound level will vary depending on a range of factors
dB(A) such as the construction (acoustic absorption
Sound pressure level coefficient) of the particular room in which the
Model 220-240/220V, 50/60Hz equipment installed.
H L
FXHQ32MAVE 36 31
FXHQ63MAVE 39 34
FXHQ100MAVE 45 37
194 FXHQ-MA
EDIN341424 Accessories
10. Accessories
10.1 Optional Accessories (for Unit)
Model
Item
FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
Drain pump kit KDU50N60VE KDU50N125VE
Replacement long-life filter
KAF501DA56 KAF501DA80 KAF501DA112
(Resin net)
L-type piping kit
KHFP5MA63 KHFP5MA160
(for upward direction)
4D040446C
11
FXHQ-MA 195
Accessories EDIN341424
196 FXHQ-MA
EDIN341424
FXAQ-P
Wall Mounted Type
1. Specifications ......................................................................................198
2. Dimensions .........................................................................................200
3. Piping Diagrams..................................................................................203
4. Wiring Diagrams..................................................................................204
5. Electric Characteristics........................................................................205
6. Safety Devices Setting ........................................................................206
7. Capacity Tables ..................................................................................207
7.1 Cooling Capacity ..................................................................................207
7.2 Heating Capacity ..................................................................................207
8. Sound Levels ......................................................................................208
9. Recommended Mounting-plate Retention Spots and Dimensions......209
10.Accessories.........................................................................................210
10.1 Optional Accessories (for Unit).............................................................210
10.2 Optional Accessories (for Controls)......................................................210
12
FXAQ-P 197
Specifications EDIN341424
1. Specifications
Wall mounted type
Model FXAQ20PVE FXAQ25PVE FXAQ32PVE
Power supply 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz 1 phase, 220-240/220V, 50/60Hz
kcal/h 1,900 2,400 3,100
1 3 Cooling capacity Btu/h 7,500 9,600 12,300
kW 2.2 2.8 3.6
kcal/h 2,200 2,800 3,400
2 3 Heating capacity Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
Casing colour White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5)
Dimensions: (H×W×D) mm 290×795×238 290×795×238 290×795×238
Coil (Cross Rows×Stages×Fin pitch mm 2×14×1.4 2×14×1.4 2×14×1.4
fin coil) Face area m² 0.161 0.161 0.161
Model QCL9661M QCL9661M QCL9661M
Type Cross flow fan Cross flow fan Cross flow fan
Motor output × W 40×1 40×1 40×1
Number of units
Fan m³/min 7.5/4.5 8/5 8.5/5.5
Airflow rate (H/L) l/s 125/75 133/83 142/91
cfm 265/159 282/177 300/194
Drive Direct drive Direct drive Direct drive
Temperature control Microprocessor thermostat for Microprocessor thermostat for Microprocessor thermostat for
cooling and heating cooling and heating cooling and heating
Sound absorbing thermal insulation material Foamed polystyrene / Foamed polystyrene / Foamed polystyrene /
Foamed polyethylene Foamed polyethylene Foamed polyethylene
Air filter Resin net (Washable) Resin net (Washable) Resin net (Washable)
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection) φ12.7 (Flare connection)
connections
Drain pipe mm VP13 VP13 VP13
(External dia. 18 Internal dia. 13) (External dia. 18 Internal dia. 13) (External dia. 18 Internal dia. 13)
Mass kg 11 11 11
4 Sound pressure level (H/L) dB(A) 35/31 36/31 38/31
Safety devices Fuse Fuse Fuse
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Operation manual. Installation Operation manual. Installation Operation manual. Installation
Standard accessories manual. Installation panel. Paper manual. Installation panel. Paper manual. Installation panel. Paper
pattern for installation. Insulation tape. pattern for installation. Insulation tape. pattern for installation. Insulation tape.
Clamps. Screws. Clamps. Screws. Clamps. Screws.
Drawing No. C: 3D077064A
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values cfm=m³/min×35.3
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
198 FXAQ-P
EDIN341424 Specifications
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
4. Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values cfm=m³/min×35.3
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
FXAQ-P 199
Dimensions EDIN341424
2. Dimensions
FXAQ20PVE / FXAQ25PVE / FXAQ32PVE
Unit (mm)
3D065064A
200 FXAQ-P
EDIN341424 Dimensions
FXAQ40PVE / FXAQ50PVE
Unit (mm)
3D065065A
12
FXAQ-P 201
Dimensions EDIN341424
FXAQ63PVE
Unit (mm)
3D065066A
202 FXAQ-P
EDIN341424 Piping Diagrams
3. Piping Diagrams
4D034245H
FXAQ-P 203
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXAQ20PVE / FXAQ25PVE / FXAQ32PVE / FXAQ40PVE / FXAQ50PVE / FXAQ63PVE
3D076498
204 FXAQ-P
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXAQ20PVE / FXAQ25PVE / FXAQ32PVE / FXAQ40PVE / FXAQ50PVE / FXAQ63PVE
12
4D077066
FXAQ-P 205
Safety Devices Setting EDIN341424
206 FXAQ-P
EDIN341424 Capacity Tables
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.5 1.8 1.7 2.1 1.9 2.2 1.9 2.2 1.8 2.3 1.8 2.3 1.8
25 1.9 1.7 2.3 2.0 2.6 2.2 2.8 2.2 2.8 2.1 2.9 2.1 3.0 2.0
32 2.4 2.0 2.9 2.3 3.4 2.6 3.6 2.6 3.6 2.5 3.7 2.5 3.8 2.4
FXAQ-P
40 3.0 2.7 3.6 3.1 4.2 3.4 4.5 3.5 4.6 3.4 4.7 3.3 4.8 3.0
50 3.8 3.2 4.5 3.7 5.2 4.1 5.6 4.2 5.7 4.2 5.8 4.0 5.9 3.6
63 4.8 4.1 5.7 4.6 6.6 5.1 7.1 5.3 7.2 5.2 7.4 5.0 7.5 4.5
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
12
VRV system satisfies the required heat load.
2. shows rated condition.
FXAQ-P 207
Sound Levels EDIN341424
8. Sound Levels
Overall
dB(A)
Sound pressure level
Model 220-240/220V, 50/60Hz
H L
FXAQ20PVE 35 31
FXAQ25PVE 36 31
FXAQ32PVE 38 31
FXAQ40PVE 39 34
FXAQ50PVE 42 37
FXAQ63PVE 47 41
208 FXAQ-P
EDIN341424 Recommended Mounting-plate Retention Spots and Dimensions
20 21.5
37.5
outline of mounting plate
40
8.5 13 Temporary hole for fixing
109
171
outline of unit
20 20 20 20
245.5
268
290
Center of unit
30 30
Gas pipe
Liquid pipe
5 3 3 5
φ6 φ6
20
6 3 6
44.5
44.5
44.5
44.5
Drain hose position 89 Drain hose position
60 75 54 26 98
20 153 When fixing a unit with screw fix
the mounting plate with screw
Shanghai ARAI
12
C: 1P079690C
30.5
33.5
8
78.5
71.5
71.5
72.5
Use tape
78.5
83.5
80
88.5
0
–1
102
96.5
0
3
59±1 8 59 –1 8
110.5
measure
112.5±0.6
130.5
134.5
150
16
as shown.
183.6
6
197
14
44
16±0.8
79
8
11 6 6
Position the
end of tape
measure at ∇.
8 8
12 12
φ80 φ80
1.5
55
64
38
0
371 –1.5 225.5
+1
290 0
A Mounting plate
C: 2P095003D
FXAQ-P 209
Accessories EDIN341424
10. Accessories
10.1 Optional Accessories (for Unit)
Model
Item
FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
Drain pump kit K-KDU572EVE
210 FXAQ-P
EDIN341424
FXLQ-MA / FXNQ-MA
Floor Standing Type /
Concealed Floor Standing Type
1. Specifications ......................................................................................212
1.1 FXLQ-MA .............................................................................................212
1.2 FXNQ-MA.............................................................................................214
2. Dimensions .........................................................................................216
2.1 FXLQ-MA .............................................................................................216
2.2 FXNQ-MA.............................................................................................219
3. Piping Diagrams..................................................................................222
4. Wiring Diagrams..................................................................................223
5. Electric Characteristics........................................................................224
6. Safety Devices Setting ........................................................................225
7. Capacity Tables ..................................................................................226
7.1 Cooling Capacity ..................................................................................226
7.2 Heating Capacity ..................................................................................226
8. Sound Levels ......................................................................................227
9. Centre of Gravity .................................................................................229
10.Accessories.........................................................................................230
10.1 Optional Accessories (for Unit).............................................................230
10.2 Optional Accessories (for Controls)......................................................230
13
1. Specifications
1.1 FXLQ-MA
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
1.2 FXNQ-MA
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
Btu/h=kW×3412
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. cfm=m³/min×35.3
4. Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m. During actual operation, these values
are normally somewhat higher as a result of ambient conditions.
5. Refer to Electric Characteristics for the power input.
20 OR MORE
100 OR MORE 100 OR MORE DISCHARGE
1750 OR MORE
FRONT FACE
1000 OR MORE
FXLQ-MA
SUCTION
2. Dimensions
BASE
REQUIRED INSTALLATION SPACE
FXLQ20MAVE / FXLQ25MAVE
1000 222
PERFORATED HOLE FOR PIPING 143
172 15 590 149 (REAR) 88
192
1
600
65
575
2
391
3
301
233
4-12×30 SLOT HOLE
181
70
HOLE FOR REAR MOUNTING
10 42 10 5
156
219 219 13 209 2
184
194
2 GAS PIPE CONNECTION PORT φ12.7 FLARE CONNECTION
102 3 DRAIN PIPE CONNECTION PORT O. D. 21
10
PERFORATED HOLE FOR PIPING 4 SWITCH BOX
WIRING HOLE
(BOTTOM) (BOTTOM) 5 AIR FILTER
C: 3D038860B
Unit (mm)
EDIN341424
FXLQ-MA / FXNQ-MA
EDIN341424
20 OR MORE
100 OR MORE 100 OR MORE
DISCHARGE
1750 OR MORE
FXLQ-MA / FXNQ-MA
FRONT FACE
1000 OR MORE
SUCTION
BASE
REQUIRED INSTALLATION SPACE
FXLQ32MAVE / FXLQ40MAVE
1140 222
PERFORATED HOLE FOR PIPING 143
172 15 730 149 (REAR) 88
192
1
600
65
575
2
391
3
301
233
4-12×30 SLOT HOLE
181
70
HOLE FOR REAR MOUNTING
10 42 10 5
156
219 219 13 209 2
184
194
1 LIQUID PIPE CONNECTION PORT φ6.4 FLARE CONNECTION
102
10
WIRING HOLE PERFORATED HOLE FOR PIPING 3 DRAIN PIPE CONNECTION PORT O. D. 21
(BOTTOM) (BOTTOM)
4 SWITCH BOX
5 AIR FILTER
C: 3D038861B
Unit (mm)
217
Dimensions
13
218
Dimensions
20 OR MORE
100 OR MORE 100 OR MORE
DISCHARGE
1750 OR MORE
FRONT FACE
1000 OR MORE
SUCTION
BASE
REQUIRED INSTALLATION SPACE
FXLQ50MAVE / FXLQ63MAVE
192
1
600
65
575
2
391
3
301
233
4-12×30 SLOT HOLE
181
10 42 10 5
156
219 219 13 209 2
184
194
2 GAS PIPE CONNECTION FLARE CONNECTION
102
10
WIRING HOLE PERFORATED HOLE FOR PIPING 4 SWITCH BOX
(BOTTOM) (BOTTOM)
5 AIR FILTER
C: 3D038862B
Unit (mm)
EDIN341424
FXLQ-MA / FXNQ-MA
2.2
EDIN341424
20 OR MORE
TOP PLATE 2-12×18 SLOT HOLE
FXLQ-MA / FXNQ-MA
HOLE FOR FIXING 150 OR MORE
FXNQ-MA
FRONT FACE
42
1000 OR MORE
130
FXNQ20MAVE / FXNQ25MAVE
35
(DISCHARGE FLANGE) 199 562 163
(DISCHARGE FLANGE) 218
620 139
5x100=500 6-φ4.7 HOLE 84
TOTAL ON FRONT & REAR 65 74 2-φ4.7 HOLE
TOTAL ON RIGHT & LEFT
11
25
192
1
389
609
2
391
3
42
301
4-12×30 SLOT HOLE
181
233
129
HOLE FOR REAR MOUNTING
3D038863B
Unit (mm)
219
Dimensions
13
220
Dimensions
20 OR MORE
TOP PLATE 2-12×18 SLOT HOLE
HOLE FOR FIXING 150 OR MORE
736 TO THE FLOOR
FRONT FACE
42
1000 OR MORE
FXNQ32MAVE / FXNQ40MAVE
130
REQUIRED INSTALLATION SPACE
35
(DISCHARGE FLANGE) 199 702 163
218
(DISCHARGE FLANGE)
760 139
6×100=600 7-φ4.7 HOLE 84
TOTAL ON FRONT & REAR 65 74 2-φ4.7 HOLE
TOTAL ON RIGHT & LEFT
11
25
192
1
389
609
2
3
391
301
42
4-12×30 SLOT HOLE
181
233
129
730 65 LEVEL ADJUSTING SCREW
AS STANDARD ACCESSORY 103
4×M6 152
HOLE FOR FIXING 206 7
TO THE FLOOR
4 5
NUMBER NAME DESCRIPTION
1 LIQUID PIPE CONNECTION PORT φ6.4 FLARE CONNECTION
2 GAS PIPE CONNECTION PORT φ12.7 FLARE CONNECTION
3 DRAIN PIPE CONNECTION PORT O. D. 21
NOTE) 4 SWITCH BOX
1. LOCATION OF UNIT'S NAME PLATE: 5 AIR FILTER
THE RIGHT LOWER CORNER OF FRONT PLATE.
3D038864C
Unit (mm)
EDIN341424
FXLQ-MA / FXNQ-MA
EDIN341424 Dimensions
3D038865C
13
3. Piping Diagrams
4D034245H
4. Wiring Diagrams
FXLQ20MAVE / FXLQ25MAVE / FXLQ32MAVE / FXLQ40MAVE / FXLQ50MAVE / FXLQ63MAVE
FXNQ20MAVE / FXNQ25MAVE / FXNQ32MAVE / FXNQ40MAVE / FXNQ50MAVE / FXNQ63MAVE
C: 3D039826G
13
5. Electric Characteristics
FXLQ20MAVE / FXLQ25MAVE / FXLQ32MAVE / FXLQ40MAVE / FXLQ50MAVE / FXLQ63MAVE
FXNQ20MAVE / FXNQ25MAVE / FXNQ32MAVE / FXNQ40MAVE / FXNQ50MAVE / FXNQ63MAVE
C: 4D034579E
13
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.3 1.8 1.5 2.1 1.7 2.2 1.7 2.2 1.6 2.3 1.5 2.3 1.4
25 1.9 1.6 2.3 1.8 2.6 2.0 2.8 2.1 2.8 2.0 2.9 1.9 3.0 1.8
FXLQ-MA 32 2.4 1.9 2.9 2.2 3.4 2.5 3.6 2.5 3.6 2.3 3.7 2.3 3.8 2.2
FXNQ-MA 40 3.0 2.5 3.6 2.7 4.2 3.1 4.5 3.1 4.6 3.1 4.7 3.0 4.8 2.8
50 3.8 3.0 4.5 3.4 5.2 3.8 5.6 3.9 5.7 3.9 5.8 3.7 5.9 3.4
63 4.8 3.7 5.7 4.2 6.6 4.8 7.1 4.9 7.2 4.7 7.4 4.5 7.5 4.1
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
8. Sound Levels
Overall
Location of microphone (for sound pressure level) Location of microphone (for sound pressure level)
grille
dB(A) dB(A)
Sound pressure level Sound pressure level
Model 220V, 50/60Hz 240V, 50Hz Model 220V, 50/60Hz 240V, 50Hz
H L H L H L H L
FXLQ20MAVE FXNQ20MAVE
FXLQ25MAVE 35 32 37 34 FXNQ25MAVE 35 32 37 34
FXLQ32MAVE FXNQ32MAVE
FXLQ40MAVE 38 33 40 35 FXNQ40MAVE 38 33 40 35
FXLQ50MAVE 39 34 41 36 FXNQ50MAVE 39 34 41 36
FXLQ63MAVE 40 35 42 37 FXNQ63MAVE 40 35 42 37
Notes:
1. The operating conditions are assumed to be standard (JIS conditions).
2. These operating values were obtained in anechoic chamber (conversion values).
Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of
the particular room in which the equipment installed. 13
FXLQ50MAVE FXLQ63MAVE
4D034566A 4D034567A
FXNQ50MAVE FXNQ63MAVE
4D034537B 4D034538B
9. Centre of Gravity
C: 4D034527C
C: 4D034533C
10. Accessories
10.1 Optional Accessories (for Unit)
Model
Item FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE
Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
C: 4D034574B
FXVQ-M
Floor Standing Duct Type
1. Specifications ......................................................................................232
2. Dimensions .........................................................................................234
3. Piping Diagrams..................................................................................239
4. Wiring Diagrams..................................................................................240
5. Electric Characteristics........................................................................242
6. Safety Devices Setting ........................................................................243
7. Capacity Tables ..................................................................................244
7.1 Cooling Capacity ..................................................................................244
7.2 Heating Capacity ..................................................................................244
8. Fan Characteristics .............................................................................245
9. Fan Characteristics (For Pulley Selection)..........................................248
9.1 Pulley Selection....................................................................................248
9.2 Fan Motor Specifications......................................................................251
9.3 How to Select Motor Pulley ..................................................................251
9.4 Pulley and Fan Belt Adjustment ...........................................................252
9.5 V Belt Size Table..................................................................................255
10.Sound Levels ......................................................................................256
11.Centre of Gravity .................................................................................257
12.Accessories.........................................................................................258
12.1 Optional Accessories (for Unit) ............................................................258
12.2 Optional Accessories (for Control) .......................................................258
13.Dimensions of Optional Accessories...................................................259
14.Data and Notice in Using the Outdoor-Air Processing Mode ..............262 14
FXVQ-M 231
Specifications EDIN341424
1. Specifications
Floor standing duct type
Model FXVQ125MY1 FXVQ200MY1 FXVQ250MY1
Power supply 3 phase, 380-415V, 50Hz 3 phase, 380-415V, 50Hz 3 phase, 380-415V, 50Hz
kcal/h 12,000 19,300 24,100
1 3 Cooling capacity Btu/h 47,800 76,400 95,500
kW 14.0 22.4 28.0
kcal/h 13,800 21,500 27,100
2 3 Heating capacity Btu/h 54,600 85,300 107,000
kW 16.0 25.0 31.5
Casing / Colour Ivory white (5Y7.5/1) Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,670×750×510 1,670×950×510 1,670×1,170×510
Coil (Cross Rows×Stages×Fin pitch mm 3×32×2.0 3×32×2.0 3×32×2.0
fin coil) Face area m² 0.419 0.560 0.715
Model D13/4G2BM3 D13/4G3AK3 2D13/4G2CG4
Type Sirocco fan Sirocco fan Sirocco fan
Motor output × W 750×1 1,500×1 1,500×1
Number of units
Fan m³/min 43 69 86
Airflow rate
cfm 1,518 2,436 3,036
4 External static Pa 150 210 270
pressure
Drive Belt drive Belt drive Belt drive
Temperature control Microprocessor thermostat for cooling Microprocessor thermostat for cooling Microprocessor thermostat for cooling
and heating and heating and heating
Long life Long life Long life
Air filter
(Resin net with
mould resistance ) (Resin net with
mould resistance ) ( Resin net with
mould resistance )
Liquid pipes mm φ9.5 (Brazing connection) φ9.5 (Brazing connection) φ9.5 (Brazing connection)
5 Piping Gas pipes mm φ15.9 (Brazing connection) φ19.1 (Brazing connection) φ22.2 (Brazing connection)
connections
Drain pipe Rp1 (PS1B internal thread) Rp1 (PS1B internal thread) Rp1 (PS1B internal thread)
Mass kg 115 140 165
6 Sound pressure level dB(A) 52 55 59
Safety devices Fuse, Overcurrent relay Fuse, Overcurrent relay Fuse, Overcurrent relay
Refrigerant control Electronic expansion valve Electronic expansion valve Electronic expansion valve
Connection pipe. Drain plug cap. Connection pipe. Drain plug cap. Connection pipe. Drain plug cap.
Standard accessories Insulation for drain plug. Clamp. Bolt. Insulation for drain plug. Clamp. Bolt. Insulation for drain plug. Clamp. Bolt.
Nut. Operation manual. Installation Nut. Operation manual. Installation Nut. Operation manual. Installation
manual. manual. manual.
Drawing No. C: 3D085648
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4. The value is the external static pressure with standard pulley.
5. Both liquid pipe and gas pipe need insulation work.
6. Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
7. Refer to Electric Characteristics for the power input.
232 FXVQ-M
EDIN341424 Specifications
Notes:
Conversion formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
cfm=m³/min×35.3
4.
5.
The value is the external static pressure with standard pulley.
Both liquid pipe and gas pipe need insulation work. 14
6. Sound level : measured when the air discharge outlet duct (2 m) is attached (anechoic chamber conversion value).
It increases by approximately 5 dB(A) when the plenum chamber is installed to deliver direct airflow.
7. Refer to Electric Characteristics for the power input.
FXVQ-M 233
Dimensions EDIN341424
2. Dimensions
FXVQ125MY1
Unit (mm)
3D081764A
234 FXVQ-M
EDIN341424 Dimensions
FXVQ200MY1
Unit (mm)
3D081765A
14
FXVQ-M 235
Dimensions EDIN341424
FXVQ250MY1
Unit (mm)
3D081766A
236 FXVQ-M
EDIN341424 Dimensions
FXVQ400MY1
Unit (mm)
3D081767A
14
FXVQ-M 237
Dimensions EDIN341424
FXVQ500MY16
Unit (mm)
3D085649
238 FXVQ-M
EDIN341424 Piping Diagrams
3. Piping Diagrams
FXVQ125MY1 / FXVQ200MY1 / FXVQ250MY1
4D081333A
FXVQ400MY1 / FXVQ500MY16
14
4D081334A
Refrigerant pipe connection port diameters
(mm)
Model Gas Liquid
FXVQ400MY1 φ28.6 φ12.7
FXVQ500MY16 φ28.6 φ15.9
FXVQ-M 239
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXVQ125MY1 / FXVQ200MY1 / FXVQ250MY1
3D084086B
240 FXVQ-M
EDIN341424 Wiring Diagrams
FXVQ400MY1 / FXVQ500MY16
3D084089B
14
FXVQ-M 241
Electric Characteristics EDIN341424
5. Electric Characteristics
FXVQ125MY1 / FXVQ200MY1 / FXVQ250MY1 / FXVQ400MY1 / FXVQ500MY16
C: 4D085660
242 FXVQ-M
EDIN341424 Safety Devices Setting
14
FXVQ-M 243
Capacity Tables EDIN341424
7. Capacity Tables
7.1 Cooling Capacity
Indoor air temp.
Capacity 14.0°CWB 16.0°CWB 18.0°CWB 19.0°CWB 20.0°CWB 22.0°CWB 24.0°CWB
Model
indication 20.0°CDB 23.0°CDB 26.0°CDB 27.0°CDB 28.0°CDB 30.0°CDB 32.0°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
125 9.4 8.8 11.3 9.8 13.1 10.8 14.0 10.9 14.2 10.5 14.5 9.8 14.9 9.1
200 15.1 13.8 18.0 15.2 20.9 16.7 22.4 16.9 22.7 16.4 23.2 15.3 23.8 14.1
FXVQ-MY1
250 18.9 17.0 22.5 18.9 26.2 20.8 28.0 21.2 28.3 20.4 29.0 19.1 29.7 17.6
400 30.4 27.4 36.2 30.5 42.1 33.5 45.0 34.1 45.5 33.0 46.6 30.9 47.7 28.7
FXVQ-MY16 500 37.8 35.4 45.1 39.6 52.4 43.6 56.0 44.7 56.7 42.9 58.0 40.1 59.4 37.6
Notes: 1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV system satisfies the required heat load.
2. shows rated condition.
CA13A279A
244 FXVQ-M
EDIN341424 Fan Characteristics
8. Fan Characteristics
FXVQ125MY1
4D084918A
FXVQ200MY1
14
4D084919A
FXVQ-M 245
Fan Characteristics EDIN341424
FXVQ250MY1
4D084920A
FXVQ400MY1
4D084921B
246 FXVQ-M
EDIN341424 Fan Characteristics
FXVQ500MY16
4D084924A
14
FXVQ-M 247
Fan Characteristics (For Pulley Selection) EDIN341424
FXVQ125MY1
4D084342A
FXVQ200MY1
4D084343A
248 FXVQ-M
EDIN341424 Fan Characteristics (For Pulley Selection)
FXVQ250MY1
4D084344A
FXVQ400MY1
14
4D084345A
FXVQ-M 249
Fan Characteristics (For Pulley Selection) EDIN341424
FXVQ500MY16
4D084927A
250 FXVQ-M
EDIN341424 Fan Characteristics (For Pulley Selection)
2. Shaft length Q 40 50 60 60 80
5. Insulation class E E E E B
Type A and
V Pulley 2. Keyway b 6 8 8 8 10
type B
Lp (D2 – D1)2
Lp = 2C + 1.57 (D1 + D2) +
4C
D1 D2
Lp : Effective Center Periphery Length (mm)
D1 : Pitch Diameter of Motor Pulley (mm)
D2 : Pitch Diameter of Fan Pulley (mm)
C C : Distance between the shafts of the pulleys (mm)
Note: The unit of V belt length (Nominal number) is usually shown in "inch".
FXVQ-M 251
Fan Characteristics (For Pulley Selection) EDIN341424
Pulley Specification
3B • 291---- 42
Boss inner diameter The pulley makers give the pulley
(motor shaft diameter: mm) size using the pitch diameter, while
Daikin uses the pulley outer
Pulley outer diameter diameter.
B type pulley Takes 3 belts
Pitch Diameter (the actual diameter of the parts in contact with the belt)
The pulley makers often use the pitch diameter in pulley sizes.
When using air conditioners in duct connection, external static pressure and airflow rate will increase, exceeding the
range of use for standard motors and pulleys. Therefore, it is necessary to change the motor or pulley to deal with
this.
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling
work.
Fan pulley
Motor pulley
Motor pulley
Fixing nut
(B)
Fixing nut
(A)
Parallelism criteria (K)
Less than 10 arc-minutes
(discrepancies of 3mm per 1m)
252 FXVQ-M
EDIN341424 Fan Characteristics (For Pulley Selection)
Tension of V belt
• Tension of a V belt must meet the deflection load (W) as shown.
Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below.
C
L Deflection load
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley. 14
2) Measure the tension of the fan belt.
2. Make adjustments
1) Sucure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing nuts (A) (B).
2) Adjust the fan belt tension with adjustment nut (C).
3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.
FXVQ-M 253
Fan Characteristics (For Pulley Selection) EDIN341424
Motor pulley
Tension of V belt
• Tension of a V belt must meet the deflection load (W) as shown.
Calculate the required deflection length (L) by the equation (1), its tolerance must be within the range as below.
W
C
L Deflection load
Model V belt Number of belts Motor output Motor pulley diameter (mm) Deflection load W (N) per
(kW) single V belt
1 2.2 Any size 19.0~20.9
1 3.7 ~136 30.0~33.0
FXVQ400 / 500 Type B 1 3.7 143~161 25.4~27.9
1 3.7 171~ 21.1~23.2
2 3.7, 5.5 Any size 19.0~20.9
Note:
• When the new belt is used, adjust the tension to about 1.15 times the deflection load (W) shown above.
• When the belt has adopted to the pulley (after operating about 50 hours), adjust the tension to the load shown
above.
(Even if the adjustments are made on a new belt, check the load again as shown on the above table after the belt
has adopted.)
• With or without replacing the pulley, check the deflection load when about 50 hours passed after the test
operation.
• After replacing belt or pulley, conduct the test operation and check if there is no abnormal noise or vibration.
Refer to the JIS B 1854 (Pulley) and JIS K 6323 (V belt) for details. (JIS: Japanese Industrial Standards)
1. Take measurements
1) Measure the parallelism of the fan pulley and motor pulley.
2) Measure the tension of the fan belt.
254 FXVQ-M
EDIN341424 Fan Characteristics (For Pulley Selection)
2. Make adjustments
1) Secure the pulley parallelism by adjustment of the motor pulley position and adjustment of fixing bolt (A).
2) Adjust the fan belt tension by loosening fixing bolt (A) and using adjustment nut (B), (C).
Adjustment Adjustment
nut (C) nut (B)
3. Perform checks
1) Check that the pulley parallelism and the fan belt tension are within the criteria.
FXVQ-M 255
Sound Levels EDIN341424
dB(A)
Sound pressure level
Model
380-415V, 50Hz
FXVQ125MY1 52
FXVQ200MY1 55
FXVQ250MY1 59
FXVQ400MY1 64
FXVQ500MY16 67
FXVQ400MY1 FXVQ500MY16
4D085654 4D085656
256 FXVQ-M
EDIN341424 Centre of Gravity
14
C: 4D085650
FXVQ-M 257
Accessories EDIN341424
12. Accessories
12.1 Optional Accessories (for Unit)
Model
FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY16
Item
Replacement long life filter KAFJ261L140 KAFJ261L224 KAFJ261L280 KAFJ261M450 KAFJ261M560
Ultra long-life filter — KAFSJ9A400 KAFSJ9A560
Front suction base flange KD-9A140 KD-9A200 KD-9A280 KD-9A400 KD-9A560
Suction grille KDGF-9A140 KDGF-9A200 KDGF-9A280 KDGF-9A400 KDGF-9A560
Replacement long-life
KAF-91A140 KAF-91A200 KAF-91A280 KAF-91A400 KAF-91A560
filter 1, 2, 3
Front suction
filter chamber Filter Colorimetric
for high chamber method 65% KAF-92A140 KAF-92A200 KAF-92A280 KAF-92A400 KAF-92A560
Option for Replacement
discharge efficiency filter for high high 1, 3
efficiency
and filter efficiency Colorimetric
suction filter method 90% KAF-93A140 KAF-93A200 KAF-93A280 KAF-93A400 KAF-93A560
1, 2
2, 3
Filter chamber 1, 2 KDDF-9A140 KDDF-9A200 KDDF-9A280 KDDF-9A400 KDDF-9A560
Prenum chamber KPCJ140A KPC5J KPC8J KPCJ400A KPC15JA
Pulley for plenum chamber KPP8JA KPP9JA KPP10JA — 4
Discharge grill for plenum side KD101A10 KD101A20
Fresh air intake kit KD106D10 KDFJ906A560
Rear suction kit KDFJ905A140 KDFJ905A200 KDFJ905A280 KDFJ905A400 KDFJ905A560
Wood base KKWJ9A140 KWF1G5P KWF1G8P KKWJ9A400 KWF1G15
Vibration isolating frame K-ABSG1406A K-ABSG1407A K-ABSG1408A K-ABSG1409A K-ABSG1410A
C: 3D085669C
Notes:
1. When ordering a filter chamber for high efficiency filter (colorimetric method 65%), please order with all the
respective parts.
2. When ordering a filter chamber for high efficiency filter (colorimetric method 90%), please order with all the
respective parts.
3. When replacing with a new filter, please order the replacement filters with the corresponding filter model name.
4. The pulley and V belt are field supply.
Specification
Pulley V belt
FXVQ400MY1 B151 B40
FXVQ500MY16 B143 B40
258 FXVQ-M
EDIN341424 Dimensions of Optional Accessories
3D083638A
14
3D083639A
FXVQ-M 259
Dimensions of Optional Accessories EDIN341424
3D083640A
3D083641A
260 FXVQ-M
EDIN341424 Dimensions of Optional Accessories
3D085670
14
FXVQ-M 261
Data and Notice in Using the Outdoor-Air Processing Mode EDIN341424
- The combination with an outdoor unit is limited to one indoor unit and one set of outdoor unit (including multiple
connection of outdoor units). The connection of multiple floor standing duct units is prohibited. Connection of floor
standing duct units and other type of indoor units mixed together is prohibited.
• When the outdoor-air processing mode is selected, the airflow range is limited. If the airflow exceeds the specified range,
the product may stop abnormally. On the other hand, if the airflow falls below the specified range, the equipment
reliability may decrease. For details, please see the " Airflow range" section.
• When the outdoor-air processing mode is selected, the machine controls the operation so that the temperature of the
discharge air becomes closer to the preset temperature of the control panel. However, if the air-conditioning load is too
large or too small, the discharge air temperature may not become closer to the preset temperature.
Airflow range
Please set the airflow according to each operation mode. When selecting a pulley, please see "Fan characteristics (For Pully
Selection)".
Airflow range (m3/min); The value in ( ) is the rated airflow.
Operation mode
FXVQ125MY1 FXVQ200MY1 FXVQ250MY1 FXVQ400MY1 FXVQ500MY16
Standard operation mode 28 - 50 (43) 42 - 76 (69) 63 - 96 (86) 80 - 144 (134) 120 - 200 (172)
Outdoor-air processing mode 25 - 29 (27) 38 - 44 (41) 48 - 56 (52) 72 - 85 (78) 99 - 116 (107)
CJ: CA13A209
Operation limits
262 FXVQ-M
EDIN341424 Data and Notice in Using the Outdoor-Air Processing Mode
Field settings
[In case of VRV IV]
Be sure to set from both (a) Field settings from the indoor unit and (b) Field settings from the outdoor unit.
3. Push the confirmation button (BS3). The present settings of [4.] will be
indicated.
4. Push the operation button (BS2) and adjust the 7 segment "Invalid" (factory set) light off light off 0
display to the figure shown in the right. "Valid" light off light off 1
5. Push the confirmation button (BS3). The setting in [4.] is defined. It will turn to light ON.
The system starts the operation
6. Push the confirmation button (BS3) again. according to the setting. 2 0 0
7. Push the new page button (BS1). Returned to Normal mode. light off light off light off
FXVQ-M 263
Data and Notice in Using the Outdoor-Air Processing Mode EDIN341424
Capacity characteristics
Capacity
JC: CA13A209
264 FXVQ-M
EDIN341424
Part 3
FXMQ-MF
Outdoor-Air Processing
Unit
1. Specifications ......................................................................................266
2. Dimensions .........................................................................................267
2.1 Indoor Units ..........................................................................................267
2.2 Dimensions with Option........................................................................269
3. Piping Diagrams..................................................................................271
4. Wiring Diagrams..................................................................................272
5. Electric Characteristics........................................................................273
6. Safety Devices Setting ........................................................................274
7. Capacity Tables ..................................................................................275
8. Operation Limits ..................................................................................278
9. Fan Performances...............................................................................280
10.Sound Levels ......................................................................................282
11.Centre of Gravity .................................................................................283
12.Accessories.........................................................................................284
12.1 Optional Accessories (for Unit).............................................................284
12.2 Optional Accessories (for Operation Controls).....................................284
15
FXMQ-MF 265
Specifications EDIN341424
1. Specifications
Model FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Power Supply 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz 1 phase, 220-240V, 50Hz
kcal/h 12,000 19,300 24,100
1 3 Cooling Capacity Btu/h 47,800 76,400 95,500
kW 14.0 22.4 28.0
kcal/h 7,700 12,000 15,000
2 3 Heating Capacity Btu/h 30,400 47,400 59,400
kW 8.9 13.9 17.4
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 470×744×1,100 470×1,380×1,100 470×1,380×1,100
Rows×Stages×Fin mm 3×26×2.0 3×26×2.0 3×26×2.0
Coil (Cross Pitch
Fin Coil)
Face Area m² 0.28 0.65 0.65
Model D13/4G2DA1 D13/4G2DA1 D13/4G2DA1
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × W 380×1 380×1 380×1
Number of Units
m³/min 18 28 35
Fan Airflow Rate (H/L) l/s 300 466 583
cfm 635 988 1,236
External 220V, 50Hz 185 225 205
Static Pa
Pressure 240V, 50Hz 225 275 255
Drive Direct Drive Direct Drive Direct Drive
Temperature Control Microprocessor Thermostat for Microprocessor Thermostat for Microprocessor Thermostat for
Cooling and Heating Cooling and Heating Cooling and Heating
Sound Absorbing Thermal Insulation Material Glass Fiber Glass Fiber Glass Fiber
Air Filter 4 4 4
Liquid Pipes mm φ9.5 (Flare Connection) φ9.5 (Flare Connection) φ9.5 (Flare Connection)
Piping Gas Pipes mm φ15.9 (Flare Connection) φ19.1 (Brazing Connection) φ22.2 (Brazing Connection)
Connections
Drain Pipe mm PS1B (female thread) PS1B (female thread) PS1B (female thread)
Mass kg 86 123 123
5 Sound Pressure 220V, 50Hz 42 47 47
Level dB(A)
240V, 50Hz 43 48 48
Notes:
Conversion Formulae
1. Nominal cooling capacities are based on the following conditions:
Outdoor temperature: 33°CDB, 28°CWB (68% RH) kcal/h=kW×860
Btu/h=kW×3412
Discharge set temp.: 18°CDB cfm=m³/min×35.3
Equivalent ref. piping: 7.5m (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Outdoor temperature: 0°CDB, –2.9°CWB (50% RH)
Discharge set temp.: 25°CDB
Equivalent ref. piping: 7.5m (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. Air filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
5. Anechoic chamber conversion value, measured at a point 1.5m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
6. Refer to Electric Characteristics for the power input.
266 FXMQ-MF
EDIN341424 Dimensions
2. Dimensions
2.1 Indoor Units
FXMQ125MFV1
Unit (mm)
3D045129B
15
FXMQ-MF 267
Dimensions EDIN341424
FXMQ200MFV1 / FXMQ250MFV1
Unit (mm)
3D045128B
268 FXMQ-MF
2.2
FXMQ-MF
EDIN341424
FXMQ125MFV1
20 - φ4.7 HOLE
1148 (All around)
1 2 300 or less
(0~250)
360
330
685
744
3 × 100=300
222~472
250
5 × 100=500
222
20 - φ7 hole 5 × 100=500 8
Dimensions with Option
A View
650 or more
690 or more
(Service space)
(Service space)
Approx.
300
Inspection hole 600 or more
16 - φ8 HOLE
(All around)
1100 285 3 4
744
529 79
456
7 Water supply port
3 × 100=300
222
6 Drain pipe connection (drain pump kit) VP25(O. D φ32, I. D φ25)
5 Drain pump kit Built-in
8
5 × 100=500
223
C: 3D046155
Unit (mm)
269
Dimensions
15
270
Dimensions
32 - φ4.7 HOLE
1148 (All around)
1 2
300 or less
(0~250)
1296
360
330
1380
FXMQ200MFV1 / FXMQ250MFV1
3 × 100=300
222~472
250
222
11 × 100=1100
32 - φ7 hole 11 × 100=1100 8
(All around) 1200
1230
A View
650 or more
690 or more
(Service space)
(Service space)
Approx.
300
Inspection hole 600 or more
16 - φ8 HOLE
(All around)
1100 285 3 4
1380
529 79
A
200
330
360
456
8 Drain hose Attached to Drain pump kit
3 × 100=300
222
7 Water supply port
6 Drain pipe connection (drain pump kit) VP25 (O. D φ32, I. D φ25)
8
223
C: 3D046154
Unit (mm)
EDIN341424
FXMQ-MF
EDIN341424 Piping Diagrams
3. Piping Diagrams
FXMQ125MFV1 / FXMQ200MFV1 / FXMQ250MFV1
4D018650D
15
FXMQ-MF 271
Wiring Diagrams EDIN341424
4. Wiring Diagrams
FXMQ125MFV1 / FXMQ200MFV1 / FXMQ250MFV1
C: 3D044996E
272 FXMQ-MF
EDIN341424 Electric Characteristics
5. Electric Characteristics
FXMQ125MFV1 / FXMQ200MFV1 / FXMQ250MFV1
15
C: 4D046146B
FXMQ-MF 273
Safety Devices Setting EDIN341424
274 FXMQ-MF
EDIN341424 Capacity Tables
7. Capacity Tables
FXMQ125MFV1
15
4D046308D
FXMQ-MF 275
Capacity Tables EDIN341424
FXMQ200MFV1
4D046309D
276 FXMQ-MF
EDIN341424 Capacity Tables
FXMQ250MFV1
15
4D046310D
FXMQ-MF 277
Operation Limits EDIN341424
8. Operation Limits
FXMQ125MFV1
3D046312A
FXMQ200MFV1
3D047750A
278 FXMQ-MF
EDIN341424 Operation Limits
FXMQ250MFV1
3D046313B
15
FXMQ-MF 279
Fan Performances EDIN341424
9. Fan Performances
FXMQ125MFV1
3D046267A
FXMQ200MFV1
3D046266A
280 FXMQ-MF
EDIN341424 Fan Performances
FXMQ250MFV1
3D046265A
15
FXMQ-MF 281
Sound Levels EDIN341424
FXMQ125MFV1 42 43
FXMQ200MFV1 47 48
FXMQ250MFV1 47 48
282 FXMQ-MF
EDIN341424 Centre of Gravity
15
4D046143C
FXMQ-MF 283
Accessories EDIN341424
12. Accessories
12.1 Optional Accessories (for Unit)
Model
Item
FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
Drain pump kit KDU30L250VE
65% KAFJ372L140 KAFJ372L280
High efficiency filter
90% KAFJ373L140 KAFJ373L280
Filter chamber 1 KDJ3705L140 KDJ3705L280
Long life replacement filter KAFJ371L140 KAFJ371L280
C: 3D046270
Notes:
1. Filter chamber has a suction-type flange. (Main unit does not have.)
· Dimensions and weight of the equipment may vary depending on the options used.
· Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
· Some options may not be used in combination.
· Operating sound may increase somewhat depending on the options used.
284 FXMQ-MF
EDIN341424
Part 4
RXYQ-THRY6
Heat Pump 50Hz
High-COP Type
1. Specifications ......................................................................................286
1.1 Heat Pump 50Hz High-COP Type (RXYQ-THRY6) .............................286
2. Dimensions .........................................................................................296
2.1 Combination Unit..................................................................................296
3. Service Space .....................................................................................301
4. Field Wiring .........................................................................................302
5. Electric Characteristics........................................................................304
6. Capacity Tables (High-COP Type)......................................................306
6.1 Cooling Capacity for VRV Indoor Units Only (Te: 6ºC) ........................306
6.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC) ........................326
6.3 Heating Capacity ..................................................................................346
6.4 Capacity Correction Factor...................................................................366
6.5 Notes for Heating Capacity Characteristics (Heat Pump) ....................374
7. Operation Limits ..................................................................................375
8. Sound Levels ......................................................................................376
8.1 Overall ..................................................................................................376
9. Accessories.........................................................................................377
9.1 Optional Accessories............................................................................377
16
RXYQ-THRY6 285
Specifications EDIN341424
1. Specifications
1.1 Heat Pump 50Hz High-COP Type (RXYQ-THRY6)
Model Name (Combination Unit) RXYQ12THRY6(E) RXYQ14THRY6(E)
Model Name (Independent Unit) RXYQ6TRY6(E)+RXYQ6TRY6(E) RXYQ6TRY6(E)+RXYQ8TRY6(E)
Power Supply 3 phase, 380-415V, 50Hz 3 phase, 380-415V, 50Hz
kcal/h 27,500 33,000
1 Cooling Capacity Btu/h 109,000 131,000
kW 32.0 38.4
kcal/h 31,000 37,000
2 Heating Capacity Btu/h 123,000 147,000
kW 36.0 43.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm (1,657×930×765)+(1,657×930×765) (1,657×930×765)+(1,657×930×765)
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Displacement m³/h (16.24)+(16.24) (16.24)+(16.24)
Number of Revolutions r/min (7,668)+(7,668) (7,668)+(7,668)
Comp.
Motor Output×
kW (2.4×1)+(2.4×1) (2.4×1)+(3.4×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW (0.55×1)+(0.55×1) (0.55×1)+(0.55×1)
Fan
Airflow Rate m³/min 119+119 119+157
Drive Direct drive Direct drive
Connecting Liquid Pipe mm φ12.7 C1220T (Brazing connection) φ12.7 C1220T (Brazing connection)
Pipes Gas Pipe mm φ28.6 C1220T (Brazing connection) φ28.6 C1220T (Brazing connection)
Mass kg 185+185 185+185
3 Sound Pressure Level dB(A) 58 59
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Overcurrent relay, Inverter overload protector, Overvoltage Overcurrent relay, Inverter overload protector, Overvoltage
protector protector
Capacity Control % 10-100 10-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 5.9+5.9 5.9+5.9
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Drawing No.
286 RXYQ-THRY6
EDIN341424 Specifications
16
RXYQ-THRY6 287
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
288 RXYQ-THRY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
16
RXYQ-THRY6 289
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
290 RXYQ-THRY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
16
RXYQ-THRY6 291
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
292 RXYQ-THRY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
16
RXYQ-THRY6 293
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
294 RXYQ-THRY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
16
RXYQ-THRY6 295
Dimensions EDIN341424
2. Dimensions
2.1 Combination Unit
3D088931
296 RXYQ-THRY6
EDIN341424 Dimensions
3D088934
16
RXYQ-THRY6 297
Dimensions EDIN341424
RXYQ34THRY6 / RXYQ38THRY6
Unit (mm)
3D089374
298 RXYQ-THRY6
EDIN341424 Dimensions
RXYQ36THRY6 / RXYQ40THRY6
Unit (mm)
3D089381
16
RXYQ-THRY6 299
Dimensions EDIN341424
3D088933
300 RXYQ-THRY6
EDIN341424 Service Space
3. Service Space
RXYQ12THRY6 / RXYQ14THRY6 / RXYQ16THRY6 / RXYQ18THRY6 / RXYQ20THRY6 / RXYQ22THRY6 /
RXYQ24THRY6 / RXYQ26THRY6 / RXYQ28THRY6 / RXYQ30THRY6 / RXYQ32THRY6 / RXYQ34THRY6 /
RXYQ36THRY6 / RXYQ38THRY6 / RXYQ40THRY6 / RXYQ42THRY6 / RXYQ44THRY6 / RXYQ46THRY6 /
RXYQ48THRY6 / RXYQ50THRY6
Unit (mm)
3D084449A
16
RXYQ-THRY6 301
Field Wiring EDIN341424
4. Field Wiring
RXYQ12THRY6 / RXYQ14THRY6 / RXYQ16THRY6
3D084407A
302 RXYQ-THRY6
EDIN341424 Field Wiring
3D084410A
16
RXYQ-THRY6 303
Electric Characteristics EDIN341424
5. Electric Characteristics
RXYQ12THRY6 / RXYQ14THRY6 / RXYQ16THRY6 / RXYQ18THRY6 / RXYQ20THRY6 / RXYQ22THRY6 /
RXYQ24THRY6 / RXYQ26THRY6 / RXYQ28THRY6 / RXYQ30THRY6
3D088898A
304 RXYQ-THRY6
EDIN341424 Electric Characteristics
3D088899A
16
RXYQ-THRY6 305
Capacity Tables (High-COP Type) EDIN341424
306 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 307
Capacity Tables (High-COP Type) EDIN341424
308 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 309
Capacity Tables (High-COP Type) EDIN341424
310 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 311
Capacity Tables (High-COP Type) EDIN341424
312 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 313
Capacity Tables (High-COP Type) EDIN341424
314 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 315
Capacity Tables (High-COP Type) EDIN341424
316 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 317
Capacity Tables (High-COP Type) EDIN341424
318 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 319
Capacity Tables (High-COP Type) EDIN341424
320 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 321
Capacity Tables (High-COP Type) EDIN341424
322 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 323
Capacity Tables (High-COP Type) EDIN341424
324 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 325
Capacity Tables (High-COP Type) EDIN341424
6.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC)
When only VRV indoor units are connected
RXYQ12THRY6 Cooling capacity (Te: 9ºC)
Indoor air temp. (°CWB) Indoor air temp. (°CWB)
Combina- Outdoor Combina- Outdoor
tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0
(Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI (Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
index) °CDB kW kW index) °CDB kW kW
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 18.6 2.05 23.2 2.59 29.4 3.37 32.4 3.77 35.4 4.19 40.3 4.77 41.4 4.56 10 11.4 1.31 14.3 1.59 18.1 1.99 19.9 2.20 21.8 2.42 25.5 2.88 29.1 3.34
12 18.6 2.08 23.2 2.63 29.4 3.43 32.4 3.84 35.4 4.27 39.8 4.74 40.8 4.53 12 11.4 1.33 14.3 1.61 18.1 2.02 19.9 2.24 21.8 2.46 25.5 2.93 29.1 3.40
14 18.6 2.12 23.2 2.68 29.4 3.50 32.4 3.92 35.4 4.35 39.2 4.72 40.3 4.56 14 11.4 1.35 14.3 1.63 18.1 2.06 19.9 2.28 21.8 2.51 25.5 2.98 29.1 3.46
16 18.6 2.15 23.2 2.73 29.4 3.56 32.4 3.99 35.4 4.43 38.7 4.75 39.8 4.80 16 11.4 1.37 14.3 1.66 18.1 2.09 19.9 2.32 21.8 2.55 25.5 3.04 29.1 3.53
18 18.6 2.19 23.2 2.78 29.4 3.64 32.4 4.07 35.4 4.57 38.2 4.99 39.3 5.05 18 11.4 1.38 14.3 1.69 18.1 2.13 19.9 2.36 21.8 2.60 25.5 3.10 29.1 3.60
20 18.6 2.23 23.2 2.83 29.4 3.73 32.4 4.29 35.4 4.91 37.7 5.24 38.8 5.29 20 11.4 1.41 14.3 1.71 18.1 2.17 19.9 2.41 21.8 2.65 25.5 3.16 29.1 3.68
21 18.6 2.25 23.2 2.86 29.4 3.86 32.4 4.45 35.4 5.08 37.4 5.36 38.5 5.42 21 11.4 1.42 14.3 1.73 18.1 2.19 19.9 2.43 21.8 2.68 25.5 3.19 29.1 3.81
130% 23 18.6 2.30 23.2 2.98 29.4 4.13 32.4 4.77 35.4 5.45 36.9 5.61 38.0 5.67 80% 23 11.4 1.44 14.3 1.76 18.1 2.23 19.9 2.47 21.8 2.75 25.5 3.40 29.1 4.08
(390) 25 18.6 2.40 23.2 3.18 29.4 4.42 32.4 5.10 35.2 5.78 36.4 5.85 37.5 5.92 (240) 25 11.4 1.46 14.3 1.79 18.1 2.32 19.9 2.62 21.8 2.94 25.5 3.63 29.1 4.37
27 18.6 2.55 23.2 3.39 29.4 4.72 32.4 5.46 34.7 6.03 35.9 6.10 36.9 6.17 27 11.4 1.49 14.3 1.88 18.1 2.47 19.9 2.79 21.8 3.13 25.5 3.87 29.1 4.67
29 18.6 2.71 23.2 3.61 29.4 5.04 32.4 5.83 34.2 6.27 35.3 6.35 36.4 6.42 29 11.4 1.58 14.3 1.99 18.1 2.62 19.9 2.97 21.8 3.34 25.5 4.13 29.1 4.98
31 18.6 2.88 23.2 3.85 29.4 5.38 32.4 6.23 33.7 6.51 34.8 6.59 35.9 6.67 31 11.4 1.67 14.3 2.11 18.1 2.79 19.9 3.16 21.8 3.55 25.5 4.40 29.1 5.31
33 18.6 3.06 23.2 4.10 29.4 5.74 32.4 6.64 33.2 6.76 34.3 6.84 35.4 6.93 33 11.4 1.76 14.3 2.23 18.1 2.96 19.9 3.35 21.8 3.78 25.5 4.69 29.1 5.66
35 18.6 3.25 23.2 4.36 29.4 6.11 32.1 6.96 32.6 7.01 33.8 7.10 34.9 7.18 35 11.4 1.86 14.3 2.36 18.1 3.14 19.9 3.56 21.8 4.01 25.5 4.99 29.1 6.04
37 18.6 3.45 23.2 4.63 29.4 6.51 31.6 7.21 32.1 7.25 33.3 7.35 34.3 7.44 37 11.4 1.97 14.3 2.50 18.1 3.33 19.9 3.78 21.8 4.26 25.5 5.31 29.1 6.43
39 18.6 3.66 23.2 4.92 29.4 6.93 31.0 7.45 31.6 7.50 32.7 7.60 33.8 7.70 39 11.4 2.07 14.3 2.64 18.1 3.53 19.9 4.01 21.8 4.53 25.5 5.65 29.1 6.85
10 17.1 1.89 21.4 2.37 27.1 3.08 29.9 3.44 32.7 3.82 38.3 4.58 40.7 4.69 10 10.0 1.18 12.5 1.41 15.8 1.75 17.4 1.92 19.1 2.11 22.3 2.49 25.5 2.87
12 17.1 1.92 21.4 2.41 27.1 3.13 29.9 3.51 32.7 3.89 38.3 4.67 40.2 4.66 12 10.0 1.19 12.5 1.43 15.8 1.77 17.4 1.95 19.1 2.14 22.3 2.53 25.5 2.92
14 17.1 1.95 21.4 2.46 27.1 3.19 29.9 3.57 32.7 3.96 38.3 4.75 39.6 4.64 14 10.0 1.21 12.5 1.45 15.8 1.80 17.4 1.99 19.1 2.18 22.3 2.57 25.5 2.98
16 17.1 1.99 21.4 2.50 27.1 3.25 29.9 3.64 32.7 4.04 38.1 4.81 39.1 4.77 16 10.0 1.23 12.5 1.47 15.8 1.83 17.4 2.02 19.1 2.22 22.3 2.62 25.5 3.03
18 17.1 2.02 21.4 2.55 27.1 3.32 29.9 3.71 32.7 4.12 37.6 4.97 38.6 5.01 18 10.0 1.24 12.5 1.49 15.8 1.86 17.4 2.06 19.1 2.26 22.3 2.67 25.5 3.09
20 17.1 2.06 21.4 2.59 27.1 3.38 29.9 3.82 32.7 4.36 37.1 5.21 38.1 5.26 20 10.0 1.26 12.5 1.52 15.8 1.89 17.4 2.09 19.1 2.30 22.3 2.72 25.5 3.15
21 17.1 2.07 21.4 2.62 27.1 3.45 29.9 3.96 32.7 4.51 36.8 5.33 37.8 5.38 21 10.0 1.27 12.5 1.53 15.8 1.91 17.4 2.11 19.1 2.32 22.3 2.75 25.5 3.18
120% 23 17.1 2.11 21.4 2.68 27.1 3.69 29.9 4.24 32.7 4.84 36.3 5.57 37.3 5.63 70% 23 10.0 1.29 12.5 1.55 15.8 1.94 17.4 2.15 19.1 2.36 22.3 2.84 25.5 3.39
(360) 25 17.1 2.18 21.4 2.86 27.1 3.94 29.9 4.54 32.7 5.18 35.8 5.82 36.8 5.88 (210) 25 10.0 1.30 12.5 1.58 15.8 1.98 17.4 2.22 19.1 2.48 22.3 3.03 25.5 3.62
27 17.1 2.32 21.4 3.05 27.1 4.21 29.9 4.85 32.7 5.54 35.3 6.06 36.3 6.12 27 10.0 1.32 12.5 1.63 15.8 2.11 17.4 2.36 19.1 2.64 22.3 3.23 25.5 3.86
29 17.1 2.46 21.4 3.25 27.1 4.49 29.9 5.18 32.7 5.92 34.7 6.31 35.7 6.37 29 10.0 1.39 12.5 1.72 15.8 2.24 17.4 2.51 19.1 2.81 22.3 3.44 25.5 4.12
31 17.1 2.61 21.4 3.46 27.1 4.79 29.9 5.53 32.7 6.32 34.2 6.55 35.2 6.62 31 10.0 1.47 12.5 1.82 15.8 2.37 17.4 2.67 19.1 2.98 22.3 3.66 25.5 4.39
33 17.1 2.77 21.4 3.68 27.1 5.10 29.9 5.89 32.7 6.72 33.7 6.80 34.7 6.88 33 10.0 1.55 12.5 1.93 15.8 2.51 17.4 2.83 19.1 3.17 22.3 3.90 25.5 4.67
35 17.1 2.94 21.4 3.91 27.1 5.44 29.9 6.28 32.1 6.97 33.2 7.05 34.2 7.13 35 10.0 1.63 12.5 2.04 15.8 2.66 17.4 3.00 19.1 3.36 22.3 4.14 25.5 4.97
37 17.1 3.12 21.4 4.15 27.1 5.79 29.9 6.69 31.6 7.21 32.7 7.30 33.7 7.38 37 10.0 1.72 12.5 2.15 15.8 2.82 17.4 3.18 19.1 3.57 22.3 4.40 25.5 5.29
39 17.1 3.30 21.4 4.41 27.1 6.16 29.9 7.13 31.1 7.46 32.1 7.55 33.1 7.64 39 10.0 1.81 12.5 2.28 15.8 2.99 17.4 3.37 19.1 3.79 22.3 4.68 25.5 5.63
10 15.7 1.74 19.6 2.16 24.8 2.79 27.4 3.12 30.0 3.45 35.1 4.14 40.0 4.82 10 8.57 1.06 10.7 1.24 13.5 1.52 15.0 1.66 16.4 1.81 19.1 2.11 21.8 2.42
12 15.7 1.76 19.6 2.20 24.8 2.84 27.4 3.17 30.0 3.52 35.1 4.22 39.5 4.79 12 8.57 1.07 10.7 1.26 13.5 1.54 15.0 1.68 16.4 1.83 19.1 2.15 21.8 2.47
14 15.7 1.79 19.6 2.24 24.8 2.89 27.4 3.23 30.0 3.58 35.1 4.30 39.0 4.77 14 8.57 1.08 10.7 1.27 13.5 1.56 15.0 1.71 16.4 1.86 19.1 2.18 21.8 2.51
16 15.7 1.82 19.6 2.28 24.8 2.95 27.4 3.30 30.0 3.65 35.1 4.38 38.4 4.75 16 8.57 1.09 10.7 1.29 13.5 1.58 15.0 1.74 16.4 1.89 19.1 2.22 21.8 2.56
18 15.7 1.85 19.6 2.32 24.8 3.01 27.4 3.36 30.0 3.73 35.1 4.50 37.9 4.98 18 8.57 1.11 10.7 1.31 13.5 1.61 15.0 1.76 16.4 1.93 19.1 2.26 21.8 2.60
20 15.7 1.88 19.6 2.36 24.8 3.06 27.4 3.43 30.0 3.84 35.1 4.84 37.4 5.22 20 8.57 1.12 10.7 1.33 13.5 1.63 15.0 1.79 16.4 1.96 19.1 2.30 21.8 2.65
21 15.7 1.90 19.6 2.38 24.8 3.09 27.4 3.50 30.0 3.98 35.1 5.01 37.1 5.35 21 8.57 1.13 10.7 1.34 13.5 1.65 15.0 1.81 16.4 1.98 19.1 2.33 21.8 2.68
110% 23 15.7 1.93 19.6 2.43 24.8 3.27 27.4 3.75 30.0 4.26 35.1 5.37 36.6 5.59 60% 23 8.57 1.14 10.7 1.36 13.5 1.68 15.0 1.84 16.4 2.01 19.1 2.37 21.8 2.76
(330) 25 15.7 1.97 19.6 2.56 24.8 3.50 27.4 4.01 30.0 4.56 35.1 5.75 36.1 5.83 (180) 25 8.57 1.16 10.7 1.38 13.5 1.70 15.0 1.87 16.4 2.06 19.1 2.49 21.8 2.94
27 15.7 2.09 19.6 2.73 24.8 3.73 27.4 4.28 30.0 4.87 34.7 6.02 35.6 6.08 27 8.57 1.17 10.7 1.40 13.5 1.78 15.0 1.98 16.4 2.19 19.1 2.65 21.8 3.14
29 15.7 2.22 19.6 2.90 24.8 3.98 27.4 4.57 30.0 5.20 34.1 6.27 35.1 6.33 29 8.57 1.22 10.7 1.48 13.5 1.88 15.0 2.10 16.4 2.33 19.1 2.82 21.8 3.34
31 15.7 2.36 19.6 3.09 24.8 4.24 27.4 4.87 30.0 5.55 33.6 6.51 34.5 6.58 31 8.57 1.28 10.7 1.56 13.5 1.99 15.0 2.22 16.4 2.47 19.1 3.00 21.8 3.55
33 15.7 2.50 19.6 3.28 24.8 4.51 27.4 5.19 30.0 5.92 33.1 6.76 34.0 6.82 33 8.57 1.35 10.7 1.65 13.5 2.11 15.0 2.36 16.4 2.62 19.1 3.18 21.8 3.78
35 15.7 2.65 19.6 3.48 24.8 4.80 27.4 5.53 30.0 6.31 32.6 7.00 33.5 7.07 35 8.57 1.42 10.7 1.74 13.5 2.23 15.0 2.50 16.4 2.78 19.1 3.38 21.8 4.02
37 15.7 2.80 19.6 3.70 24.8 5.11 27.4 5.89 30.0 6.72 32.1 7.25 33.0 7.33 37 8.57 1.50 10.7 1.84 13.5 2.36 15.0 2.64 16.4 2.94 19.1 3.58 21.8 4.27
39 15.7 2.97 19.6 3.92 24.8 5.43 27.4 6.26 30.0 7.16 31.5 7.50 32.5 7.58 39 8.57 1.57 10.7 1.94 13.5 2.49 15.0 2.80 16.4 3.12 19.1 3.80 21.8 4.53
10 14.3 1.59 17.8 1.96 22.6 2.51 24.9 2.80 27.3 3.10 31.9 3.71 36.4 4.32 10 7.15 0.94 8.91 1.08 11.3 1.30 12.5 1.41 13.6 1.52 16.0 1.76 18.2 2.01
12 14.3 1.61 17.8 2.00 22.6 2.56 24.9 2.85 27.3 3.16 31.9 3.78 36.4 4.40 12 7.15 0.95 8.91 1.10 11.3 1.31 12.5 1.43 13.6 1.55 16.0 1.79 18.2 2.04
14 14.3 1.64 17.8 2.03 22.6 2.61 24.9 2.90 27.3 3.21 31.9 3.85 36.4 4.48 14 7.15 0.96 8.91 1.11 11.3 1.33 12.5 1.45 13.6 1.57 16.0 1.82 18.2 2.07
16 14.3 1.66 17.8 2.06 22.6 2.65 24.9 2.96 27.3 3.28 31.9 3.92 36.4 4.57 16 7.15 0.97 8.91 1.12 11.3 1.35 12.5 1.47 13.6 1.59 16.0 1.85 18.2 2.11
18 14.3 1.69 17.8 2.10 22.6 2.70 24.9 3.02 27.3 3.34 31.9 4.00 36.4 4.75 18 7.15 0.98 8.91 1.14 11.3 1.37 12.5 1.49 13.6 1.62 16.0 1.88 18.2 2.15
20 14.3 1.72 17.8 2.14 22.6 2.75 24.9 3.08 27.3 3.41 31.9 4.20 36.4 5.10 20 7.15 0.99 8.91 1.15 11.3 1.39 12.5 1.51 13.6 1.64 16.0 1.91 18.2 2.18
21 14.3 1.73 17.8 2.16 22.6 2.78 24.9 3.11 27.3 3.48 31.9 4.35 36.4 5.29 21 7.15 0.99 8.91 1.16 11.3 1.40 12.5 1.53 13.6 1.66 16.0 1.93 18.2 2.20
100% 23 14.3 1.76 17.8 2.20 22.6 2.88 24.9 3.29 27.3 3.72 31.9 4.66 35.9 5.55 50% 23 7.15 1.01 8.91 1.17 11.3 1.42 12.5 1.55 13.6 1.68 16.0 1.96 18.2 2.25
(300) 25 14.3 1.79 17.8 2.28 22.6 3.08 24.9 3.51 27.3 3.98 31.9 4.99 35.4 5.79 (150) 25 7.15 1.02 8.91 1.19 11.3 1.44 12.5 1.58 13.6 1.71 16.0 2.00 18.2 2.34
27 14.3 1.88 17.8 2.43 22.6 3.28 24.9 3.75 27.3 4.25 31.9 5.34 34.9 6.04 27 7.15 1.03 8.91 1.21 11.3 1.47 12.5 1.63 13.6 1.79 16.0 2.13 18.2 2.49
29 14.3 1.99 17.8 2.58 22.6 3.49 24.9 3.99 27.3 4.53 31.9 5.70 34.4 6.28 29 7.15 1.05 8.91 1.26 11.3 1.56 12.5 1.72 13.6 1.89 16.0 2.26 18.2 2.65
31 14.3 2.11 17.8 2.74 22.6 3.72 24.9 4.26 27.3 4.83 31.9 6.09 33.9 6.53 31 7.15 1.11 8.91 1.32 11.3 1.65 12.5 1.82 13.6 2.01 16.0 2.40 18.2 2.81
33 14.3 2.24 17.8 2.91 22.6 3.96 24.9 4.53 27.3 5.15 31.9 6.49 33.3 6.77 33 7.15 1.17 8.91 1.40 11.3 1.74 12.5 1.93 13.6 2.12 16.0 2.54 18.2 2.98
35 14.3 2.37 17.8 3.08 22.6 4.21 24.9 4.82 27.3 5.49 31.9 6.92 32.8 7.02 35 7.15 1.23 8.91 1.47 11.3 1.84 12.5 2.04 13.6 2.25 16.0 2.69 18.2 3.17
37 14.3 2.51 17.8 3.27 22.6 4.47 24.9 5.13 27.3 5.84 31.5 7.20 32.3 7.27 37 7.15 1.29 8.91 1.55 11.3 1.94 12.5 2.15 13.6 2.38 16.0 2.85 18.2 3.36
39 14.3 2.65 17.8 3.47 22.6 4.75 24.9 5.46 27.3 6.22 30.9 7.45 31.8 7.52 39 7.15 1.35 8.91 1.63 11.3 2.05 12.5 2.27 13.6 2.51 16.0 3.02 18.2 3.56
10 12.9 1.45 16.0 1.77 20.3 2.25 22.4 2.50 24.5 2.75 28.7 3.29 32.7 3.82
12 12.9 1.47 16.0 1.80 20.3 2.29 22.4 2.54 24.5 2.80 28.7 3.35 32.7 3.89 TC: Total capacity: kW
14 12.9 1.49 16.0 1.83 20.3 2.33 22.4 2.59 24.5 2.86 28.7 3.41 32.7 3.97 PI: Power input: kW (Compressor+Outdoor fan motor)
16 12.9 1.51 16.0 1.86 20.3 2.37 22.4 2.63 24.5 2.91 28.7 3.48 32.7 4.04 Notes: 1. This table shows the average value of conditions which may occur.
18 12.9 1.53 16.0 1.89 20.3 2.41 22.4 2.68 24.5 2.96 28.7 3.54 32.7 4.13 2. This table indicates the situation of 50~130% combination of indoor units.
20 12.9 1.56 16.0 1.92 20.3 2.46 22.4 2.73 24.5 3.02 28.7 3.62 32.7 4.36 3. If connecting the indoor units over 130% of outdoor unit capacity, capacity of
21 12.9 1.57 16.0 1.94 20.3 2.48 22.4 2.76 24.5 3.05 28.7 3.74 32.7 4.52 indoor unit will decrease.
4. shows rated condition.
90% 23 12.9 1.60 16.0 1.97 20.3 2.53 22.4 2.86 24.5 3.22 28.7 4.00 32.7 4.84
(270) 25 12.9 1.62 16.0 2.01 20.3 2.68 22.4 3.05 24.5 3.44 28.7 4.28 32.7 5.19
27 12.9 1.68 16.0 2.14 20.3 2.86 22.4 3.25 24.5 3.67 28.7 4.57 32.7 5.55
29 12.9 1.78 16.0 2.27 20.3 3.04 22.4 3.46 24.5 3.91 28.7 4.88 32.7 5.93
31 12.9 1.88 16.0 2.41 20.3 3.23 22.4 3.68 24.5 4.17 28.7 5.21 32.7 6.33
33 12.9 1.99 16.0 2.56 20.3 3.44 22.4 3.92 24.5 4.44 28.7 5.55 32.7 6.72
35 12.9 2.11 16.0 2.71 20.3 3.65 22.4 4.17 24.5 4.72 28.7 5.92 32.1 6.97
37 12.9 2.23 16.0 2.87 20.3 3.88 22.4 4.43 24.5 5.02 28.7 6.30 31.6 7.21
39 12.9 2.35 16.0 3.04 20.3 4.12 22.4 4.71 24.5 5.34 28.7 6.71 31.1 7.46
326 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 327
Capacity Tables (High-COP Type) EDIN341424
328 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 329
Capacity Tables (High-COP Type) EDIN341424
330 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 331
Capacity Tables (High-COP Type) EDIN341424
332 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 333
Capacity Tables (High-COP Type) EDIN341424
334 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 335
Capacity Tables (High-COP Type) EDIN341424
336 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 337
Capacity Tables (High-COP Type) EDIN341424
338 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 339
Capacity Tables (High-COP Type) EDIN341424
340 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 341
Capacity Tables (High-COP Type) EDIN341424
342 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 343
Capacity Tables (High-COP Type) EDIN341424
344 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 345
Capacity Tables (High-COP Type) EDIN341424
346 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 347
Capacity Tables (High-COP Type) EDIN341424
348 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 349
Capacity Tables (High-COP Type) EDIN341424
350 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 351
Capacity Tables (High-COP Type) EDIN341424
352 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 353
Capacity Tables (High-COP Type) EDIN341424
354 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 355
Capacity Tables (High-COP Type) EDIN341424
356 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 357
Capacity Tables (High-COP Type) EDIN341424
358 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 359
Capacity Tables (High-COP Type) EDIN341424
360 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 361
Capacity Tables (High-COP Type) EDIN341424
362 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 363
Capacity Tables (High-COP Type) EDIN341424
364 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ-THRY6 365
Capacity Tables (High-COP Type) EDIN341424
3D086178
366 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ16THRY6
3D086183
16
RXYQ-THRY6 367
Capacity Tables (High-COP Type) EDIN341424
3D086184
368 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
3D086186
16
RXYQ-THRY6 369
Capacity Tables (High-COP Type) EDIN341424
RXYQ22THRY6
3D086185
370 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ46THRY6
3D086189
16
RXYQ-THRY6 371
Capacity Tables (High-COP Type) EDIN341424
RXYQ48THRY6
3D086190
372 RXYQ-THRY6
EDIN341424 Capacity Tables (High-COP Type)
RXYQ50THRY6
3D086200
16
RXYQ-THRY6 373
Capacity Tables (High-COP Type) EDIN341424
Formula
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation = C
A=B×C
Note:
It will be seen from the figure above that the integrated heating capacity expresses the integrated heating capacity for
a single cycle (from defrosting operation to defrosting operation) in terms of time.
Please take note that when there is an accumulation of snow against the outside surface of the outdoor unit heat
exchanger there will always be a temporary reduction in capacity although this will, of course, vary in degree in
accordance with a number of other factors such as the outdoor temperature (°CDB), relative humidity (RH) and
the amount of frosting which occurs.
374 RXYQ-THRY6
EDIN341424 Operation Limits
7. Operation Limits
RXYQ12THRY6 / RXYQ14THRY6 / RXYQ16THRY6 / RXYQ18THRY6 / RXYQ20THRY6 / RXYQ22THRY6 /
RXYQ24THRY6 / RXYQ26THRY6 / RXYQ28THRY6 / RXYQ30THRY6 / RXYQ32THRY6 / RXYQ34THRY6 /
RXYQ36THRY6 / RXYQ38THRY6 / RXYQ40THRY6 / RXYQ42THRY6 / RXYQ44THRY6 / RXYQ46THRY6 /
RXYQ48THRY6 / RXYQ50THRY6
Cooling
Heating
3D092065
16
RXYQ-THRY6 375
Sound Levels EDIN341424
8. Sound Levels
8.1 Overall
dB(A) dB(A) dB(A)
Sound pressure level Sound pressure level Sound pressure level
Model Model Model
380-415V, 50Hz 380-415V, 50Hz 380-415V, 50Hz
RXYQ12THRY6 58 RXYQ26THRY6 61 RXYQ40THRY6 64
RXYQ14THRY6 59 RXYQ28THRY6 62 RXYQ42THRY6 65
RXYQ16THRY6 59 RXYQ30THRY6 62 RXYQ44THRY6 65
RXYQ18THRY6 60 RXYQ32THRY6 63 RXYQ46THRY6 65
RXYQ20THRY6 60 RXYQ34THRY6 63 RXYQ48THRY6 66
RXYQ22THRY6 60 RXYQ36THRY6 64 RXYQ50THRY6 66
RXYQ24THRY6 61 RXYQ38THRY6 64
Note:
Sound pressure level:
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Location of microphone
376 RXYQ-THRY6
EDIN341424 Accessories
9. Accessories
9.1 Optional Accessories
RXYQ12THRY6(E)
Optional accessories RXYQ14THRY6(E)
RXYQ16THRY6(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H
Distributive Refnet header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Piping
Refnet joint KHRP26A22T, KHRP26A33T, KHRP26A72T
Outdoor unit multi connection piping kit BHFP22P100
Cool/Heat selector KRC19-26A
C: 3D085857B
RXYQ24THRY6(E)
RXYQ18THRY6(E) RXYQ26THRY6(E)
Optional accessories RXYQ20THRY6(E) RXYQ28THRY6(E) RXYQ34THRY6(E)
RXYQ22THRY6(E) RXYQ30THRY6(E)
RXYQ32THRY6(E)
KHRP26M22H
(Max. 4 branch),
Refnet header KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive (Max. 8 branch), (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping KHRP26M72H
(Max. 8 branch)
RXYQ42THRY6(E)
RXYQ44THRY6(E)
Optional accessories RXYQ36THRY6(E) RXYQ38THRY6(E) RXYQ40THRY6(E) RXYQ46THRY6(E)
RXYQ48THRY6(E)
RXYQ50THRY6(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive Refnet header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping
Refnet joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P151
Cool/Heat selector KRC19-26A
C: 3D085857B
16
RXYQ-THRY6 377
Accessories EDIN341424
378 RXYQ-THRY6
EDIN341424
Part 5
RXYQ-T(N)RY6
Heat Pump 50Hz
Standard Type
1. Specifications ......................................................................................380
1.1 Heat Pump 50Hz Standard Type (RXYQ-T(N)RY6) ............................380
2. Dimensions .........................................................................................394
2.1 Independent Unit ..................................................................................394
2.2 Combination Unit..................................................................................396
3. Service Space .....................................................................................403
4. Piping Diagrams..................................................................................404
5. Wiring Diagrams..................................................................................406
6. Field Wiring .........................................................................................409
7. Electric Characteristics........................................................................412
8. Safety Devices Setting ........................................................................415
9. Capacity Tables (Standard Type) .......................................................416
9.1 Cooling Capacity for VRV Indoor Units Only (Te: 6ºC) ........................416
9.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC) ........................444
9.3 Heating Capacity ..................................................................................472
9.4 Capacity Correction Factor...................................................................500
9.5 Notes for Heating Capacity Characteristics (Heat Pump) ....................514
9.6 Cooling Part Load Performance for VRV Indoor Units Only.................515
9.7 Heating Part Load Performance for VRV Indoor Units Only ................521
10.Operation Limits ..................................................................................527
11.Sound Levels ......................................................................................528
11.1 Overall ..................................................................................................528
11.2 Octave Band Level ...............................................................................528
12.Accessories.........................................................................................529
12.1 Optional Accessories............................................................................529 17
RXYQ-T(N)RY6 379
Specifications EDIN341424
1. Specifications
1.1 Heat Pump 50Hz Standard Type (RXYQ-T(N)RY6)
Model Name RXYQ6TRY6(E) RXYQ8TRY6(E)
Power Supply 3 phase, 380-415V, 50Hz 3 phase, 380-415V, 50Hz
kcal/h 13,800 19,300
1 Cooling Capacity Btu/h 54,600 76,400
kW 16.0 22.4
kcal/h 15,500 21,500
2 Heating Capacity Btu/h 61,400 85,300
kW 18.0 25.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×930×765 1,657×930×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Displacement m³/h 16.24 16.24
Number of Revolutions r/min 7,668 7,668
Comp.
Motor Output×
kW 2.4×1 3.4×1
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.55×1 0.55×1
Fan
Airflow Rate m³/min 119 157
Drive Direct drive Direct drive
Connecting Liquid Pipe mm φ9.5 C1220T (Brazing connection) φ9.5 C1220T (Brazing connection)
Pipes Gas Pipe mm φ19.1 C1220T (Brazing connection) φ19.1 C1220T (Brazing connection)
Mass kg 185 185
3 Sound Pressure Level dB(A) 55 56
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Overcurrent relay, Inverter overload protector, Overvoltage Overcurrent relay, Inverter overload protector, Overvoltage
protector protector
Capacity Control % 20-100 20-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 5.9 5.9
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Clamps Clamps
Drawing No. C: 4D088864 C: 4D088864
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
380 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 381
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
382 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 383
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
384 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 385
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
386 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 387
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
388 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 389
Specifications EDIN341424
390 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 391
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
392 RXYQ-T(N)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
17
RXYQ-T(N)RY6 393
Dimensions EDIN341424
2. Dimensions
2.1 Independent Unit
3D084511C
394 RXYQ-T(N)RY6
EDIN341424 Dimensions
RXYQ14TRY6 / RXYQ16TRY6
Unit (mm)
3D084507C
17
RXYQ-T(N)RY6 395
Dimensions EDIN341424
RXYQ18TNRY6 / RXYQ20TNRY6
Unit (mm)
3D088931
396 RXYQ-T(N)RY6
EDIN341424 Dimensions
3D089394
17
RXYQ-T(N)RY6 397
Dimensions EDIN341424
3D088932
398 RXYQ-T(N)RY6
EDIN341424 Dimensions
RXYQ34TNRY6 / RXYQ36TNRY6
Unit (mm)
3D088934
17
RXYQ-T(N)RY6 399
Dimensions EDIN341424
RXYQ38TNRY6 / RXYQ40TNRY6
Unit (mm)
3D089374
400 RXYQ-T(N)RY6
EDIN341424 Dimensions
RXYQ42TNRY6 / RXYQ44TNRY6
Unit (mm)
3D089381
17
RXYQ-T(N)RY6 401
Dimensions EDIN341424
3D088933
402 RXYQ-T(N)RY6
EDIN341424 Service Space
3. Service Space
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6 / RXYQ14TRY6 / RXYQ16TRY6 /
RXYQ18TNRY6 / RXYQ20TNRY6 / RXYQ22TNRY6 / RXYQ24TNRY6 / RXYQ26TNRY6 /
RXYQ28TNRY6 / RXYQ30TNRY6 / RXYQ32TNRY6 / RXYQ34TNRY6 / RXYQ36TNRY6 / RXYQ38TNRY6 /
RXYQ40TNRY6 / RXYQ42TNRY6 / RXYQ44TNRY6 / RXYQ46TNRY6 / RXYQ48TNRY6 / RXYQ50TNRY6 /
RXYQ52TNRY6 / RXYQ54TNRY6 / RXYQ56TNRY6 / RXYQ58TNRY6 / RXYQ60TNRY6
Unit (mm)
3D084449A
17
RXYQ-T(N)RY6 403
Piping Diagrams EDIN341424
4. Piping Diagrams
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6
3D085856
404 RXYQ-T(N)RY6
EDIN341424 Piping Diagrams
RXYQ14TRY6 / RXYQ16TRY6
3D085859A
17
RXYQ-T(N)RY6 405
Wiring Diagrams EDIN341424
5. Wiring Diagrams
RXYQ6TRY6 / RXYQ8TRY6
3D089044D
406 RXYQ-T(N)RY6
EDIN341424 Wiring Diagrams
RXYQ10TRY6 / RXYQ12TRY6
17
3D089045A
RXYQ-T(N)RY6 407
Wiring Diagrams EDIN341424
RXYQ14TRY6 / RXYQ16TRY6
2D089046D
408 RXYQ-T(N)RY6
EDIN341424 Field Wiring
6. Field Wiring
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6 / RXYQ14TRY6 / RXYQ16TRY6
3D084395A
17
RXYQ-T(N)RY6 409
Field Wiring EDIN341424
3D084407A
410 RXYQ-T(N)RY6
EDIN341424 Field Wiring
3D084410A
17
RXYQ-T(N)RY6 411
Electric Characteristics EDIN341424
7. Electric Characteristics
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6 / RXYQ14TRY6 / RXYQ16TRY6 /
RXYQ18TNRY6 / RXYQ20TNRY6 / RXYQ22TNRY6
3D088894A
412 RXYQ-T(N)RY6
EDIN341424 Electric Characteristics
3D088900A
17
RXYQ-T(N)RY6 413
Electric Characteristics EDIN341424
3D088930A
414 RXYQ-T(N)RY6
EDIN341424 Safety Devices Setting
17
RXYQ-T(N)RY6 415
Capacity Tables (Standard Type) EDIN341424
416 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 417
Capacity Tables (Standard Type) EDIN341424
418 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 419
Capacity Tables (Standard Type) EDIN341424
420 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 421
Capacity Tables (Standard Type) EDIN341424
422 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 423
Capacity Tables (Standard Type) EDIN341424
424 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 425
Capacity Tables (Standard Type) EDIN341424
426 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 427
Capacity Tables (Standard Type) EDIN341424
428 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 429
Capacity Tables (Standard Type) EDIN341424
430 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 431
Capacity Tables (Standard Type) EDIN341424
432 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 433
Capacity Tables (Standard Type) EDIN341424
434 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 435
Capacity Tables (Standard Type) EDIN341424
436 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 437
Capacity Tables (Standard Type) EDIN341424
438 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 439
Capacity Tables (Standard Type) EDIN341424
440 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 441
Capacity Tables (Standard Type) EDIN341424
442 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 443
Capacity Tables (Standard Type) EDIN341424
9.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC)
When only VRV indoor units are connected
RXYQ6TRY6 Cooling capacity (Te: 9ºC)
Indoor air temp. (°CWB) Indoor air temp. (°CWB)
Combina- Outdoor Combina- Outdoor
tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0
(Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI (Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
index) °CDB kW kW index) °CDB kW kW
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 9.29 1.02 11.6 1.29 14.7 1.68 16.2 1.89 17.7 2.09 20.1 2.38 20.7 2.28 10 5.72 0.66 7.13 0.79 9.03 1.00 9.97 1.10 10.9 1.21 12.8 1.44 14.6 1.67
12 9.29 1.04 11.6 1.32 14.7 1.72 16.2 1.92 17.7 2.13 19.9 2.37 20.4 2.26 12 5.72 0.66 7.13 0.80 9.03 1.01 9.97 1.12 10.9 1.23 12.8 1.46 14.6 1.70
14 9.29 1.06 11.6 1.34 14.7 1.75 16.2 1.96 17.7 2.17 19.6 2.36 20.2 2.28 14 5.72 0.67 7.13 0.82 9.03 1.03 9.97 1.14 10.9 1.25 12.8 1.49 14.6 1.73
16 9.29 1.08 11.6 1.36 14.7 1.78 16.2 2.00 17.7 2.22 19.4 2.38 19.9 2.40 16 5.72 0.68 7.13 0.83 9.03 1.05 9.97 1.16 10.9 1.28 12.8 1.52 14.6 1.77
18 9.29 1.10 11.6 1.39 14.7 1.82 16.2 2.04 17.7 2.28 19.1 2.50 19.6 2.52 18 5.72 0.69 7.13 0.84 9.03 1.07 9.97 1.18 10.9 1.30 12.8 1.55 14.6 1.80
20 9.29 1.12 11.6 1.42 14.7 1.86 16.2 2.15 17.7 2.45 18.8 2.62 19.4 2.65 20 5.72 0.70 7.13 0.86 9.03 1.08 9.97 1.20 10.9 1.33 12.8 1.58 14.6 1.84
21 9.29 1.13 11.6 1.43 14.7 1.93 16.2 2.22 17.7 2.54 18.7 2.68 19.3 2.71 21 5.72 0.71 7.13 0.86 9.03 1.09 9.97 1.21 10.9 1.34 12.8 1.60 14.6 1.91
130% 23 9.29 1.15 11.6 1.49 14.7 2.07 16.2 2.38 17.7 2.73 18.4 2.80 19.0 2.83 80% 23 5.72 0.72 7.13 0.88 9.03 1.11 9.97 1.24 10.9 1.38 12.8 1.70 14.6 2.04
(195) 25 9.29 1.20 11.6 1.59 14.7 2.21 16.2 2.55 17.6 2.89 18.2 2.93 18.7 2.96 (120) 25 5.72 0.73 7.13 0.89 9.03 1.16 9.97 1.31 10.9 1.47 12.8 1.81 14.6 2.18
27 9.29 1.28 11.6 1.70 14.7 2.36 16.2 2.73 17.4 3.01 17.9 3.05 18.5 3.08 27 5.72 0.75 7.13 0.94 9.03 1.23 9.97 1.39 10.9 1.57 12.8 1.94 14.6 2.33
29 9.29 1.36 11.6 1.81 14.7 2.52 16.2 2.92 17.1 3.14 17.7 3.17 18.2 3.21 29 5.72 0.79 7.13 0.99 9.03 1.31 9.97 1.48 10.9 1.67 12.8 2.07 14.6 2.49
31 9.29 1.44 11.6 1.92 14.7 2.69 16.2 3.11 16.8 3.26 17.4 3.30 18.0 3.34 31 5.72 0.83 7.13 1.05 9.03 1.39 9.97 1.58 10.9 1.77 12.8 2.20 14.6 2.66
33 9.29 1.53 11.6 2.05 14.7 2.87 16.2 3.32 16.6 3.38 17.1 3.42 17.7 3.46 33 5.72 0.88 7.13 1.12 9.03 1.48 9.97 1.68 10.9 1.89 12.8 2.34 14.6 2.83
35 9.29 1.63 11.6 2.18 14.7 3.06 16.0 3.48 16.3 3.50 16.9 3.55 17.4 3.59 35 5.72 0.93 7.13 1.18 9.03 1.57 9.97 1.78 10.9 2.01 12.8 2.49 14.6 3.02
37 9.29 1.72 11.6 2.32 14.7 3.26 15.8 3.60 16.1 3.63 16.6 3.67 17.2 3.72 37 5.72 0.98 7.13 1.25 9.03 1.66 9.97 1.89 10.9 2.13 12.8 2.65 14.6 3.22
39 9.29 1.83 11.6 2.46 14.7 3.47 15.5 3.73 15.8 3.75 16.4 3.80 16.9 3.85 39 5.72 1.04 7.13 1.32 9.03 1.76 9.97 2.01 10.9 2.26 12.8 2.82 14.6 3.42
10 8.57 0.95 10.7 1.19 13.5 1.54 15.0 1.72 16.4 1.91 19.1 2.29 20.3 2.34 10 5.00 0.59 6.24 0.70 7.90 0.87 8.72 0.96 9.54 1.05 11.2 1.24 12.7 1.44
12 8.57 0.96 10.7 1.21 13.5 1.57 15.0 1.75 16.4 1.94 19.1 2.33 20.1 2.33 12 5.00 0.60 6.24 0.71 7.90 0.89 8.72 0.98 9.54 1.07 11.2 1.26 12.7 1.46
14 8.57 0.98 10.7 1.23 13.5 1.60 15.0 1.79 16.4 1.98 19.1 2.38 19.8 2.32 14 5.00 0.60 6.24 0.72 7.90 0.90 8.72 0.99 9.54 1.09 11.2 1.29 12.7 1.49
16 8.57 0.99 10.7 1.25 13.5 1.63 15.0 1.82 16.4 2.02 19.1 2.41 19.6 2.39 16 5.00 0.61 6.24 0.74 7.90 0.92 8.72 1.01 9.54 1.11 11.2 1.31 12.7 1.52
18 8.57 1.01 10.7 1.27 13.5 1.66 15.0 1.86 16.4 2.06 18.8 2.48 19.3 2.51 18 5.00 0.62 6.24 0.75 7.90 0.93 8.72 1.03 9.54 1.13 11.2 1.34 12.7 1.55
20 8.57 1.03 10.7 1.30 13.5 1.69 15.0 1.91 16.4 2.18 18.5 2.60 19.0 2.63 20 5.00 0.63 6.24 0.76 7.90 0.95 8.72 1.05 9.54 1.15 11.2 1.36 12.7 1.58
21 8.57 1.04 10.7 1.31 13.5 1.72 15.0 1.98 16.4 2.26 18.4 2.66 18.9 2.69 21 5.00 0.63 6.24 0.76 7.90 0.96 8.72 1.06 9.54 1.16 11.2 1.37 12.7 1.59
120% 23 8.57 1.06 10.7 1.34 13.5 1.84 15.0 2.12 16.4 2.42 18.1 2.79 18.7 2.81 70% 23 5.00 0.64 6.24 0.78 7.90 0.97 8.72 1.07 9.54 1.18 11.2 1.42 12.7 1.69
(180) 25 8.57 1.09 10.7 1.43 13.5 1.97 15.0 2.27 16.4 2.59 17.9 2.91 18.4 2.94 (105) 25 5.00 0.65 6.24 0.79 7.90 0.99 8.72 1.11 9.54 1.24 11.2 1.52 12.7 1.81
27 8.57 1.16 10.7 1.53 13.5 2.11 15.0 2.43 16.4 2.77 17.6 3.03 18.1 3.06 27 5.00 0.66 6.24 0.81 7.90 1.05 8.72 1.18 9.54 1.32 11.2 1.62 12.7 1.93
29 8.57 1.23 10.7 1.62 13.5 2.25 15.0 2.59 16.4 2.96 17.4 3.15 17.9 3.19 29 5.00 0.70 6.24 0.86 7.90 1.12 8.72 1.26 9.54 1.40 11.2 1.72 12.7 2.06
31 8.57 1.31 10.7 1.73 13.5 2.40 15.0 2.76 16.4 3.16 17.1 3.28 17.6 3.31 31 5.00 0.73 6.24 0.91 7.90 1.19 8.72 1.33 9.54 1.49 11.2 1.83 12.7 2.19
33 8.57 1.39 10.7 1.84 13.5 2.55 15.0 2.95 16.3 3.36 16.8 3.40 17.4 3.44 33 5.00 0.77 6.24 0.96 7.90 1.26 8.72 1.42 9.54 1.58 11.2 1.95 12.7 2.34
35 8.57 1.47 10.7 1.95 13.5 2.72 15.0 3.14 16.1 3.48 16.6 3.52 17.1 3.56 35 5.00 0.82 6.24 1.02 7.90 1.33 8.72 1.50 9.54 1.68 11.2 2.07 12.7 2.49
37 8.57 1.56 10.7 2.07 13.5 2.89 15.0 3.35 15.8 3.61 16.3 3.65 16.8 3.69 37 5.00 0.86 6.24 1.08 7.90 1.41 8.72 1.59 9.54 1.79 11.2 2.20 12.7 2.65
39 8.57 1.65 10.7 2.20 13.5 3.08 15.0 3.56 15.5 3.73 16.1 3.78 16.6 3.82 39 5.00 0.91 6.24 1.14 7.90 1.49 8.72 1.69 9.54 1.89 11.2 2.34 12.7 2.81
10 7.86 0.87 9.80 1.08 12.4 1.40 13.7 1.56 15.0 1.73 17.5 2.07 20.0 2.41 10 4.29 0.53 5.34 0.62 6.77 0.76 7.48 0.83 8.18 0.90 9.57 1.06 10.9 1.21
12 7.86 0.88 9.80 1.10 12.4 1.42 13.7 1.59 15.0 1.76 17.5 2.11 19.7 2.40 12 4.29 0.53 5.34 0.63 6.77 0.77 7.48 0.84 8.18 0.92 9.57 1.07 10.9 1.23
14 7.86 0.90 9.80 1.12 12.4 1.45 13.7 1.62 15.0 1.79 17.5 2.15 19.5 2.39 14 4.29 0.54 5.34 0.64 6.77 0.78 7.48 0.85 8.18 0.93 9.57 1.09 10.9 1.26
16 7.86 0.91 9.80 1.14 12.4 1.47 13.7 1.65 15.0 1.83 17.5 2.19 19.2 2.37 16 4.29 0.55 5.34 0.65 6.77 0.79 7.48 0.87 8.18 0.95 9.57 1.11 10.9 1.28
18 7.86 0.93 9.80 1.16 12.4 1.50 13.7 1.68 15.0 1.86 17.5 2.25 19.0 2.49 18 4.29 0.55 5.34 0.65 6.77 0.80 7.48 0.88 8.18 0.96 9.57 1.13 10.9 1.30
20 7.86 0.94 9.80 1.18 12.4 1.53 13.7 1.71 15.0 1.92 17.5 2.42 18.7 2.61 20 4.29 0.56 5.34 0.66 6.77 0.82 7.48 0.90 8.18 0.98 9.57 1.15 10.9 1.33
21 7.86 0.95 9.80 1.19 12.4 1.55 13.7 1.75 15.0 1.99 17.5 2.50 18.6 2.67 21 4.29 0.56 5.34 0.67 6.77 0.82 7.48 0.90 8.18 0.99 9.57 1.16 10.9 1.34
110% 23 7.86 0.97 9.80 1.22 12.4 1.64 13.7 1.87 15.0 2.13 17.5 2.69 18.3 2.80 60% 23 4.29 0.57 5.34 0.68 6.77 0.84 7.48 0.92 8.18 1.01 9.57 1.18 10.9 1.38
(165) 25 7.86 0.98 9.80 1.28 12.4 1.75 13.7 2.00 15.0 2.28 17.5 2.88 18.1 2.92 (90) 25 4.29 0.58 5.34 0.69 6.77 0.85 7.48 0.94 8.18 1.03 9.57 1.24 10.9 1.47
27 7.86 1.05 9.80 1.36 12.4 1.87 13.7 2.14 15.0 2.44 17.3 3.01 17.8 3.04 27 4.29 0.59 5.34 0.70 6.77 0.89 7.48 0.99 8.18 1.10 9.57 1.33 10.9 1.57
29 7.86 1.11 9.80 1.45 12.4 1.99 13.7 2.28 15.0 2.60 17.1 3.13 17.5 3.16 29 4.29 0.61 5.34 0.74 6.77 0.94 7.48 1.05 8.18 1.16 9.57 1.41 10.9 1.67
31 7.86 1.18 9.80 1.54 12.4 2.12 13.7 2.44 15.0 2.78 16.8 3.26 17.3 3.29 31 4.29 0.64 5.34 0.78 6.77 1.00 7.48 1.11 8.18 1.24 9.57 1.50 10.9 1.78
33 7.86 1.25 9.80 1.64 12.4 2.26 13.7 2.60 15.0 2.96 16.5 3.38 17.0 3.41 33 4.29 0.68 5.34 0.83 6.77 1.05 7.48 1.18 8.18 1.31 9.57 1.59 10.9 1.89
35 7.86 1.32 9.80 1.74 12.4 2.40 13.7 2.76 15.0 3.16 16.3 3.50 16.8 3.54 35 4.29 0.71 5.34 0.87 6.77 1.12 7.48 1.25 8.18 1.39 9.57 1.69 10.9 2.01
37 7.86 1.40 9.80 1.85 12.4 2.55 13.7 2.94 15.0 3.36 16.0 3.62 16.5 3.66 37 4.29 0.75 5.34 0.92 6.77 1.18 7.48 1.32 8.18 1.47 9.57 1.79 10.9 2.13
39 7.86 1.48 9.80 1.96 12.4 2.72 13.7 3.13 15.0 3.58 15.8 3.75 16.2 3.79 39 4.29 0.79 5.34 0.97 6.77 1.25 7.48 1.40 8.18 1.56 9.57 1.90 10.9 2.27
10 7.15 0.79 8.91 0.98 11.3 1.26 12.5 1.40 13.6 1.55 16.0 1.85 18.2 2.16 10 3.57 0.47 4.45 0.54 5.65 0.65 6.23 0.70 6.82 0.76 7.98 0.88 9.10 1.00
12 7.15 0.81 8.91 1.00 11.3 1.28 12.5 1.43 13.6 1.58 16.0 1.89 18.2 2.20 12 3.57 0.47 4.45 0.55 5.65 0.66 6.23 0.71 6.82 0.77 7.98 0.89 9.10 1.02
14 7.15 0.82 8.91 1.01 11.3 1.30 12.5 1.45 13.6 1.61 16.0 1.92 18.2 2.24 14 3.57 0.48 4.45 0.55 5.65 0.67 6.23 0.72 6.82 0.78 7.98 0.91 9.10 1.04
16 7.15 0.83 8.91 1.03 11.3 1.33 12.5 1.48 13.6 1.64 16.0 1.96 18.2 2.29 16 3.57 0.48 4.45 0.56 5.65 0.68 6.23 0.73 6.82 0.80 7.98 0.92 9.10 1.05
18 7.15 0.85 8.91 1.05 11.3 1.35 12.5 1.51 13.6 1.67 16.0 2.00 18.2 2.37 18 3.57 0.49 4.45 0.57 5.65 0.69 6.23 0.75 6.82 0.81 7.98 0.94 9.10 1.07
20 7.15 0.86 8.91 1.07 11.3 1.38 12.5 1.54 13.6 1.70 16.0 2.10 18.2 2.55 20 3.57 0.49 4.45 0.58 5.65 0.70 6.23 0.76 6.82 0.82 7.98 0.96 9.10 1.09
21 7.15 0.87 8.91 1.08 11.3 1.39 12.5 1.55 13.6 1.74 16.0 2.18 18.2 2.64 21 3.57 0.50 4.45 0.58 5.65 0.70 6.23 0.76 6.82 0.83 7.98 0.96 9.10 1.10
100% 23 7.15 0.88 8.91 1.10 11.3 1.44 12.5 1.64 13.6 1.86 16.0 2.33 18.0 2.78 50% 23 3.57 0.50 4.45 0.59 5.65 0.71 6.23 0.78 6.82 0.84 7.98 0.98 9.10 1.12
(150) 25 7.15 0.90 8.91 1.14 11.3 1.54 12.5 1.76 13.6 1.99 16.0 2.50 17.7 2.90 (75) 25 3.57 0.51 4.45 0.60 5.65 0.72 6.23 0.79 6.82 0.86 7.98 1.00 9.10 1.17
27 7.15 0.94 8.91 1.21 11.3 1.64 12.5 1.87 13.6 2.12 16.0 2.67 17.5 3.02 27 3.57 0.52 4.45 0.60 5.65 0.74 6.23 0.81 6.82 0.89 7.98 1.06 9.10 1.24
29 7.15 1.00 8.91 1.29 11.3 1.75 12.5 2.00 13.6 2.27 16.0 2.85 17.2 3.14 29 3.57 0.53 4.45 0.63 5.65 0.78 6.23 0.86 6.82 0.95 7.98 1.13 9.10 1.32
31 7.15 1.06 8.91 1.37 11.3 1.86 12.5 2.13 13.6 2.42 16.0 3.04 16.9 3.26 31 3.57 0.55 4.45 0.66 5.65 0.82 6.23 0.91 6.82 1.00 7.98 1.20 9.10 1.41
33 7.15 1.12 8.91 1.45 11.3 1.98 12.5 2.27 13.6 2.58 16.0 3.25 16.7 3.39 33 3.57 0.58 4.45 0.70 5.65 0.87 6.23 0.96 6.82 1.06 7.98 1.27 9.10 1.49
35 7.15 1.18 8.91 1.54 11.3 2.10 12.5 2.41 13.6 2.74 16.0 3.46 16.4 3.51 35 3.57 0.61 4.45 0.73 5.65 0.92 6.23 1.02 6.82 1.12 7.98 1.35 9.10 1.58
37 7.15 1.25 8.91 1.64 11.3 2.24 12.5 2.57 13.6 2.92 15.7 3.60 16.1 3.63 37 3.57 0.64 4.45 0.77 5.65 0.97 6.23 1.08 6.82 1.19 7.98 1.43 9.10 1.68
39 7.15 1.33 8.91 1.73 11.3 2.37 12.5 2.73 13.6 3.11 15.5 3.72 15.9 3.76 39 3.57 0.68 4.45 0.81 5.65 1.02 6.23 1.14 6.82 1.26 7.98 1.51 9.10 1.78
10 6.43 0.72 8.02 0.89 10.2 1.12 11.2 1.25 12.3 1.38 14.4 1.64 16.4 1.91
12 6.43 0.73 8.02 0.90 10.2 1.14 11.2 1.27 12.3 1.40 14.4 1.67 16.4 1.95 TC: Total capacity: kW
14 6.43 0.74 8.02 0.91 10.2 1.16 11.2 1.29 12.3 1.43 14.4 1.71 16.4 1.98 PI: Power input: kW (Compressor+Outdoor fan motor)
16 6.43 0.76 8.02 0.93 10.2 1.18 11.2 1.32 12.3 1.45 14.4 1.74 16.4 2.02 Notes: 1. This table shows the average value of conditions which may occur.
18 6.43 0.77 8.02 0.94 10.2 1.21 11.2 1.34 12.3 1.48 14.4 1.77 16.4 2.06 2. This table indicates the situation of 50~130% combination of indoor units.
20 6.43 0.78 8.02 0.96 10.2 1.23 11.2 1.37 12.3 1.51 14.4 1.81 16.4 2.18 3. If connecting the indoor units over 130% of outdoor unit capacity, capacity of
21 6.43 0.79 8.02 0.97 10.2 1.24 11.2 1.38 12.3 1.53 14.4 1.87 16.4 2.26 indoor unit will decrease.
90% 23 6.43 0.80 8.02 0.99 10.2 1.26 11.2 1.43 12.3 1.61 14.4 2.00 16.4 2.42 4. shows rated condition.
(135) 25 6.43 0.81 8.02 1.01 10.2 1.34 11.2 1.52 12.3 1.72 14.4 2.14 16.4 2.59
27 6.43 0.84 8.02 1.07 10.2 1.43 11.2 1.62 12.3 1.83 14.4 2.29 16.4 2.77
29 6.43 0.89 8.02 1.14 10.2 1.52 11.2 1.73 12.3 1.96 14.4 2.44 16.4 2.96
31 6.43 0.94 8.02 1.21 10.2 1.62 11.2 1.84 12.3 2.08 14.4 2.60 16.4 3.16
33 6.43 1.00 8.02 1.28 10.2 1.72 11.2 1.96 12.3 2.22 14.4 2.78 16.3 3.36
35 6.43 1.05 8.02 1.36 10.2 1.83 11.2 2.08 12.3 2.36 14.4 2.96 16.1 3.48
37 6.43 1.11 8.02 1.44 10.2 1.94 11.2 2.21 12.3 2.51 14.4 3.15 15.8 3.61
39 6.43 1.18 8.02 1.52 10.2 2.06 11.2 2.35 12.3 2.67 14.4 3.36 15.5 3.73
444 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 445
Capacity Tables (Standard Type) EDIN341424
446 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 447
Capacity Tables (Standard Type) EDIN341424
448 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 449
Capacity Tables (Standard Type) EDIN341424
450 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 451
Capacity Tables (Standard Type) EDIN341424
452 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 453
Capacity Tables (Standard Type) EDIN341424
454 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 455
Capacity Tables (Standard Type) EDIN341424
456 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 457
Capacity Tables (Standard Type) EDIN341424
458 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 459
Capacity Tables (Standard Type) EDIN341424
460 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 461
Capacity Tables (Standard Type) EDIN341424
462 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 463
Capacity Tables (Standard Type) EDIN341424
464 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 465
Capacity Tables (Standard Type) EDIN341424
466 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 467
Capacity Tables (Standard Type) EDIN341424
468 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 469
Capacity Tables (Standard Type) EDIN341424
470 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 471
Capacity Tables (Standard Type) EDIN341424
472 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 473
Capacity Tables (Standard Type) EDIN341424
474 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 475
Capacity Tables (Standard Type) EDIN341424
476 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 477
Capacity Tables (Standard Type) EDIN341424
478 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 479
Capacity Tables (Standard Type) EDIN341424
480 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 481
Capacity Tables (Standard Type) EDIN341424
482 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 483
Capacity Tables (Standard Type) EDIN341424
484 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 485
Capacity Tables (Standard Type) EDIN341424
486 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 487
Capacity Tables (Standard Type) EDIN341424
488 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 489
Capacity Tables (Standard Type) EDIN341424
490 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 491
Capacity Tables (Standard Type) EDIN341424
492 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 493
Capacity Tables (Standard Type) EDIN341424
494 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 495
Capacity Tables (Standard Type) EDIN341424
496 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 497
Capacity Tables (Standard Type) EDIN341424
498 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 499
Capacity Tables (Standard Type) EDIN341424
3D086173A
500 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ10TRY6
3D086174A
17
RXYQ-T(N)RY6 501
Capacity Tables (Standard Type) EDIN341424
3D086178
502 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ16TRY6
3D086183
17
RXYQ-T(N)RY6 503
Capacity Tables (Standard Type) EDIN341424
3D086184
504 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
3D086186
17
RXYQ-T(N)RY6 505
Capacity Tables (Standard Type) EDIN341424
RXYQ22TNRY6
3D086185
506 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ46TNRY6
3D086189
17
RXYQ-T(N)RY6 507
Capacity Tables (Standard Type) EDIN341424
RXYQ48TNRY6
3D086190
508 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ50TNRY6
3D086200
17
RXYQ-T(N)RY6 509
Capacity Tables (Standard Type) EDIN341424
RXYQ52TNRY6
3D086201
510 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ54TNRY6
3D086242
17
RXYQ-T(N)RY6 511
Capacity Tables (Standard Type) EDIN341424
RXYQ56TNRY6 / RXYQ58TNRY6
3D086243
512 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ60TNRY6
3D086244
17
RXYQ-T(N)RY6 513
Capacity Tables (Standard Type) EDIN341424
Formula
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation = C
A=B×C
Note:
It will be seen from the figure above that the integrated heating capacity expresses the integrated heating capacity for
a single cycle (from defrosting operation to defrosting operation) in terms of time.
Please take note that when there is an accumulation of snow against the outside surface of the outdoor unit heat
exchanger there will always be a temporary reduction in capacity although this will, of course, vary in degree in
accordance with a number of other factors such as the outdoor temperature (°CDB), relative humidity (RH) and
the amount of frosting which occurs.
514 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
9.6 Cooling Part Load Performance for VRV Indoor Units Only
RXYQ-T(N)RY6 515
Capacity Tables (Standard Type) EDIN341424
516 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 517
Capacity Tables (Standard Type) EDIN341424
518 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 519
Capacity Tables (Standard Type) EDIN341424
520 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
9.7 Heating Part Load Performance for VRV Indoor Units Only
RXYQ-T(N)RY6 521
Capacity Tables (Standard Type) EDIN341424
522 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 523
Capacity Tables (Standard Type) EDIN341424
524 RXYQ-T(N)RY6
EDIN341424 Capacity Tables (Standard Type)
RXYQ-T(N)RY6 525
Capacity Tables (Standard Type) EDIN341424
526 RXYQ-T(N)RY6
EDIN341424 Operation Limits
Heating
3D092065
17
RXYQ-T(N)RY6 527
Sound Levels EDIN341424
528 RXYQ-T(N)RY6
EDIN341424 Accessories
12. Accessories
12.1 Optional Accessories
RXYQ6TRY6(E) RXYQ14TRY6(E)
Optional accessories RXYQ8TRY6(E) RXYQ12TRY6(E)
RXYQ16TRY6(E)
RXYQ10TRY6(E)
KHRP26M22H
(Max. 4 branch), KHRP26M22H, KHRP26M33H, KHRP26M72H
Refnet header
Distributive KHRP26M33H (Max. 4 branch) (Max. 8 branch) (Max. 8 branch)
Piping (Max. 8 branch)
KHRP26A22T,
Refnet joint KHRP26A22T, KHRP26A33T, KHRP26A72T
KHRP26A33T
Cool/Heat selector KRC19-26A
C: 3D085855B
RXYQ46TNRY6(E)
RXYQ48TNRY6(E)
RXYQ50TNRY6(E)
Optional accessories RXYQ34TNRY6(E) RXYQ38TNRY6(E) RXYQ42TNRY6(E) RXYQ52TNRY6(E)
RXYQ36TNRY6(E) RXYQ40TNRY6(E) RXYQ44TNRY6(E) RXYQ54TNRY6(E)
RXYQ56TNRY6(E)
RXYQ58TNRY6(E)
RXYQ60TNRY6(E)
KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Distributive Refnet header
(Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
Piping
Refnet joint KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
Pipe size reducer KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P151
Cool/Heat selector KRC19-26A
C: 3D085855B
17
RXYQ-T(N)RY6 529
Accessories EDIN341424
530 RXYQ-T(N)RY6
EDIN341424
Part 6
RXYQ-T(S)RY6
Heat Pump 50Hz
Space Saving Type
1. Specifications ......................................................................................532
1.1 Heat Pump 50Hz Space Saving Type (RXYQ-T(S)RY6) .....................532
2. Dimensions .........................................................................................541
2.1 Independent Unit ..................................................................................541
2.2 Combination Unit..................................................................................542
3. Service Space .....................................................................................547
4. Piping Diagrams..................................................................................548
5. Wiring Diagrams..................................................................................549
6. Field Wiring .........................................................................................551
7. Electric Characteristics........................................................................554
8. Safety Devices Setting ........................................................................556
9. Capacity Tables (Space Saving Type)................................................557
9.1 Cooling Capacity for VRV Indoor Units Only (Te: 6ºC) ........................557
9.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC) ........................574
9.3 Heating Capacity ..................................................................................591
9.4 Capacity Correction Factor...................................................................608
9.5 Notes for Heating Capacity Characteristics (Heat Pump) ....................615
9.6 Cooling Part Load Performance for VRV Indoor Units Only.................616
9.7 Heating Part Load Performance for VRV Indoor Units Only ................618
10.Operation Limits ..................................................................................620
11.Sound Levels ......................................................................................621
11.1 Overall ..................................................................................................621
11.2 Octave Band Level ...............................................................................621
12.Accessories.........................................................................................622
12.1 Optional Accessories............................................................................622
18
RXYQ-T(S)RY6 531
Specifications EDIN341424
1. Specifications
1.1 Heat Pump 50Hz Space Saving Type (RXYQ-T(S)RY6)
Model Name (Combination Unit) RXYQ18TRY6(E) RXYQ20TRY6(E)
Power Supply 3 phase, 380-415V, 50Hz 3 phase, 380-415V, 50Hz
kcal/h 43,000 48,200
1 Cooling Capacity Btu/h 171,000 191,000
kW 50.0 56.0
kcal/h 48,200 54,200
2 Heating Capacity Btu/h 191,000 215,000
kW 56.0 63.0
Casing Color Ivory white (5Y7.5/1) Ivory white (5Y7.5/1)
Dimensions: (H×W×D) mm 1,657×1,240×765 1,657×1,240×765
Heat Exchanger Cross fin coil Cross fin coil
Type Hermetically sealed scroll type Hermetically sealed scroll type
Displacement m³/h 16.27+17.54 16.90+26.28
Number of Revolutions r/min 7,680+8,280 7,980+8,250
Comp.
Motor Output×
kW (4.4×1)+(4.0×1) (4.6×1)+(5.5×1)
Number of Units
Starting Method Soft start Soft start
Type Propeller fan Propeller fan
Motor Output kW 0.75×2 0.75×2
Fan
Airflow Rate m³/min 233 268
Drive Direct drive Direct drive
Connecting Liquid Pipe mm φ15.9 C1220T (Brazing connection) φ15.9 C1220T (Brazing connection)
Pipes Gas Pipe mm φ28.6 C1220T (Brazing connection) φ28.6 C1220T (Brazing connection)
Mass kg 300 320
3 Sound Pressure Level dB(A) 62 65
High pressure switch, Fan driver overload protector, High pressure switch, Fan driver overload protector,
Safety Devices Overcurrent relay, Inverter overload protector, Overvoltage Overcurrent relay, Inverter overload protector, Overvoltage
protector protector
Capacity Control % 10-100 8-100
Refrigerant Name R410A R410A
Refrigerant Charge kg 11.7 11.8
Control Electronic expansion valve Electronic expansion valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Installation manual, Operation manual, Connection pipes, Installation manual, Operation manual, Connection pipes,
Standard Accessories Clamps Clamps
Drawing No. C: 4D088880 C: 4D088874
532 RXYQ-T(S)RY6
EDIN341424 Specifications
18
RXYQ-T(S)RY6 533
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
534 RXYQ-T(S)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
18
RXYQ-T(S)RY6 535
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
536 RXYQ-T(S)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
18
RXYQ-T(S)RY6 537
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
538 RXYQ-T(S)RY6
EDIN341424 Specifications
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
18
RXYQ-T(S)RY6 539
Specifications EDIN341424
Notes:
Conversion Formulae
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level difference: 0m.
2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference: 0m. kcal/h=kW×860
Btu/h=kW×3412
3. Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5m. cfm=m³/min×35.3
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
4. Refer to Capacity Tables for the power input (PI) (Compressor + Outdoor fan motor).
5. Models with (E) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric
component box, in addition to the fins of the heat exchanger. These models are designed specifically for use in areas which are subject to
salt damage and atmospheric pollution. Please contact Daikin for more information.
540 RXYQ-T(S)RY6
EDIN341424 Dimensions
2. Dimensions
2.1 Independent Unit
RXYQ18TRY6 / RXYQ20TRY6
Unit (mm)
3D084507C
18
RXYQ-T(S)RY6 541
Dimensions EDIN341424
RXYQ22TSRY6 / RXYQ24TSRY6
Unit (mm)
3D088931
542 RXYQ-T(S)RY6
EDIN341424 Dimensions
3D089394
18
RXYQ-T(S)RY6 543
Dimensions EDIN341424
3D088932
544 RXYQ-T(S)RY6
EDIN341424 Dimensions
RXYQ42TSRY6 / RXYQ44TSRY6
Unit (mm)
3D089374
18
RXYQ-T(S)RY6 545
Dimensions EDIN341424
3D089381
546 RXYQ-T(S)RY6
EDIN341424 Service Space
3. Service Space
RXYQ18TRY6 / RXYQ20TRY6 / RXYQ22TSRY6 / RXYQ24TSRY6 / RXYQ26TSRY6 /
RXYQ28TSRY6 / RXYQ30TSRY6 / RXYQ32TSRY6 / RXYQ34TSRY6 / RXYQ36TSRY6 / RXYQ38TSRY6 /
RXYQ40TSRY6 / RXYQ42TSRY6 / RXYQ44TSRY6 / RXYQ46TSRY6 / RXYQ48TSRY6 / RXYQ50TSRY6
Unit (mm)
3D084449A
18
RXYQ-T(S)RY6 547
Piping Diagrams EDIN341424
4. Piping Diagrams
RXYQ18TRY6 / RXYQ20TRY6
3D085859A
548 RXYQ-T(S)RY6
EDIN341424 Wiring Diagrams
5. Wiring Diagrams
RXYQ18TRY6
2D089046D
18
RXYQ-T(S)RY6 549
Wiring Diagrams EDIN341424
RXYQ20TRY6
2D089047A
550 RXYQ-T(S)RY6
EDIN341424 Field Wiring
6. Field Wiring
RXYQ18TRY6 / RXYQ20TRY6
3D084395A
18
RXYQ-T(S)RY6 551
Field Wiring EDIN341424
3D084407A
552 RXYQ-T(S)RY6
EDIN341424 Field Wiring
3D084410A
18
RXYQ-T(S)RY6 553
Electric Characteristics EDIN341424
7. Electric Characteristics
RXYQ18TRY6 / RXYQ20TRY6 / RXYQ22TSRY6 / RXYQ24TSRY6 / RXYQ26TSRY6 / RXYQ28TSRY6 /
RXYQ30TSRY6 / RXYQ32TSRY6 / RXYQ34TSRY6
3D088896A
554 RXYQ-T(S)RY6
EDIN341424 Electric Characteristics
3D088897A
18
RXYQ-T(S)RY6 555
Safety Devices Setting EDIN341424
556 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 557
Capacity Tables (Space Saving Type) EDIN341424
558 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 559
Capacity Tables (Space Saving Type) EDIN341424
560 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 561
Capacity Tables (Space Saving Type) EDIN341424
562 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 563
Capacity Tables (Space Saving Type) EDIN341424
564 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 565
Capacity Tables (Space Saving Type) EDIN341424
566 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 567
Capacity Tables (Space Saving Type) EDIN341424
568 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 569
Capacity Tables (Space Saving Type) EDIN341424
570 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 571
Capacity Tables (Space Saving Type) EDIN341424
572 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 573
Capacity Tables (Space Saving Type) EDIN341424
9.2 Cooling Capacity for VRV Indoor Units Only (Te: 9ºC)
When only VRV indoor units are connected
RXYQ18TRY6 Cooling capacity (Te: 9ºC)
Indoor air temp. (°CWB) Indoor air temp. (°CWB)
Combina- Outdoor Combina- Outdoor
tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0 tion (%) air 14.0 16.0 18.0 19.0 20.0 22.0 24.0
(Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI (Capacity temp. TC PI TC PI TC PI TC PI TC PI TC PI TC PI
index) °CDB kW kW index) °CDB kW kW
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
10 29.0 4.14 36.2 5.22 45.9 6.80 50.6 7.62 55.4 8.46 62.9 9.62 64.6 9.20 10 17.9 2.65 22.3 3.20 28.2 4.02 31.1 4.45 34.1 4.89 39.9 5.81 45.5 6.74
12 29.0 4.20 36.2 5.31 45.9 6.93 50.6 7.76 55.4 8.62 62.1 9.57 63.8 9.14 12 17.9 2.68 22.3 3.25 28.2 4.09 31.1 4.52 34.1 4.98 39.9 5.92 45.5 6.86
14 29.0 4.28 36.2 5.41 45.9 7.06 50.6 7.91 55.4 8.78 61.3 9.52 63.0 9.20 14 17.9 2.72 22.3 3.30 28.2 4.16 31.1 4.60 34.1 5.07 39.9 6.03 45.5 6.99
16 29.0 4.35 36.2 5.51 45.9 7.20 50.6 8.07 55.4 8.95 60.5 9.60 62.2 9.69 16 17.9 2.76 22.3 3.35 28.2 4.23 31.1 4.68 34.1 5.16 39.9 6.14 45.5 7.13
18 29.0 4.43 36.2 5.61 45.9 7.34 50.6 8.23 55.4 9.22 59.7 10.1 61.4 10.2 18 17.9 2.80 22.3 3.40 28.2 4.30 31.1 4.77 34.1 5.25 39.9 6.26 45.5 7.27
20 29.0 4.51 36.2 5.72 45.9 7.52 50.6 8.67 55.4 9.91 58.9 10.6 60.6 10.7 20 17.9 2.84 22.3 3.46 28.2 4.38 31.1 4.86 34.1 5.35 39.9 6.38 45.5 7.43
21 29.0 4.55 36.2 5.78 45.9 7.79 50.6 8.98 55.4 10.3 58.5 10.8 60.2 10.9 21 17.9 2.86 22.3 3.49 28.2 4.42 31.1 4.90 34.1 5.41 39.9 6.44 45.5 7.70
130% 23 29.0 4.64 36.2 6.02 45.9 8.34 50.6 9.63 55.4 11.0 57.7 11.3 59.4 11.4 80% 23 17.9 2.90 22.3 3.55 28.2 4.50 31.1 5.00 34.1 5.56 39.9 6.86 45.5 8.24
(585) 25 29.0 4.84 36.2 6.42 45.9 8.92 50.6 10.3 55.1 11.7 56.8 11.8 58.5 11.9 (360) 25 17.9 2.95 22.3 3.61 28.2 4.68 31.1 5.29 34.1 5.93 39.9 7.33 45.5 8.82
27 29.0 5.16 36.2 6.85 45.9 9.54 50.6 11.0 54.3 12.2 56.0 12.3 57.7 12.5 27 17.9 3.01 22.3 3.79 28.2 4.98 31.1 5.63 34.1 6.32 39.9 7.82 45.5 9.42
29 29.0 5.48 36.2 7.30 45.9 10.2 50.6 11.8 53.4 12.7 55.2 12.8 56.9 13.0 29 17.9 3.19 22.3 4.02 28.2 5.30 31.1 5.99 34.1 6.74 39.9 8.34 45.5 10.1
31 29.0 5.83 36.2 7.77 45.9 10.9 50.6 12.6 52.6 13.2 54.4 13.3 56.1 13.5 31 17.9 3.37 22.3 4.26 28.2 5.63 31.1 6.37 34.1 7.17 39.9 8.89 45.5 10.7
33 29.0 6.19 36.2 8.27 45.9 11.6 50.6 13.4 51.8 13.7 53.6 13.8 55.3 14.0 33 17.9 3.56 22.3 4.51 28.2 5.97 31.1 6.77 34.1 7.62 39.9 9.47 45.5 11.4
35 29.0 6.56 36.2 8.79 45.9 12.3 50.1 14.1 51.0 14.1 52.8 14.3 54.5 14.5 35 17.9 3.76 22.3 4.77 28.2 6.34 31.1 7.19 34.1 8.10 39.9 10.1 45.5 12.2
37 29.0 6.96 36.2 9.35 45.9 13.1 49.3 14.6 50.2 14.6 52.0 14.8 53.7 15.0 37 17.9 3.97 22.3 5.05 28.2 6.72 31.1 7.63 34.1 8.61 39.9 10.7 45.5 13.0
39 29.0 7.38 36.2 9.94 45.9 14.0 48.5 15.1 49.4 15.2 51.1 15.4 52.8 15.5 39 17.9 4.19 22.3 5.34 28.2 7.12 31.1 8.10 34.1 9.14 39.9 11.4 45.5 13.8
10 26.8 3.82 33.4 4.79 42.3 6.21 46.7 6.95 51.1 7.71 59.8 9.25 63.6 9.47 10 15.6 2.38 19.5 2.85 24.7 3.53 27.3 3.88 29.8 4.25 34.9 5.02 39.8 5.80
12 26.8 3.88 33.4 4.87 42.3 6.33 46.7 7.08 51.1 7.85 59.8 9.42 62.8 9.41 12 15.6 2.41 19.5 2.89 24.7 3.58 27.3 3.95 29.8 4.32 34.9 5.11 39.8 5.90
14 26.8 3.94 33.4 4.96 42.3 6.45 46.7 7.21 51.1 8.00 59.8 9.60 61.9 9.36 14 15.6 2.44 19.5 2.93 24.7 3.64 27.3 4.01 29.8 4.40 34.9 5.20 39.8 6.01
16 26.8 4.01 33.4 5.05 42.3 6.57 46.7 7.35 51.1 8.16 59.6 9.71 61.1 9.63 16 15.6 2.47 19.5 2.97 24.7 3.70 27.3 4.08 29.8 4.47 34.9 5.29 39.8 6.12
18 26.8 4.08 33.4 5.14 42.3 6.70 46.7 7.50 51.1 8.32 58.8 10.0 60.3 10.1 18 15.6 2.51 19.5 3.01 24.7 3.76 27.3 4.15 29.8 4.55 34.9 5.39 39.8 6.24
20 26.8 4.15 33.4 5.24 42.3 6.83 46.7 7.72 51.1 8.80 57.9 10.5 59.5 10.6 20 15.6 2.54 19.5 3.06 24.7 3.82 27.3 4.22 29.8 4.64 34.9 5.50 39.8 6.37
21 26.8 4.19 33.4 5.29 42.3 6.96 46.7 8.00 51.1 9.11 57.5 10.8 59.1 10.9 21 15.6 2.56 19.5 3.08 24.7 3.86 27.3 4.26 29.8 4.68 34.9 5.55 39.8 6.43
120% 23 26.8 4.26 33.4 5.42 42.3 7.45 46.7 8.57 51.1 9.77 56.7 11.3 58.3 11.4 70% 23 15.6 2.60 19.5 3.13 24.7 3.93 27.3 4.34 29.8 4.77 34.9 5.73 39.8 6.84
(540) 25 26.8 4.40 33.4 5.78 42.3 7.96 46.7 9.17 51.1 10.5 55.9 11.7 57.5 11.9 (315) 25 15.6 2.63 19.5 3.19 24.7 4.00 27.3 4.49 29.8 5.01 34.9 6.12 39.8 7.31
27 26.8 4.68 33.4 6.16 42.3 8.50 46.7 9.80 51.1 11.2 55.1 12.2 56.7 12.4 27 15.6 2.67 19.5 3.29 24.7 4.25 27.3 4.77 29.8 5.33 34.9 6.53 39.8 7.80
29 26.8 4.97 33.4 6.56 42.3 9.07 46.7 10.5 51.1 12.0 54.3 12.7 55.8 12.9 29 15.6 2.81 19.5 3.48 24.7 4.51 27.3 5.07 29.8 5.67 34.9 6.95 39.8 8.32
31 26.8 5.28 33.4 6.98 42.3 9.67 46.7 11.2 51.1 12.8 53.5 13.2 55.0 13.4 31 15.6 2.97 19.5 3.68 24.7 4.79 27.3 5.39 29.8 6.03 34.9 7.40 39.8 8.86
33 26.8 5.60 33.4 7.42 42.3 10.3 46.7 11.9 51.0 13.6 52.7 13.7 54.2 13.9 33 15.6 3.13 19.5 3.90 24.7 5.08 27.3 5.72 29.8 6.40 34.9 7.87 39.8 9.44
35 26.8 5.94 33.4 7.89 42.3 11.0 46.7 12.7 50.2 14.1 51.8 14.2 53.4 14.4 35 15.6 3.30 19.5 4.12 24.7 5.38 27.3 6.06 29.8 6.79 34.9 8.37 39.8 10.0
37 26.8 6.29 33.4 8.38 42.3 11.7 46.7 13.5 49.4 14.6 51.0 14.7 52.6 14.9 37 15.6 3.48 19.5 4.35 24.7 5.70 27.3 6.43 29.8 7.21 34.9 8.89 39.8 10.7
39 26.8 6.67 33.4 8.90 42.3 12.4 46.7 14.4 48.6 15.1 50.2 15.2 51.8 15.4 39 15.6 3.66 19.5 4.59 24.7 6.03 27.3 6.81 29.8 7.65 34.9 9.45 39.8 11.4
10 24.6 3.51 30.6 4.37 38.8 5.64 42.8 6.29 46.9 6.97 54.8 8.36 62.5 9.73 10 13.4 2.13 16.7 2.51 21.2 3.06 23.4 3.35 25.6 3.65 29.9 4.27 34.1 4.90
12 24.6 3.56 30.6 4.44 38.8 5.74 42.8 6.41 46.9 7.10 54.8 8.52 61.7 9.68 12 13.4 2.16 16.7 2.54 21.2 3.10 23.4 3.40 25.6 3.70 29.9 4.34 34.1 4.98
14 24.6 3.62 30.6 4.52 38.8 5.84 42.8 6.53 46.9 7.24 54.8 8.68 60.9 9.63 14 13.4 2.18 16.7 2.57 21.2 3.15 23.4 3.45 25.6 3.76 29.9 4.41 34.1 5.07
16 24.6 3.68 30.6 4.60 38.8 5.95 42.8 6.66 46.9 7.38 54.8 8.85 60.1 9.58 16 13.4 2.21 16.7 2.61 21.2 3.20 23.4 3.51 25.6 3.83 29.9 4.49 34.1 5.16
18 24.6 3.74 30.6 4.68 38.8 6.07 42.8 6.79 46.9 7.52 54.8 9.08 59.3 10.1 18 13.4 2.23 16.7 2.64 21.2 3.25 23.4 3.56 25.6 3.89 29.9 4.57 34.1 5.26
20 24.6 3.80 30.6 4.77 38.8 6.19 42.8 6.92 46.9 7.76 54.8 9.76 58.4 10.5 20 13.4 2.26 16.7 2.68 21.2 3.30 23.4 3.62 25.6 3.96 29.9 4.65 34.1 5.36
21 24.6 3.84 30.6 4.81 38.8 6.25 42.8 7.07 46.9 8.03 54.8 10.1 58.0 10.8 21 13.4 2.28 16.7 2.70 21.2 3.33 23.4 3.65 25.6 3.99 29.9 4.70 34.1 5.41
110% 23 24.6 3.90 30.6 4.91 38.8 6.61 42.8 7.57 46.9 8.60 54.8 10.8 57.2 11.3 60% 23 13.4 2.31 16.7 2.74 21.2 3.38 23.4 3.72 25.6 4.06 29.9 4.79 34.1 5.57
(495) 25 24.6 3.98 30.6 5.17 38.8 7.06 42.8 8.09 46.9 9.20 54.8 11.6 56.4 11.8 (270) 25 13.4 2.34 16.7 2.78 21.2 3.44 23.4 3.78 25.6 4.16 29.9 5.03 34.1 5.94
27 24.6 4.23 30.6 5.51 38.8 7.53 42.8 8.64 46.9 9.84 54.2 12.2 55.6 12.3 27 13.4 2.37 16.7 2.83 21.2 3.58 23.4 3.99 25.6 4.42 29.9 5.35 34.1 6.33
29 24.6 4.49 30.6 5.86 38.8 8.03 42.8 9.22 46.9 10.5 53.3 12.7 54.8 12.8 29 13.4 2.46 16.7 2.99 21.2 3.80 23.4 4.24 25.6 4.70 29.9 5.69 34.1 6.74
31 24.6 4.76 30.6 6.23 38.8 8.56 42.8 9.83 46.9 11.2 52.5 13.1 54.0 13.3 31 13.4 2.59 16.7 3.16 21.2 4.02 23.4 4.49 25.6 4.99 29.9 6.05 34.1 7.18
33 24.6 5.04 30.6 6.62 38.8 9.11 42.8 10.5 46.9 12.0 51.7 13.6 53.2 13.8 33 13.4 2.73 16.7 3.33 21.2 4.26 23.4 4.76 25.6 5.29 29.9 6.43 34.1 7.63
35 24.6 5.35 30.6 7.03 38.8 9.69 42.8 11.2 46.9 12.7 50.9 14.1 52.3 14.3 35 13.4 2.87 16.7 3.52 21.2 4.51 23.4 5.04 25.6 5.61 29.9 6.82 34.1 8.11
37 24.6 5.66 30.6 7.46 38.8 10.3 42.8 11.9 46.9 13.6 50.1 14.6 51.5 14.8 37 13.4 3.02 16.7 3.71 21.2 4.76 23.4 5.33 25.6 5.94 29.9 7.24 34.1 8.62
39 24.6 5.99 30.6 7.92 38.8 11.0 42.8 12.6 46.9 14.5 49.3 15.1 50.7 15.3 39 13.4 3.18 16.7 3.91 21.2 5.04 23.4 5.64 25.6 6.29 29.9 7.68 34.1 9.16
10 22.3 3.21 27.8 3.97 35.3 5.08 38.9 5.66 42.6 6.26 49.9 7.49 56.9 8.72 10 11.2 1.89 13.9 2.19 17.6 2.62 19.5 2.84 21.3 3.08 24.9 3.56 28.4 4.05
12 22.3 3.26 27.8 4.03 35.3 5.17 38.9 5.76 42.6 6.37 49.9 7.63 56.9 8.88 12 11.2 1.91 13.9 2.22 17.6 2.65 19.5 2.88 21.3 3.12 24.9 3.61 28.4 4.12
14 22.3 3.31 27.8 4.10 35.3 5.26 38.9 5.87 42.6 6.49 49.9 7.77 56.9 9.05 14 11.2 1.93 13.9 2.24 17.6 2.69 19.5 2.92 21.3 3.17 24.9 3.67 28.4 4.19
16 22.3 3.36 27.8 4.17 35.3 5.36 38.9 5.98 42.6 6.61 49.9 7.93 56.9 9.23 16 11.2 1.95 13.9 2.27 17.6 2.73 19.5 2.97 21.3 3.22 24.9 3.73 28.4 4.26
18 22.3 3.41 27.8 4.24 35.3 5.46 38.9 6.09 42.6 6.74 49.9 8.08 56.9 9.59 18 11.2 1.97 13.9 2.30 17.6 2.77 19.5 3.01 21.3 3.27 24.9 3.79 28.4 4.33
20 22.3 3.47 27.8 4.32 35.3 5.56 38.9 6.21 42.6 6.88 49.9 8.48 56.9 10.3 20 11.2 2.00 13.9 2.33 17.6 2.81 19.5 3.06 21.3 3.32 24.9 3.86 28.4 4.41
21 22.3 3.50 27.8 4.36 35.3 5.62 38.9 6.27 42.6 7.02 49.9 8.78 56.9 10.7 21 11.2 2.01 13.9 2.34 17.6 2.83 19.5 3.08 21.3 3.35 24.9 3.89 28.4 4.45
100% 23 22.3 3.56 27.8 4.44 35.3 5.82 38.9 6.64 42.6 7.51 49.9 9.41 56.2 11.2 50% 23 11.2 2.03 13.9 2.37 17.6 2.87 19.5 3.13 21.3 3.40 24.9 3.96 28.4 4.53
(450) 25 22.3 3.62 27.8 4.60 35.3 6.21 38.9 7.09 42.6 8.03 49.9 10.1 55.3 11.7 (225) 25 11.2 2.06 13.9 2.41 17.6 2.92 19.5 3.18 21.3 3.46 24.9 4.04 28.4 4.72
27 22.3 3.80 27.8 4.90 35.3 6.62 38.9 7.57 42.6 8.58 49.9 10.8 54.5 12.2 27 11.2 2.08 13.9 2.44 17.6 2.98 19.5 3.28 21.3 3.61 24.9 4.30 28.4 5.02
29 22.3 4.03 27.8 5.21 35.3 7.05 38.9 8.07 42.6 9.15 49.9 11.5 53.7 12.7 29 11.2 2.13 13.9 2.54 17.6 3.15 19.5 3.48 21.3 3.83 24.9 4.56 28.4 5.34
31 22.3 4.27 27.8 5.53 35.3 7.51 38.9 8.59 42.6 9.76 49.9 12.3 52.9 13.2 31 11.2 2.24 13.9 2.67 17.6 3.33 19.5 3.68 21.3 4.05 24.9 4.84 28.4 5.67
33 22.3 4.52 27.8 5.87 35.3 7.99 38.9 9.15 42.6 10.4 49.9 13.1 52.1 13.7 33 11.2 2.35 13.9 2.82 17.6 3.52 19.5 3.89 21.3 4.29 24.9 5.13 28.4 6.02
35 22.3 4.78 27.8 6.23 35.3 8.49 38.9 9.74 42.6 11.1 49.9 14.0 51.3 14.2 35 11.2 2.47 13.9 2.97 17.6 3.71 19.5 4.11 21.3 4.54 24.9 5.44 28.4 6.39
37 22.3 5.06 27.8 6.60 35.3 9.03 38.9 10.4 42.6 11.8 49.2 14.5 50.5 14.7 37 11.2 2.60 13.9 3.12 17.6 3.92 19.5 4.35 21.3 4.80 24.9 5.76 28.4 6.78
39 22.3 5.35 27.8 7.00 35.3 9.59 38.9 11.0 42.6 12.5 48.3 15.0 49.7 15.2 39 11.2 2.73 13.9 3.29 17.6 4.13 19.5 4.59 21.3 5.07 24.9 6.10 28.4 7.19
10 20.1 2.92 25.1 3.58 31.8 4.54 35.0 5.04 38.3 5.56 44.9 6.63 51.2 7.72
12 20.1 2.96 25.1 3.63 31.8 4.62 35.0 5.13 38.3 5.66 44.9 6.76 51.2 7.86 TC: Total capacity: kW
14 20.1 3.01 25.1 3.69 31.8 4.70 35.0 5.22 38.3 5.77 44.9 6.89 51.2 8.01 PI: Power input: kW (Compressor+Outdoor fan motor)
16 20.1 3.05 25.1 3.75 31.8 4.78 35.0 5.32 38.3 5.87 44.9 7.02 51.2 8.17 Notes: 1. This table shows the average value of conditions which may occur.
18 20.1 3.10 25.1 3.81 31.8 4.87 35.0 5.42 38.3 5.99 44.9 7.16 51.2 8.33 2. This table indicates the situation of 50~130% combination of indoor units.
20 20.1 3.15 25.1 3.88 31.8 4.96 35.0 5.52 38.3 6.10 44.9 7.30 51.2 8.81 3. If connecting the indoor units over 130% of outdoor unit capacity, capacity of
21 20.1 3.17 25.1 3.91 31.8 5.01 35.0 5.57 38.3 6.16 44.9 7.55 51.2 9.13 indoor unit will decrease.
90% 23 20.1 3.22 25.1 3.98 31.8 5.10 35.0 5.77 38.3 6.50 44.9 8.08 51.2 9.78 4. shows rated condition.
(405) 25 20.1 3.28 25.1 4.07 31.8 5.42 35.0 6.15 38.3 6.94 44.9 8.65 51.2 10.5
27 20.1 3.39 25.1 4.32 31.8 5.77 35.0 6.56 38.3 7.41 44.9 9.24 51.2 11.2
29 20.1 3.60 25.1 4.59 31.8 6.14 35.0 6.99 38.3 7.90 44.9 9.86 51.2 12.0
31 20.1 3.81 25.1 4.87 31.8 6.53 35.0 7.44 38.3 8.41 44.9 10.5 51.2 12.8
33 20.1 4.03 25.1 5.16 31.8 6.94 35.0 7.91 38.3 8.96 44.9 11.2 51.0 13.6
35 20.1 4.26 25.1 5.47 31.8 7.37 35.0 8.41 38.3 9.53 44.9 11.9 50.2 14.1
37 20.1 4.50 25.1 5.80 31.8 7.83 35.0 8.94 38.3 10.1 44.9 12.7 49.4 14.6
39 20.1 4.75 25.1 6.14 31.8 8.31 35.0 9.50 38.3 10.8 44.9 13.5 48.6 15.1
574 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 575
Capacity Tables (Space Saving Type) EDIN341424
576 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 577
Capacity Tables (Space Saving Type) EDIN341424
578 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 579
Capacity Tables (Space Saving Type) EDIN341424
580 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 581
Capacity Tables (Space Saving Type) EDIN341424
582 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 583
Capacity Tables (Space Saving Type) EDIN341424
584 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 585
Capacity Tables (Space Saving Type) EDIN341424
586 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 587
Capacity Tables (Space Saving Type) EDIN341424
588 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 589
Capacity Tables (Space Saving Type) EDIN341424
590 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 591
Capacity Tables (Space Saving Type) EDIN341424
592 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 593
Capacity Tables (Space Saving Type) EDIN341424
594 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 595
Capacity Tables (Space Saving Type) EDIN341424
596 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 597
Capacity Tables (Space Saving Type) EDIN341424
598 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 599
Capacity Tables (Space Saving Type) EDIN341424
600 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 601
Capacity Tables (Space Saving Type) EDIN341424
602 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 603
Capacity Tables (Space Saving Type) EDIN341424
604 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 605
Capacity Tables (Space Saving Type) EDIN341424
606 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 607
Capacity Tables (Space Saving Type) EDIN341424
3D086184
608 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
3D086186
18
RXYQ-T(S)RY6 609
Capacity Tables (Space Saving Type) EDIN341424
RXYQ22TSRY6
3D086185
610 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ24TSRY6 / RXYQ36TSRY6
3D086178
18
RXYQ-T(S)RY6 611
Capacity Tables (Space Saving Type) EDIN341424
RXYQ46TSRY6
3D086189
612 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ48TSRY6
3D086190
18
RXYQ-T(S)RY6 613
Capacity Tables (Space Saving Type) EDIN341424
RXYQ50TSRY6
3D086200
614 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
Formula
Integrated heating capacity = A
Value given in table of capacity characteristics = B
Integrating correction factor for frost accumulation = C
A=B×C
Note:
It will be seen from the figure above that the integrated heating capacity expresses the integrated heating capacity for
a single cycle (from defrosting operation to defrosting operation) in terms of time.
Please take note that when there is an accumulation of snow against the outside surface of the outdoor unit heat
exchanger there will always be a temporary reduction in capacity although this will, of course, vary in degree in
accordance with a number of other factors such as the outdoor temperature (°CDB), relative humidity (RH) and
the amount of frosting which occurs.
18
RXYQ-T(S)RY6 615
Capacity Tables (Space Saving Type) EDIN341424
9.6 Cooling Part Load Performance for VRV Indoor Units Only
616 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 617
Capacity Tables (Space Saving Type) EDIN341424
9.7 Heating Part Load Performance for VRV Indoor Units Only
618 RXYQ-T(S)RY6
EDIN341424 Capacity Tables (Space Saving Type)
RXYQ-T(S)RY6 619
Operation Limits EDIN341424
Heating
3D092065
620 RXYQ-T(S)RY6
EDIN341424 Sound Levels
Note:
Sound pressure level:
Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Location of microphone
RXYQ18TRY6 RXYQ20TRY6
4D084624A 4D084997A
18
RXYQ-T(S)RY6 621
Accessories EDIN341424
12. Accessories
12.1 Optional Accessories
RXYQ26TSRY6(E) RXYQ34TSRY6(E)
Optional accessories RXYQ28TSRY6(E) RXYQ36TSRY6(E)
RXYQ22TSRY6(E) RXYQ24TSRY6(E) RXYQ30TSRY6(E) RXYQ38TSRY6(E)
RXYQ32TSRY6(E) RXYQ40TSRY6(E)
KHRP26M22H
(Max. 4 branch),
KHRP26M33H KHRP26M22H, KHRP26M33H, KHRP26M72H, KHRP26M73H
Refnet header (Max. 4 branch) (Max. 8 branch) (Max. 8 branch) (Max. 8 branch)
(Max. 8 branch),
Distributive KHRP26M72H
Piping (Max. 8 branch)
KHRP26A22T,
Refnet joint KHRP26A33T, KHRP26A22T, KHRP26A33T, KHRP26A72T, KHRP26A73T
KHRP26A72T
Pipe size reducer — KHRP26M73TP, KHRP26M73HP
Outdoor unit multi connection piping kit BHFP22P100
Cool/Heat selector KRC19-26A
C: 3D085858B
RXYQ46TSRY6(E)
Optional accessories RXYQ42TSRY6(E)
RXYQ48TSRY6(E)
RXYQ44TSRY6(E)
RXYQ50TSRY6(E)
622 RXYQ-T(S)RY6
EDIN341424
Part 7
Installation of
Outdoor Units
1. Centre of Gravity .................................................................................624
2. Foundation of Units .............................................................................625
3. Installation Manual ..............................................................................626
3.1 RXYQ-TRY6.........................................................................................626
4. REFNET Pipe System.........................................................................667
4.1 Layout Example....................................................................................667
4.2 REFNET Joints and Headers ...............................................................669
5. REFNET Joint and Header .................................................................671
5.1 REFNET Joint (Branch Kit) ..................................................................671
5.2 REFNET Header (Branch Kit) ..............................................................674
5.3 Reducer................................................................................................677
5.4 Outdoor Unit Multi Connection Piping Kit .............................................678
6. Caution Label ......................................................................................684
6.1 RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6...........684
6.2 RXYQ14TRY6 / RXYQ16TRY6 / RXYQ18TRY6 / RXYQ20TRY6 ......688
19
1. Centre of Gravity
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6
Unit (mm)
4D085346
4D085343
2. Foundation of Units
RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6 / RXYQ14TRY6 / RXYQ16TRY6 / RXYQ18TRY6 /
RXYQ20TRY6
Unit (mm)
3D084454A
19
3. Installation Manual
3.1 RXYQ-TRY6
7 15
7 15
9
9 16 4
16 4
5 8 5 3
8 3 18
18
17 17
10 10
10
2 1
1 6 13 12
6
12
11 11
1 2
6 12 10 6 10
3
3
14
14
4 4
5 5
18
18
8
8
7
16
16
17
17
15 11 1 15 11 2 1
3 4
3P391148-1
Installation manual
Contents Page Thank you for purchasing this Daikin VRV IV system.
Installation manual.......................................................................... 1 The original instructions are written in English. All other languages
1. Definitions.................................................................................. 1 are translations of the original instructions.
1.1. Meaning of warnings and symbols................................................. 1
1.2. Meaning of used terms .................................................................. 2 CAREFULLY READ THESE INSTRUCTIONS BEFORE
2. General safety precautions........................................................ 2 INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL
2.1. Safety precautions ........................................................................ 2
AND HOW TO CONFIGURE THE UNIT PROPERLY.
2.2. Special notice of product ............................................................... 3 KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE
2.3. Disposal requirements ................................................................. 3 REFERENCE.
3. Introduction................................................................................ 4
3.1. General information ....................................................................... 4
3.2.
3.3.
Combination .................................................................................. 4
Scope of the manual ...................................................................... 5
1. Definitions
4. Accessories ............................................................................... 5
4.1. Accessories supplied with this unit ................................................ 5
4.2. Option accessory ...........................................................................6 1.1 Meaning of warnings and symbols
5. Overview of unit......................................................................... 6 Warnings in this manual are classified according to their severity and
5.1. Opening the unit............................................................................. 6 probability of occurrence.
5.2. Main components in the unit .......................................................... 6
5.3. Main components in the electrical component box ........................ 6
DANGER
6. Selecting an installation location ............................................... 7
6.1. General precautions on installation................................................ 7 Indicates an imminently hazardous situation which, if not
6.2. Weather related precautions .......................................................... 7 avoided, will result in death or serious injury.
6.3. Selecting a location in cold climates................................................ 8
7. Dimensions and service space.................................................. 8
WARNING
7.1. Dimensions of outdoor unit ............................................................ 8
7.2. Service space ................................................................................ 8 Indicates a potentially hazardous situation which, if not
8. Inspecting and handling the unit ................................................9 avoided, could result in death or serious injury.
8.1. Inspection....................................................................................... 9
8.2. Handling........................................................................................ 9
8.3. Installing the unit ............................................................................ 9 CAUTION
9. Refrigerant pipe size and allowable pipe length .......................10
Indicates a potentially hazardous situation which, if not
9.1. Selection of piping material...........................................................10
avoided, may result in minor or moderate injury. It may also
9.2. Selection of piping size .................................................................10
be used to alert against unsafe practices.
9.3. Selection of refrigerant branch kits .............................................. 11
9.4. System piping (length) limitations ................................................ 12
9.5. Multi system piping installation .................................................... 14
NOTICE
10. Precautions on refrigerant piping............................................. 15
10.1. Caution for brazing....................................................................... 15 Indicates situations that may result in equipment or
10.2. Connecting the refrigerant piping................................................. 16 property-damage accidents only.
10.3. Guidelines for handling stop valve ............................................... 18
10.4. Leak test and vacuum drying ....................................................... 19
11. Pipe insulation ......................................................................... 20 INFORMATION
12. Electrical wiring work ............................................................... 20 This symbol identifies useful tips or additional information.
12.1. Precautions on electrical wiring work ........................................... 20
12.2. System overview of field wiring.................................................... 21
12.3. Opening and closing the electrical component box ..................... 21
12.4. Requirements............................................................................... 22 Some types of danger are represented by special symbols:
12.5. Routing......................................................................................... 22
12.6. Connection................................................................................... 25 Electric current.
13. Making field settings ................................................................ 27
13.1. Accessing the push buttons on the logic board ........................... 27
13.2. Operating the push buttons and DIP switches on the logic board 27
Danger of burning and scalding.
14. Charging refrigerant................................................................. 29
14.1. Precautions .................................................................................. 29
14.2. Calculating the additional refrigerant charge ............................... 29
14.3. Method for adding refrigerant....................................................... 30
15. Monitoring function and field settings....................................... 32
15.1. Mode 1.......................................................................................... 32
15.2. Mode 2.......................................................................................... 33
15.3. Energy saving and optimum operation...... ... . .................................... 35
16. Test run.....................................................................................36
16.1. Test operation ...............................................................................36
16.2. Malfunction code list .....................................................................37
17. Operation of the unit ................................................................ 40
18. Caution for refrigerant leaks .................................................... 40
18.1. Introduction ...................................................................................40 19
18.2. Maximum concentration level .......................................................40
18.3. Procedure for checking maximum concentration..........................40
1
3P391148-1
Instruction manual specified for a certain product or application, Do not touch the refrigerant piping, water piping or internal
explaining how to install, configure and maintain it. parts during and immediately after operation. The piping
and internal parts may be hot or cold depending on the
Operation manual: working condition of the unit.
Instruction manual specified for a certain product or application, Your hand may suffer burns or frostbite if you touch the
explaining how to operate it. piping or internal parts. To avoid injury, give the piping and
Maintenance instructions: internal parts time to return to normal temperature or, if you
must touch them, be sure to wear protective gloves.
Instruction manual specified for a certain product or application,
which explains (if relevant) how to install, configure, operate and/or
Also, at least, following information shall be provided at an accessible
maintain the product or application.
place of the system:
Dealer: t Instructions for shutting down the system in case of an
Sales distributor for products as per the subject of this manual. emergency.
Installer:
t Name and address of fire department, police and hospital.
t Name, address and day and night telephone numbers for
Technical skilled person who is qualified to install products as per the obtaining service.
subject of this manual.
User:
Person who is owner of the product and/or operates the product. FIRST OF ALL
Service company:
t This document is an installation manual for the Daikin RXYQ
Series VRV Inverter. Before installing the unit, read this manual
Qualified company which can perform or coordinate the required thoroughly, and following the instructions contained in it. After
service to the unit. installation, do a test run to make sure the unit runs properly, and
then explain how to operate and take care of the unit to the
Applicable legislation:
customer, using the operation manual.
All international, European, national and local directives, laws, t Lastly, make sure the customer keeps this manual, along with
regulations and/or codes which are relevant and applicable for a theoperation manual, in a safe place.
certain product or domain. This manual does not describe how to install the indoor unit.
Accessories:
t Refer to the installation manual included with the indoor unit for
that.
Equipment which is delivered with the unit and which needs to be
installed according to instructions in the documentation. 2.1 Safety precautions
Optional equipment: Please read these “Safety precautions” carefully before installing
air conditioning unit and be sure to install it correctly.
Equipment which can optionally be combined to the products as per
After completing the installation, make sure that the unit operates
the subject of this manual.
properly during the start-up operation.
Field supply: Also, inform customers that they should store this installation
Equipment which needs to be installed according to instructions in manual along with the operation manual for future reference.
this manual, but which are not supplied by Daikin. After completing installation, conduct a trial operation to check for
faults and explain to the customer how to operate the air conditioner
and take care of it with the aid of operation manual. Ask the customer
to store the installation manual along with the operation manual for
2. General safety precautions future reference.
The precautions listed here are divided into the following four types.
They all cover very important topics, so be sure to follow them This air conditioner comes under the term “appliances not
carefully. accessible to the general public”.
Please instruct the customer on how to operate the unit and
DANGER: ELECTRICAL SHOCK keep it maintained.
Meaning of WARNING and CAUTION notices
Switch off all power supply before removing the electrical
component box service panel or before making any WARNING .....Failure to follow these instructions properly
connections or touching electrical parts. may result in personal injury or loss of life.
Do not touch any switch with wet fingers. Touching a switch CAUTION......Failure to observe these instructions properly
with wet fingers can cause electrical shock. Before touching may result in property damage or personal injury,
electrical parts, turn off all applicable power supply. which may be serious depending on the
circumstances.
To avoid electric shock, be sure to disconnect the power
supply 1 minute or more before servicing the electrical
parts. Even after 1 minute, always measure the voltage at
the terminals of the main terminal, main circuit capacitors
or electrical parts and, before touching, be sure that those
voltages are 50 V DC or less.
When service panels are removed, live parts can easily be
touched by accident. Never leave the unit unattended
during installation or servicing when the service panel is
removed.
2
3P391148-1
WARNING CAUTION
Ask your dealer or qualifies personnel to carry out installation work. While following the instructions in this installation manual, install
Do not attempt to install the air conditioner yourself. Improper drain piping to ensure proper drainage and insulate piping to prevent
installation may result in water leakage, electric shocks or fire. condensation.
Consult your local regarding what to do in case of refrigerant Improper drain piping may result in indoor water leakage and
leakage, when the air conditioner is to be installed in a small room, property damage.
it is necessary to take proper measures so that the amount of any Install the indoor and outdoor units, power cord and connecting
leaked refrigerant does not exceed the concentration limit in the wires at least 1 meter away from televisions or radios to prevent
event of leakage. Otherwise, this may lead to an accident due to picture interference and noise.
oxygen depletion. (Depending on the incoming signal strength, a distance of 1 meter
Install the air conditioner in accordance with the instructions in this may not be sufficient to eliminate noise.)
installation manual. Remote controller (wireless kit) transmitting distance can be shorter
Improper installation may result in water leakage, electric shocks than expected in rooms with electronic fluorescent lamps (inverter
or fire. or rapid start types).
When installing the unit in a small room, take measures against to Install the indoor unit as far away from fluorescent lamps as possible.
keep refrigerant concentration from exceeding allowable safety Make sure to provide for adequate measures in order to prevent
limits in the event of refrigerant leakage. that the outdoor unit be used as a shelter by samll animals.
Contact the place of purchase for more information. Excessive Small animals making contact with electrical parts can cause
refrigerant in a closed ambient can lead to oxygen deficiency. malfunctions, smoke or fire. Please instruct the customer to keep
Be sure to use only the specified accessories and parts for the area around the unit clean.
installation work. Install in a machine room that is free of moisture.
Failure to use the specified parts may result in the unit falling, The unit is designed for indoor use.
water leakage, electric shocks or fire. Do not install the air conditioner in the following locations:
Install the air conditioner on a foundation strong enough to 1. Where there is a high concentration of mineral oil spray or
withstand the weight of the unit. vapour (e.g. a kitchen).
A foundation of insufficient strength may result in the equipment Please pasts will deteriorate, parts may fall off and water
falling and causing injury. leakage could result.
Carry out the specified installation work after taking into account 2. Where corrosive gas, such as sulphurous acid gas, is produced.
strong winds, typhoons or earthquakes. Corroding of copper pipes or soldered parts may result in
Failure to do so during installation work may result in the unit falling refrigerant leakage.
and causing accidents. 3. Near machinery emitting electromagnetic radiation.
Make sure that a separate power supply circuit is provided for this Electromagnetic radiation may disturb the operation of the
unit and that all electrical work is carried out by qualified personnel control system and result in a malfunction of the unit.
according to local laws and regulations and this installation manual. 4. Where flammable gas may leak, where there is carbon fibre or
An insufficient power supply capacity or improper electrical ignitable dust suspensions in the air, or where volatile
construction may lead to electric shocks or fire. flammables such as paint thinner or gasoline are handled.
Make sure that all wiring is secured, the specified wires are used, Operating the unit in such conditions may result in fire.
and that there is no strain on the terminal connections or wires. In a domestic environment this product may cause radio
Improper connections or securing of wires may result in abnormal interference in which case the user may be required to take
heat build-up pr fire. adequate measures.
When wiring the power supply and connecting the ermote controller
wiring and transmission wiring, position the wires so that the 2.2 Special notice of product
EL.COMPO.BOX lid can be securely fastened.
Improper positioning of the EL.COMPO.BOX lid may result in
electric shocks, fire or the terminals overheating. VRV- V System use R410A refrigerant.
If refrigerant gas leaks during installation, ventilate the area The refrigerant R410A requires that strict precautions be
immediately. observed for keeping the system clean, dry and tightly sealed.
Toxic gas may be produced if the refrigerant comes into contact Read the chapter “REFRIGERANT PIPING” carefully and follow
with fire. these procedures correctly.
After completing installation, check for refrigerant gas leakage. A. Clean and dry
Toxic gas may be produced if the refrigerant gas leaks into the Strict measures must be taken to keep impurities (including
room and comes into contact with a source of fire, such as a fan SUNISO oil and other mineral oils as well as moisture) out of
heater, stove or cooker. the system.
Do not directly touch refrigerant that has leaked from refrigerant B. Tight sealed
pipes or other areas, as there is a danger of frostbite. Take care to keep the system tight when installing.
Be sure to switch off the unit before touching any electrical parts. R410A contains no chlorine, does not destroy the ozone layer
Do not allow children to climb on the outdoor unit and avoid placing and so does not reduce the earth’s protection against harmful
objects on the unit. ultraviolet radiation.
Injury may result if the unit becomes loose and falls. R410A will contribute only slightly to the greenhouse effect if
Be sure to earth the air conditioner. released into the atmosphere.
Do not earth the unit to a utility pipe, lightning conductor
or telephone earth lead.
[DESIGN PRESSURE]
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may cause Since design pressure is 4.0 MPa or 40 bar (for R407C units : 3.3 MPa
damage to the air conditioner. or 33 bar) the thickness of pipes must be greater than previously.
Be sure to install an earth leakage breaker. Since R410A is a mixed refrigerant, the required additional refrigerant
Failure to install an earth leakage breaker may result in electric must be charged in its liquid state. (If the system is charged with
shocks or fire. refrigerant in its gaseous state, due to compositions change, the system
will not function normally). The indoor units is designed for R410A use.
See the catalogue for indoor unit models that can be connected.
(Normal operation is not possible when connecting units that are
originally designed for other refrigerants)
3
3P391148-1
Depending on the type of outdoor unit which is chosen, some <Combination unit> <Independent unit>
functionality will or will not exist. It will be indicated throughout this
RXYQ6T RXYQ6T
installation manual and brought to your attention. Certain features
have exclusive model rights. RXYQ8T RXYQ8T
RXYQ10T RXYQ10T
These units have (in single use) heating capacities ranging from 18 RXYQ12T RXYQ12T
to 63 kW and cooling capacities rating from 16 to 56 kW. In multi
RXYQ14T RXYQ14T
combination the heating capacity can go up till 189 kW and in cooling
till 168 kW. RXYQ16T RXYQ16T
RXYQ18TN RXYQ8T + RXYQ10T
The outdoor unit is designed to work in heating mode at ambient RXYQ20TN RXYQ8T + RXYQ12T
temperatures from –20°C to 21°C and in cooling mode at ambient
RXYQ22TN RXYQ8T + RXYQ14T
temperatures from –5°C to 4°C.
RXYQ24TN RXYQ10T + RXYQ14T
NOTICE RXYQ26TN RXYQ12T + RXYQ14T
RXYQ28TN RXYQ14T + RXYQ14T
Design of the system must not be done at temperatures
below –15°C. RXYQ30TN RXYQ14T + RXYQ16T
RXYQ32TN RXYQ14T + RXYQ18T
1 RXYQ34TN RXYQ10T + RXYQ12T + RXYQ12T
8
RXYQ36TN RXYQ12T + RXYQ12T + RXYQ12T
RXYQ38TN RXYQ8T + RXYQ12T + RXYQ18T
RXYQ40TN RXYQ12T + RXYQ12T + RXYQ16T
2 3 3 4 3 3 RXYQ42TN RXYQ12T + RXYQ14T + RXYQ16T
5 RXYQ44TN RXYQ12T + RXYQ16T + RXYQ16T
RXYQ46TN RXYQ14T + RXYQ14T + RXYQ18T
6 6 7 6 6 RXYQ48TN RXYQ14T + RXYQ16T + RXYQ18T
RXYQ50TN RXYQ14T + RXYQ18T + RXYQ18T
1 VRV IV heat pump outdoor unit RXYQ52TN RXYQ16T + RXYQ18T + RXYQ18T
2 Refrigerant piping RXYQ54TN RXYQ18T + RXYQ18T + RXYQ18T
3 VRV indoor unit
4 BP box (required to connect Residential Air (RA) indoor units) RXYQ56TN RXYQ18T + RXYQ18T + RXYQ20T
5 Residential Air (RA) indoor units RXYQ58TN RXYQ18T + RXYQ20T + RXYQ20T
6 User interface (dedicated depending on indoor unit type) RXYQ60TN RXYQ20T + RXYQ20T + RXYQ20T
7 User interface (wireless, dedicated depending on indoor
unit type)
8 Cool/Heat changeover remote control switch 3.2.2 High COP Type
4
3P391148-1
<Combination unit> <Independent unit> s If the total capacity of the connected indoor units exceeds the
RXYQ22TH RXYQ6T + RXYQ8T + RXYQ8T capacity of the outdoor unit, cooling performance may drop
RXYQ8T + RXYQ8T + RXYQ8T when running the indoor units. See the capacity table in the
RXYQ24TH
Engineering Data Book for details.
RXYQ26TH RXYQ8T + RXYQ8T + RXYQ10T s There are restrictions on the refrigerant pipe connecting order
RXYQ28TH RXYQ8T + RXYQ8T + RXYQ12T between outdoor unit in the case of the multi system. Install so
RXYQ30TH RXYQ8T + RXYQ10T + RXYQ12T that the following restrLFWLRQVDUHVDWLV¿HG
RXYQ32TH RXYQ8T + RXYQ12T + RXYQ12T <Restrictions>
The capacities of outdoor units A, B and C mXVWIXO¿OOWKH
RXYQ34TH RXYQ8T + RXYQ12T + RXYQ14T following conditions.
RXYQ36TH RXYQ8T + RXYQ14T + RXYQ14T A≥B≥C
Outdoor Outdoor Outdoor
RXYQ38TH RXYQ12T + RXYQ12T + RXYQ14T unit A unit B unit C
RXYQ40TH RXYQ12T + RXYQ14T + RXYQ14T
RXYQ42TH RXYQ14T + RXYQ14T + RXYQ14T
to indoor unit
RXYQ44TH RXYQ14T + RXYQ14T + RXYQ16T
RXYQ46TH RXYQ14T + RXYQ16T + RXYQ16T Outdoor unit
multi connection Outdoor unit multi
RXYQ48TH RXYQ16T + RXYQ16T + RXYQ16T piping kit connection piping kit
RXYQ50TH RXYQ16T + RXYQ16T + RXYQ18T (first branch) (second branch)
(Outdoor unit) (Total capacity (Total quantity 3.3 Scope of the manual
of indoor units *1) of indoor units) This manual describes the procedures for handling, installing and
RXYQ18T .............. 225 ~ 585 (900) 29 (45) units connecting the VRV IV heat pump outdoor units. This manual has
RXYQ20T .............. 250 ~ 650 (1,000) 32 (50) units been prepared to ensure adequate maintenance of the unit, and it
will provide help in case problems occur.
RXYQ22TS .............. 275 ~ 715 (880) 35 (44) units
RXYQ24TS .............. 300 ~ 780 (960) 39 (48) units INFORMATION
RXYQ26TS .............. 325 ~ 845 (1,040) 42 (52) units
The installation of the indoor unit(s) is described in the indoor
RXYQ28TS .............. 350 ~ 910 (1,120) 45 (56) units
unit installation manual provided with the indoor units.
RXYQ30TS .............. 375 ~ 975 (1,200) 48 (60) units
RXYQ32TS .............. 400 ~ 1,040 (1,280) 52 (64) units
RXYQ34TS .............. 425 ~ 1,105 (1,360) 55 (64) units
4. Accessories
RXYQ36TS .............. 450 ~ 1,170 (1,440) 58 (64) units 4.1 Accessories supplied with this unit
RXYQ38TS .............. 475 ~ 1,235 (1,520) 61 (64) units RXYQ6~12 RXYQ14~20
RXYQ40TS .............. 500 ~ 1,300 (1,600) 64 (64) units
RXYQ42TS .............. 525 ~ 1,365 (1,365) 64 (64) units
RXYQ44TS .............. 550 ~ 1,430 (1,430) 64 (64) units
RXYQ46TS .............. 575 ~ 1,495 (1,495) 64 (64) units
RXYQ48TS .............. 600 ~ 1,560 (1,560) 64 (64) units
RXYQ50TS .............. 625 ~ 1,625 (1,625) 64 (64) units
RXYQ18T RXYQ18T See location 1 in the figure above for reference to where following
RXYQ20T RXYQ20T accessories are supplied with the unit.
RXYQ22TS RXYQ10T + RXYQ12T
RXYQ24TS RXYQ12T + RXYQ12T Tie wrap Tie wrap Tie wrap
RXYQ26TS RXYQ8T + RXYQ18T (1) (2) (3)
RXYQ28TS RXYQ12T + RXYQ16T
RXYQ30TS RXYQ12T + RXYQ18T Front connection
RXYQ32TS RXYQ12T + RXYQ20T
RXYQ34TS RXYQ16T + RXYQ18T
RXYQ36TS RXYQ18T + RXYQ18T
RXYQ38TS RXYQ18T + RXYQ20T
RXYQ40TS RXYQ20T + RXYQ20T
RXYQ42TS RXYQ12T + RXYQ12T + RXYQ18T
RXYQ44TS RXYQ12T + RXYQ12T + RXYQ20T
RXYQ46TS RXYQ12T + RXYQ16T + RXYQ18T
RXYQ48TS RXYQ12T + RXYQ18T + RXYQ18T Operation
Bottom Front Bottom manual
RXYQ50TS RXYQ12T + RXYQ18T + RXYQ20T connection connection connection Installation
manual
Note Caution
Be sure to connect an R410A indoor unit. label
See the catalog for indoor unit models which can be connected. (Addition
refrigerant
*1. Values inside brackets are based on connection of indoor units
6-8HP, 10HP 12HP, charge
rated at maximum capacity, 200% for single outdoor units,
160% for double outdoor units, and 130% for triple outdoor units.
20HP 14-18HP record) 19
NOTICE Note
When selecting the total capacity higher than mentioned in (a) For RXYQ20, Front connection pipe require the combination of
above table, cooling and heating capacity will drop. gas accessory pipe(1) and gas accessory pipe(2).
For additional information see technical engineering data.
5
3P391148-1
Make sure that any separate purchased accessories are designed for
use with R410A. 5.2.1 RXYQ* (6~12 HP)
Piping diagram
See figure 1.
5. Overview of unit
Outlook drawing
5.1 Opening the unit See figure 3.
To gain access to the unit, front plates need to be opened as follows: 5.2.2 RXYQ* (14~20 HP)
RXYQ6~12
12x 12x
Once the front plates open, the electrical component box can be
accessed by removing the electrical component box cover as follows.
RXYQ6~12 RXYQ14~20 1
6x 2
2x
4
For service purposes, the push buttons on the main PCB need to be
accessed. To access these push buttons, the electrical component
box cover does not need to be opened. See "13.Making field settings"
on page 27.
6
3P391148-1
RXYQ14~20 NOTICE
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
4 2 3 1 equipment, personal computers, etc.
2 5 (mm)
3 3
2
1 Main PCB. 4
2 Terminal block X1M: main terminal block which allows easy 4
connection of field wiring for power supply.
3 Terminal X1M on main PCB: terminal block for
transmission wiring. 6
4 Cable tie mountings: the cable tie mountings allow to fix 1
the field wiring with cable ties to the electrical component
box to ensure strain relief.
1 Personal computer or radio
2 Fuse
INFORMATION 3 Earth leakage protector
For more details refer to the wiring diagram of the units. 4 User interface
The wiring diagram is located on the inside of the electrical 5 Indoor unit
6 Outdoor unit
component box.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes
for power and transmission lines.
6. Selecting an installation location The refrigerant R410A itself is nontoxic, non-flammable and is
safe. If the refrigerant should leak however, its concentration
may exceed the allowable limit depending on room size. Due to
CAUTION
this, it could be necessary to take measures against leakage.
Appliance not accessible to the general public, install it in a Do not install in the following locations:
secured area, protected from easy access. - Locations where sulphurous acids and other corrosive gases
This unit, both indoor and outdoor, is suitable for installation may be present in the atmosphere. Copper piping and
in a commercial and light industrial environment. soldered joints may corrode, causing refrigerant to leak.
- Locations where a mineral oil mist, spray or vapour may be
6.1 General precautions on installation present in the atmosphere. Plastic parts may deteriorate and
fall off or cause water leakage.
Select an installation site that meets the following requirements: - Locations where equipment that produces electromagnetic
The foundation must be strong enough to support the weight of waves is found. The electromagnetic waves may cause the
the unit. (refer to “7.2 Service space” on page 8) control system to malfunction, preventing normal operation.
The floor is flat to prevent vibrations and noise generation - Locations where flammable gases may leak, where thinner,
and to have sufficient stability. gasoline and other volatile substances are handled, or where
carbon dust and other incendiary substances are found in the
The space around the unit is adequate for maintenance and
atmosphere. Leaked gas may accumulate around the unit,
servicing.
causing an explosion.
The space around the unit allows for sufficient air circulation.
When installing, take strong winds, typhoons or earthquakes into
There is no danger of fire due to leakage of inflammable gas. account, improper installation may result in the unit turning over.
The equipment is not intended for use in a potentially explosive
6.2 Weather related precautions
atmosphere.
Select the location of the unit in such a way that the sound Select a place where the rain can be avoided as much as possible.
generated by the unit does not disturb anyone, and the location Be sure that the air inlet of the unit is not positioned towards the
is selected according the applicable legislation. main wind direction. Frontal wind will disturb the operation of the
unit. If necessary, use a screen to block the wind.
All piping lengths and distances have been taken into
consideration. (refer to “9.4 System piping (length) limitation” Ensure that water cannot cause any damage to the location by
on page 12) adding water drains to the foundation and prevent water traps in
the construction.
Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings. Do not install the unit in areas where the air contains high levels
of salt such as that near the ocean.
When installing the unit in a smallroom, take measures in order
to keep the refrigerant concentration from exceeding allowable
safety limits in the event of a refrigerant leak.
CAUTION
19
Excessive refrigerant concentrations in a closed room can
lead to oxygen deficiency.
7
3P391148-1
RXYQ14~20 1076
6.3 Selecting a location in cold climates
NOTICE
737
When operating the unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below. 4-15x22.5
To prevent exposure to wind and snow, install a baffle plate on the air
side of the outdoor unit:
1657
131 122
515
276
259
179
76 76 97 107
1 137 272
765 328
373
(mm) 1240
d d
b b
c c
e e
2 f d
aa aa
d b
1 Construct a large canopy.
2 Construct a pedestal.
Install the unit high enough from the ground to prevent
burying in snow. b
c
e
f
7. Dimensions and service space
aa
RXYQ6~12
766 A+B+C+D A+B
a10 mm a50 mm a200 mm
b300 mm b100 mm b300 mm
c10 mm c50 mm
737
d500 mm d500 mm
a10 mm a50 mm a200 mm
4-15x22.5 b300 mm b100 mm b300 mm
c10 mm c50 mm
d500 mm d500 mm
e20 mm e100 mm e400 mm
a10 mm a50 mm
b300 mm b100 mm
c10 mm c50 mm
d500 mm d500 mm
1657
e20 mm e100 mm
f600 mm f500 mm
a10 mm a50 mm
b300 mm b100 mm
122
515
c10 mm c50 mm
d500 mm d500 mm
276
259
179
e20 mm e100 mm
131
76 76
137
97 107 a10 mm a50 mm
272 b500 mm b500 mm
765 328 c10 mm c50 mm
373
(mm) 930 d500 mm d500 mm
e20 mm e100 mm
f900 mm f600 mm
8
3P391148-1
500
NOTICE
(mm) When the installation height of the unit needs to be
ABCD Sides along the installation site with obstacles
increased, do not use stands to only support the corners.
F Front side
Suction side
t The installation space required on these drawings are for full The height of the foundation must at least be 150 mm from
load heating operation without considering possible ice the floor.
accumulation.
If the location of the installation is in a cold climate, then all In heavy snowfall areas, this height should be increased,
depending on the installation place and condition.
dimensions above should be >500 mm to avoid accumulation of
ice in between the outdoor units. The unit must be installed on a solid longitudinal foundation
(steel beam frame or concrete) and make sure the base under
INFORMATION the unit is larger than the grey marked area.
t The service space dimensions in above figure are based 4 3 6 7 1 2 5
on cooling operation at 35°C ambient temperature
(standard conditions). B
t Further specifications can be found in the technical A
engineering data.
631
729
765
8.1 Inspection
At delivery, the unit must be checked and any damage must be
reported immediately to the carrier's claims agent.
(mm)
8.2 Handling 1 Hole for foundation bolt (ø15 dia. : 4 positions)
2 Inner dimension of the base
1 When handling the unit, take into account the following: 3 Distance between foundation bolt holes
4 Depth of unit
Fragile, handle the unit with care.
5 Outer dimension of the base
6 Longitudinal foundation dimension
Keep the unit upright in order to avoid compressor damage.
7 Distance between foundation bolt holes
2 Choose on beforehand the path along which the unit is to be
brought in.
3 Bring the unit as close as possible to its final installation position 6 8 10 12HP type 766 930
in its original package to prevent damage during transport.
14 16 18 20HP type 1076 1240
2
3
NOTICE
t Prepare a water drainage channel around the
foundation to drain waste water from around the unit.
During heating operation and when the outdoor
temperatures are negative, the drained water from the
outdoor unit will freeze up. If the water drainage is not
1 Packaging material taken care of, the area around the unit might be very
2 Belt sling slippery.
3 Opening
t When installed in a corrosive
4
4 Protector
9
3P391148-1
9. Refrigerant pipe size and allowable 9.2.2 Piping between refrigerant branch kits: D
pipe length Choose from the following table in accordance with the indoor unit
WRWDOFDSDFLW\W\SHFRQQHFWHGGRZQVWUHDP'RQRWOHWWKHFRQQHFWLRQ
piping exceed the refrigerant piping size chosen by the general
9.1 Selection of piping material V\VWHPPRGHOQDPH
A B B B
a x C y
Example:
D F 'RZQVWUHDPFDSDFLW\IRU) FDSDFLW\LQGH[RIXQLWFDSDFLW\LQGH[RI
b unit 5
G
10
3P391148-1
9.2.5 Piping between refrigerant branch kit and indoor unit: E 9.3 Selection of refrigerant branch kits
Pipe size for direct connection to indoor unit must be the same as the Refrigerant REFNETS
connection size of the indoor unit (in case indoor unit is VRV Indoor). For piping example, refer to "9.2. Selection of piping size" on page 10.
Piping outer diameter size t When using REFNET joints at the first branch counted from the
(mm) outdoor unit side, choose from the following table in accordance
Indoor unit capacity index Gas pipe Liquid pipe with the capacity of the outdoor unit (example: REFNET joint a).
20, 25, 32, 40, 50 Ø 12.7 (1/2“) Ø 6.4 (1/4“) Outdoor unit capacity type (HP) 2 pipes
63, 80, 100, 125, 140 Ø 15.9 (5/8“) 6~10 KHRP26A33T
200 Ø 19.1 (3/4“) Ø 9.5 (3/8“) 12~22 KHRP26A72T
250 Ø 22.2 (7/8“) 24~60 KHRP26A73T + KHRP26M73TP
400 Ø 12.7 (1/2“)
Ø 28.6 (1 1/8“) t For REFNETS joints other than the first branch (example REFNET
500 Ø 15.9 (5/8“)
joint b), select the proper branch kit model based on the total
capacity index of all indoor units connected after the refrigerant
When the equivalent pipe length between outdoor and indoor branch.
units is 90 m or more, the size of the main pipes (both gas side
Indoor unit capacity index 2 pipes
and liquid side) must be increased. Depending on the length of
the piping, the capacity may drop, but even in such a case it is <200 KHRP26A22T
possible to increase the size of the main pipes. 200x<290 KHRP26A33T
290x<640 KHRP26A72T
1 2 3 5
6 4 0 KHRP26A73T + KHRP26M73TP
11
3P391148-1
Total piping length: total piping length from the outdoor(1) to all indoor
units.
Difference in height between outdoor and indoor units: H1.
Difference in height between indoor and indoor units: H2.
Difference in height between outdoor and outdoor units: H3.
Difference in height between outdoor and BP unit: H4.
Difference in height between BP unit and BP unit: H5.
Difference in height between BP unit and RA indoor unit: H6.
(1) In case of multi outdoor system, re-read to the first outdoor unit multi connection
piping kit as seen from the indoor unit.
(2) Assume equivalent piping length of REFNET joint=0.5 m and REFNET
header=1 m (for calculation purposes).
Single outdoor
i
a a
A B
a b c d e f g k
H1 H1 b j
A B C D E F G
p 7 8 H1
h i j k l m n H2
1 2 3 4 5 6 7 c d e f g h b c d e f g h i
1 2 3 4 5 6 1 2 3 4 5 6 7
H2 8
H2 8
Example 1.1 Example 1.2 Example 1.3
Multi outdoor
H3 H3 H3
Indoor unit r t
r s t s r s t
u u a u
a b c d e f g A B H1 a
REFNET joint H1 H1
A B C D E F G b j k
p 7 8
h i j k l m n H2
REFNET header 1 2 3 4 5 6 7 c d e f g h b c d e f g h i
8 1 2 3 4 5 6 1 2 3 4 5 6 7
Outdoor multi 8
connection piping
kit Example 2.1 Example 2.2 Example 2.3
12
3P391148-1
Example 3 : with standard multi layout c. When the piping size is increased (step b), the piping length has
to be counted as double (except for the main pipe and the pipes
that are not increased in pipe size).
The total piping length has to be within limitations (see table
above).
r s t Example:
a+b*2+c*2+d*2+e*2+f*2+g*2+h+i+j+k+l+m+n+p1000 m
(500 m).
u d. The piping length difference between the nearest indoor from
first branch to the outdoor unit and farthest indoor to the outdoor
unit is 40 m.
t Between outdoor branch and outdoor unit. Example: The farthest indoor unit 8. The nearest indoor unit 1
Actual piping length 10 m Example 3 (a+b+c+d+e+f+g+p)–(a+h)40 m.
r, s, t10 m; u5 m
Equivalent length 13 m —
9.4.3 System containing VRV indoor units and RA indoor units
Maximum allowable height difference
System setup
H1 50 m (a)
H2 30 m
H3 5 m
(a) Conditional extension up till 90 m is possible. a b d
In case the outdoor location is higher than indoor: extension is possible up till A B
90 m and following 2 conditions must be fulfilled: c
Liquid piping size up (see table "Size up" on page11).
Dedicated setting on outdoor unit is required H4
(see [2-49] in Monitoring function and field settings, page 35) e f g
H5 BP1 6 7
In case the outdoor location is lower than indoor: extension is possible up till 90 m H1
and following 1 condition must be fulfilled: h i j BP2
Liquid piping size up (see table "Size up" on page11). 1 2 3 H2 k
4 H6 l
Maximum allowable length after branch
5
The pipe length from the first refrigerant branch kit to the indoor unit
Header
40 m.
BP box
Example 1.1: unit 8: b+c+d+e+f+g+p40 m 1~5 RA indoor units
6,7 VRV indoor units
Example 1.2: unit 6: b+h40 m, unit 8: i+k40 m
Maximum allowable length
Example 1.3: unit 8: i40 m
t Between outdoor unit and indoor unit.
(3) If this pipe diameter is unobtainable on site, the piping length Maximum allowable length after branch
19
limitation cannot extended.
The pipe length from the first refrigerant branch kit to the indoor unit
50 m.
13
3P391148-1
1 To indoor unit
2 Piping between outdoor units
1 1
2 2
t Bottom connection
Remove the knock out holes on the bottom frame and route the 1 To indoor unit
2 Piping between outdoor units
piping under the bottom frame (see figure below).
1
2 1 2 1 2
1 To indoor unit
2 Oil collects to the outmost outdoor unit when the system
stops
14
3P391148-1
Correct configuration Block all gaps in the holes for passing out piping and wiring using
sealing material (field supply) (the capacity of the unit will drop and
small animals may enter the machine).
Example: passing piping out through the front.
1 1 Close the areas marked with " ".
1
(When the piping is routed from the
1 1 front panel.)
1 To indoor unit
t If the piping length between the outdoor units exceeds 2m,
create a rise of 200mm or more in the gas line within a length of
2m from the kit.
If 2 m
1 To indoor unit
2 Piping between outdoor units NOTICE
If >2 m After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
19
15
3P391148-1
NOTICE • :KHQFRQQHFWLQJUHIULJHUDQWSLSLQJWRDQRXWGRRUXQLW
UHPRYHWKHVHDOHGUXEEHUSOXJ5HIHUWREHORZJLYHQILJXUH
Installation shall be done by an installer, the choice of
materials and installation shall comply with the applicable • 6HDOHGUXEEHUSOXJVKRXOGEHUHPRYHGXVLQJWKH
SURFHGXUHLQWKHEHORZILJXUH
legislation.
(Refer to EHORZfigure)
. Shutoff valve (liquid side · gas side)
10.2.1 Decide front or side (bottom) connection . Service port
Installation of refrigerant piping is possible as front connection or side 3. Sealed rubber plug
connection (when taken out from the bottom) as shown in the figure 4. Procedure 1:
below. Confirm the shutoff valve is closed.
5. Procedure 2:
1 Left-side connection Connect a charge hose to the service port of the liquid
2 Front connection side and gas side shutoff valves and remove the gas
3 Right-side connection from the pipe.
3 1 2
4 5
1 2
For side connections, the knockout hole on the bottom plate should
3
be removed:
NOTICE
Precautions when knocking out knockout holes:
t Be sure to avoid damaging the casing.
t After knocking out the knockout holes, we recommend
you remove the burrs and paint the edges and areas
around the edges using repair paint to prevent rusting.
t When passing electrical wiring through the knockout
holes, wrap the wiring with protective tape to prevent
damage as shown above.
16
3P391148-1
INFORMATION max
15 A
All local inter unit piping are field supplied except the
accessory pipes.
1
NOTICE
Precautions when connecting field piping. Add brazing
material as shown in the figure.
B
1
1 1
2 2
1
1
>12
0
>50 mm
NOTICE 0m
m
t Be sure to use the supplied accessory pipes when
carrying out piping work in the field.
t Be sure that the field installed piping does not touch
other pipes, the bottom panel or side panel. Especially
1 Install the joints horizontally, so that the caution label (1)
for the bottom and side connection, be sure to protect
attached to the joint comes to the top.
the piping with suitable insulation, to prevent it from
coming into contact with the casing. - Do not tilt the joint more than 15° (see view A).
- Do not install the joint vertically (see view B).
Connection from the stop valves to the field piping can be done by 2 Make sure that the total length of the piping connected to the
using accessory pipes supplied as accessory. joint is absolute straight for more than 500 mm. Only if a
straight field piping of more than 120 mm is connected, more
The connections to the branch kits are the responsibility of the
than 500 mm of straight section can be ensured.
installer (field piping).
3 Improper installation may lead to malfunction of the outdoor
unit.
10.2.4 Branching the refrigerant piping
t For installation of the refrigerant branching kit, refer to the
installation manual delivered with the kit.
±30°
1
A
1
B
1 Horizontal surface
1 Mount the refnet joint so that it branches either horizontally or
vertically.
2 Mount the refnet header so that it branches horizontally.
19
17
3P391148-1
10.3 Guidelines for handling stop valve 10.3.3 Cautions on handling the stop valve cover
2 <Tightening torque>
3 7LJKWHQWRUTXH1P
1 (Turn clockwise to close)
Shutoff Stop Valve
4 valve size Seal Structure Cap Service
Shaft (valve body)
(valve lid) port
18
3P391148-1
Yes
When all piping work is complete, it is necessary to:
t Check for any leakages in the refrigerant piping.
The indoor units and/or No Use procedure
outdoor unit were already "10.4.2. Installation of
t Perform vacuum drying to remove all moisture, air or nitrogen in
powered ON? refrigerant piping, leak test, the refrigerant piping.
vacuuming before electrical
Yes installation is done (regular If there is a possibility of moisture being present in the refrigerant
installation method)" piping (for example, rainwater may have entered the piping), first
Use procedure carry out the vacuum drying procedure below until all moisture has
"10.4.3. Installation of been removed.
refrigerant piping, leak test,
vacuuming after electrical All piping inside the unit has been factory tested for leaks.
installation is done on any
indoor or outdoor unit" Only field installed refrigerant piping needs to be checked. Therefore,
make sure that all the stop valves are firmly closed before performing
leak test or vacuum drying. (See “10.4.4 Set up” and “10.4 Leak test
and vacuum drying”)
10.4.1 General guidelines
t Use a 2-stage vacuum pump with a non-return valve which can 10.4.4 Setup
evacuate to a gauge pressure of –100.7 kPa (5 Torr absolute, 6 9 9 9
–755 mm Hg).
1 7
t Connect the vacuum pump to the service port of all 3 stop valves 8
to increase efficiency (refer to "10.4.4.Setup").
4 A
10
NOTICE 2 3 5 B 11
14
12
Do not purge the air with refrigerants. Use a vacuum pump
13
to evacuate the installation.
1 Gauge manifold
2 Nitrogen
10.4.2 Installation of refrigerant piping, leak test, vacuuming 3 Measuring instrument
before electrical installation is done (regular installation 4 Refrigerant R410A tank (siphon system)
method) 5 Vacuum pump
6 Charge hose
When all piping work is complete, it is necessary to: 7 Gas line stop valve
t Check for any leakages in the refrigerant piping. 8 Liquid line stop valve
9 Outdoor unit
t Perform vacuum drying to remove all moisture, air or nitrogen in
10 To indoor unit
the refrigerant piping. 11 Stop valve
If there is a possibility of moisture being present in the refrigerant 12 Field piping
piping (for example, rainwater may have entered the piping), carry 13 Gas flow
14 Stop valve service port
out the vacuum drying procedure below until all moisture has been
A Valve A
removed. B Valve B
All piping inside the unit has been factory tested for leaks.
Which valves? State of valves
Only field installed refrigerant piping needs to be checked. Therefore, State of the valves A and B and Performing the airtightness test and
make sure that all the outdoor unit stop valves are firmly closed the stop valve vacuum drying
before performing leak test or vacuum drying.
Valve A Open
NOTICE Valve B Open
Make sure that all (field supplied) field piping valves are Liquid side stop valve Close
OPEN (not outdoor unit stop valves!) before you start leak Gas side stop valve Close
test and vacuuming.
NOTICE
10.4.3 Installation of refrigerant piping, leak test, vacuuming The connections to the indoor units and all indoor units
after electrical installation is done on any indoor or should also be leak and vacuum tested. Keep any possible
outdoor unit (field supplied) field piping valves open as well.
Refer to the indoor unit installation manual for more details.
Apply outdoor unit setting [2-21]=1 before starting leak test and
Leak test and vacuum drying should be done before the
vacuuming.
This setting will open field expansion valves to guarantee a R410A
power supply is set to the unit. If not, see also the flow
chart earlier described in this chapter (see "10.4.Leak test
19
piping pathway.
and vacuum drying").
19
3P391148-1
20
3P391148-1
21
3P391148-1
The power supply must be protected with the required safety devices, It is important to keep the powersupply and the transmission wiring
i.e. a main switch, a slow blow fuse on each phase and an earth separated from each other. In order to avoid any electrical
leakage protector in accordance with the applicable legislation. interference the distance between both wiring should always be at
least 25 mm.
Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below. 12.5.1 Transmission wiring routing
The transmission wiring outside the unit should be wrapped and
Minimum circuit Recommended routed together with the field piping.
ampere fuses
Field piping can be routed from front or bottom of the unit (going left
RXYQ6 16.1 A 20 A or right). Refer to "10.2.Connecting the refrigerant piping" on
RXYQ8 16.1 A 20 A page 16.
RXYQ10 22.0 A 25 A
RXYQ12 24.0 A 25 A Rules for transmission wiring routing
RXYQ14 28.0 A 35 A t Be sure to follow the limits below. If the unit-to-unit cables are
RXYQ16 31.0 A 35 A beyond these limits, it may result in malfunction of transmission:
RXYQ18 31.0 A 35 A - Maximum wiring length: 1000 m.
RXYQ20 40.0 A 50 A
- Total wiring length: 2000 m.
- Maximum inter unit wiring length between outdoor units:
RXYQ22 46.0 A 50 A
30 m.
RXYQ24 46.0 A 50 A - Maximum number of branches: 16.
RXYQ26 52.0 A 60 A
- Maximum number of independent interconnectable
RXYQ28 55.0 A 60 A systems: 10.
RXYQ30 55.0 A 60 A - Tranmission wiring to cool/heat selector : 500 m.
RXYQ32 62.0 A 70 A
RXYQ34 62.0 A 70 A
t Up to 16 branches are possible for unit-to-unit cabling. No
branching is allowed after branching (see figure below).
RXYQ36 71.0 A 80 A
RXYQ38 77.0 A 90 A
RXYQ40 77.0 A 90 A 1 1 1
RXYQ42 84.0 A 100 A 8
B
RXYQ44 86.0 A 100 A A
4
RXYQ46 90.0 A 100 A 2
RXYQ48 93.0 A 110 A 5
RXYQ50 93.0 A 110 A 2
RXYQ52 93.0 A 110 A 7
RXYQ54 93.0 A 110 A 2
RXYQ56 102.0 A 125 A 6
RXYQ58 111.0 A 125 A 2
RXYQ60 120.0 A 150 A 7
For all models: 2
Phase and frequency: 3N~ 50 Hz
Voltage: 380-415 V 3
Transmission line section: 0.75~1.25 mm2, maximum length is 1000 m. 2
1 Outdoor unit
2 Indoor unit
If the total transmission wiring exceeds these limits, it may result in 3 Main line
communication error. 4 Branch line 1
5 Branch line 2
6 Branch line 3
7 No branch is allowed after branch
NOTICE 8 Central user interface (etc...)
A Transmission wiring between outdoor unit and indoor
When using residual current operated circuit breakers, unit(s)
be sure to use a high-speed type 300 mA rated residual B Transmission wiring between outdoor units
operating current.
22
3P391148-1
t Never connect the power supply to transmission wiring terminal Transmission wiring routing to the unit and inside the unit.
block. Otherwise the entire system may break down. Transmission wiring can be routed through the front side only:
t Never connect 400 V to the terminal block of the transmission
wiring. Doing so will break the entire system: t Fix transmission wire with tie wrap (1) to low voltage wiring.
See figures below, item 6.
- The wiring from the indoor units must be connected to the
F1/F2 (In-Out) terminals on the PC board in the outdoor unit. t Possible transmission wire entrance hole (close hole to avoid
- After installing the transmission wires inside the unit, wrap bugs/dirt from entering). See figures below, item 4.
them along with the on-site refrigerant pipes using finishing t Possible transmission wire entrance hole (close hole to avoid
tape, as shown in figure below. bugs/dirt from entering). Fix transmission wiring to pipe insulation
with tie wraps. See figures below, item 5.
1 3 2 5 4
t Inside the electronic component box, the transmission wire
should be fixed on several locations with tie wraps to low voltage
wiring. See figures below, items 2 and 6.
t Fix transmission wire with tie wrap (2) to heat exchanger fixing
plate (hole). See figures below, item 8.
For the above wiring, always use vinyl cords with 0.75 to
1.25mm 2 sheath or cables (2-core wires).
(3-core wire cables are allowable for the cooler/heater changeover 6
user interface only.)
6
NOTICE 7
t Be sure to keep the power line and transmission line
apart from each other. Transmission wiring and power 6
supply wiring may cross, but may not run parallel.
t Transmission wiring and power supply wiring may not 1
touch internal piping (except INV PCB cooling pipe) in
order to avoid wire damage due to high temperature
piping. 2
t Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.
4+5 4 3 3
19
23
3P391148-1
t Front side. In order to route the power supply from the front side,
6 the available knockout holes can be used:
t Fix the power supply cable to the foreseen wire clips with a
tie wrap. See figures below, item 2.
2
t Front plate: possible power supply wire entrance hole (close
7 hole to avoid bugs/dirt from entering). See figures below,
item 3.
t Side plate: possible power supply wire entrance hole (close
hole to avoid bugs/dirt from entering). Use conduit. See
1 figures below, item 4.
RXYQ6~12
4+5 4 3 3 6
1 Transmission wiring
2 Fix wiring with tie wrap 1
3 Possible power supply wire entrance hole (a)
4 Possible transmission wire entrance hole (a)
5 Possible transmission wire entrance hole. (a) Fix wiring to pipe
insulation with tie wraps
6 Inside the electronic component box, the wiring should be
fixed on several locations with tie wraps to the factory
mounted low voltage wiring.
7 Factory mounted low voltage wiring
8 Fix wiring with tie wrap (2) to heat exchanger fixing plate (hole).
(a) Knockout hole has to be removed. Close the hole to avoid small animals
or dirt from entering.
5
3+4 3 3
24
3P391148-1
2 A1P
F1 F2 F1 F2 Q1 Q2
F1 F2 F1 F2 Q1 Q2
5
1 4
F1 F2 F1 F2 F1 F2
2
3
F1 F2 F1 F2 F1 F2
2
1 Outdoor unit PCB board (A1P)
2 Use the conductor of sheathed wire (2 wire) (no polarity)
3 Terminal board (field supply)
1 4 Indoor unit
5 Outdoor unit
1 2 3
A1P
F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q1 Q2
5 3+4 3 3
1 2 3 4
1 Knockout hole
2 Burr
3
4
Remove burrs
If there are any possibilities that small animals enter the
system through the knockout holes, plug the holes with
19
packing materials (to be prepared on-site)
25
3P391148-1
INFORMATION
5
Installation and routing in case the cool/heat selector is
4 uesd : refer to installation manual of the cool/heat selector.
NOTICE
5
L1 L2 L3 N
t When routing earth wires, secure clearance of 25 mm
or more away from compressor lead wires. Failure to
4 observe this instruction properly may adversely affect
correct operation of other units connected to the same
earth.
t When connecting the power supply, the earth
connection must be made before the current-carrying
4
connections are established. When disconnecting the
5
power supply, the current-carrying connections must
1 Fix to the indicated plastic brackets using field supplied
clamping material
be separated before the earth connection is. The
2 Wiring between the units (indoor-outdoor) (F1/F2 left) length of the conductors between the power supply
3 Internal transmission wiring (Q1/Q2) stress relief and the terminal block itself must be as
4 Plastic bracket such that the current-carrying wires are tautened
5 Field supplied clamps before the earth wire is in case the power supply is
Care should be taken for connecting the wires to the terminal block. pulled loose from the stress relief.
See the table below for the tightening torque of the transmission
wiring terminals. NOTICE
Screw size Tightening torque (Nm) Precautions when laying power wiring:
M3.5 (A1P) 0.80~0.96 t Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
t Never connect the power supply to transmission wiring terminal cause abnormal heat).
block. Otherwise the entire system may break down. t When connecting wiring which is the same thickness,
t Be careful about polarity of the transmission wiring. do as shown in the figure below.
Power supply
The power supply must be clamped to the plastic bracket using field
supplied clamp material.
The green and yellow striped wire must be used for earthing only
(refer to the figure below). t For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
RXYQ6~12 exerted on the terminal board.
5 t Use an appropriate screwdriver for tightening the terminal
screws. A screwdriver with a small head will damage
6 the head and make proper tightening impossible.
7 t Over-tightening the terminal screws may break them.
10 t See the table below for tightening torque for the
11 terminal screws.
1 3 2 4 8
9
7
10 NOTICE
11
1 3 2 4 8 Recommendations when connecting the earth wire
9 Wire it so that it comes through the cut out section of the
cup washer. (An improper earth connection may prevent a
1 Power supply (380~415 V - 3N~ 50Hz) good earthing from being achieved.)
2 Fuse
3 Earth leakage protector
4 Earth wire
5 Power supply terminal block
6 Connect each power wire: RED to L1, WHT to L2, BLK to
L3 and BLU to N
26
3P391148-1
Connecting the power supply to multiple outdoor units Location of the segment displays, buttons and DIP switches:
To connect the power supply for multiple outdoor units to each other, 1 2
ring tongues have to be used. No bare cable can be used.
The ring washer which is standard provided should be removed in
that case.
BS1 BS2 BS3 DS1 DS2
1 Front plate
2 Inspection cover When no trouble occurs: lighted as indicated (8~10 min).
3 Main PCB with 3 seven segment display and 3 push
buttons
Operate the switches and push buttons with an insulated stick (such Ready for operation: blank display indication as indicated.
as a closed ball-point pen) to avoid touching of live parts.
19
27
3P391148-1
t Push BS1 1 time; result segment display: t To leave the monitoring function, push BS1 2 times, you will
return to the default situation when shipped from factory.
28
3P391148-1
13.2.2 Operating the DIP switches 14.2 Calculating the additional refrigerant charge
By operating the DIP switches it is possible to:
How to calculate the additional refrigerant to be charged
What to do with DIP switch DS1 Additional refrigerant to be charged=R (kg). R should be rounded off
COOL/HEAT selector (refer to the manual of the cool/heat in units of 0.1 kg.
selector switch)237,21$/ R=[(X1@ Ø22.2) x 0.36+(X2 @ Ø19.1) x 0.26+(X3 @ Ø15.9) x 0.17+(X4
1 OFF=not installed=factory setting @ Ø12.7) x 0.11+(X5 @ Ø9.5) x 0.057+(X6 @ Ø6.4) x 0.022 ]+A
NOT USED
2-4 X1...6 =Total length (m) of liquid piping size at Øa
DO NOT CHANGE THE FACTORY SETTING
What to do with DIP switch DS2 HP
NOT USED A parameter Total indoor unit
1-4
DO NOT CHANGE THE FACTORY SETTING (kg) capacity CR(a) 6~8 10~12 14~18 20
50%CR105% 0 0.5
14. Charging refrigerant Piping
length30 m 105%<CR130% 0.5 1
50%CR70% 0 0.5
14.1 Precautions 70%<CR85% 0.3 0.5 1.0
Piping
length>30 m 85%<CR105% 0.7 1 1.5
NOTICE 105%<CR130% 1.2 1.5 2.0
t Refrigerant cannot be charged until field wiring has (a) CR=Connection ratio.
been completed.
t Refrigerant may only be charged after performing the Piping length is considered the distance from the outdoor unit to
leak test and the vacuum drying. the farthest indoor unit.
t When charging a system, care shall be taken that its
When using metric piping, please take into account following table
maximum permissible charge is never exceeded, in
concerning the weight factor to be allocated. It should be substituted
view of the danger of liquid hammer.
in the formula for R.
t Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant R410A is charged. Inch piping
t Refrigerant containers shall be opened slowly. size (Ø) (mm) Weight factor
t Always use protective gloves and protect your eyes Ø6.4 (1/4“) 0.022
when charging refrigerant. Ø9.5 (3/8“) 0.057
t When the refrigerant system is to be opened, Ø12.7 (1/2“) 0.11
refrigerant must be treated according to the applicable Ø15.9 (5/8“) 0.17
legislation.
Ø19.1 (3/4“) 0.26
Ø22.2 (7/8“) 0.36
t In case re-charge is required, refer to the nameplate of the unit. VRV 50~130% 50~130% —
It states the type of refrigerant and necessary amount. VRV +
80~130% 0~130% 0~130%
RA
RA 80~130% — 80~130%
19
29
3P391148-1
Step 1
Calculate additional refrigerant
charge amount: R (kg) (see
“14.2 Calculating the
additional refrigerant charge”
on page 29
Step 4a
Step 2+3 Close valve A
R<Q Open valve A to field piping via R=Q
Refrigerant overcharge happened Charging is finished
Recover refrigerant to reach liquid stop valve Fill in the amount on the
R=Q Execute pre-charging amount: additional refrigerant charge
Go to step 4a Q (kg) label
Close valve A if no additional Go to test run (see "16.1 Test
refrigerant can be charged operation" on page 36)
R>Q
A
Step 4b+5
Manual refrigerant charging
method (in cooling operation)
Step 6
Activate field setting [2-20]=1
Unit will start manual refrigerant
charging operation.
Step 6
Open valve B
Charge remaining amount of
refrigerant P (kg)
R=Q+P
Step 6
Close valve B
Push BS3 to stop manual
charging
Charging is finished
Fill in the amount on the
additional refrigerant charge
label
Go to test run (see "16.1 Test
operation" on page 36)
See figure "Location of valves" on page 31; for more information refer to the text in this chapter.
30
3P391148-1
Follow the steps as described below and take into account whether
CAUTION you want to use the automatic charge function or not.
t When the refrigerant charging procedure is done or 1 Calculate the additional amount of refrigerant to be added using
when pausing, close the valve of the refrigerant tank the formula mentioned in "14.2 Calculating the additional
immediately. If the tank is left with the valve open, the refrigerant charge" on page 29.
amount of refrigerant which is properly charged may
2 The first 10 kg of additional refrigerant can be charged without
get off point. More refrigerant may be charged by any
outdoor unit operation.
remaining pressure after the unit has stopped.
If the additional refrigerant amount is smaller than 10 kg,
perform the pre-charging procedure as explained in step 3 and
NOTICE 4a below.
If the additional refrigerant charge is larger than 10 kg, perform
t If the power of some units is turned off, the charging
step 3 till the end of the procedure.
procedure cannot be finished properly.
3 Pre-charging can be done without compressor running by
t In case of a multiple outdoor system, turn on the power
connecting the refrigerant bottle only to the liquid stop valve
of all outdoor units.
service port (open valve A). Make sure that the stop valves are
t Make sure to turn ON the power 6 hours before starting closed (valve B+liquid line stop valve+gas line stop valve
the operation. This is necessary to warm the crankcase
by the electric heater.
t If operation is performed within 12 minutes after the 3 6 6 6
indoor and outdoor units are turned on, the compressor
4
will not operate before the communication is established 5
in a correct way between outdoor unit(s) and indoor
2 A
units. 7
B
t Before starting charging procedures, check if the 1 11 8
9
segment display indication of the outdoor unit A1P
10
PCB is as normal (see "Functions of the push button
switches which are located on the outdoor PCB
1 Measuring instrument
(A1P)" on page 27). If a malfunction code is present, 2 Refrigerant R410A tank (siphon system)
see "16.2. Malfunction code list" on page 37. 3 Charge hose
t Make sure all connected indoor units are recognised 4 Gas line stop valve
5 Liquid line stop valve
t Close the front panel before any refrigerant charge 6 Outdoor unit
operation is executed. Without the front panel 7 To indoor unit
attached the unit cannot judge correctly whether it is 8 Stop valve
operating properly or not. 9 Field piping
10 Gas flow
11 Stop valve service port
NOTICE A Valve A
B Valve B
In case of maintenance and the system (outdoor unit+field
piping+indoor units) does not contain any refrigerant any
more (e.g., after refrigerant reclaim operation), the unit has
4 a) If the calculated additional refrigerant amount is reached by
to be charged with its original amount of refrigerant (refer
above pre-charging procedure, close valve A.
to the nameplate on the unit) by pre-charging before the
b) If the total amount of refrigerant could not be charged by pre-
automatic charging function can be started.
charging, then close valve A and go to step 5. Follow
step 6 depending on the chosen charging method.
19
31
3P391148-1
32
3P391148-1
The second method is to enable power consumption [2-0]= Cool/Heat selection setting
limitation based on an external input. For this operation
an optional accessory is required.
.
Default value=0.
0=Each individual outdoor unit can select Cool/Heat
[1-5]= shows the current Te target parameter position.
Refer to “15.3 Energy saving and optimum operation” . operation
1=Master unit decides Cool/Heat operation when
on page 35 for more details about the contents of this outdoor units are connected in multiple system
.
(a)
value combination
2=Slave unit for Cool/Heat operation when outdoor
[1-6]= shows the current Tc target parameter position units are connected in multiple system combination(a)
Refer to “15.3 Energy saving and optimum operation”
on page 35 for more details about the contents of this Change [2-0]=0,1 or 2 in function of required functionality.
value
[2-8]= Te target temperature during cooling operation
[1-10]= shows the total number of connected indoor units Default value=2
It can be convenient to check if the total number of
indoor units which are installed match the total number Value
of indoor units which are recognized by the system. In [2-8] Te target
case there is a mismatch, It is advised to check the 0 A u to
communication wiring path between outdoor and indoor 2 6
units (F1/F2 communication line).
3 7
[1-13]= shows the total number of connected outdoor units (in 4 8
case of multiple outdoor system). 5 9
It can be convenient to check if the total number of
6 10
outdoor units which are installed matches the total
number of outdoor units which are recognized by the 7 11
system. In case there is a mismatch, It is advised to
check the communication wiring path between outdoor Change [2-8]=0, 2~7 in function of required operation
and outdoor units (Q1/Q2 communication line). method during cooling.
[1-17]= shows the latest malfunction code. For more information and advice about the impact of
these settings, see “15.3 Energy saving and optimum
[1-18]= shows the malfunction code which occurred 1 time operation” on page 35.
before current malfunction code.
[2-9]= Tc target temperature during heating operation
[1-19]= shows the malfunction code which occurred 2 time Default value=6
before current malfunction code.
Value
When the latest malfunction codes were reset by [2-9] Tc target
accident on an indoor unit user interface, they can be
checked again through this monitoring settings. For the 0 A u to
content or reason behind the malfunction code see 1 41
“16.2 Malfunction code list” on page 37, where most 3 43
relevant malfunction codes are expained. Detailed
6 46
information about malfunction codes can be consulted
in the service manual of this unit.
Change [2-9]=0,1,3 or 6 in function of required operation
[1-38]= shows the number of RA indoor units connected to the method during heating.
system.
For more information and advice about the impact of
[1-40]= shows the current cooling comfort setting. See these settings, see “15.3 Energy saving and optimum
“15.3 Energy saving and optimum operation” on operation” on page 35.
page 35 for more details about this setting.
[2-12]= Enable the low noise function and/or power consumption
[1-41]= shows the current heating comfort setting. See limitation via external control adaptor (DTA104A61/62)
“15.3 Energy saving and optimum operation” on
page 35 for more details about this setting. If the system needs to be runnig under low noise
operation or under power consumption limitation
15.2 Mode 2 conditions when an external signal is sent to the unit,
this setting should be changed. This setting will only be
Mode 2 is used to change the field settings of the system. effective when the optional external control adaptor
Consulting the current field setting value and changing the current (DTA104A61/62) is installed.
field setting value is possible.
Default value=0
In general, normal operation can be resumed without special To activate this function change [2-12]=1.
intervention after changing field settings.
[2-18]= Fan high static pressure setting
Some field settings are used for special operation (e.g., 1 time In order to increase the static pressure the outdoor unit
operation, recovery/vacuuming setting, manual adding refrigerant fan is delivering, this setting should be activated. For
setting, etc.). In such a case, it is required to abort the special details about this setting,see technical specifications.
operation before normal operation can restart. It will be indicated
in below explanations. Default value=0.
19
To activate this function change [2-18]=1.
33
3P391148-1
[2-20]= Manual additional refrigerant charge [2-27]= Low noise operation stop time
Default value=3
In order to add the additional refrigerant charge amount in
a manual way (without automatic refrigerant charging Value Stop time automatic low noise
functionality), following setting should be applied. Further [2-27] operation (approximately)
instructions regarding the different ways to charge 1 6:00
additional refrigerant into your system can be found in
2 7:00
chapter “14.3 Method for adding refrigerant” on page 30.
3 8:00 (default)
Default value=0
To activate this function change [2-20]=1 This setting is used in conjunction with setting [2-22].
To stop the manual additional refrigerant charge operation [2-30]= Power consumption limitation level (step 1) via the
(when the required additional refrigerant amount is external control adaptor (DTA104A61/62).
charged), push BS3. If this function was not aborted by
pushing BS3, the unit will stop its operation after 30 If the system needs to be running under power
minutes. If 30 minutes was not sufficient to add the consumption limitation conditions when an external signal
needed refrigerant amount, the function can be is sent to the unit, this setting defines the level power
reactivated by changing the field setting again. consumption limitation that will be applied for step 1. The
level is according to the table.
[2-21]= Refrigerant recovery/vacuuming mode
Default value=3
In order to achieve a free pathway to reclaim refrigerant
out of the system or to remove residual substances or to Change [2-30]=1,2,3,4,5,6,7 or 8 in function of required
vacuum the system it is necessary to apply a setting limitation.
which will open required valves in the refrigerant circuit
so the reclaim of refrigerant or vacuuming process can be Value Power comsumption limitation
[2-30] (approximately)
done properly.
1 6 0%
Default value=0 2 6 5%
To activate function change [2-21]=1
3 7 0 % ( d e f a u lt )
[2-22]= Automatic low noise setting and level during night time 7 9 0%
8 9 5%
By changing this setting, you activate the automatic low
noise operation function of the unit and define the level [2-31]= Power consumption limitation level (step 2) via the
of operation. Depending on the chosen level, the noise external control adaptor (DTA104A61/62).
level will be lowered (3:Level3<2:Level2<1:Level1).
The start and stop moments for this function are defined If the system needs to be running under power
under setting [2-26] and [2-27]. consumption limitation conditions when an external signal
is sent to the unit, this setting defines the level power
Default value=0. consumption limitation that will be applied for step 2.
To activate function change [2-22]=1,2 or 3. The level is according to the table.
[2-25]= Low noise operation level via the external control adaptor Default value=1.
If the system needs to be running under low noise
operation conditions when an external signal is sent to o the Change [2-31]=1,2 or 3 in function of required limitation.
unit, this setting defines the level of low noise that will be
applied (3:Level3<2:Level2<1:Level1). Value Power comsumption limitation
[2-31] (approximately)
This setting will only be effective when the optional 1 4 0 % ( d e f a u lt )
external control adaptor (DTA104A61/62) is installed and
2 5 0%
the setting [2-12] was activated.
3 5 5%
Default value=2. [2-32]= Forced, all time, power consumption limitation operation
To activate function change [2-25]=1,2 or 3. (no external control adaptor is required to perform power
consumption limitation).
[2-26]= Low noise operation start time
If the system always needs to be running under power
Change [2-26]=1,2 or 3 in function of required timing. consumption limitation conditions, this setting activates
and defines the level power consumption limitation that will
Default value=2. be applied continuously. The level is according to the
table.
Value Start time automatic low noise
[2-26] operation (approximately) Default value=0 (OFF).
1 20:00
Valu
Value
2 22:00 (default) [2-32]
[2-32] Restriction
Restrictionreference
reference
3 24:00 0 Function not active (default)
1 Follows [2-30] setting
This setting is used in conjunction with setting [2-22].
2 Follows [2-31] setting
34
3P391148-1
.
7 11
these settings, see “15.3 Energy saving and optimum
operation” on page 35.
To activate this setting under heating operation: change field
setting [2-9] to the appropriate value, matching the
[2-83]= Master user interface allocation in case VRV indoor units
requirements of the pre-designed system containing a high
and RA indoor units are used at the same time.
sensible solution.
By changing setting [2-83], you can allow the VRV indoor
unit to be the operation mode selector (system power Value
.
OFF/ON is required after applying this setting). [2-9] Te target
1 41
[2-83]=1 RA indoor unit has mode selection right
. (default setting).
[2-83]=0 VRV indoor unit has mode selection right.
3
.
temperature very fast. The overshoot is allowed from the start up
15.3.1 Three main operation methods are available: moment.
Basic In case of cooling operation the evaporating temperature is
The refrigerant temperature is fixed independent from the allowed to go down to 3°C on temporary base depending on the
situation. It corresponds to the standard operation which is
known and can be expected from/under previous VRV systems:
situation.
In case of heating operation the condense temperature is 19
. allowed to go down to 49°C on temporary base depending on the
.
To activate this operation method under cooling operation: situation.
Change field setting [2-8]=2. When the request from the indoor units becomes more moderate,
To activate this operation method under heating operation: the system will eventually go to the steady state condition which
Change field setting [2-9]=6. is defined by the operation method above.
35
3P391148-1
t To activate the powerful comfort setting under cooling 16. Test run
operation, change field setting [2-81]=3.
This setting is used in conjunction with setting [2-8].
t To activate the powerful comfort setting under heating 16.1 Test operation
operation, change field setting [2-82]=3.
This setting is used in conjunction with setting [2-9]. After installation and once the field settings are defined, the installer
is obliged to verify correct operation. Therefore a test run must be
t Quick performed according to the procedures described below.
Overshoot (during heating operation) or undershoot (during
cooling operation) is allowed compared to the requested 16.1.1 Precautions before starting test operation
refrigerant temperature, in order to achieve the required room During test operation, the outdoor unit and the indoor units will start
temperature very fast. The overshoot is allowed from the start up up:
moment.
In case of cooling operation the evaporating temperature is
t Make sure that the preparations of all indoor units are finished
allowed to go down to 6°C on temporary base depending on the (field piping, electrical wiring, air purge, ...). See installation
situation. manual of the indoor units for details.
In case of heating operation the condense temperature is
allowed to go up to 46°C on temporary base depending on the CAUTION
situation. Do not insert fingers, rods or other objects into the air inlet
When the request from the indoor units becomes more moderate, or outlet. When the fan is rotating at high speed, it will
the system will eventually go to the steady state condition which cause injury.
is defined by the operation method above.
t To activate the mild comfort setting under cooling operation, See "2. General safety precautions" on page 2.
change field setting [2-81]=1.
This setting is used in conjunction with setting [2-8]. DANGER: Electrical shock
t To activate the mild comfort setting under heating operation,
See "2. General safety precautions" on page 2.
change field setting [2-82]=1.
This setting is used in conjunction with setting [2-9].
INFORMATION
t Eco
Note that during the first running period of the unit,
The original refrigerant temperature target, which is defined by
required power input may be higher. This phenomenon
the operation method (see above) is kept without any correction,
unless for protection control. originates from the compressor that requires a 50 hour run
elapse before reaching smooth operation and stable power
t To activate the mild comfort setting under cooling operation, consumption. Reason is that the scroll is made out of iron
change field setting [2-81]=0. and that it takes some time to smooth the surfaces that
This setting is used in conjunction with setting [2-8]. make contact.
t To activate the mild comfort setting under heating operation,
change field setting [2-82]=0.
This setting is used in conjunction with setting [2-9].
36
3P391148-1
16.1.2 Test operation 5 Check the test operation results on the outdoor unit segment
display.
The procedure below describes the test operation of the complete
- Normal completion: no indication on the segment display
system. This operation checks and judges following items:
(idle)
t Check of wrong wiring (communication check with indoor units). - Abnormal completion: indication of malfunction code on the
t Check of the stop valves opening. segment display
Refer to take actions for correcting the abnormality. When
t Judgement of piping length.
the test operation is fully completed, normal operation will
On top of this system test operation, indoor units operation should be possible after 5 minutes.
also be checked separately.
t Make sure to carry out the system test operation after the first
installation. Otherwise, the malfunction code will be displayed 16.1.3 Correcting after abnormal completion of the test
on the user interface and normal operation or individual indoor operation
unit test run cannot be carried out.
The test operation is only completed if there is no malfunction code
t Abnormalities on indoor units cannot be checked for each unit
displayed on the user interface or outdoor unit segment display. In
separately. After the test operation is finished , check the indoor
case of a displayed malfunction code, perform correcting actions as
units one by one by performing a normal operation using the
explained in the malfunction code table. Carry out the test operation
user interface. Refer to the indoor unit installation manual for
again and confirm that the abnormality is properly corrected.
more details concerning the individual test run.
INFORMATION INFORMATION
t It may take 10 minutes to achieve a uniform refrigerant Refer to the installation manual of the indoor unit for other
state before the compressor starts. detailed malfunction codes related to indoor units.
t During the test operation, the refrigerant running sound
or the magnetic sound of a solenoid valve may
become loud and the display indication may change.
16.2 Malfunction code list
These are not malfunctions.
In case of a displayed malfunction code, perform correcting actions
Procedure as explained in the malfunction code table.
1 Close all front panels in order to not let it be the cause of After correcting the abnormality, press BS3 to reset the malfunction
misjudgement (except the electrical component box inspection code and retry operation.
opening service cover).
The malfunction code which is displayed on the outdoor unit will
2 Make sure all field settings you want are set. indicate a main malfunction code and a sub code. The sub code
3 Turn ON the power to the outdoor unit and the connected indoor indicates more detailed informati on about the malfunction code. The
units. malfunction code will be displayed intermittent.
Example:
NOTICE
Main code Sub code
Be sure to turn on the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
With an interval of 1second, the display will switch between main
code and sub code.
4 Make sure the default (idle) situation is existing; see
"13.2 Operating the push buttons and DIP switches on the logic
board" on page 27. Push BS2 for 5 seconds or more. The unit
will start test operation.
t The test operation is automatically carried out, the outdoor
unit display will indicate " " and the indication "Test
operation" and "Under centralized control" will display on the
user interface of indoor units.
Steps during the automatic system test run procedure:
- " ": control before start up (pressure equalization)
- " ": cooling start up control
- " ": cooling stable condition
- " ": communication check
- " ": stop valve check
- " ": pipe length check
- " ": refrigerant amount check
- " ": in case [2-88]=0, detailed refrigerant situation
check
- " ": pump down operation
- " ": unit stop
t During the test operation, it is not possible to stop the unit
operation from a user interface. To abort the operation, press
BS3. The unit will stop after ±30 seconds.
19
37
3P391148-1
Below table gives an overview of the malfunction codes which may appear.
Malfunction code
Main Sub code
code Master/slave 1/slave 2 Contents Solution
01/03/05 High pressure switch was activated (S1PH, S2PH) - A1P Check stop valve situation or abnormalities in (field) piping or
(X3A; X4A) airflow over air cooled coil.
02/04/06 Refrigerant overcharge Check refrigerant amount+recharge unit
Stop valve closed Open stop valves
13/14/15 Stop valve closed (liquid) Open liquid stop valve
18 Refrigerant overcharge Check refrigerant amount+recharge unit
Stop valve closed Open stop valves
01/02/03 Low pressure malfunction: Open stop valves
Stop valve closed Check refrigerant amount+recharge unit
Refrigerant shortage Check the user interface's display or
Indoor unit malfunction Transmission wiring between the outdoor unit and the
indoor unit
01/05/08 Electronic expansion valve malfunction (subcool) (Y2E) - A1P Check connection on PCB or actuator
(X21A)
04/07/10 Electronic expansion valve malfunction (main) (Y1E) - A1P Check connection on PCB or actuator
(X23A)
16/22/28 Discharge temperature sensor malfunction (R21T): open Check connection on PCB or actuator
circuit - A1P (X29A)
17/23/29 Discharge temperature sensor malfunction (R21T): short Check connection on PCB or actuator
circuit - A1P (X29A)
18/24/30 Discharge temperature sensor malfunction (R22T): open Check connection on PCB or actuator
circuit - A1P (X29A)
19/25/31 Discharge temperature sensor malfunction (R22T): short Check connection on PCB or actuator
circuit - A1P (X29A)
47/49/51 Compressor casing temperature sensor malfunction (R8T): Check connection on PCB or actuator
open circuit - A1P (X29A)
48/50/52 Compressor casing temperature sensor malfunction (R8T): Check connection on PCB or actuator
short circuit - A1P (X29A)
01/03/05 Suction temperature sensor malfunction (R3T) - A1P (X30A) Check connection on PCB or actuator
01/02/03 De-icing temperature sensor malfunction (R7T) - A1P (X30A) Check connection on PCB or actuator
06/07/08 Liquid temperature sensor (after subcool HE) malfunction Check connection on PCB or actuator
(R5T) - A1P (X30A)
01/02/03 Liquid temperature sensor (coil) malfunction (R4T) - A1P Check connection on PCB or actuator
(X30A)
01/02/03 Gas temperature sensor (after subcool HE) malfunction (R6T) Check connection on PCB or actuator
- A1P (X30A)
06/08/10 High pressure sensor malfunction (S1NPH): open circuit - Check connection on PCB or actuator
A1P (X32A)
07/09/11 High pressure sensor malfunction (S1NPH): short circuit - Check connection on PCB or actuator
A1P (X32A)
06/08/10 Low pressure sensor malfunction (S1NPL): open circuit - A1P Check connection on PCB or actuator
(X31A)
07/09/11 Low pressure sensor malfunction (S1NPL): short circuit - A1P Check connection on PCB or actuator
(X31A)
14 Transmission outdoor unit - inverter: INV1 transmission Check connection
trouble - A1P (X20A, X28A, X40A)
19 Transmission outdoor unit - inverter: FAN1 transmission Check connection
trouble - A1P (X20A, X28A, X40A)
24 Transmission outdoor unit - inverter: FAN2 transmission Check connection
trouble - A1P (X20A, X28A, X40A)
30 Transmission outdoor unit - inverter: INV2 transmission Check connection
trouble - A1P (X20A, X28A, X40A)
38
3P391148-1
Malfunction code
Main Sub code
code Master/slave 1/slave 2 Contents Solution
01/02/03 INV1 unbalanced power supply voltage Check if power supply is within range
07/08/09 INV2 unbalanced power supply voltage Check if power supply is within range
01/05/07 Reversed power supply phase malfunction Correct phase order
04/06/08 Reversed power supply phase malfunction Correct phase order
01/08/11 INV1 voltage power shortage Check if power supply is within range
02/09/12 INV1 power phase loss Check if power supply is within range
22/25/28 INV2 voltage power shortage Check if power supply is within range
23/26/29 INV2 power phase loss Check if power supply is within range
03 Malfunction code: System test run not yet executed Execute system test run
(system operation not possible) Execute autocharge function (see manual); unit not ready
Warning indication: Leak detection or refrigerant amount for leak detection functionality
check not performed (system operation possible)
04 System test run abnormal ending Execute test run again
01 Faulty wiring to Q1/Q2 or indoor - outdoor Check (Q1/Q2) wiring
03 Faulty wiring to Q1/Q2 or indoor - outdoor Check (Q1/Q2) wiring
01 Warning: faulty wiring to Q1/Q2 Check Q1/Q2 wiring
02 Malfunction code: faulty wiring to Q1/Q2 Check Q1/Q2 wiring
11 Too many indoor units are connected to F1/F2 line Check indoor unit amount and total capacity connected
Bad wiring between outdoor and indoor units
01 System mismatch. Wrong type of indoor units combined Check if other indoor units have malfunction and confirm
(R410A, R407C, RA). indoor unit mix is allowed.
Indoor unit malfunction.
03 Connection malfunction over indoor units or type mismatch Check if other indoor units have malfunction and confirm
(R410A, R407C, RA). indoor unit mix is allowed.
18 Connection malfunction over indoor units or type mismatch Check if other indoor units have malfunction and confirm
(R410A, R407C, RA). indoor unit mix is allowed.
31 Wrong unit combination (multi system) Check if unit types are compatible
49 Wrong unit combination (multi system) Check if unit types are compatible
01 Auto address malfunction (inconsistency) Check if transmission wired unit amount matches with
powered unit amount (by monitor mode) or wait till
initialisation is finished.
01 Auto address malfunction (inconsistency) Check if transmission wired unit amount matches with
powered unit amount (by monitor mode) or wait till
initialisation is finished.
05 Stop valve closed or wrong (during system test run) Open stop valves
INFORMATION
References can be found on the wiring diagram.
Information code
Main code Contents Solution
Leak detection function related
Unit is not prepared to execute leak detection operation Refer to requirements to be able to execute leak detection
operation.
Indoor unit is out of temperature range for leak detection Retry when ambient conditions are satisfied
operation
Outdoor unit is out of temperature range for leak detection Retry when ambient conditions are satisfied
operation
Too low pressure was noticed during leak detection operation Restart leak detection operation
Indicates an indoor unit which is not compatible with leak Refer to requirements to be able to execute leak detection
detection functionality is installed operation.
19
39
3P391148-1
17. Operation of the unit 2 Calculate the volume of the room (m 3) where the indoor unit is
installed.
Once the unit is installed and test operation of outdoor unit and In a case such as the following, calculate the volume of (A), (B)
indoor units is finished, the operation of the system can start. as a single room or as the smallest room.
For operating the indoor unit, the user interface of the indoor unit A Where there are no smaller room divisions:
should be switched ON. Refer to the indoor unit operation manual for
more details.
installed
2
If the result of the above calculation exceeds the maximum
concentration level, a ventilation opening to the adjacent room
shall be made.
4 Calculate the refrigerant density taking the volume of the room
where the indoor unit is installed and the adjacent room.
1 Direction of the refrigerant flow
2 Room where refrigerant leak has occurred (outflow of all Install ventilation openings in the door of adjacent rooms until
the refrigerant from the system) the refrigerant density is smaller than the maximum
concentration level.
Pay special attention to places, such as basements etc., where
refrigerant can stay, since refrigerant is heavier than air.
NOTICE
Where a single refrigerant facility is divided into 2 entirely
independent refrigerant systems, use the amount of
refrigerant with which each separate system is charged.
40
3P391148-1
Indoor unit
Outdoor unit
(Piping consists of REFNET headers only)
Header branch fitting
Outdoor unit
(Piping including both headers and joints)
Units can be added by connecting them directly to the REFNET header or REFNET joint. Further branches cannot be 19
included in the system below the REFNET header branch.
Notes:
1. When the capacity ratio of the indoor system to the outdoor unit is more than 100% and when all the indoor units
are in operation at the same time then the rated capacity of each unit will be somewhat reduced.
2. Special purpose REFNET pipe components must be used for all the pipe work. For further details concerning
choice of components, types of components, etc.
0.16 0.18 0.20 0.25 0.35 0.40 0.45 0.55 0.60 0.65 0.75
0.5
1.0
* When the equivalent piping length in cooling operation is calculated, the gas pipe size is selected.
When the equivalent piping length in heating operation is calculated, the liquid pipe size is selected.
Make sure that all branch pipes are fitted such that they branch either horizontally or vertically.
When the size of the selected field piping is different from that of branch pipe then the connecting section should
be cut with a pipe cutter as shown in the figure below.
When you are cutting an inlet or outlet pipe with a pipe cutter make sure that you make the cut in the center of the
connection area.
Branch pipes must be insulated in accordance with the handbook which comes with each kit.
19
When the number of indoor units to be connected to the branch pipes is less than the number of branch pipes
available for connection then cap pipes should be fitted to the surplus branches.
When the size of the selected field piping is different from that of branch pipe then the connecting section should
be cut with a pipe cutter as shown in the figure below.
When field piping is connected to the B section of the inlet/outlet pipe on the outdoor unit side of the liquid pipe
header.
Cut the B section with a pipe cutter as shown below and connect it to the A section.
Connect the flared section of the field pipe to the B section.
Fit the branch pipe so that the branch lies in a horizontal plane.
The branch pipe must be insulated in accordance with the instruction manual which comes with each kit.
1. Use the insulator included in the kit to insulate the header.
2. Joints between insulators included in the kit and those already applied to the field piping should be sealed with the
tape which is also included in each kit.
3. Any cap pipes should also be insulated using the insulator provided with each kit and then taped as described
above.
I.D. φ15.9
80
I.D. φ12.7
80
I.D. φ9.5
I.D. φ6.4
338 (42)
380 250 (40)
80 D3K05234A
100
I.D. φ15.9
80
80
I.D. φ12.7 I.D. φ9.5
I.D. φ6.4
I.D. φ25.4 O.D. φ22.2 O.D. φ19.1 I.D. φ22.2 O.D. φ15.9 I.D. φ19.1
I.D. φ12.7
I.D. φ19.1
448 (55 ) I.D. φ15.9
503
I.D. φ6.4
I.D. φ12.7 I.D. φ9.5
D3K05236A
534 (100)
400 (38)
634
438
D3K05237A
2P182411-1
19
2P182411-1
77
40
80
120
130 2 × 60 = 120 60
I.D. φ15.9
410
3-I.D. φ12.7 I.D. φ6.4
3-I.D. φ6.4
150 2 × 60 = 120 60 I.D. φ9.5
380 I.D. φ12.7
93
I.D. φ22.2
O.D. φ12.7
60
O.D. φ19.1
I.D. φ15.9
×2
100 80 I.D. φ9.5
D3K03629C
77
I.D. φ22.2
40
81
121
171
93
I.D. φ9.5
60
615
I.D. φ12.7 2-I.D. φ12.7
I.D. φ25.4 O.D. φ12.7
O.D. φ22.2 I.D. φ15.9
×2
80
100 D3K03630C
77
83
I.D. φ31.8
123
140 5 × 60 = 300
173
6-I.D. φ9.5
185 2 × 160 = 320 2-I.D. φ12.7
I.D. φ12.7
93
755
3-I.D. φ12.7 3-I.D. φ12.7
I.D. φ15.9
O.D. φ12.7 I.D. φ19.1 O.D. φ6.4
I.D. φ15.9 O.D. φ15.9 I.D. φ9.5
×2 ×2
80 40
80 D3K03631C
INSULATION
INSULATION
I.D. φ31.8
76
93
I.D. φ38.1
135
180 7 × 60 = 420
710
8-I.D. φ9.5
I.D. φ15.9
165 5 × 80 = 400 80 80
60
775
I.D. φ19.1
I.D. φ15.9
I.D. φ15.9
I.D. φ19.1
O.D. φ15.9
I.D. φ12.7 O.D. φ9.5
I.D. φ22.2 O.D. φ19.1 I.D. φ6.4
×6
×6
80 100 50
D3K03632C
19
3P113151-1C
3P113151-1C
5.3 Reducer
KHRP26M73TP / KHRP26M73HP
19
C: 3P113129-1B
3D052312
3D052280
BHFP22P151
Gas side Unit (mm)
3D052314
19
3D052279
BHFP22P100 / BHFP22P151
1P173261-1A
19
1P173261-1A
1P173262-1A
19
1P173262-1A
6. Caution Label
6.1 RXYQ6TRY6 / RXYQ8TRY6 / RXYQ10TRY6 / RXYQ12TRY6
2P343554-1C
2P343554-1C
19
3P342938-1A
19
3P342938-1A
3P346357-1A
19
3P350959-1B
3P350959-1B
3P350960-1B
19
3P350960-1B
3P350960-1B
19
3P343021-1A
19
3P343021-1A
Part 8
Option of Control
1. Option List of Controllers.....................................................................698
1.1 Operation Control System Optional Accessories .................................698
1.2 System Configuration ...........................................................................699
1.3 Building Management System..............................................................700
20
Notes:
1. Installation box (No.8) is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box (No. 8) is necessary for second adaptor.
6. Installation box (No. 8) is necessary for each adaptor.
7. Individual airflow direction, auto airflow rate and sensing sensor control can be set only via wired remote controller
BRC1E62. Cannot be set via other remote controllers.
8. Since the control panel is equipped as standard, use the option for 2 remote control system.
9. When using BRC1E62, be sure to remove the control panel and since BRC1E62 cannot be stored inside the
indoor unit, please place it separately.
10.Remove the group control adaptor which is a standard equipment before mounting KRP6A1 and DTA104A62.
KRP6A1 and DTA104A62 cannot be mounted to the same indoor unit at the same time.
5 Interface adaptor for SkyAir For FCQ-B, FFQ-B, DTA112BA51 Adaptors required to connect products other than those of the
series FHQ-BV, FBQ-B VRV system to the high-speed DIII-NET communication
system adopted for the VRV system.
6 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55 To use any of the above optional controllers, an appropriate
7 Wiring adaptor for other air-conditioner DTA103A51 adaptor must be installed on the product unit to be controlled.
Up to 1024 units can be centrally controlled in 64 different
groups.
8 DIII-NET Expander Adaptor DTA109A51 Wiring restrictions (max. length: 1,000m, total wiring length:
2,000m, max. number of branches: 16) apply to each adaptor.
8-1 Mounting plate KRP4A92 Fixing plate for DTA109A51
Notes:
1. Installation box for adaptor must be obtained locally.
2. For residential use only. Cannot be used with other centralized control equipment.
20
Notes:
1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE).
2. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries.
3. Installation box for adaptor must be obtained locally.
Part 9
Guide Specifications
1. Guide Specifications ...........................................................................702
1.1 Indoor Unit............................................................................................702
1.2 Outdoor Unit .........................................................................................702
1.3 Control..................................................................................................702
21
1. Guide Specifications
Unit is air cooled, split type multi-system air conditioner consisting of plural indoor and outdoor units, having
capability to cool or heat for the requirements of the rooms.
1.1 Indoor Unit
Various type's and capacity's indoor units can be connected to one refrigerant circuit and controlled individually.
Refer to the chapter of Indoor Units for connectable models.
1.3 Control
Indoor unit, BP unit or BS unit, etc. have electronic control device which control refrigerant flow in respond to
required load of the room.
The address of the indoor unit can be set automatically.
In case of centralized control, it can be set with the remote controller.
Unit is equipped with a self-diagnosis for easy and quick maintenance and service.
The LCD (Liquid Crystal Display) remote controller memorizes the malfunction code for easy maintenance.
Various control system are available as option such as iTM, Central Remote Controller, Unified ON / OFF
Controller, etc. Refer to the chapter of Option of Control for details.
Specifications, designs and other content appearing in this brochure are current as of December 2014 but subject to change without notice.