You are on page 1of 6

Protection of VSC-Multi-Terminal HVDC against DC Faults

Lianxiang Tang, Boon-Teck Ooi, Senior Member, IEEE


Department of Electrical and Computer Engineering
McGill University
3480 University Street
Montreal, P. Q.
CANADA, H3A 2A7

Abstract-Voltage-Source Converters (VSCs), by themselves, The DC grid is assumed to be made up of Overhead


are defenseless against dc faults. Their anti-parallel diodes Lines (as their faults are more frequent than cable lines).
conduct as rectifier bridges to feed the fault. Their IGBTs The protection cycle is envisaged as follows: the presence
(Insulated Gate Bipolar Transistors) are helplessly by-passed, of a Line-to-Ground DC Fault or a Line-to-Line DC Fault is
unable to extinguish the fault current. This paper shows how a
VSC-Multi-Terminal High Voltage Direct Current (MTDC) detected, whereupon the IGBT-Circuit Breakers (IGBT-
transmission system can survive dc faults by a Protection Scheme CB) and the IGBTs of the VSCs block to protect the VSCs.
based on: (1) fast, reliable fault detection; (2) blocking of IGBT- In order to extinguish the fault current, it is necessary to
Circuit Breakers (IGBT-CBs) and blocking of the IGBTs of block all the VSCs and IGBT-CBs thus causing a brief
VSCs; (3) locating of the faulted dc line; (4) isolating of the disruption of service. The faulted transmission line section
faulted dc line by economical Fast DC Switches; (5) de-blocking has to be identified quickly (based on feature extraction of
of IGBT-CBs and IGBTs of VSCs to resume normal service. the voltage and current waveforms). If the fault has been
verified as permanent rather than temporary, the Fast DC
Keywords-- Voltage-Source Converter, HVDC, Multi-Terminal Switches (SW) (cheap mechanical switches which can
HVDC, DC Fault, Protection, Fault Detection, Fault
Identification, Fast DC Switch, IGBT-Circuit Breaker. isolate the faulted transmission line but cannot break a dc
fault current) on either end of identified faulted dc line are
I. INTRODUCTION opened. The IGBT-CBs and the Converter Stations unblock
and the M-VSC-HVDC system resumes service.
HVDC transmission system based on Voltage-Source The research is conducted by digital simulation studies
Converters (VSCs) is no longer academic research [ 1,2] but using EMTDC-PSCAD of Manitoba HVDC Research
a commercial product [3-51. Revenue installations of point- Center, Winnipeg, MB, Canada. The ground rules placed
to-point VSC-HVDC are now in service in Sweden on the detection and identification schemes are: (1) only the
(Hellsjohn and Gotland), Denmark (Tjaereborg), Australia local information at each VSC is to be used; (2) minimum
(DirectLink and Murray Link) and USA (Eagle Pass and interruption time; (3) fast computation for feature extraction
Cross Sound Cable). The next challenge is to realize Multi- to identify the faulted DC line will be available.
Terminal HVDC (MTDC) based on VSCs. H.Jiang and
A.Ekstrom [6] proposed a MTDC system for urban sub- 11. MODEL OF M-VSC-HVDC SYSTEM
transmission. MTDC has also been proposed for off-shore
wind-farms [7,8] and Premium Quality Power Park [9]. The single-line diagram of Fig. 1 shows a MTDC system
MTDC has the potential of enabling electricity to be traded consisting of a ring network of 5 Converter Stations
more conveniently between generators and customers thus VSC(i), i=1,2..5, tied together by 5 Overhead DC Lines
(Lineu), j=1,2..5). Line6 is an additional line joining VSC3

-
promoting competition in electricitymarkets.
Voltage-Source Converters (VSCs), by themselves, are .................................................................
defenseless against dc faults. During such faults, the anti- i A S AC2
'
parallel diodes conduct as rectifier bridges. Because the VSCl vsc2
fault current continues to be fed, it does not extinguish.
.................... Node 1
Meanwhile, the IGBTs, IGCTs or GTOs, which are in
Line 5 Line 2

- -
parallel to the anti-parallel diodes, have lost control. As the
viability of MTDC systems depends on the capability to IlOKm
survive this worst case scenario, a program has been AC5 AC3
initiated to research on dc fault protection. Three methods vsc5 vsc3
of extinguishing the dc fault current have been studied by
Line 4 Line 3
the authors: (1) AC Circuit Breakers on the ac side of the
VSCs (cheapest but longest interruption time); (2) IGBT- 1 4 h V 1 2 h
Circuit Breakers (IGBT-CBs) placed between each VSC
and the dc network (intermediate interruption time); (3)
IGBT-CBs at each end of a dc branch line (most expensive
Ivsc4 1
but with no interruption of service). Page limit allows only ' 5 4
the second method (2) to be presented in this paper. Future Fig. 1MTDC System
papers will address the other methods.

0-7803-7262-X/02/$10.00 0 2002 IEEE. 719


1
to VSC5. The lengths of the lines are given in Fig. 1. The dc
lines are built up of 2 km length R,L,C models. In Fig.1
AC(i), i=1,2..5, represent the 3-phase ac systems. Other
notations used in the text are: igbt(i)---IGBT-CB at
VSC(i)); SW-ji--- Fast DC Switch; ib(jix)---branch
currents, where j=line number, i=VSC number and x=p,n
denotes positive, negative pole.
L
A. Protection of Converter Stations VSC)
The protection of all converter stations is exemplified by
A
the example for VSC 1. Fig. 2 shows the connection of
VSCl to the dc lines. The DC capacitors of the 3-phase
bridge converter have mid-point grounding. Protection
against DC faults is provided by igbtl---IGBT-CB, which Fig. 3 IGBT-Circuit Breaker (IGBT-CB)
consists of IGBT switches and anti-parallel diodes placed
between the dc capacitor nodes and the dc line nodes. This C. Fast DC Switches
IGBT-CB design is relatively economical but it does not Fast DC Switches (SW-ji) are relatively cheap
have bi-directional blocking capability. Refemng to Fig.3, mechanical switches which can isolate a dc line after the
when the dc current through the VSC is in the direction of fault current has been extinguished. But they are not
the dashed arrow, blocking the IGBTs in the CB cuts off capable of breaking any fault current. They are placed at
the flow of current to the dc network. When the dc current both ends of each dc line. Fig.2 shows SW-11 and SW-51
has the opposite direction of the solid arrow, it cannot be which can isolate Linel and Line5 from VSC1. The Fast
blocked by the IGBT-CB as there is a path through the anti- DC Switches are activated from the Converter Station after
parallel diodes. For this reason, the blocking of the IGBT- local identification from the branch currents (ibl l x and
CB must be accompanied by the blocking of the IGBTs in ib5lbx) that the faulted line belongs to one of its branches
the VSC (illustrated by one leg in Fig.3). and after it has been verified that the fault is permanent.
The detection of the DC fault is based on the
measurements of: (1) the voltages, u&), across the DC D. Types of DC Fault
capacitors and (2) the currents, Ik(i), passing through the The class of DC faults under consideration are: (1)
IGBT-CB. When the pre-set thresholds of the dc voltages Positive Line-to-Ground Fault; (2) Negative Line-to-
and the incremental dc currents are crossed simultaneously Ground Fault; and (3) Line-to-Line Fault. The protection
for a preset time, both the igbtl and the VSCl are blocked method described in this paper has been proven to be
simultaneously. successful for the 3 types of DC Faults. Because of the page
limit, only illustrative examples are presented.
B. Data for Identification ofLine with DC Fault
The ground rule concerning local information means that 111. PROTECTION CYCLE FOLLOWING A DC FAULT
the faulted line should be identified at each VSCi. In Fig. 2
for example, the waveform pattern in the branch currents A. Prior to DC Fault
ibll and ib51, which are locally accessible to VSC1, are to In the beginning of each simulation, the DC voltage
be used in determining whether Linel or Line5 has or does reference of the DC Voltage Regulator (VSC1 in Fig. 1) is
not have a DC fault. set. The other VSCs, operating as inverters or rectifiers, are
set to deliver their specified real and reactive ac powers.
After the steady-state operation is reached in the digital
simulation, the fault is introduced. Fig.4 shows the branch
currents ib(ji) as measured at each VSC(i) during a Positive

-2 4 l7x
sw-11
Line-to-Ground fault situated in Linel near VSC1. The
blocking of igbt(i) (and VSC(i), not shown) is shown by the
Fast DC
Switch
4 dash-dot-dash lines in Fig.4.

B. Immediate Eflect ofDC Fault on Converter Stations


4

' I i
vsc 1
R.( ioiiny

ih5lnk
Fast
sw-5DC
1

Switch
A DC fault draws large currents from the VSCs on both
ends of the faulted line because of the large potential
differences between the dc voltages of the VSCs and the
short circuit voltage at the fault (which is close to zero).
The size of the large currents depends on the line
resistances and inductances (proportional to distance)
\ between the fault and the VSCs.
Fig. 2 Detail of VSCl and IGBT-CBs In Fig.4 the onset of the fault in Line 1 is noticed by the
sharp rise of ibllp and ibl2p. Meanwhile, the branch
currents ib23p, ib33p, ib63p from VSC3, ib45p, ib55p,

720
ib65p from VSCS and ib34p, ib44p from VSC4 are less In the first step towards restoration, the IGBT-CBs and
affected because the voltage differences between the VSCs on either side of the faulted line are unblocked so that
capacitor supported nodal voltages are very much less than the dc network becomes charged. When the other stations
the voltage differences with the fault. detect the network voltage, their IGBT-CBs and VSCs
unblock and the MTDC system resumes operation without
C. Blocking of IGBT-CB and Converter Station the isolated line.
The large currents quickly discharge the DC capacitors
of the nearest two VSCs so that their dc voltages drop IV. DC FAULT DETECTION
abruptly. These two concomitant factors: the decrease in the
dc voltages of the VSCl and VSC2 and the increase in their The blocking of igbt(i) and VSC(i) is based on the dc
dc currents, form the basis of reliable detection. On voltage at the dc network node of VSC(i) decreasing below
detection of the fault, (igbtl, VSC1) and (igbt2, VSC2) a Voltage Threshold and lAIdc(i)\,the incremental dc current
block so that the fault current ceases to be fed from the of VSC(i) injected into the dc network, simultaneously
severed Converter Stations VSCl and VSC2. The fault exceeding a Current Threshold for a Preset Time Duration.
current is then drawn from the capacitors of the VSCS and The simultaneous cross-over of the thresholds for a
VSC3. The current increase of ib55p is less than ibllp sufficiently long duration allows the dc fault to be
because of the greater distance to the fault. The conhtions distinguished from other dwturbances. The Voltage
are set for igbt5 and VSCS to block. Threshold, the Incremental Current Threshold and Preset
Time Duration will have to be determined for specific
D. Domino Blocking of IGBT-CBs and Converter Stations MTDC systems, when the parameters of the dc lines are
As VSCS and igbt5 block, they in turn set up the known (overhead or underground cables, length of dc lines,
conditions for igbt3, VSC3 and then igbt4, VSC4, which etc.).
are electrically further away from the fault, to block. At the Precautions have been taken to ensure that AC faults
end of the sequential severing of all VSCs ,the dc network cannot be mistaken by the DC Fault Detection. It has been
is isolated from any source that can feed the fault. Given found that the strategy of blocking the IGBTs of the VSC
sufficient time for the arc to de-ionize, the fault is self- when AC faults occur, isolates the effects of ac faults on
clearing. Otherwise, the fault is possibly a permanent fault the dc system. The dc capacitors of the VSC also filter out
and there is a test to confirm it. the effects of AC fault disturbances thus smoothing the
currents flowing through the IGBT-CBs. As a result, the
E. Local Identifzcation of Faulted Line currents through the IGBT-CBs have low dlAIdc(i)l/dt. In
Because of the requirement that the Protection System contrast, DC faults are associated with high ldIdc(i)l/dt since
must be based on its local measurements, each Converter there is a large voltage difference between the dc capacitor
Station must be able to identify if any one of the branch voltage and the voltage at the fault location. Thus a high
lines emanating from it has a fault. This is done by using dlAIdc(i)l/dtis essential to confirm a DC fault. This ensures
the features in the waveforms of branch currents for that an AC fault cannot be mistaken by the DC Fault
identificationas will be explained in Section V. Detection.

F. Verification of Permanent/TemporaryFault V. FEATURE EXTRACTION FOR LOCATING


ARer all the IGBT-CBs and all the VSCs have blocked FAULTED LINE
and sufficient time has been given for the fault to
extinguish naturally, a test is performed to verify if the fault From Fig. 4, one sees that the initial surge in ibllp and
is temporary or permanent. This consists of momentarily ibl2p is distinguishable from the other initial surges by
unblocking the IGBT-CBs on either side of the identified having: (i) the largest initial change in current; and (ii) the
faulted line. Because the dc capacitors of all the blocked longest rise time interval (from the onset of the fault to peak
VSCs are continually being charged by the anti-parallel current value). Such features are used to identify Line1 as
diodes, the capacitor charges are momentarily transferred to having the dc fault.
the dc network to raise the network voltage. Thus, the Prior to a dc fault, all the branch currents are in steady
voltage sensors at the network node of each VSC will state so that their dib(i)/dt are equal to zero, where ib(i) is
record sustained dc voltages in the case when the fault has the measurement of the branch current ibjip. At to, the
been cleared. However, if the fault is permanent, the dc instant of the fault, the branch current at each end of the
voltages will return to zero, which is the voltage of the faulted dc line increases with high dib(i)/dt because of the
permanent fault. large voltage difference between the dc capacitor voltage
and the voltage at the fault location. Therefore the initial
G . Fault Isolation and Restoration change of a branch current of the faulted line is the largest.
When the fault is temporary, all VSCs can unblock. The In contrast, the initial change of the branch current in each
MTDC system resumes operation. un-faulted line is small. This is because the voltage
When the fault is permanent, the control stations on difference of the dc capacitors at both ends of each un-
either end of the permanently faulted line open the Fast DC faulted dc line is small. However, this initial change is big
Switches, thereby isolating the fault. enough for to to be detected in all the branch currents.

721
-intibl lp ---- intib5lp

0.~1
r
V

0.5 -intibl2p ---- intib22p


n

4 -2
2 -ib23p
r --- ib33p --ib63p---igbt3

Time (s)
Fig.4. Branch Currents

second feature relates to the fact that the faulted Method B - Tfigp-Rise-Timeof First Wavefiont
branch currents ibl l p and ibl2p have the longest rise time. The index T(ji)p of method B is a measurement of the
The initial long rise time is related to the growth of fault Rise-Time of the first wavefront of the branch current
currents which are drawn from the dc capacitors of VSCl ib(ji)p. Fig. 6 shows that the dominating indexes are again
and VSC2 through relatively short sections of Linel. After T1 l p and T12p.
igbtl and igbt2 have blocked, the fault currents have their
sources from the more distant VSC3 and VSC5. The Method C - ind(ijk)-Oscillation Pattern
subsequent oscillations in the current pattems bear the Fig. 7 displays the index ind(ijk)=SGN[d{ib(ji)p-
resonance frequency of the L-C-R circuits of the ib(ki)p)/dt], which is the sign [SGN] of the time derivative
transmission line models. Thus the later rise times are of the difference of the currents of the Line(j) and Line(k)
shorter. emanating from VSC(i). Fig.7 shows that this index
The features are embodied in 3 indexes which are captures the changing fkequency of the network resonance
computed from records of the measurements of the branch evident in Fig.4. The signals indl 15p and ind221p are wide
currents ibji. The computation of each index ceases when pulses with single polarity before. the IGBT-CBs block.
the IGBT-CB and its VSC block. Each index has its This feature allows Linel to be identified as the faulted
discriminant by which a dc line without a fault can be line.
distinguished from a dc line which has the fault.
VI. RESULTS OF IDENTIFICATION TESTS
Method A - intibogp-Large Initial Current Change
Fig. 5 displays the index intib(ji)p which is the time Each VSCi, i=1,2..5 will have its indexes intib(ji)p of
integral of {ib(t)-ib(to)}evaluated from to to t,+AT, where Fig. 4, T(ji)p of Fig. 5 and ind(ijk)p of Fig. 6 computed by
ib(t) is the measurement of the branch current ibjip. AT is a Digital Signal Processors (DSPs) from memory storage of
fixed short time span chosen to maximize the feature. The the recent measurements of the branch currents. Note that
time to is the instant when disturbance in the current is many of the indexes are very close to zero so that they are
detected. Only the disturbances prior to the blocking of the not visible in the graphs. As {intibl lp, T1 lp, indl 15p)
IGBT-CB and the converter are used in order to avoid false and {intibl2p, T12p, and ind22lp) dominate over other
identification. The index intib(ji)p exaggerates the initial indexes, both VSCl and VSC2 identify that the fault is in
dib(i)/dt feature which is largest in the line which contains Linel, and open the Fast DC Switches SW-11 and SW-12
the fault. after it has been verified that the fault is a permanent fault.

722
methods are prone to false crossings. To guard against false
crossings, the computed data are considered valid only
when they lie between the blocking of the IGBT-CB and a
few milliseconds before. When there is no real fault, the
IGBT-CBs will not block. Thus erroneously generated data
will not be used.

B. Polling Indexes
Although the three methods are not truly independent,
they represent different ways of extracting the features.
Polling of the three indexes ensures greater reliability.

C. Extensive Tests
Simulation tests on DC Faults have been conducted in
each of the 6 lines of Fig. 1. Three types of fault have been
simulated for every line, at each end of the line. The three
types of fault conducted are: (1) Positive Line-to-Ground
Fault; (2) Negative Line-to-Ground Fault; (3) Line-to-Line
Fault. The same Voltage Threshold and Incremental
Current Threshold have been used to block the VSCs and
the IGBT-CBs in all the three types of fault. In all cases, the
three indexes identifying the faulted dc line stand out as
U
clearly as in Fig. 5, 6 and 7 and a common discriminant for
0.144 0.146 0.148 0.15 each index exists which can classify a line as containing a
fault or as being free of faults.
Time (s)
Fig.6. Method B VII. COMPLETE PROTECTION CYCLE

Fig. 8 (a) and (b) show the dc voltages measured on the


indl 15 ---igbt 1 VSC-side of igbt4 and on the network side of igbt4 during a
I permanent Line-to-Line Fault in Line3 near VSC4. Fig. 8
(c) shows the branch currents ib34p and ib44p. The fault
occurs at 144 ms. From indexes similar to Fig.5, 6 and 7,
VSC3 and VSC4 are able to identify that Line3 is the
-e
faulted line. A test is necessary to dwover if the fault is
-ind332 -.- igbt3 temporary or permanent. At 195 ms, after allowing 50 ms
for the fault to extinguish naturally, igbt3 and igbt4 unblock
for 1 ms. The dc capacitors of VSC3 and VSC4 recharge
the lines but as shown in Fig. 8 (b) the dc voltages drop to
zero again because the fault has been simulated as a
permanent fault. As Fast DC Switches are incapable of
interrupting a fault current, another 50 ms is allowed for the
fault current to extinguish. At 250 ms, VSC3 and VSC4
activate the Fast DC Switches SW-33 and SW-34 to isolate
Line3 from the dc network. The voltages of the dc network
which have been kept at zero by the fault until this time, are
charged by the back biased anti-parallel diodes. At 330 ms,
the IGBT-CBs and VSCs are all unblocked.
The complete protection cycle of a Line-to-Ground Fault
is similar, except that at the end the unbalanced voltages of
the positive and negative poles must be equalized before the
VSCs are permitted to unblock.
Time(s)
VIII. CONCLUSION
Fig.7 Method C
The research has shown that Line-to-Ground and Line-
A. Guard against False Zdentzjication to-Line Faults in the overhead dc lines of M-VSC-HVDC
The initiations of the computation of the indexes are system can be protected by fast detection which blocks the
based on the branch currents and their gradients exceeding IGBT-CBs and the Converter Stations. Each Converter
some pre-set thresholds. Because of noise, pre-set threshold Station can quickly identify if the fault comes from any

723
U
0.15 0.2 0.25 0.3 0.35 t (s)
CO)
+
a r
ib44p
!’ I I I I I
-2
0.15 0.2 0.25 0.3 0.35 t(S)
(c)
Fig.8 Complete Protection Cycle (Lto-L Line-to-Line Voltage; Gto-G Line-to-Ground Voltages)
(a) Voltages of nodes between VSC and IGBT-CB (b) Voltages of nodes between IGBT-CB and DC Network (c) Branch Currents

one of its branch lines so that the Fast DC Switches [ 5 ] F.Schettler, H.Huang and N.Christ1, “HVDC Transmission System
belonging to the faulted line will be opened to isolate it, if a using Voltage Sourced Converters-Design and Applications”, IEEE
PES Summer Meeting, July 2000.
verification test shows that the fault is permanent. [6] H.Jiang and A.Ekstrom, “Multiterminal HVDC Systems in Urban
Thereafter, the IGBT-CBs and the Converter Stations Areas of Large Cities”, IEEE Transactions on Power Delivery,
unblock and the MTDC system resumes service, as will V01.13, N0.4, October 1998, pp 1278-1284.
[7] Weixing Lu and Boon Teck Ooi, “ Multi-terminal DC transmission
also be for the case of a temporary fault. system for wind-farms.” Power Engineering Society Winter
Meeting, 2001. IEEE, Volume: 3 ,2001 Page@): 1091 -1096
M. ACKNOWLEDGEMENT [8] Weixing Lu and Boon Teck Ooi, “Multi-Terminal LVDC System for
Optimal Acquisition of Power in Wind-Farm Using Induction
Generators,” Power Electronics Specialists’ Conference, June 2001,
The authors thank Mr. Mats Hyttinen, Dr. Ying Jiang- Vancouver.
Hafker and Mr. Gunnar Asplund for their guidance, [9] Weixing Lu and Boon Teck Ooi, “Multi-Terminal HVDC as Enabling
direction and encouragement. The research is supported by Technology of Premium Power Quality Park,” IEEE Power
a contract from ABB Power Systems, AB, Ludvika, Engineering Society, 2002 Winter Meeting, New York.
Sweden.
XI. BIOGRAPHIES
X. REFERENCES Lianxiang Tang (tanglx4310@yahoo.com) was bom in Yiyang City,
Hunan Province, China, 1970. He received his Bachelor’s degree in July
[ 11 B.T. Ooi and X. Wang, “Voltage Angle Lock Loop Control of Boost 1993 and his Master’s degree in March 1996, both in the Department of
Type PWM Converter for HVDC Application,” IEEE Transactions Electrical Engineering, Tsinghua University, China. He was working with
on Power Electronics, Vol. 5, April 1990, pp. 229-235. Xuji Group Corporation in China from April 1996 to October 1999.
[2] B.T.Ooi and X.Wang, “Boost Type PWM-HVDC Transmission Presently he is a Ph.D candidate in the Department of Electrical and
System,” IEEE Transactions on Power Delivery, Vol. 6, No.4, Computer Engineering, McGill University.
October 1991, pp. 1557-1563.
[3] G.Asplund, KEriksson, K. Svensson, “DC Transmission based on Boon-Teck Ooi was bom in Kuala Lumpur, Malaysia. He received the
Voltage Source Converters,’’ CIGRE SC14 Colloquium in South B.Eng. (Honours) from the University of Adelaide, Australia, the S.M.
Atiica 1997. from the Massachusetts Institute of Technology, USA and the Ph.D. from
[4] T.Nakjima et al, “Field Testing of 53 MVA Three-Terminal DC Link McGill University, Canada. He is presently Professor in the Department of
between Power Systems Using GTO Converters,” International Electrical and Computer Engineering, McGill University.
Power Electronics Conference-Tokyo 2000.

724

You might also like