DA Phase-1 300 Substation Point to Point Testing

Zone: JAL2
Substations: LAKE Substaion To Control Centers - Point To Point Test Results and Signal List
Station: SS4833A
Test Result
SI. KV Level Bayname B3 Text Element Name Alarm text for DCC Signal Discreption Info Sig IEC Test
Priority DCC Remarks
No (B2) (B3 Name) (LBS Toward) (SND use only) (Element Text) Type Address (SND use only)
SLD GenS
Open
1 LAKE 1E1180 LBS Load Break Switch Load Break Switch Status Status DPI 152 LB tc
Close
Open
2 LAKE 1E1180 LBS Load Break Switch Load Break Switch Command Control DC 202 LB tc
Close
11 LAKE 1E1180 App
3 LAKE 1E1180 EFIBTLW EFI Battery Low EFI Low Battery Alarm AIStat SPI 69 AI AD5-1
Disp
App
4 LAKE 1E1180 EFIOPTD EFI Operated EFI Operated Status SPI 68 EFIOP_ts
Disp
Open
5 LAKE 1E1180 Iso ETH Earth Switch Status LBS1 ETH STATUS Status DPI 158 IsoE-1-S
Close
Open
6 SS4833B LBS Load Break Switch Load Break Switch Status Status DPI 153 LB tc
Close
11 SS4833B Open
7 SS4833B LBS Load Break Switch Load Break Switch Command Control DC 203 LB tc
Close
Open
8 SS4833B Iso ETH Earth Switch Status LBS2 ETH STATUS Status DPI 159 IsoE-1-S
Close
Open
9 CB Circuit Breaker Transformer Switch Status Status DPI 154 CB-2
Close
Open
10 Iso ETH Earth Switch Status Trafo LBS Earth Status Status DPI 156 IsoE-1-S
Close
App
11 TROVLDTR Overload trip Transformer Tripping Alarm AlStat SPI 64 AI-A1-1
Disp
App
12 11 T1 LD1 TRFHITMP High Temperature TRF High Temperature Alarm AlStat SPI 66 AI AD2-1
Disp
App
13 TRMDI100 Transformer MDI 100% Transformer MDI Trip 100% AlStat SPI 71 AI AD2-1
Disp
App
14 TRMDI80 Transformer MDI 80% Transformer MDI Alarm 80% AlStat SPI 73 AI AD2-1
Disp
Analog
15 I Balanced Current Transformer Load Current 1 mv-l11
(MN)
Open
16 CB Circuit Breaker Transformer Switch Status Status DPI 155 CB-2
Close
Open
17 Iso ETH Earth Switch Status Trafo LBS Earth Status Status DPI 157 Iso-E-1-s
Close
App
18 TROVLDTR Overload trip Transformer Tripping Alarm AlStat SPI 65 AI-A1-1
Disp
App
19 11 T2 LD2 TRFHITMP High Temperature TRF High Temperature Alarm AlStat SPI 67 AI AD2-1
Disp
App
20 TRMDI100 Transformer MDI 100% Transformer MDI Trip 100% AlStat SPI 72 AI AD2-1
Disp
App
21 TRMDI80 Transformer MDI 80% Transformer MDI Alarm 80% AlStat SPI 74 AI AD2-1
Disp
Analog
22 I Balanced Current Transformer Load Current MvMoment 2 mv-l11
(MN)

19/06/2017 1 of 2 Rev-02
App
23 DoorOpen Substation Door Open Door Open/Close AIStat SPI 60 AI-AD6-1 Sensor Not Available
Disp
local
24 SuperMod RMU Selector Switch Local/Remote Switch AIStat SPI 75 SuperMod
remote
Open
25 Test Point Test Point Dummy Control Status DPI 151 CB-0
Close
Open
26 Test Point Test Point Dummy Status Status DC 206 CB-0
Close
App
27 DSHITemp DA High Temperature Alarm DSA Panel High Temperature AIStat SPI 56 AI-AD2-1
Disp

COMMON

COMMON
App
28 DSACFAIL AC Supply Fail DSA AC Supply Fail AIStat SPI 54 AI AD2-1
Disp
App
11

29 DBatCHAl Battery Charger Alarm DSA Battery Charger Alarm AIStat SPI 55 AI-AD2-1
Disp
App
30 RMUGASL Gas Pressure Low RMU Gas Pressure Low AIStat SPI 59 AI AD2-1
Disp
App
31 RTUMaAL RTU Major Alarm RTU Major Alarm AIStat SPI 52 AI-AD5-1
Disp
App
32 RTUMinAL RTU Minor Alarm RTU Minor Alarm AIStat SPI 53 AI-AD5-1
Disp
App
33 RTU-MCB RTU MCB Trip RTU CTRL MCBTRP AIStat SPI 51 AI-AD5-1
Disp
App
34 EARTTFTA Earth Wire Theft Alarm Earth Theft Alarm AIStat SPI 63 AI AD2-1 Sensor Not Available
Disp
App
35 PDCablTR PD for Cable Termination Partial Disch Cable Trmintn AIStat SPI 62 AI AD2-1 Sensor Not Available
Disp

Verified By:

Contractor Dewa/DAM Dewa/OTD-TCS Dewa/DO-DFO Dewa/DO-DCC Dewa/OTD-MS

Name: Name: Name: Name: Name: Name:

Signature: Signature: Signature: Signature: Signature: Signature:

Date: Date: Date: Date: Date: Date:

19/06/2017 2 of 2 Rev-02