Professional Documents
Culture Documents
Abstract: A reasonable amount of spinning reserve is essential to satisfy system security constraints
when the power system encounters a contingency. For isolated power systems, the influence of the
system characteristics on spinning reserve requirements (such as load models_ load variational
characteristics, frequency sensitivity of loads) is more important than the reliability of individual
units. The paper proposes a method that takes into consideration load variational characteristics,
system load, load-frequency sensitivity factor and frequency operating standards to schedule
spinning reserve requirements, which are called reasonable spinning reserve requirements. The one-
minute recovery frequency following a contingency would be a more appropriate measure of
system security and would represent an enhanced frequency regulating reserve policy. To examine
the merits of the proposed method, simulation runs were performed on the Taiwan Power System
(TPS) and compared with the Taiwan Power Company (TPC) manual dispatch.
3- no
I Select the reasonable Soinnina reserve Ieouirement 1RSRRl I
$ q 4
yes
1 ouput the reasonable spinning reserve schedule , 1
RSRR = PG.,,,~~-PMPS
4
used for hydro units. Any unit not providing reserve at no load or minimum load, pumped storage and
capability in the event of a contingency was modelled as a automatic load shedding.
constant generation. Comparisons of the frequency re-
sponse rales among prime movers showed that hydro units
have an excellent frequency response rate, the secondary is 3.3 Extended reserve
combustion turbines, the smallest are reheat and gas The response of this reserve is not fast enough either to limit
turbines [IO]. Therefore, the hydro units are the most the fall in frequency, or to assist in the recovery of
suitable for the spinning reserve units. This paper proposes frequency, to within frequency operating standards. The
that isolated power systems divide their reserves into four response would be commencing no later than one minute
types based on the frequency response rate of prime movers. after the beginning of the event and for at least a further
the missions and capability of the reserves, as follows: 15min thereafter. Extended reserve would be composed of
spinning thermal units at partial load or minimum load and
fast start-up units, such as combustion turbines (combined
3.1 Frequency regulating reserve (FRR) cycle).
This resewe would be available to use for controlling
frequency within the normal limits, the response time being
sufficiently fast to control the frequency within the normal 3.4 Stand-by reserve
limits for small changes in frequency. The FRR would be This reserve would represent the capability of generators to
composed of spinning hydro units. inject energy into the grid system within 15min of receiving
instructions from the system operator. Stand-by reserve
3.2 Instantaneous reserve (IR} would include that energy injection capability for which an
This reserve would be able to counter any under-frequency energy injection proposal currently exists from a generator,
excursion arising from a contingency, the response being hut which has not been dispatched, as well as any
fast enough either to limit the fall in frequency, or assist in interruptible demand or energy injection capability for
the recovery of frequency, to within frequency operating which the system operator has specifically contracted as
standards. IR would be composed of spinning hydro units stand-by reserve.
456 i E E Proc-Gmer. Tronrni. Di.wih., Vol. ISO. No. 4, July 2003
In this paper, the sum of FRR and IR is called as the gency. This information would ensure that the one-minute
reasonable spinning reserve requirement (RSRR) of an recovery frequency following the largest online generator
isolated power system. outage for given dispatch,& stays above a system specific
absolute minimum frequency k.:
4 Reasonable spinning reserve requirement
fm 2 h. (10)
scheduling
Equation (10) is called the frequency-based reserve
This paper suggests that the magnitude of RSRR depends constraint (FBRC). Thefmi, is a user specified variable: if
on load variational characteristics, system load and set below the highest value for the activation of under-
frequency operating standards, to ensure system safety frequency relays, load shedding will occur. The one-minute
and uninterruptahle operations when the power system recovery frequency after the largest generator outage is
encounters a contingency. For the proposed method to be given as (1 1):
practical, the calculation of reasonable spinning reserve
requirements must be as simple as possible, the proposed
method can ignore the effects of voltage dependency on
loads and need not take into consideration the intrinsic If f m is below fmin, based on ( I I), the & is recalculated
reliability of each scheduled generator. The RSRR is given using the dispatch repeatedly to increase FRR until f,
as equals&.
RSRR = max(SR, Pc-,,,] (1)
6 Determinative criteria of LFSF
where
S R = spinning reserve The rebationship between load-frequency sensitivity factor
PG,,,,,= the output of the maximum generation unit (LFSF), the magnitude and characteristics of system load is
The SR. FRR and IR are given as close. During light-load duration, system frequency is
influenced easily hy the variation of load, which means
that the value of LFSF will he larger. On the other hand,
during heavy-load duration, the value of LFSF will be
smaller. The tendency of system load variation (dPsySt,/df)
also influences the value of LFSF in addition to the
magnitude of system load, as shown in Fig. 2. Following a
1R = RSRR - FRR (4) generator forced outage or a great load variation, during
where hour 0 to hour 3 and hour 17 to hour 24, the value of
PSySim
= system load dPsySiem/dtis less than zero, therefore the dropped depth of
a=
af
the load-frequency sensitivity factor (LFSF) of the
system frequency will he smaller; however, during hour 3 to
hour 17, the value of dPsyst,,/dt is greater than zero, so that
system the dropped depth of system frequency will be larger.
Fl =the frequency at which load shedding is initiated
F2= the frequency meant to provide some margin to
frequency Fl
When pumped storage ( P M P S ) is in use, which can be a
partial or entire of the IR, the RSRR can he decreased. If
PMPS>Ph,,, the IR can be served by PMPS, therefore,
the RSRR needs only serve as FRR. The RSRR and IR are
given as ( 5 ) and (6):
RSRR = FRR (5)
IR = PMPS (6)
If PMPSIP,,, and (SR+PMPS)>PP,,,,, the RSRR
are given as (7), or (8), and the IR is given as (9):
RSRR = SR (7) 14000 , , , , , , , , , , , , , , , , , ~ , , , , , 1
0 8 16 24
RSXR = Pc-,, - PMFS (8) hour
IR = RSXR - ERR + Phlps (9) Fig. 2 Daily had curtie sfn power .vysrem
5 System security constraints (SSC) It is infeasible and difficult to measure real frequency
variations, due to great load variations. This paper employs
Following the loss of an online generator, it is essential to a statistical approach to calculate the mean value p and
maintain system frequency within acceptable levels without standard deviation U of LFSF for three durations in one
load shedding within a few seconds. Having determined the day, and then, based on the conditions of pumped storage
RSRR, the following step constitutes the allocation of FRR application, uncertainty of the forecast load and the
among the spinning reserve units. This allocation must take dPsySt~,,,/dt of duration, the LFSF of the duration can he
into account, not only the economic impact of the units for determined. The determinative criteria of LFSF are
reserve purpose, but also the response rate and response presented in Table 1. The LFSF is not a constant; therefore
capability of them. It is more appropriate to ask what is the the LFSF must be recalculated when a forced generator
one-minute recovery frequency ),f( following a contin- outage occurs.
IEE Pror:-(;mer Trmsm. Dhirib.. V d ISO, No 4, July 2W3 451
Table 1: Determinative criteria of LFSF 26000 7
24000
22000
n- 20000
y, 16000
7 Operating experience
Period I (hour &hour 8 ) Period II (hour E h o u r 16) Period 111 (hour 1 6 h o u r 24)
111 "1 P2 c2 113 "3
However. during the other times, the proportions of FRR below 59.70 Hr, as shown in Fig. 6, showing a comparison
are so high to causc system excessive security, a situation of f m , calculated by (ll), during a 24h period between
which will increase operating costs. The FRR maintains RSRR dispatch and the TPC manual dispatch. The results
around 450 MW during hour 0 to hour 6 , around 700 MW showed the proposed method can maintain acceptable
during hour 7 to hour 14 and around 550 MW during hour levels of system security followin_p the largest online
15 to hour 23 for the proposed method, allowing for a generator outage.
decrease in the on and off times for hydro units. Thus, the After many simulations, the TPC system operation
redispatching costs of hydro units which offer FRR could be departtnent confirmed that the proposed method could
decreased substantially. Nevertheless system security was decrease operating costs substantially, as presented in
not compromised, as the one-minute recovery frequency Table 6. The proposed method with the frequency-based
following the largest online generator outage never fell reserve constraint is implemented 011 the TPS, which not
1600 7 2910512002 11:53:00 Frequency Variation History Curve 180 Sec
60.05
z
0
1400
1200
-I
N
60.00
59.95
-c
.-
1000
L-. _-.*\
\ _.-_.
r e , \ , , , , , ,
t
800
.. .I_
-.___
... 59.75
600
e >
* 59.65
U,
.-
C 400 - - - - - - - TPC manualdispatch 59.60
200 59.55
59.50
0 59.45
0 8 16 24 0 15 30 45 0 15 30 45 0 15 30 45 0
hour time. s
Fig. 4 Spinning reserw .scheduling rompari.ron between RSRR and Fig. 7 Frequency variarion curve following the loss of the largest
TPC manual disparch generaring unit of the Taiwan Power System on 29 May 20112
1600
1400 1 levels of security following a contingency. Fig. 7 shows a
frequency variation curve following the loss of the largest
eI 1200 4 generator (950MW) of the TPS at 1153 on 29 May 2002.
The recovery of frequency remained above 59.5 Hz all along
and no load-shedding occurred.
8 Conclusions
59.40
0 6 16 24
9 Acknowledgments
hour
Fig. 6 The one-minute recowry frequency fdloiving the largest The authors wish to express their thanks to the Taiwan
online generator outage conipariron between RSRR and TPC Power Company for granting permission to publish this
manual dispatrlr paper, particularly the frequency variation curve.
Table 6 Comparison of the cost of spinning reserve for 2001-year load of the TPS
IEE Prm-Cmer Transm. Dhrrfh., VoL 150, No. 4, July 2003 461