You are on page 1of 10

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO.

2, APRIL 2013 955

Transmission-Line Protection: A Directional


Comparison Scheme Using the Average of
Superimposed Components
S. M. Hashemi, M. Tarafdar Hagh, Member, IEEE, and H. Seyedi

Abstract—In this paper, a new protection scheme for transmis- swings, current-transformer (CT) saturation, and long lines ca-
sion lines is presented. The method has some advantages in com- pacitance which make it more robust than traditional distance
parison with conventional line protection schemes. Faster fault de- protection [5]. TW-based protection may determine the fault di-
tection and instantaneous coverage of almost 100% of the line are
the main advantages of the new method. A full-cycle averaging rection by comparing the polarities of superimposed quantities
window is used for fault detection. While the power system is in of voltages and currents. Besides, the protection can measure
normal operation conditions, this average is approximately equal the fault distance using the time difference between forward and
to zero. As soon as the faulty signals enter the window, the average backward TWs. A common feature is observed among many
is changed to a nonzero value. It is shown that the product of this TW-based protection schemes in the literature [6]–[9]. These
average value for voltage and current of the faulty phase, in a spe-
cific time interval after fault inception, is negative for the forward schemes usually require high sampling frequency between sev-
faults and positive for the reverse faults. The fault is detected by eral hundreds of kilohertz to 1 MHz, which is more than the
communication between the local and the remote relays. Simula- sampling rate of conventional digital relays [7]. Furthermore,
tion and experimental results show the efficiency of the proposed limitations in the bandwidth of conventional VTs and CTs, are
method in fast detection of line faults in less than a half cycle. also introduced and there are some difficulties in measuring su-
Index Terms—Directional comparison, protection, relaying, su- perimposed components for TW applications [10], [11].
perimposed component, transmission line. Superimposed-based protection is not limited to TWs. It is
shown in [12]–[14] that distance protection using superimposed
components, so-called delta quantities, instead of fundamental
I. INTRODUCTION
frequency impedance, may solve some problems in the conven-

T RANSMISSION lines are prevalently protected by dis-


tance relays as the main protection, and overcurrent re-
lays as the backup protection. Both distance and overcurrent
tional distance relaying. Superimposed currents are proposed
in [15] for the phase comparison protection to remove the
sensitivity of this protection to heavy load conditions. In [16],
protections use fundamental or power frequency components superimposed components are used for providing high-speed
to detect the faults. In microprocessor relays, the extraction of directional comparison bus protection. The transient energy
fundamental frequency voltages and currents is, conventionally, produced by superimposed components is used in [17] for
provided by phasor estimation methods such as the Fourier al- directional comparison relaying. Positive-sequence superim-
gorithm [1], [2]. The common required time for fault detection posed components are used in [18] for directional protection
in these relays is approximately one to two cycles. Fast detec- of EHV transmission lines. In [19], it has been shown that su-
tion and clearing of faults improves the stability of power sys- perimposed-based directional comparison offers some benefits
tems, especially in extremely high voltage (EHV) transmission compared with the line differential protection.
lines. Therefore, the trend is toward faster protection schemes This paper introduces a directional comparison protective
in modern integrated power systems. scheme using the average value of superimposed components.
Superimposed components are changes in voltage and current The method is able to detect the faulty phase and the fault
signals with respect to the normal or steady-state conditions. direction in less than a half-cycle. Applying the sampling rate
These changes cause voltage and current traveling waves (TWs) of 64 samples/cycle makes the proposed method compatible
to propagate away from the fault location. Protection schemes with the commercial relays. Moreover, using the average of
using TWs are capable of detecting the fault in the first millisec- voltage and current signals in a full cycle for fault detection, the
onds following the fault inception [3], [4]. TW-based protec- buffer size applied in the proposed method is reduced compared
tion has some outstanding features, such as immunity to power with some superimposed-based protection schemes where the
samples of two or four full cycles are required to be saved [11],
Manuscript received May 08, 2012; revised September 07, 2012; accepted [20].
October 16, 2012. Date of publication February 05, 2013; date of current version
March 21, 2013. Paper no. TPWRD-00476-2012. II. BRIEF REVIEW ON THE FAULT SUPERIMPOSED COMPONENTS
The authors are with the Faculty of Electrical and Computer Engineering,
University of Tabriz, Tabriz 51666-15813, Iran (e-mail: m_hashemi89@ms. Consider a simple transmission system, shown in Fig. 1(a).
tabrizu.ac.ir; tarafdar@tabrizu.ac.ir; hseyedi@tabrizu.ac.ir).
This fault can be modeled by a voltage source, which is equal
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. in magnitude and opposite in sign to the prefault voltage at
Digital Object Identifier 10.1109/TPWRD.2012.2226609 the fault point [2]. According to the superposition theorem, the

0885-8977/$31.00 © 2013 IEEE


956 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

Fig. 1. Simple transmission system with (a) steady-state (prefault) and (b) su-
perimposed-state representation. A three-phase fault is assumed to occur in the
forward direction, with respect to the relay R.
Fig. 2. Output of the averaging filter for a typical current waveform.

changes in the relay point (R) voltage and current might be com-
called the averaging filter. The filter proceeds sample by sample
puted by zeroing all prefault voltage sources and representing
along the input signal. While the protected transmission system
all network components and loads with their impedances [21].
operates in healthy conditions, the input signal, whether voltage
The obtained circuit, which is depicted in Fig. 1(b), is known
or current, has a pure sinusoidal waveform, and the output of the
as a superimposed network. For simplicity, only the inductive
filter is near zero. As soon as the faulty samples enter the filter,
portion of impedances is considered in Fig. 1(b). Therefore, the
its output changes to a nonzero value. As mentioned before,
postfault voltage and current at any point of the network can be
this value is equal to the average of the superimposed compo-
acquired by superposition of their prefault values and superim-
nents. Referring to Fig. 1(b), the superimposed components can
posed values, as
be considered as the zero-state response of the electric circuit.
(1) According to the electrical circuit theory, this response consists
of two parts, which are transient and steady-state responses, re-
where is the superimposed voltage. A similar relation spectively. For example, if the transmission line is modeled by
may be written for the current. The superimposed components a series branch, the superimposed current consists of one
contain dc offset, harmonics, and high-frequency transients. decaying dc component and one steady-state sinusoidal com-
Their salient feature is that the product of superimposed voltage ponent. The average of this current is, therefore, equal to its dc
and current at the relay point is negative for the forward faults value. However, as shown in Fig. 2, since the input signal passes
and positive for the reverse faults. These properties, providing sample by sample through the averaging filter, one cycle should
an excellent criterion for directional comparison relaying, be elapsed after the fault inception instant in order for that output
form the basis of TW-based protective schemes [2]. In digital of filter to become equal to the signal dc value. Moreover, the
protection, the superimposed components may be extracted output of the filter during this cycle has an interesting feature
by subtracting each sample from its corresponding sample in which is investigated for forward and reverse faults, as follows.
the previous cycle. This process extracts the superimposed
components in only one cycle after fault inception, and the
relay would take its decision in this interval. A. Forward Faults
Considering Fig. 1, suppose that a three-phase fault occurs
III. PROPOSED PROTECTIVE METHOD in the forward direction, with respect to the relay R, at point F.
In the steady-state conditions, the voltage and current signals Shifting the time origin to the fault inception instant, the super-
in the transmission lines are almost pure sinusoidal. This im- imposed voltage and current can be computed as
plies that the average value of voltage and current signals, in
steady-state conditions, is almost equal to zero. Referring to (1), (4)
it may be concluded that the average value of postfault voltage
(or current) is equal to that of superimposed voltage (or current)

(2) (5)

where denotes the average value of the periodic signal


, with the period , which is represented in the continuous
(6)
time form by . In the discrete time
form, the average value can be represented as
The discrete time representations of (5) and (6), assuming
and
(3) can be written as

where is the number of samples per cycle. Selecting a data (7)


window with the length of one cycle, the above equation may be (8)
HASHEMI et al.: TRANSMISSION-LINE PROTECTION 957

TABLE I
DETERMINING THE SIGN OF IN THE FIRST CYCLE AFTER
FAULT INCEPTION

Fig. 3. One-line diagram of a simple transmission system with (a) steady-state


(prefault) and (b) superimposed-state representation. A three-phase fault is as-
sumed to occur in the reverse direction, with respect to the relay R.

B. Reverse Faults
For the reverse faults condition, Fig. 3 can be investigated

(9)
where the sign of is invariant, becomes very
(10) short and may include only one or two samples. It means that
the dependability of the relay would decrease. Since the value
of is variable, can be controlled only by . In other words,
for increasing the interval where the sign of
(11) is negative for forward faults and positive for reverse faults, the
sampling frequency should be increased. As before, this incre-
ment is a shortcoming for practical implementation in the con-
Here, assuming ventional relays. This problem can be solved by the proposed
and , the discrete time method, as follows.
representations of (9) and (10) can be written as The average value of the voltage and current signal in each
phase is calculated using (3). Assume is the number of super-
(12)
imposed samples entering the averaging window. The output of
(13) the window for forward faults is given by (16) and (17) at the
bottom of the next page. For the reverse faults, similar equations
Comparing (7), (8), (12), and (13) and considering that result by replacing in (16) with , and in (17) with
, and are positive values, it can be realized that . It can be shown that the first interval after the fault incep-
the sign of in the forward faults is opposite that sign in tion instant, where the sign of
the reverse faults, while the sign of is similar in both is invariant, is equal to for and
forward and reverse faults. This property may be used as a cri- for . Comparing these values with
terion for discriminating between the forward and the reverse Table I demonstrates that the interval becomes almost twice. In
faults. For this purpose, let us compute the product of Fig. 4, the product of (16) and (17) is compared with (14) for two
and . For the forward faults, we have different fault inception angles. It is shown that the mentioned
interval is extended. The proposed method consists of (16) and
(17)of the following stages. The rate of sampling is assumed to
(14) be 64 samples/cycle. The relay detects the fault using eight con-
secutive superimposed samples.
For the reverse faults 1) Phase Selection: Phase selectivity provides the capability
of single-phase automatic reclosing. On overhead lines, most
faults are of a transient nature and disappear when the infeed is
switched off. Therefore, following the fault clearance, the line
can be returned to service [12]. This means that the single-phase
(15) tripping is preferred for single-phase-to-ground faults. Single-
phase automatic reclosing basically improves the transient sta-
The sign of in the first cycle after fault bility of power systems. The process of phase selection in the
inception is given in Table I, where it can be shown that this proposed method is performed by comparing the absolute value
sign is dependent on the sample number . Moreover, is re- of the average of superimposed currents in the eight consecutive
stricted by the number of samples per cycle and the value of windows with a threshold value. This value can be selected sim-
fault inception angle . For particular values of , the interval ilar to the setting of overcurrent relays. It means that assuming
958 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

Fig. 5. Directional relaying by the proposed method in phase A. A similar


Fig. 4. Normalized values of (14) and (16) (17) for various fault inception process is performed in phases B and C.
angles. (a) . (b) .

exceeds their corresponding thresholds, the relay computes the


the minimum fault current level of 1.25 times the maximum load sum of and the sum of in the eight con-
current, the threshold value may be set to , where secutive windows. The product of these values forms the
is the rated current in the secondary side of CT which is typi- basis of directional relaying: The negative indicates forward
cally 5 A. (The division to is because of the averaging nature faults, while the positive indicates reverse faults (Fig. 5). In
of the proposed method.) Single-phase tripping is executed by very rare situations where the value of becomes almost zero
the proposed algorithm if a single-phase fault is detected for the , the fault direction is detected in one or two subse-
first time. Otherwise, all three phases should be tripped. quent windows.
2) Detecting the Fault Direction: A flowchart of the pro- 3) Communication With the Remote Relay: So far, the relay
posed directional relaying is shown in Fig. 5. When a short-cir- discriminates between forward and reverse faults. Additional
cuit fault occurs, it changes the output of the averaging filter to a discrimination should be performed between the internal faults
nonzero value. However, because of VT and CT errors and some (i.e., the faults between the close-in and the remote bus and the
environmental noises, during normal operation of the system external faults, that is, the faults beyond the remote bus). This
and in the absence of any fault, this output may not be exactly can be provided by communication between local and remote
equal to zero. A threshold level is, therefore, needed to detect relays. Assume the forward direction for the local and the re-
the fault conditions. This threshold for the current signals is se- mote relays as depicted in Fig. 6. If one relay detects a fault that
lected as the aforementioned value (i.e., ), and for the is in the forward direction, it will wait for the permissive signal
voltage signals, is assumed to be , where is the rated from the remote bus relay. The internal fault is, therefore, de-
voltage in the secondary side of VT which is typically 110 V. tected if both relays detect the fault in the forward direction.
Provided that the average of superimposed voltages and currents This provides extremely fast protection for the entire line.

(16)

(17)
HASHEMI et al.: TRANSMISSION-LINE PROTECTION 959

Fig. 6. Directional comparison relaying by the proposed method.

Fig. 7. First simulated system.

TABLE II
SIMULATION RESULTS FOR THE STUDY ON THE EFFECT
OF FAULT LOCATION OF THE PROPOSED METHOD

Fig. 8. Simulation result of an Ag fault in the forward direction. (a) Voltage


and current of phase A. (b) Averages of the superimposed voltage and current.

50 Hz. For the internal faults as , both relays R and R should


detect the fault in the forward direction while for the external
faults as , relay R, on the contrary of relay R , should detect
IV. SIMULATION RESULTS the fault in the reverse direction. Neglecting the delay of the
communication channel, the total time required for fault detec-
The proposed method is tested on two different systems under
tion is determined by the relay with longer operating time.
several operating conditions. The results are given in the fol-
2) Effect of Fault Resistance: The presence of resistance
lowing subsections A and B.
in the fault path causes the dc component of fault current in
(7) and (10) (i.e., the term to decay exponentially).
A. System I
Since the fault resistance is remarkable in the case of earth
This system is a part of an Iranian 230-kV transmission net- faults, performance of the proposed method is tested on some
work, depicted in Fig. 7. The system data are given in Table X. single-line-to-ground faults with fault resistances between 5 to
The system is simulated in PSCAD/EMTDC where the voltage 100 . As shown in Table III, the proposed method seems to not
and current signals in the relay point are used for running be sensitive to the fault resistance.
the proposed scheme in MATLAB. The frequency-dependent 3) Effect of Fault Inception Angle: The presence of the dc
model is used for transmission lines in order to increase the component in the fault current depends on the fault inception
accuracy of simulation. Performance of the proposed method angle. In other words, it would be some angles, or equally some
is evaluated in many various conditions which are summarized instants, that the corresponding fault current does not have any
as follows. dc value. Nevertheless, as the averaging window moves sample
1) Effect of Fault Location: Various types of fault in dif- by sample, it needs at least one full cycle to compute the new
ferent points of the transmission line are tested. Table II shows dc value after fault inception. In this interval, the estimated dc
that the proposed algorithm is able to detect the fault in less component changes from zero to a nonzero value and returns to
than a half cycle. In this table and the following tables, Ag, zero at the end of one cycle. Fig. 9 represents an example of this
AB, ABg, and ABC stand for single-phase-to-ground, double- condition for a reverse three-phase fault at 0.204 s.
phase, double-phase-to-ground, and three-phase faults, respec- The effect of the fault inception angle on the proposed method
tively. Moreover, F and R denote forward and reverse, and the can be considered in Table IV. In order to cover the entire in-
negative locations represent the faults occurring in the reverse terval of 0 to , the fault inception instant is gradually in-
direction. For the fault Ag at 10 km far from bus B, the details of creased in one full cycle. The results of Table IV demonstrate
waveforms are shown in Fig. 8, where the system frequency is that the required time for fault detection has increased in some
960 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

TABLE III TABLE IV


SIMULATION RESULTS FOR THE STUDY ON EFFECT OF FAULT RESISTANCE SIMULATION RESULTS FOR THE STUDY ON EFFECT OF FAULT INCEPTION
ON THE PROPOSED METHOD ANGLE ON THE PROPOSED METHOD

TABLE V
SIMULATION RESULTS IN THE CASE OF NOISY SIGNALS

Fig. 9. Example of zero dc current for a particular fault inception angle. Only
phase A is represented.

inception angles. However, the delay, in the worst condition, is


less than half a cycle.
4) Effect of Noisy Fault Signals: Since the nature of the pro-
posed method is averaging signals during one full cycle, it is
expected that the noise effect on the proposed method is not
considerable. This is due to the fact that the average of white
noise is zero. Various faults with different signal-to-noise ratios
(SNRs) are tested, and the results are shown in Table V. For this
purpose, the Gaussian white noise with the signal-to-noise ratio
(SNR) of 60, 40, and 20 dB are added to the main signals. For
increasing the security of the proposed method in the presence
of noise-polluted signals, the value of thresholds should be set
more accurately. The inception instant of all faults in Table V is
0.2 s.

B. System II the Electromagnetic Transients Porgram (EMTP). It should be


The purpose of simulation studies in this case is to evaluate noted that for each of the following cases, according to [22],
the performance of the proposed method in situations where the some changes on the topology of Fig. 10 are applied. The system
line distance protection, as the prevailing protection in trans- frequency is 60 Hz, and the sampling rate is 64 samples/cycle.
mission lines, is encountered with challenges and difficulties. Referring to Table X, the protection in two challenging con-
The IEEE Power System Relaying Committee (PSRC) proposes ditions (i.e., the presence of short line and the maximum line
the system depicted in Fig. 10 for testing most transmission- loading) has been considered in the previous subsection. The
line protection applications [22]. The system is simulated in other cases are investigated as follows.
HASHEMI et al.: TRANSMISSION-LINE PROTECTION 961

TABLE VII
SIMULATION RESULTS FOR EVALUATING THE PROPOSED METHOD IN
THREE-TERMINAL LINES

Fig. 10. IEEE PSRC recommended model for testing transmission-line protec-
tion in EMTP.

TABLE VI
SIMULATION RESULTS FOR EVALUATING THE PROPOSED METHOD IN
DOUBLE-CIRCUIT LINES

TABLE VIII
SIMULATION RESULTS FOR EVALUATING THE PROPOSED METHOD IN POWER
SWING CONDITIONS

1) Double-Circuit Lines: Mutual inductive coupling be-


tween transmission lines on the same tower or parallel along
the same right of way introduces some errors in the impedance
measured by distance relays. These errors are negligible in
positive- and negative-sequence impedances. Nevertheless, as
the zero-sequence mutual impedance of parallel lines can be
50% to 70% of zero-sequence self-impedance, the impact of (at 66% of the length of line AB) and F3 (at 33% of the length
mutual coupling is more significant in the case of ground faults of line BD). As considered in Table VII, the results show the
[12], [23]. Therefore, the performance of the proposed method efficiency of the proposed algorithm in this case.
in parallel lines is evaluated only for the earth faults. For this 3) Power Swings: From the reliability point of view, the dis-
purpose, the switch SW in Fig. 10 remains open and the relay tance relays have two fundamental problems in the presence of
is tested for faults on 66% of the lower line AB, and power swings. The first problem is the possibility of detecting
on 11% of the upper line AB. The results are given in Table VI. power swing as a fault, which causes the loss of security. For
2) Three-Terminal Lines: Sometimes, usually due to eco- preventing these conditions, distance relays are equipped with
nomic restrictions, transmission lines are tapped to provide in- the power swing blocking (PSB) units, which blind the relay
termediate connections to loads, or to reinforce the underlying to see the faults while the power swing persists. This function,
lower voltage network through a transformer. These connec- however, leads to the second problem, which is loss of de-
tions introduce some problems in distance protection, especially pendability for the faults occurring during a power swing. The
when sources of generation exist behind the tap points [24]. The problem is considerable only for symmetrical or three-phase
fundamental problem with this line configuration is the inter- faults [25], since asymmetrical faults can be detected by other
mediate infeed to the fault location from the third terminal [12]. protective approaches, like applying the negative-sequence
Besides, the application of travelling-wave-based protection in components. The proposed method is, however, immune to
three-terminal lines requires careful study, since the travelling the power swing conditions. According to [22], power swing
waves are strongly affected by the connected taps. can be created in Fig. 10 by applying a three-phase fault at
To create this condition in Fig. 10, the upper line AB is bus A and removing the fault before the generator loses
opened and the switch SW is closed. The tap point is located synchronism. The second cited problem is investigated by
at 33% of the length of line AB. Afterwards, the performance applying three-phase faults at points and (defined in
of relays R1 and R2 is evaluated for the faults located at F1 Subsection B.2), where the results are presented in Table VIII.
962 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

TABLE IX
SIMULATION RESULTS FOR EVALUATING THE PROPOSED METHOD IN SERIES-COMPENSATED LINES

Fig. 11. Experimental prototype setup.

4) Series-Compensated Lines: Compensation of transmis-


sion lines by series capacitors imposes some significant effects
on both directionality and reach of distance relays. The details
are out of the scope of this paper and can be found in [26] and
[27]. These effects become more severe in double-circuit se-
ries-compensated lines. In Fig. 10, the source -connected line
is removed and the double-circuit line AB is compensated by the
degrees of 70%.
The performance of relays and is tested for the faults
at points and , where the results are given in Table IX.
With protection of series-compensated lines, the location of the
fault has a key role, since the well-known phenomena of voltage
and current inversions are affected by the fault location. For
Fig. 12. Experimental results of an SLG fault on phase A: (a) three-phase volt-
the sake of briefness, these phenomena are not investigated fur- ages, (b) three-phase currents at the relaying point, (c) averages of voltage and
ther. However, they are considered in Table IX. The presence of current of the faulty phase, (d) output of the proposed method in simulation, (e)
experimental averages of voltage and current computed by the relay, and (f) the
metal–oxide varistors (MOVs) is also considered in this table.
experimental result of the fault direction by the relay.
As shown, the presence of two capacitors in the path of reverse
faults at point , in some situations, makes the direction de-
tected by relays and inversed. However, since this inver- the series capacitor and the line series impedance which consists
sion occurs for both relays, it does not impact the fault detection of subsynchronous oscillations.
criterion used by the proposed method. It should be noted that
this condition is only present in double-circuit series-compen- V. EXPERIMENTAL RESULTS
sated lines. Our extensive studies show that this inversion is not The proposed method is tested, also, on an experimental
present in single-circuit series-compensated lines. prototype setup, which is depicted in Fig. 11. The relay is de-
It is remarkable that, in comparison with Fig. 2, the output of signed using an AVR microcontroller (ATMEGA32A). In order
the averaging filter in series-compensated lines is equal to that of to make the laboratory tests compatible with the real world,
the zero-state response of the second-order circuit composed by the real voltage and current signals saved by a fault recorder
HASHEMI et al.: TRANSMISSION-LINE PROTECTION 963

Fig. 12(c). The output of the proposed method, which is pro-


vided by simulation, is represented in Fig. 12(d). In this figure,
the fault direction signal is 0, where there is no fault or there
is a reverse fault. As soon as a forward fault is detected by the
relay, this signal becomes 1. The results of the experimental test
are shown in Fig. 12(e) and (f), where the relay has detected
the fault direction within less than a quarter of a cycle after the
fault inception.
Another experimental test is carried out for an SLG fault on
phase C, where the obtained results are shown in Fig. 13.

VI. CONCLUSION
This paper presents a high-speed directional comparison pro-
tective scheme for transmission lines, using the average value
of superimposed components. Extensive simulation studies are
performed to evaluate the proposed method in different oper-
ating conditions, including double-circuit lines, three terminal
lines, power swing conditions, and series-compensated lines.
The impact of important parameters, such as fault resistance,
fault location, fault inception angle, and noise-polluted fault sig-
nals on the protection systems are also considered in evaluating
the proposed method. The obtained simulation results, in addi-
tion to the experimental results, show that the proposed method
is competent for being applied to line protection.
Fig. 13. Experimental results of an SLG fault on phase C: (a) three phase volt-
ages, (b) three-phase currents at the relaying point, (c) averages of voltage and REFERENCES
current of the faulty phase, (d) output of the proposed method in simulation,
[1] A. G. Phadke and J. S. Thorp, Computer Relaying for Power Systems,
(e) experimental averages of voltage and current computed by the relay, (f) and
2nd ed. Hoboken, NJ: Wiley, 2009.
experimental result of the fault direction by the relay.
[2] A. T. Johns and S. K. Salman, Digital Protection for Power Systems.
London, U.K.: Peregrinus, 1995.
[3] M. Vitins, “A fundamental concept for high speed relaying,” IEEE
TABLE X Trans. Power App. Syst, vol. PAS-100, no. 1, pp. 163–173, Jan. 1981.
PARAMETERS OF THE SYSTEM I [4] D. W. P. Thomas, M. S. Jones, and C. Christopoulos, “Phase selection
based on superimposed components,” in Proc. Inst. Eng. Technol. Gen.
Transm. Distrib., May 1996, vol. 143, no. 3, pp. 1011–1018.
[5] X. Dong, Y. Ge, and J. He, “Surge impedance relay,” IEEE Trans.
Power Del., vol. 20, no. 2, pt. 2, pp. 1247–1256, Apr. 2005.
[6] C. Aguilera, E. Orduña, and G. Rattá, “Directional traveling—Wave-
protection based on slope change analysis,” IEEE Trans. Power Del.,
vol. 22, no. 4, pp. 2025–2033, Oct. 2007.
[7] E. Vázquez, J. Castruita, O. L. Chacón, and A. Conde, “A new ap-
proach traveling-wave distance protection—Part I: Algorithm,” IEEE
Trans. Power Del., vol. 22, no. 2, pp. 795–800, Apr. 2007.
[8] P. Jafarian and M. Sanaye-Pasand, “A traveling-wave-based protection
technique using wavelet/PCA analysis,” IEEE Trans. Power Del., vol.
25, no. 2, pp. 588–599, Apr. 2010.
[9] A. Sharafi, M. Sanaye-Pasand, and P. Jafarian, “Ultra-high-speed pro-
tection of parallel transmission lines using current travelling waves,”
Inst. Eng. Technol. Gen. Transm. Distrib., vol. 5, no. 6, pp. 656–666,
2011.
have been used. These data include three-phase voltages and [10] C. Xianghui, Z. Xiangjun, M. Hongjiang, L. Zewen, L. Ling, and D.
currents measured at the relaying point in the substation of one Feng, “Rogowski sensor for power grid traveling wave based fault lo-
cation,” in Proc. Inst. Eng. Technol. 9th Int. Conf. Develop. Power Syst
side of the line. These voltages and currents are saved into a Protect., Glasgow, U.K., Mar. 2008, pp. 438–443.
personal computer and played back as the inputs of the relay. [11] P. Jafarian and M. Sanaye-Pasand, “High-speed superimposed-based
Considering restrictions in the space of this paper, only the protection of series-compensated transmission lines,” Inst. Eng.
Technol. Gen. Transm. Distrib., vol. 5, no. 12, pp. 1290–1300, 2011.
results of two single-phase-to-ground (SLG) faults are pre- [12] G. Ziegler, Numerical Distance Protection; Principles and Applica-
sented here. All faults are internal and, therefore, the protective tions. Erlangen, Germany: Publicis, 2006.
relays of the line had to trip the line. Fig. 12 shows the result [13] C. Dzienis, M. Kereit, J. Blumschein, and M. Claus, “An experi-
mental analysis of high-speed-distance protection,” in Proc. Int. Symp.
of an SLG fault on phase A. The voltages and currents of three Modern Electric Power Syst., Poland, 2010, pp. 1–8.
phases, which are acquired by the fault recorder, are depicted [14] Z. Li, X. Lin, H. Weng, and Z. Bo, “Efforts on improving the per-
in Fig. 12(a) and (b), respectively. formance of superimposed-based distance protection,” IEEE Trans.
Power Del., vol. 27, no. 1, pp. 186–194, Jan. 2012.
The averages of voltage and current of phase A, which [15] G. Ziegler, Numerical Differential Protection. Erlangen, Germany:
are used for the detection of fault direction, are depicted in Publicis, 2005.
964 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

[16] M. R. D. Zadeh, T. S. Sidhu, and A. Klimek, “Implementation and S. M. Hashemi received the B.Sc. degree in elec-
testing of directional comparison bus protection based on IEC61850 trical engineering from the Bu-Ali Sina University,
process bus,” IEEE Trans. Power Del., vol. 26, no. 3, pp. 1530–1537, Hamedan, Iran, and is currently pursuing the M.Sc.
Jul. 2011. degree in electrical engineering at the University of
[17] J. Tan, D. Tholomier, G. Bin, and W. Hua, “Sensitivity and stability of Tabriz, Tabriz, Iran.
superimposed component based directional comparison protection,” in His research interests include power system
Proc. Can. Conf. Elect. Comput. Eng., 2007, pp. 280–283. protection, flexible ac transmission systems, HVDC,
[18] H. Gao and P. A. Crossley, “Design and evaluation of a directional power system operation, and electricity markets.
algorithm for transmission-line protection based on positive sequence
fault components,” in Proc. Inst. Elect. Eng., Gen. Transm. Distrib.,
Nov. 2006, vol. 153, no. 6, pp. 711–718.
[19] D. Tholomier, S. Richards, and A. Apostolov, “Which one is better-line
differential or directional comparison?,” in Proc. 9th Int. Conf. De-
velop. Power Syst. Protect. Inst. Eng. Technol., Montreal, QC, Canada,
2008, pp. 86–91. M. Tarafdar Hagh (S’98–M’06) received the M.Sc.
[20] A. P. Apostolov, D. Tholomier, and S. H. Richards, “Superimposed (Hons.) and Ph.D. degrees in power engineering from
components based sub-cycle protection of transmission lines,” in Proc. the University of Tabriz, Tabriz, Iran, in 1992 and
IEEE Power Eng. Soc. Power Syst. Conf. Expo., New York, 2004, pp. 2000, respectively.
592–597. He has been with the Faculty of Electrical and
[21] H. Saadat, Power System Analysis. New York: McGraw-Hill, 1999. Computer Engineering, University of Tabriz, since
[22] Power Syst. Relaying Comm., “EMTP reference models for transmis- 2000, where he is currently a Professor. He has
sion line relay testing,” Final, Tech. Rep., 2005. [Online]. Available: published more than 150 papers in power system
www.pes-psrc.org and power electronics-related topics. His interest
[23] H. Seyedi and L. Behroozi, “New distance relay compensation al- topics include power system operation, flexible ac
gorithm for double-circuit transmission line protection,” Inst. Eng. transmission systems,and power quality.
Technol. Gen. Transm. Distrib., vol. 5, no. 1, pp. 1011–1018, 2011.
[24] S. H. Horowitz and A. G. Phadke, Power System Relaying, 3rd ed.
Hoboken, NJ: Wiley, 2008.
[25] C. Pang and M. Kezunovic, “Fast distance relay scheme for detecting H. Seyedi was born in Iran in 1979. He received the
symmetrical fault during power swing,” IEEE Trans. Power Del., vol. B.Sc., M.Sc., and Ph.D. degrees in electrical engi-
25, no. 4, pp. 2205–2212, Oct. 2010. neering from the University of Tehran, Tehran, Iran,
[26] P. M. Anderson, Power System Protection. New York: IEEE, 1999. in 2001, 2003, and 2008, respectively, .
[27] P. Jena and A. K. Pradhan, “A positive-sequence directional relaying Currently, he is with the faculty of Electrical and
algorithm for series-compensated line,” IEEE Trans. Power Del., vol. Computer Engineering, University of Tabriz, Tabriz,
24, no. 4, pp. 2288–2298, Oct. 2010. Iran. His areas of interest include digital protection
of power systems and power system transients

You might also like