You are on page 1of 37

Building Bulletin 87, 2nd Edition Version 1 (May 2003)

This edition replaces Building Bulletin 87 (1997) as referenced


in building regulations Approved Document Part L2 2002

Guidelines for Environmental


Design in Schools
School Building and Design Unit
Department for Education and Skills

© Crown copyright 2003

Produced by the Department for Department for Education and Skills

You may copy extracts from this document for non-commercial or educational
purposes as long as you mention the source

1
Contents

Introduction .................................................................................. 3 Design criteria ................................................................................ 20


Daylighting ....................................................................................... 20
Scope of BB87 (2003) .................................................................... 3
Electric lighting ............................................................................... 20
Scope of the Building Regulations ............................................... 4
Combined daylighting and electric lighting ............................. 21
Lighting quality ............................................................................... 21
Section 1: BB87 and Approved Document External lighting .............................................................................. 22
Part L2 2002 requirements for schools .................... 5 Emergency lighting ........................................................................ 22
Energy efficiency rating .................................................................. 5 Lighting for pupils with visual and hearing impairments ..... 23
Elemental method ............................................................................. 5
Whole building method .................................................................... 5
Section 5: Hot and cold water supplies ............ 26
Carbon emission calculation method .......................................... 6
The School Premises Regulations ............................................. 26
Interpretation of the elemental method
of AD L2 2002 for schools ............................................................ 6 Main summary of standards and regulations ......................... 26
U-values ............................................................................................... 6 Cold water ........................................................................................ 26
Lighting efficacy ................................................................................ 6 Drinking water ................................................................................. 27
Glazing ................................................................................................. 6 Hot water .......................................................................................... 29
External lighting ................................................................................. 6 Legionellaosis (including legionnaires desease) ................... 29
Summertime overheating prevention Hot and cold water sevices ........................................................ 29
in schools relating to ADL2 2002 ................................................ 6 Water pollution ................................................................................ 31
Building Log-books ........................................................................... 7 Lead pipework ................................................................................ 31

Section 2: Heating and Thermal Performance ..... 8 The School Premises Regulations
Thermal conditions ........................................................................... 9
Summary Sheet ...................................................................... 32
Temperatures in the heating season ........................................... 9 Acoustics .......................................................................................... 32
Summertime temperatures ............................................................ 9 Lighting ............................................................................................. 32
Thermal insulation .......................................................................... 10 Heating .............................................................................................. 32
Heat gains ........................................................................................ 10 Ventilation ......................................................................................... 32
Heating system design ................................................................. 10 Water supplies ................................................................................ 32
Choice of fuel and heating system ........................................... 11 Drainage ........................................................................................... 32
Heating Plant Carbon Intensity ................................................... 12
Heating control ............................................................................... 12 Standards for environmental conditions and
Building Energy Management Systems ................................... 13 energy conservation for new school buildings
Frost protection .............................................................................. 14
summary sheet ....................................................................... 33
Conservation of fuel and power –Energy efficiency
Section 3: Ventilation and Indoor Air Quality ...... 15 rating ................................................................................................. 33
Indoor Air Quality (IAQ) ................................................................. 15 Acoustics .......................................................................................... 33
Purpose of ventilation ................................................................... 15 Lighting ............................................................................................. 33
Indoor air quality (IAQ) .................................................................. 15 External lighting .............................................................................. 33
Natural ventilation .......................................................................... 16 Heating .............................................................................................. 33
Mechanical ventilation ................................................................... 16 Thermal performance ................................................................... 33
Controlling summertime overheating ....................................... 17 Ventilation ......................................................................................... 34
Hot and cold water ........................................................................ 34

Section 4: Lighting ................................................................ 18


Design framework ......................................................................... 18
References ................................................................................. 35
Task/activity lighting ..................................................................... 19 Bibliography – further reading ..................................... 37
Lighting for visual amenity .......................................................... 19
Lighting and architectural integration ...................................... 19
Lighting and energy efficiency ................................................... 19
Lighting maintenance .................................................................... 19
Lighting costs ................................................................................. 19

2
Introduction

Building Bulletin 87 is the Department beginning of each section of BB87. Those


for Education and Skills’ Constructional Constructional Standards which are
Standard[Ref.1] for Environmental specifically mentioned in ADF 1995 or
Conditions and the Conservation of Fuel ADL2 2002 or other Approved
and Power. Documents in support of the Building
Regulations, or other Regulations, are
In addition BB87 contains further listed beneath the appropriate Approved
constructional standards applying to such Document or Regulation.
things as water supplies and the
prevention of summertime overheating, The constructional standard for acoustics
and also general design guidance on is now Building Bulletin 93[Ref.5],
environmental design to achieve energy see www.teachernet.gov.uk/acoustics
efficient school buildings. BB93 is quoted in ADE2003 and
supersedes the acoustics section in the
The Building Regulations Part F: 1997 version of BB87.
Ventilation and Part L2: Conservation of
Fuel and Power apply to all schools since The standards and guidance given in the
the ending of the exemption of LEA 1997 edition of BB87 have been largely
maintained schools from the Building superseded by the requirements of Part
Regulations in 2000. The Constructional L2 of the Building Regulations and
Standards such as BB87 and BB93 which hence, this 2003 revision of BB87 has
are mentioned in the Approved been prepared. This 2nd. Edition of BB87,
Documents are used by Building Control being the current Constructional
Bodies as the normal means of assessing Standard for schools, therefore replaces
compliance with the Building Regulations the 1st. Edition of Building Bulletin 87
for schools. The Approved Documents published in 1997. All references to that
(AD) in support of Part F 1995[Ref.2] and document, for the purposes of
Part L2, 2002[Ref.3] both quote BB87 as a compliance with Building Regulations
means of compliance with the Building Part F 1995 and Part L2 2002 and in the
Regulations. DfES Constructional Standards[1], should
therefore be considered as references to
This 2003 revision updates BB87 and the current version of this 2nd edition of
brings it in line with the current Building Building Bulletin 87. The current version
Regulations and other legislation such as can be downloaded from the DfES
the Drinking Water Regulations. In a few website http://teachernet.gov.uk/energy
respects, for schools the Constructional
Standards refine the recommendations
given in certain Approved Documents in Scope of BB87 (2003)
support of the Building Regulations. The intention of this document is to
However, it should be pointed out that provide advice on the environmental
only the School Premises design of schools such that compliance
Regulations[Ref.4], the Building with Requirements of ADL2 2002 and
Regulations and other Regulations are of ADF 1995 of the Building Regulations
legally binding. In addition to the are achieved, and the energy and
regulatory requirements, the environmental performance of new and
Constructional Standards for Schools refurbished school buildings is compatible
included in BB87 are often quoted as a with current building standards.
basis of funding agreements and Building
Contracts. The design guidance relating to
Approved Document L2 2002 is
For ease of reference, the relevant formulated in a format similar to that of
Constructional Standards and School ADL2 2002, so that it reflects the three
Premises Regulations can be found at the

3
Introduction

alternative means of compliance with the Temporary buildings are exempt from the
Energy Efficiency Requirements of Part Building Regulations. Temporary
L2 of the Building Regulations. buildings are defined in Schedule 2 to the
However, BB87 contains some specific Building Regulations as those which are
Constructional Standards for school not intended to remain in place for
buildings which refine and override the longer than 28 days. What are commonly
recommendations for compliance with called temporary buildings in schools are
Building Regulations given in ADL2 classed as prefabricated buildings and are
2002 and ADF 1995. For example the normally subject to the same building
means of avoiding solar overheating given regulation requirements as other types of
in Section 1 adds to the guidance on this building. Additional guidance is given in
topic in ADL2 2002. Clause 0.6 of ADE, and clauses 0.25 and
0.26 of ADL2.
Notwithstanding the obligations required
under the Building Regulations it should A building that is created by dismantling,
also be borne in mind that The Education transporting and re-erecting the
(School Premises) Regulations 1999, sub-assemblies on the same premises, or
SI 1999 No.2[Ref. 4] are still in force and is constructed from sub-assemblies
Note
contain minimum environmental obtained from other premises or from
1 The definition of a school standards that apply to both new and stock manufactured before the
is given in Section 4 of the existing school buildings. Note that appropriate AD came into force, would
1996 Education Act. In the ADL2 2002 also refers to requirements normally be considered to meet the
case of sixth form colleges when undertaking work on existing requirements for school if it satisfies,
the Section 4 of the 1996
buildings and this applies equally eg the 1995 edition of ADL.
Act should be read in
conjunction with Section 2 to schools.
of the same Act, in The Building Regulations Part F 1995
particular subsections (2), Scope of the Building Regulations and Part L2 2002 apply to most non-
(2A) and (4) which deal domestic buildings. Whereas, BB87
with the definition of Although Building Regulations do not
apply to all alteration and refurbishment applies, and sets the constructional
“secondary education”.
work, it is desirable that such work should standards, for all areas of schools
If a sixth form college is consider environmental conditions and including nursery and adult/community
established as a school
energy efficiency and incorporate education within school complexes. It
under the 1998 School does not apply to nursery schools which
Standards and Framework
upgrading of plant and controls and also
the building fabric as is appropriate and are not part of a primary school, sixth
Act then it will be classed
cost effective. For the application of the form colleges which have not been
as a school under section
4 of the 1996 Education Building Regulations see Regulations 3 established as schools, and Universities or
Act and BB87 will apply. and 4 of Building Regulations 2000 Colleges of Further and Higher
Only one sixth form
(as amended). Education1. However many of the
college has done this to performance requirements are desirable
date. Therefore, most
The exemption of Local Education and BB87 can be used as a guide to the
sixth form colleges are
institutions in the Further Authority (LEA) maintained schools from design of these buildings.
Education sector and are the Building Regulations has ended and
not schools and hence
school Buildings are now subject to the
BB87 will not apply.
Building Regulations and may be subject to
In the case of a new sixth detailed design checks and on-site
form college it will be inspections by the Building Control Bodies.
necessary to contact the
LEA to enquire if the sixth The Building Regulations apply in
form college has been
England and Wales. They apply to
established as a school or
as an institute of further both LEA maintained schools and
education. independent schools.

4
Section 1: BB87 and Approved Document Part L2 2002
requirements for schools

BB87 Constructional Standard Building Regulations

Summertime overheating BB87 and Approved Document Part L2: Conservation of


Fuel and PowerEnergy efficiency rating
For school buildings it is accepted
practice to define overheating as The designer of a school has three options in the design of a new
occurring when the internal air school building.
temperature exceeds 28oC. 1. To use the elemental method as described in Section 1 of ADL2
An allowable degree of overheating in 2002 of the Building Regulations, together with the advice
a school is that this may occur for up contained in the revised BB87.
to 80 occupied hours in a year. The 2. To use the Whole Building Method described in BB87 (2003) to
CIBSE test Reference Years from estimate the total energy consumption of the building and
CIBSE Guides J[Ref. 6] should be used achieve a carbon performance rating of better than 5 kgC/m2
as the basis of predicting the number per year.
of occupied hours when the 3. To use the carbon emission calculation method as described in
temperature exceeds 28oC. ADL2 2002. This technique is advised for innovative or passive
designs that will benefit from detailed whole building simulation
procedures.

Approved Document L2 2002 gives three Whole Building Method


methods of compliance for the energy
The whole building method has been
efficiency of a building. ADL2 also
developed to deal with ‘offices’,
contains requirements, for example for
‘hospitals’ and ‘schools‘. Targets have
air tightness testing, provision of Note
been set for ‘whole-office carbon
commissioning logbooks and 1
The standards and
performance ratings’, whilst for schools it guidance given in the
prevention of summertime overheating.
is stated that: 1997 edition of BB87 have
This 2nd. Edition of BB87 gives specific
For schools a way of complying with the require- been largely superseded
constructional standards for schools by the requirements of
ments would be to show that the proposed
relating to the elemental method and Part L2 of the Building
building conforms with the DfEE guidance note.’
other requirements of ADL2. Regulations and hence,
The guidance note being BB87 (1997).1
this 2003 revision of BB87
has been prepared. This
The Whole Building Method estimates 2nd. Edition of BB87,
Energy efficiency rating the total annual energy consumption of being the current
the school taking into account the Constructional Standard
In addition to the elemental method there for schools, therefore
are two further means of complying with building fabric, services installed and
replaces the 1st. Edition
Part L2 of the Building Regulation. These operating conditions (including weather).
of Building Bulletin 87
deal with the carbon emission of the published in 1997. All
school building as a complete building The calculation procedure is available references to that

rather than the elements of which it is from the Schools Building & Design Unit document, for the
website at: http://teachernet.gov.uk/energy purposes of compliance
composed. The methods are as follows. with Building Regulations
The spreadsheet contains all the data
Part F 1995 and Part L2
required to make calculations of the 2002 and in the DfES
carbon rating for the school building. Constructional Standards
Elemental Method By following the design guidance [Ref.1], should therefore
For the elemental method of compliance contained within BB87 and ADL2 2002, be considered as
the distinction is generally made between the building should achieve a carbon references to the current
version of this 2nd edition
‘offices, industrial and storage buildings’ performance rating of better than
of Building Bulletin 87.
and ‘all other building types’. Specific 5 kgC/m2 per year. The current version can be
guidance is given for offices etc, and downloaded from the DfES
separate information for ‘all other website http://
building types’ – which includes schools. teachernet.gov.uk/energy.

5
Section 1: BB87 and Approved Document Part L2 2002 requirements for schools

Carbon Emission Lighting Efficacy


To provide energy efficient lighting
Calculation Method
suggests that a higher lighting efficacy
The carbon emission calculation method can be specified for school buildings. A
is advised for innovative or passive designs minimum of 65 lamp lumens/circuit watt
that will benefit from detailed whole should be adopted and therefore the light
building simulation procedures. It is sources in table 8 of ADL2 2002 would
necessary to follow the carbon emission be appropriate with the exception of
calculation method as described in ADL2 “Other; any type and rating with an
2002. efficacy of greater than 50 lumens per
circuit watt.” All the advice on controls
The designer of a school can design a new should be adopted.
school building to comply by any of these
three methods. Glazing
The maximum glazed area of 40%, which
is adopted for heat loss purposes, should
Interpretation of the be accepted and will allow for an element
elemental method of ADL2 of passive design and good daylight
design. If a larger glass area is required it
2002 for schools will be necessary to trade-off any heat loss
The following recommendations relate to by increasing the thermal performance of
the standards set by ADL2 2002 for the building fabric.
compliance with the Regulations by the
Elemental Method. External Lighting
External lighting is not explicitly
U-values mentioned in the ADL2 2002 but is
U-values of the building envelope’s being increasingly used on school
constructional elements shall meet the premises for safety and security. It is
requirements of ADL2 2002 paragraphs recommended that all external lighting is
1.7 to 1.16 inclusive, and will provide provided with lamps having an efficacy of
energy efficient school building at least 65 lumens per circuit watt that are
envelopes. Note that these are minimum fitted with both time control and daylight
standards and higher standards are level photocell control.
desirable for energy efficiency and carbon
emission reduction. Although ‘trade-offs’
between fabric performance and heating Summertime overheating
plant are allowable under the elemental
means of compliance it is recommended requirements for schools
that any change is restricted to a trade-off relating to Part L2
in fabric performance to achieve a more
Schools and their periods of occupancy
environmentally sensitive design.
are different to other building types and
the conventional means of establishing
Note that ADL2 2002 also refers to
overheating can be relaxed. For school
requirements when undertaking work on
buildings it is accepted practice to define
existing buildings and this applies equally
overheating as occurring when the
to schools.
internal air temperature exceeds 28oC.
An allowable degree of overheating in a
school is that this may occur for up to 80

6
Section 1: BB87 and Approved Document Part L2 2002 requirements for schools

occupied hours in a year, normally non- consumption. If less efficient equipment


heating periods are May to September is used then other elements of the
excluding August. Simulation has shown building must be improved to
that this can be achieved with compensate for the increased equipment
conventional natural ventilation designs loads. In particular, summertime
using medium to high thermal mass in overheating may result from excessive
the fabric for normal occupancy levels and heat gains from inefficient equipment.
up to five desktop PCs in a classroom. Additional information on the efficiencies
The glazing distribution as given in of equipment can be found from the
Table 4 of ADL2 2002 is a useful guide following websites:
to avoiding overheating problems.
www.ukepic.co.uk
UK Environmental Product
Appropriate use of shading device and
Information Consortium
good facade design, together with use of
thermal mass, helps to limit summertime www.mtprog.co.uk
overheating. Market Transformation Programme

Designers wishing to use more than the www.sedbuk.com


suggested glazing to achieve a passive Boiler efficiency database
environmentally sensitive design are
advised to adopt the Carbon Emission
Calculation Method for compliance. When predictions of overheating suggest
Passive designs using this amount of that ACMV is required then the existing
glazing need careful consideration to specific fan powers are adopted. That is
avoid overheating and would probably 2 W/l/s is allowed for mechanical
require an appropriate design tool. ventilation in new buildings and 3 W/l/s
for refurbishment. Note: 2 W/l/s is a
Currently, it should be assumed that minimum standard for mechanical
natural ventilation will be used for ventilation and current good practice is
standard teaching zones with limited 1 W/l/s for new build installations.
computer equipment. For guidance it is
suggested that up to five desktop PCs In areas with high levels of ICT – ie above
with CRT screens, a laser printer and an the basic provision of five PCs and a laser
OHP/computer projector will constitute printer and OHP/computer projector –
the ICT equipment in a ‘typical’ then mechanical ventilation and comfort
classroom. Above this threshold, cooling may be provided as indicated by
additional ICT equipment should be ADL2 2002 paragraph 1.60d. In this
considered as a process load and treated case provision should also be made to
as such in interpretation of the Approved record the energy consumption of this
Document. equipment as indicated in paragraph 3.4
of ADL2 2002.
These internal gains, which provide useful
heat in the heating season, can lead to
overheating in the summer and therefore Building Logbooks
should be reduced as much as possible by
As indicated in Section 3 of ADL2 2002
selection of efficient appliances with low log-books and manuals for the user
heat rejection. Energy labelling schemes should be available, and a user guide
for domestic equipment, such as personal should tell school staff how to operate
computers, cookers and other kitchen those parts of the heating system over
equipment, fridges, and washing which they can and should exercise
machines, indicate bands of energy control.
efficiency. Selecting band A and B rated
equipment will reduce energy

7
Section 2 : Heating and Thermal Performance

School Premises Regulations Constructional Standards


(1) Each room or other space in a school The heating system should be capable of
building shall have such system of heating, maintaining the minimum air temperatures
if any, as is appropriate to its normal use. quoted in the School Premises Regulations.
The heating system should be provided with
(2) Any such heating system shall be capable of frost protection.
maintaining the air temperature, at a height
of 0.5m above floor level, at the specified Vertical glazed areas (including clerestory or
level, in the areas set out in the Table below, monitor lights) should not normally exceed an
when the external air temperature is –1oC: average of 40% of the internal elevation of the
external wall. However, where a passive or
Area Temperature daylight design strategy has been adopted the
o
C
percentage glazing may exceed 40%,
Areas where there is the 18 provided the insulation of the building fabric is
normal level of physical increased to compensate for the increased
activity associated with heat loss through the glazing or the heating
teaching, private study
plant carbon intensity is traded up accordingly.
or examinations

Areas where there is a lower than 21 Horizontal or near horizontal glazing should
normal level of physical activity not normally exceed 20% of the roof area.
because of sickness or physical
disability including sick rooms
and isolation rooms but not
other sleeping accommodation
Building Regulations
Areas where there is a higher 15 Central heating systems should have
than normal level of physical
appropriate controls complying with the
activity (for example arising out
requirements in ADL2 2002, in support of
of physical education) and
washrooms, sleeping the Building Regulations.
accommodation and circulation
spaces The air supply to and discharge of products of
combustion from heat producing appliances
and the protection of the building from the
(3) Each room or other space which has a appliances and their flue pipes and chimneys
heating system shall, if the temperature should comply with Building Regulations,
during any period during which it is occupied Part J, 2002.
would otherwise be below that appropriate
to its normal use, be heated to a The fabric insulation should comply with the
temperature which is so appropriate. recommended maximum values given in the
‘Elemental Method’ in Table 1 of section 1 of
(4) In a special school, nursery school or ADL2 2002 in support of the Building
teaching accommodation used by a nursery Regulations, 2002.
class in a school the surface temperature of
any radiator, including exposed pipework,
which is in a position where it may be
touched by a pupil shall not exceed 43 oC.

8
Section 2 : Heating and Thermal Performance

Thermal conditions considered. Recirculation of warm air to


low level using ‘punka’ or ducted fans
The thermal conditions within may be worthwhile in the heating season.
educational buildings should be
appropriate to the activities and clothing Multi-purpose spaces should have heating
of the occupants. Thermal comfort is capable of adjustment, so that the space is
achieved when a balance is maintained kept at the temperature required for the
between the heat produced by the body activity and not at a higher or lower level
and the loss of heat to the surroundings. than is needed. This is particularly so with
The rate of heat loss is dependent upon sports and assembly halls, which may be
the amount of clothing worn and the used for both strenuous activities and
temperature of the air and surrounding sedentary occupations eg. during
surfaces. In a normal school environment examinations.
the hourly rate of heat production by the
children varies with activity. This heat is In some establishments like nursery
lost to the surroundings by the normal schools and those for the severely
processes of convection, conduction, handicapped, it is necessary to prevent
radiation and evaporation. It is therefore children from touching heated surfaces
necessary for the designer to take account above 43oC by the use of suitable screens
of the functions of spaces and the or guards.
activities that they contain, and the type
of clothing likely to be worn.

Summertime temperatures
Temperatures in the An undesirable rise in temperature during
warm weather can be caused by
heating season uncontrolled incidental and solar heat
The air temperatures quoted in The gains, or by high densities of occupation,
School Premises Regulations are the eg in lecture rooms. In these
minimum temperatures that should be circumstances sufficient natural
maintained during normal hours of ventilation is particularly important.
occupation throughout the heating Mechanical ventilation may be necessary
season, assuming an external temperature in some instances to help to control air
of -1oC. These room temperatures and temperature.
this external temperature are not intended
for use in the design of the heating plant. Reflective, white or very light roof
For sizing of the heating system, surfaces reduce the solar heat gain
reference should be made to CIBSE through the roof as well as reducing the
Guide B[Ref. 7]. thermal stress in the weatherproof
covering, but will tend to become less
Higher air temperatures are often needed effective without adequate maintenance.
in schools to maintain comfort conditions Insulation in the roof and walls also helps
and for those children with special to reduce this solar gain, but will also
educational needs, or those who may be reduce the ability of the excess heat to
more sensitive to the cold. escape from the space. Increased thermal
mass in the conditioned space controls
Excessive vertical temperature gradients the degree of temperature swing.
should be avoided and the temperature at
2.0 m should not exceed that at floor Excessive solar heat gain through
level by more than 3oC. In school windows can be minimised by appropriate
buildings with spaces higher than 3 m orientation and by the use of brise soleil
temperatures greater than normal will structural shading, louvres, blinds and
occur at ceiling level. In these cases curtains. Shading the glass from the
increased roof insulation should be outside is the most effective method of

9
Section 2: Heating and Thermal Performance

control. However, this calls for careful the solar radiation is more intense. West
design of sun shading devices to avoid and south-west facing glazing leads to the
impairing the daylighting of a classroom. greatest risk of overheating.

Storage temperatures for food, including


lunch boxes need to be considered.
Heating system design
The heating installation should be
capable of achieving the temperatures
Thermal insulation recommended in The School Premises
Compliance with the current Building Regulations. Occupancy and solar gains
Regulations ADL2 2002 is considered as may provide additional heat. However,
a minimum requirement that must be met the heating system must be responsive
and attempts should always be made to enough to adjust to these gains. Good
adopt more energy efficient techniques control of the heating system is essential
when appropriate. not only to maintain comfortable
conditions but also to eliminate waste of
Adequate thermal insulation of roof and fuel.
walls is necessary not only to reduce heat
loss, but also to make the internal surfaces Consequently, the choice of heating
of the building warmer and to reduce the system and heat emitter is an important
risk of condensation. The provisions in design decision. Among other factors, it
ADL2 2002 will be adequate to ensure will depend on the thermal mass of the
this in all normal circumstances. construction, the use of solar heat gain,
the type of ventilation and the level of
In addition to insulating the building fabric fabric insulation.
it is important also to insulate adequately all
heating mains including valves and hot Radiators are generally the most suitable
water storage tanks. Thermal insulation of heat emitters for teaching spaces. In some
vessels, pipes and ducts according to ADL2 primary schools where extensive use is
2002 is sufficient. made of the floor hot water underfloor
heating is preferred. This is not
appropriate where the floor area is likely
to be covered, eg with insulating mats or
Heat gains
bleacher seating and should not be the
Incidental heat gains (eg solar, teaching only form of heating in spaces such as
equipment and light fittings) will also nurseries, where doors are often opened
contribute heat to the space. Allowing for for outside activities even during the
these and designing suitably responsive heating season.
controls and heating systems will help to
reduce fuel consumption. With the Large infrequently used spaces such as
increasing use of Information halls can benefit from a faster response
Communication Technology (ICT) in and fan convectors or low temperature
schools these incidental gains become radiant panels are often used. Low
increasingly significant and may require temperature radiant panels can be fixed to
special consideration. ceilings rather than taking up valuable
wall space. However, they can produce
Solar gains can be beneficial if careful thermal stratification and this should be
consideration is given to the design and considered at the design stage.
orientation of the building, but excessive
solar gains may lead to overheating. Underfloor heating is sometimes used in
Windows on a south-east facing facade halls to keep walls clear and to avoid
will allow entry of sunlight early in the background noise but its thermal
morning but will avoid direct sunlight response is slower than for other systems.
during midday and early afternoon when

10
Section 2: Heating and Thermal Performance

Wall space is often a priority in schools Where multiple boiler installations are
and fan convectors can then be used in being designed, condensing boilers
preference to radiators. However, it should be considered for the lead boilers
should be remembered that fan to take advantage of hot water loads and
convectors have a high maintenance cost. the long run time for the base load of the
The background noise level of the fan space heating. Small stand-alone gas-fired
convectors across the frequency spectrum boilers or direct gas-fired heaters used in
should not be too high for the planned remote classrooms can allow more flexible
activities, see Building Bulletin 93. use of the buildings than large central
boiler plant.
To achieve an effective and efficient heat-
up, optimum start controls should Heat pumps may be a viable option for
generally be provided. This is the case the heating, particularly in rural schools
particularly in buildings with intermittent away from gas main networks. Heat
occupancy such as schools. Similarly, an pumps can be air to air, air to water, or
optimum-off facility should be provided water to water. Supplementary heating is
to minimise the heating overrun at the normally required when external
end of the school day. temperatures fall below approximately
3 oC. This can be by use of a heat store
Careful design of the number and size and off-peak electric heating.
of boilers to match load variations is
required to ensure optimum efficiency
throughout the heating season and to
Choice of fuel and heating
have a reasonable standby capacity when
implementing major boiler maintenance. system
The choice of fuel and heating system
It should be remembered that plant sized should be based on calculations of the
for steady-state design conditions always carbon efficiency of the system and its net
has excess capacity when outside present value, taking into account capital,
conditions are less severe than design maintenance and running costs. In
conditions. Plant over-sizing in excess of practice the selection procedure is
25% of steady-state design requirements complicated by the unpredictability of
is unlikely to be justified unless very fuel price trends and fuel availability.
substantial deviations in flow
temperatures are required. Reference In the choice of heating systems the
should be made to Sections A2, A3, and option should be kept open where
A9 of the CIBSE Guide[Ref.8] when possible to change from one type of fuel
calculating the heat losses and designing to another during the life of a building.
the heating system. Design loads should Systems where heat is delivered by hot
take into account the considerable water or warm air can possibly be
incidental heat gains that are available in converted to coal, gas, oil or electricity.
occupied schools. This is particularly Dual fuel burners for oil and gas are
important in determining ventilation heat readily available and allow the site
loads, the majority of which will only manager to choose the cheaper fuel.
occur during occupied periods when (Where oil tanks already exist the extra
there are high heat gains to offset part cost is small.)
of the heat loss.
Modular boilers (perhaps using a
Pupils in a classroom will compensate for condensing lead boiler) should be
all fabric losses and a major part of considered. Smaller installations can
ventilation heat losses. Equipment and economically use condensing boilers with
solar gains further reduce the heating underfloor heating systems.
demand. During pre-heat the ventilation
loss will be minimal.

11
Section 2: Heating and Thermal Performance

Hot water generation should be on a 2006 asks member states to ensure that
separate circuit or a separate system to the technical, environmental and economic
main heating. Point of use systems can be feasibility studies of alternative systems
the most energy efficient option. are carried out.

Electric off-peak storage heater


Heating Plant Carbon
installations cannot be adapted to any
other fuel use, and electric storage Intensity
heaters are also unresponsive to changing The level of carbon (C) produced by
heat gains. different fuels varies according to the
initial proportion of carbon in the fossil
Electricity that is derived from renewable fuel. ADL2 2002 refers to the ‘Carbon
sources, but supplied from the grid (such Emission Factor’ of the fuel. They are
as ‘green tariff’ electricity) is not provided in Table 6 of the Approved
considered as an appropriate way of Document and included in a table in the
meeting the carbon emission calculations. BB87 calculation spreadsheet. As can be
seen for each unit (kWh) of electricity
One of the most effective ways of delivered more than twice the amount of
conserving energy in existing schools is to carbon is produced as for natural gas.
improve the efficiency and responsiveness
of the heating installation so that it comes However, the conversion of the fossil fuel
as close as possible to the performance of delivered to the school takes place at less
a well designed new installation. Before than 100% efficiency and this has to be
any improvements are considered the taken into account. This is achieved by
operation of existing plant and controls calculating the heating plant carbon
should be checked. Simple re- intensity, in kgC/kWh of useful heat.
commissioning of systems often leads to The elemental method sets an overall
large fuel savings, for little or no cost. maximum value for the carbon intensity
Improvements that may be worthwhile of the heating plant. It is this value that
range from the re-design and renewal of can be traded-off against fabric insulation
plant to the re-assessment of its operating levels, although this is not recommended
pattern. Fuller details are given in for schools other than to achieve a more
Building Bulletin 73[Ref.9]. environmentally sensitive design.

When designing new buildings to improve (Note: for conversion from kg of carbon
energy efficiency it is important to consider to kg of CO2 multiply the carbon figure
the inclusion of systems based upon by 44/12.)
renewable energy and other innovative
technologies eg micro CHP (Combined
Heat and Power) systems. For further
information see the following websites: Heating control
• DTI Photovoltaic ADL2 2002, paragraph 1.33
Demonstration programme recommends space heating controls such
www.solarpvgrants.co.uk that the required temperature is only
maintained when required in areas in use.
• Renewable energy capital grants
The type of space heating control and the
www.dti.gov.uk/renew/eoi.htm
way in which it is operated have a
• Community and household significant influence on fuel
Note renewable energy grants consumption. Investing in control
1 EU Directive on the Energy www.clear-skies.org
Performance of Buildings equipment can produce a relatively quick
adopted in January 2003 pay-back, and zone control of buildings
http://europa.eu.int/eur-
The EU Directive on Environmental can help with lettings, out of hours use
lex/en/com/pdf/2001/ Performance of buildings1 which will be and catering contracts.
en_501PC0226.pdf included in the Building Regulations by

12
Section 2: Heating and Thermal Performance

Space heating controls should be user- occupied during the holidays. Here,
friendly, reliable and as far as possible electric heating can be used as an
automatic. Simple and inexpensive alternative to the main heating system.
controls are now available which provide
variable time control with optimum start.
It is preferable if a member of the school
Building Energy
staff can easily change heating periods, set
holidays, change temperatures according Management Systems
to use, and extend heating periods. These Depending on diversity and out of hours
controls are economic even in the smallest use a building energy management system
of schools. may be considered. Building energy
management systems (BEMS) are
Adjustable components (such as becoming increasingly common and can
temperature sensors) should be tamper- significantly improve both the
proof. For the most accurate control, and performance of the building and its
improved energy efficiency, electronic controllability. Within the BEMS,
thermostats (rather than bi-metallic strip optimum start/stop controls and
devices) should be specified. Similarly, automatic frost protection will normally
tamper-proof thermostatic radiator valves be provided. Occupancy sensors and
(TRVs) have been shown to give good manual override to allow occasional use
local control of heat emitters to minimise out of hours should also be considered.
overheating and underheating of areas Weather compensation should be used
with different thermal mass and incidental where the boiler plant capacity exceeds
heat gains. 100 kW and may also be usefully applied
to smaller heating zones, eg to allow for
aspect zoning. Weather compensation
Good design of heating controls alone is
may be of the central plant or the local
not sufficient to ensure fuel economy. It
zones. It is not advised on circuits serving
is also necessary for the controls to be
fan convectors.
properly commissioned and maintained in
good working order. The use of BEMS will only be successful
where a member of staff is available who
Zoning and individual temperature is fully conversant with its operation and
sensors should be provided to account for ensures the system is running correctly.
orientation and pattern of use. Heating There should be provision of training for
zones should be chosen to suit the solar the site staff and a back-up advice service
and incidental heat gains and to allow out should be provided if required.
of hours use of selected zones.
Where a building energy management
Large secondary schools require careful system is provided it can be used to
design of the control system to take monitor electrical and thermal energy as
account of the greater range of operating well as water consumption. Remote meter
hours and diversity of use including possible reading is likely to provide quick paybacks
out of hours use by the local community. as it allows staff to identify waste by real-
Care should be taken to ensure that the time monitoring of consumption. It can
heat load required in these areas can be also help to monitor running costs.
provided from the heating system efficiently
by avoiding long distribution runs and Meter reading software is available at low
ensuring the boiler plant can operate cost where there is no control BMS and
efficiently at part load. some of this software has been designed
for curriculum use, eg mathematics.
A number of zones may be provided to
An economic assessment of cost savings
allow only the areas that are in use to be
and payback periods should be made
heated. A particular problem is offices
before installing complex control systems.
that may be the only part of the building

13
Section 2: Heating and Thermal Performance

The calculations should include predicted Where pipework runs externally or the
maintenance costs of the control boiler house has a poorer level of
equipment and its anticipated life insulation than the heated spaces, the
expectancy. stage 1 and 2 thermostats may need to be
set to higher temperatures.

Suitable indicators should be provided to


Frost protection show on the boiler control panel that the
When unoccupied, a building should be various stages of frost protection are
heated only for frost protection or during working.
the pre-occupation heat-up period. Frost
protection is for the hot and cold water An outside air temperature sensor should
services and the heating system only, not be used to directly bring on the
unless there is a need to preserve the boiler plant.
structure, as with wooden panels in
ancient buildings. This method of protection assumes that
domestic hot water and cold water
A three-stage frost protection is services are within the insulated building
recommended for larger heating systems. envelope. If they are not, additional frost
Designs often omit stage 2 or 3 but the protection for these services may be
cost saving is small. The set points quoted needed.
are for bimetallic thermostats. Electronic
temperature sensors have much smaller Single stage frost protection, omitting
switching differentials allowing set points stages 1 and 2 is adequate for smaller gas
to be lower which saves energy. fired heating systems.

Stage 1. An outside thermostat located In a building with high thermal storage,


in a position, which cannot be affected by the use of night setback operation should
sunlight, to bring on all pumps both be considered for unoccupied hours
heating and hot water service. This during term time. This would top up
should be set to 2 oC (just above heating as required but rely mainly on
freezing). stored heat in the fabric to avoid frost
damage. This could use less energy than
Stage 2. An immersion/strap-on the frost thermostat protection and
thermostat should be fitted in the reduce boost heating requirements on
common return from the heating and hot start up for this type of building.
water service which will bring into
operation the boiler plant. This should be In some highly vulnerable areas,
set at 5 oC. Conventional optimisers often consideration should be given to using
provide this function. The water self-regulating tracer cable as a last resort.
temperature should rise high enough to This should be switched on and off by a
prevent freezing of remote pipework due thermostat set at 2 oC.
to very low outside temperatures and to
prevent back-end corrosion of oil boilers. Where air, via fresh air inlets, is heated by
This can be achieved by providing a timer hot water heater batteries, provision of
to ensure that the plant runs for 30-60 frost temperature sensors to protect them
minutes dependent on the size of the is essential. When the plant is not
system. operational, the control valve should be
open to the coil and the associated
Stage 3. A standard low temperature dampers closed.
thermostat installed in a normally heated
room with maximum exposure should be Cold water tanks and pipework need to
set to bring the boiler plant into be insulated to prevent freezing as well as
operation when the internal temperature to prevent overheating in summer. (see
drops below 5 oC. This temperature Section 5).
should be adequate for most buildings
where condensation is not a problem.

14
Section 3 : Ventilation and Indoor Air Quality

School Premises Regulations Constructional Standards


(1) All occupied areas in a school building It is recommended that in all teaching accommodation, medical
shall have controllable ventilation at a examination or treatment rooms, sick rooms, isolation rooms, sleeping
minimum rate of 3 litres of fresh air and living accommodation, ventilation systems, whether natural or
per second for each of the maximum mechanical, are capable of providing a minimum of 8 litres per second of
number of persons the area will fresh air for each of the usual number of people in those areas when
accommodate. such areas are occupied.
All other areas, such as corridors, halls and circulation spaces, shall be
capable of being ventilated to a minimum of 3 litres per second of fresh
(2) All teaching accommodation, medical
air for each of the maximum number of persons the area will
examination or treatment rooms, sick
accommodate.
rooms, isolation rooms, sleeping and
living accommodation shall also be Natural ventilation is the preferred method of ventilation in schools and it
capable of being ventilated at a should be easily and readily controlled by the occupants.
minimum rate of 8 litres of fresh air
Spaces where noxious fumes or dust are generated may need additional
per second for each of the usual
ventilation. Laboratories may require the use of fume cupboards, which
number of people in those areas when
should be designed in accordance with DfES Building Bulletin 88[Ref.10].
such areas are occupied.
Design technology areas may require local exhaust ventilation.

(3) All washrooms shall also be capable All washrooms in which at least 6 air changes per hour cannot be
of being ventilated at a rate of at least achieved on average by natural means should be mechanically ventilated
six air changes an hour. and the air expelled from the building. Heat recovery fans can be used.

(4) Adequate measures shall be taken to


prevent condensation in, and remove During the summer, when the heating system is not in operation, the
noxious fumes from, every kitchen and recommended design temperature for all spaces should be 24 oC with a
other room in which there may be swing of not more than +/- 4 oC. It is undesirable for peak air
steam or fumes. temperatures to exceed 28 oC during normal working hours but a higher
temperature for 80 hours during the summer term is acceptable.

Purpose of Ventilation volatile organic compounds, dirt or


mould in mechanical ventilation systems
It should be remembered that the due to poor maintenance and external
primary purpose of ventilation is to pollution. Increasing numbers of children
provide good indoor air quality in both are reported to be asthmatic and/or
winter and summer. The supply of fresh sensitive to some of these contaminants.
external air, at a level required to meet
the need for odour control and adequate Much research has recently been done on
indoor air quality, suggests that 8 litre per IAQ in school classrooms, which usually
second per person (l/s/p) are provided. have high occupancies. It has been found
In the summer it may be desirable to that the concentration of carbon dioxide
provide more than this to remove in the air in a classroom is a good
unwanted heat gains that may lead to indicator of the IAQ. For this reason
overheating. In winter lower ventilation limiting carbon dioxide concentrations
rates are usual. This together with are increasingly being used in design. For
incidental heat gains limits the wintertime example, in Finland, design guidelines
heat demand. recommend that in classrooms, natural
ventilation systems should achieve a
concentration of carbon dioxide of less
Indoor Air Quality (IAQ) than 1500 parts per million (ppm) under
design conditions and mechanical
There are many factors which influence
ventilation systems achieve a
IAQ in schools, such as damp conditions,
concentration of less than 1000 ppm. In
allergens from dust mites in carpets,

15
Section 3 : Ventilation and Indoor Air Quality

normal classroom occupancy, a assumption that these will be either: used


concentration of 1000 ppm corresponds intermittently; large volume spaces
to a ventilation rate of approximately 8 providing a dilution effect; or have high
litres per second per person of fresh air levels of ventilation occuring between
whereas a concentration of 1500 ppm teaching periods, eg in circulation spaces by
corresponds to 4.5 l/s/p. opening of external windows and doors.

Carbon dioxide concentrations of 2000 As it is difficult to predict the actual rates


to 3000 ppm are often found in school required, the emphasis should be on the
classrooms and levels of up to 3500 ppm provision of easily adjustable openings
are considered perfectly safe. (Note: The whether they are windows, slot ventilators
threshold limit value for an adult for or adjustable grilles. The ventilation
continuous eight hour exposure to system should be designed to ensure that
carbon dioxide is 5000 ppm.) Exposure air movement at the occupants’ level is at
to this level is not dangerous but may such a temperature and velocity as to
affect performance. ensure comfort; window design is
important for this. Ventilation suitable for
A simple cost effective measure is to the occupancy level is required whenever
provide visual CO2 indicators and to give spaces are occupied. Window-vents and
guidance to teachers that high CO2 levels extract grilles to ventilation stacks,
are likely to lead to a fall off in the controlled by the occupants are an
concentration of pupils. effective way of providing natural
ventilation. In practice, adequate
ventilation rates may be higher or lower
than the rates quoted.
Natural ventilation
Generally it is assumed that school In classrooms designed to be ventlated by
classrooms can be ventilated to 8 l/s/p opening windows trickle vents should also
by natural means alone and natural be fitted. This is particularly important
ventilation is taken to be the default with modern airtight construction.
design solution for the ventilation of
school classrooms. Some supplementary
mechanical ventilation will be required in
most schools, for example, in toilets, Mechanical Ventilation
changing rooms and spaces with high In a well insulated building, ventilation
functional heat gains, such as kitchens heat losses account for a major part of the
and home economics rooms, and also in energy consumed and any mechanically
some laboratories, and areas producing ventilated part of the building should
water vapour or fumes. include, wherever possible, heat recovery,
as this can reduce ventilation heat losses
Given that natural ventilation is driven by by up to 80%. The potential savings from
the combined wind and stack effect, the heat recovery systems will only be realised
rates of natural ventilation provided should if a building is very airtight, therefore
be calculated to give good indoor air where heat recovery is used there is
quality in the typical conditions of wind increased need for airtightness.
speed and inside to outside air temperature Infiltration through joints in the external
difference. The minimum design envelope, around door and window
requirement of 3 l/s /p, for spaces other openings and service penetrations can
than those defined as teaching represent a large part of these losses and
accommodation, offices, medical should be reduced as far as possible[Ref.11].
examination or treatment rooms, sick Draught lobbies, auto-closing doors and
rooms, isolation rooms, sleeping and living internal fire doors can all play their part in
accommodation, is based on the reducing infiltration.

16
Section 3 : Ventilation and Indoor Air Quality

Although internal gains may provide for In addition to ensuring that all internal
heat losses the incoming air will still need gains are reduced to a minimum it is
to be tempered to avoid draughts, for this necessary to control solar gains.
the heat recovery can be beneficial. Small For those sensitive areas that cannot be
input/extract fan units including heat oriented to the north, some form of
recovery are now available for use in solar shading may be required - either
toilets and smaller rooms, these are using special glass or blinds or a
economical and give good energy savings. combination of the two.
However, there will be additional
electricity used particularly in larger heat The first means of removing the
recovery systems, by the fans and filters, unwanted heat is by natural ventilation.
ductwork and grilles. Also, these items all The ventilation rate for cooling in
need maintenance. One hundred percent summer is significantly more than that
fresh air mechanical ventilation systems required for the hygiene of the
with heat recovery by thermal wheels occupants. Therefore, particular
minimise the potential for IAQ problems consideration should be given to the
associated with recirculation systems and design of the building so that natural
can have heat recovery efficiencies of 80%. ventilation can achieve these supply rates.

Ventilation systems must be designed Deep plan spaces should be avoided and
together with any fume cupboards and classrooms should have the provision for
local exhaust ventilation systems so that cross-ventilation. As the worst situation is
they do not disturb the operation of the likely to be at times of high solar
fume cupboards or exhaust radiation it may be possible for the
ventilation.[Ref.10] ventilation to be driven by a solar
induced stack effect - solar chimneys are
Whichever ventilation system is selected it one way to utilise this effect. This will
is important to note that IAQ is highly encourage ventilation on days with little
dependent on the cleanliness of the or no wind. It may be useful to
spaces and ductwork for a mechanical supplement the natural ventilation with
system. Therefore, cleaning of carpets fan assistance in a hybrid system for those
and room surfaces such as bookshelves to times when the design requirements (either
limit the contaminants is as important for for fresh air for IAQ or reduction of
good IAQ as adequate fresh air internal temperatures) are not being met.
ventilation rates.
Simple methods can be used to calculate
the size of opening vents in classrooms.
In the case of deep plan spaces more
Controlling summertime
complex design methods are required to
overheating predict the ventilation rates [Refs.12 & 13].
One of the main design problems faced
by the designers of modern schools is the
prevention of overheating. Classrooms
can be subject to substantial heat gains
from electrical equipment, the pupils and
from solar gain. Electronic white board
projectors and overhead projectors are in
use for a large part of the school day in
some schools. When in use, blinds are
usually drawn to provide easier vision of
the board and this again increases the
heat load from the electric lights.

17
Section 4 : Lighting

The School Premises Constructional Standards


Regulations Where possible, priority should be given to design for daylight as the main
(1) Each room or other space in a source of light in working areas.
school building -
The uniformity ratio (minimum/average daylight factor) of the daylight should
(a) shall have lighting appropriate be in the range 0.3 to 0.4 for side-lit rooms. Where spaces are top-lit, eg,
to its normal use; and atria, then higher uniformities should be expected of the order of 0.7.
(b) shall satisfy the requirements The uniformity ratio (minimum/average maintained illuminance) of the electric
of paragraphs (2) to (4) lighting in teaching areas should be not less than 0.8 over the task
area[Ref.14].
(2) Subject to paragraph (3), the
Teaching spaces should have views out except in special circumstances. A
maintained illuminance of teaching
minimum glazed area of 20% of the internal elevation of the exterior wall is
accommodation shall be not less
recommended to provide adequate views out.
than 300 lux on the working plane.
A maintained illuminance at floor level in the range 80 - 120 lux is
(3) In teaching accommodation where recommended for stairs and corridors.
visually demanding tasks are
Entrance halls, lobbies and waiting rooms require a higher illuminance in the
carried out provision shall be made
range 175 - 250 lux on the appropriate plane.
for a maintained illuminance of not
less than 500 lux on the working The type of luminaires should be chosen to give an average initial circuit
plane. luminous efficacy of 65 lumens/circuit watt for the fixed lighting equipment
within the building, excluding track-mounted luminaires and emergency
(4) The glare index shall be limited to lighting. In all other respects the lighting efficiency and controls should
no more than 19. comply with Approved Document Part L2, in support of the Building
Regulations.
Note: Recommended illuminance is
External lighting is not explicitly mentioned in the ADL2 2002 but is being
described as maintained illuminance, and
increasingly used on school premises for safety and security. It is
is defined in the CIBSE Code for
recommended that all external lighting is provided with lamps having an
Lighting, 2002[Ref. 14] as: ‘The average
efficacy of at least 65 lumens per circuit watt that are fitted with both time
illuminance over the reference surface at
controls and daylight level photocell control.
the time maintenance has to be carried
out by replacing lamps and/or cleaning
the equipment and room surfaces’.

Design framework
This section of BB87 is based on the
more detailed design advice given in
Building Bulletin 90, Lighting Design for
Schools [Ref.15]. A successful lighting
installation is one that satisfies a number
of different criteria shown in the lighting
design framework. The criteria will not
have equal weight but all should be
considered to arrive at the best solution.

18
Section 4 : Lighting

Task/activity lighting Lighting and energy efficiency


Here the designer needs to examine the This will mean making the maximum use
functional requirements of the particular of daylight, using electric light to
space. It is necessary to consider the complement daylight, and using energy
amount of light and the type of lighting efficient electric lighting that only
required to ensure that the users of the operates when it is required. This last
space can carry out their particular tasks point can be covered by the positions of
without visual difficulty and in a the control switches, by the organisation
comfortable visual environment. Hence of the lighting circuits to relate to the
the first consideration here is to analyse daylight distribution and to the use of the
the activity requirements for particular space. Automatic controls can provide
spaces. useful energy savings but it is essential
that any controls are user friendly, ie they
It may be necessary to provide flexibility do not hinder the use of the space.[Ref.16]
in the lighting to allow for a variety of
activities. Local task lighting can be very The type of luminaires should be chosen
useful for specific tasks. Safety should be to give an average initial circuit luminous
considered in choosing the type of local efficacy of 65 lumens/circuit watt for the
task light, eg surface temperature of the fixed lighting equipment within the
fitting. building. Both emergency lighting
systems and equipment which is not
An increase in the size or contrast of the fixed, eg track-mounted luminaires are
task detail, eg typeface may be an excluded from this figure.
alternative to higher levels of illuminance
particularly for the visually impaired.
Lighting maintenance
All lighting will deteriorate with time due
Lighting for visual amenity to dirt build-up on the lamps and
This aspect of lighting addresses the luminaires, on the windows, on the
appearance of the lit scene, the aim being reflecting surfaces of the space and also
to create a ‘light’ environment that is due to lamp light output depreciation.
visually interesting and pleasant. This The designer will need to consider these
means creating a light pattern that has matters in making decisions to ensure
luminance variation and a sensitive use of that the lit environment is satisfactory
surface colour. over the whole maintenance cycle. This
will mean liaising with the client to plan a
suitable maintenance programme.
Lighting and architectural It is worth remembering that use of a
wide range of different lamp types makes
integration subsequent replacement more
It is important that a lighting installation, complicated.
both natural and electric, appears an
integrated part of the architecture. This All lighting elements including windows
will apply both to the lighting elements should be easy to clean and maintain.
(windows and luminaires) and the light
patterns they produce.
Lighting costs
Both capital costs and running costs will
need to be considered to ensure a cost
effective design. This is particularly
important if the two costs are to be met
by different budgets.

19
Section 4 : Lighting

Design criteria Windows are important as they provide


natural variation of light through the day
Daylighting and external visual interest. For the window
area to be adequate for this purpose, it is
Natural light should be the prime means
recommended that a minimum glazed area
of lighting during daylight hours. A space
of 20% of the internal elevation of the
is likely to be considered well lit if there is
exterior wall is provided.
an average daylight factor of 4-5%. For
the daylight illuminance to be adequate
Windows, in addition to being treated as a
for the task, it will be necessary to achieve
lighting source and providing a view out,
a level of not less than 300 lux, and for
need to be considered in terms of other
particularly demanding tasks not less than
environmental factors, eg, the thermal and
500 lux. When this cannot be achieved,
acoustic performance together with the
the daylight will need to be supplemented
energy efficiency of the building.
by electric light. Light exterior surfaces
can sometimes be used to increase
reflected light. Light shelves and special Where windows are used for ventilation,
refractive glazing can be used to redirect the openings need to be controlled to
light from perimeter windows deeper into provide the necessary ventilation without
spaces to increase the uniformity of the draughts.
daylight [Ref. 17].

The design of the fenestration should Electric lighting


relate to the layout and activities planned The electric lighting installation will need
for the internal space, eg, to avoid to meet all the requirements shown in the
silhouetting effects and excessive contrasts design framework.
in brightness.
In terms of task lighting, for most school
Discomfort and disability glare are tasks, a maintained illuminance of
possible from daylight, and in particular 300 lux will be appropriate. If the task is
from direct sunlight. This potential particularly demanding, eg, the task detail
problem can often be solved by careful
content is small or it has a low contrast,
design of the fenestration to minimise
then a value of not less than 500 lux will
glare. Alternatively, adjustable blinds can
be necessary: in some situations, this can
be provided to screen the glare source
be provided by a local supplement to the
when necessary. Blinds can also improve
general lighting.
the thermal environment by reducing
heat gains. Although they are more
A maintained illuminance at floor level in
expensive than internal blinds, external
the range 80 - 120 lux is recommended
blinds are more effective in preventing
for stairs and corridors. Entrance halls,
solar heat gain. Internal blinds are often
lobbies and waiting rooms require a
difficult to maintain and are a source of
higher illuminance in the range 175 - 250
noise when windows are open.
lux at an appropriate level. Reception
areas should be lit to a level in the range
A low maintenance solution is a tripled
250 - 350 lux on the working plane.
glazed window with an internal double
glazed unit and an interstitial blind
located between this and the external In terms of avoiding discomfort glare,
single glazed element. This gives a very where a regular array of luminaires is
low U-value of around 1.6 W/m2 0C used, the Glare Index shall be limited to
without using specialised double glazed no more than 19. It will also be
units and also enables the outer pane to important to avoid visual discomfort from
be easily replaced in the event of individual luminaires and from reflected
breakage. The external cavity can also be images, particularly on computer screens.
ventilated to dissipate heat gains.

20
Section 4 : Lighting

An additional consideration on visual In these spaces, it is recommended that


comfort is the avoidance of subliminal the colour appearance of the lamps used
lamp flicker. This can be important as it should be in the Intermediate
can induce epileptic fits in susceptible classification with a Correlated Colour
pupils. It can be minimised by the use of Temperature of about 4000oK.
high frequency control gear or using
more than one phase of a three phase
supply in a lead-lag arrangement. The Lighting quality
stroboscopic effect of lamp flicker must
In terms of the appearance of the
be addressed in areas with rotating
lighting, both natural and electric, it will
machinery, eg lathes, cnc machines, band
be necessary to consider the overall light
saws and circular saws.
pattern in terms of ‘apparent lightness’, ie
the overall lightness of the space and
Colour appreciation is an important part
‘visual interest’, a term relating to the
of learning, and hence it is necessary to
degree of non-uniformity in the light
use electric light sources that present
pattern. The bright parts can frequently
colours accurately, particularly in art and
be the highlight areas used for display
design rooms. Good colour rendering is
purposes.
now not very expensive to achieve. In this
respect, lamps with a CIE Colour
Another aspect that is important is the
Rendering Index (Ra) of not less than 80
integration of the lighting (equipment
are recommended. With regard to colour
and light pattern) with the the surface
appearance, lamps with a Warm to
colours and textures and the overall
Intermediate classification (Correlated
architecture.
Colour Temperature 2800oK - 4000oK
should be used).
These are attributes which recent research
has shown are important for the users of a
Switching arrangements should facilitate
space, but because they are subjective,
shared use of spaces and changes to the
they cannot easily be quantified.
layout of spaces, where appropriate.

However, for the space to have an


acceptable ‘apparent lightness’, it will be
Combined daylighting and necessary to use relatively high surface
electric lighting reflectances, which requires a wall finish
A specially designed supplement of reflectance not less than 0.6 with a ceiling
electric lighting should be provided when finish reflectance not less than 0.7 and a
Note
the daylighting recommendations cannot floor reflectance as high as is practicable. 1
Since it is common
be achieved throughout a space. In Glossy finishes to ceilings and walls practice for teachers to
addition to providing a combined should be avoided to minimise confusing use the wall surfaces for
illuminance for the task or activities being reflections and glare1. display, a lower average
wall reflectance value of
undertaken, a satisfactory appearance
0.3 - 0.5 will need to be
should be obtained by a balance of The choice of surface colours is important
used for calculations,
brightness throughout the space to cope as it affects not only the surface depending on the wall
with relatively bright windows. This can reflectances but also the overall visual finish and the amount of
be achieved by preferential lighting, and impression. display material.

particularly wall lighting in areas remote


from the window.

21
Section 4 : Lighting

External lighting especially concerning effects on local


residents[Ref.18]. Planning Departments
Exterior lighting may be needed for: often turn down proposals which would
• roadway/pathway lighting; introduce major new light sources into
areas with only low to moderate levels of
• floodlighting of the building at
illumination and which would create
night;
substantial sky glow.
• floodlighting of outdoor sports.
External lighting without automatic
External lighting is not explicitly control is not energy efficient. Some form
mentioned in the ADL2 2002 but is of automatic control should be provided.
being increasingly used on school Control can be by photocells and
premises for safety and security. It is timeswitches or passive infra-red
recommended that all external lighting is detectors.
provided with lamps having an efficacy of
at least 65 lumens per circuit watt that are
fitted with both time control and daylight
Emergency lighting
level photocell control.
The purpose of emergency lighting is to
Attention is needed to avoid light trespass provide sufficient illumination, in the
which can cause a nuisance to people and event of a failure of the electricity supply
dwellings in the neighbourhood. Light to the normal electric lighting, to enable
pollution which affects the local the building to be evacuated quickly and
environment and atmosphere should be safely and to control processes,
avoided. machinery, etc, securely.

Light trespass can be controlled by In schools, emergency lighting is only


suitable selection of the light distribution usually provided in areas accessible to the
of luminaires to avoid 'spill light' and by general public during the evenings. These
careful aiming of floodlights with the use include halls and drama spaces used for
of shields if necessary. performances. Emergency lighting is not
usually provided on escape routes, except
Generally the intensity of a floodlight from public areas, as the children are
beam diminishes away from the centre. In generally familiar with the buildings and
order to control glare from light it is there is only a relatively small part of the
often necessary to refer to the beam angle school year during the hours of darkness.
within which the intensity of the light
falls to one tenth of the peak intensity of Exceptions where emergency lighting
the beam. might be considered are upstairs escape
corridors, escape stairways, corridors
To prevent light pollution, the light without any windows and areas with
defined by this beam angle must fall dangerous machinery.
within an angle of 70o from the
downward vertical. These are called It is recommended that for halls,
full-cut lanterns and usually require gymnasia and other areas used by the
flat glasses. public during the hours of darkness the
emergency lighting should be of the
To achieve the correct uniformity in car maintained type. Where part of the
parks or playing fields higher columns or premises is licensed it will be necessary to
closer spacing may be required. seek the advice and guidance of the Local
While there is no legislation concerning Fire Authority.
light pollution it has become a major
planning issue with Local Authorities

22
Section 4 : Lighting

Emergency Lighting should reveal safe Field defects


passageways out of the building together
Firstly, there are conditions where what is
with the fire alarm call points, the fire
seen is seen clearly but the visual field is
fighting equipment, escape signs and any
restricted. It may be that only the central
permanent hazards along the escape
part of the field is seen (tunnel vision). In
routes such as changes of direction or
this case mobility would be impaired
stairs. Further detail is given in Building
although reading and the ability to do
Bulletin 90, Lighting Design for
fine work would be largely unaffected.
Schools.[Ref.15]
The converse, loss of central vision,
would mean that movement could be
made in safety but the ability to perform
Lighting for pupils with detailed tasks such as reading or sewing
would be extremely difficult if not
visual and hearing
impossible.
impairments
Lighting and acoustic criteria are very In all types of field defect the quantity of
important both to the hearing impaired task illumination is generally unimportant
and to the visually impaired. If one providing normal recommendations are
sensory channel is impaired more reliance followed. Glare should be avoided (see
is placed on the unimpaired sensory section on loss of acuity below) and decor
channel. For example, the use of aural can help rapid orientation (see section on
cues by the visually impaired and lip- use of colour below).
reading by the hearing impaired. See also
the advice on acoustics in Section 6 of
Building Bulletin 93.[Ref.5] Loss of acuity
The other main condition is a loss of
The design of specialist accommodation acuity or a blurring of vision. The extent
for the visually impaired is beyond the of the blurring varies widely and some
scope of this document and specialist pupils may have to bring objects and print
advice should be sought.[Refs.19 & 20] extremely close to their eyes to see best.
However, there are design choices that There may also be an associated loss of
should be considered for all schools. colour vision.
Many of the low cost or no cost measures
can be applied to existing buildings such Large print will, and higher illuminance
as the choice of decor, tactile surfaces and may, be of assistance depending upon the
types of luminaires. For a detailed cause of the loss of acuity. Many schools
description of possible measures see now have the facility to produce their
Building Sight published by the own reading material and the use of a san
RNIB[Ref.21]. serif font of at least 14pt size can be a
useful aid.
Other measures, such as providing or
facilitating the use of visual aids can be The effects of low acuity can be
considered as necessary. There is no aggravated by glare, and this should be
single solution and what may assist one avoided. A ‘white’ board on a dark
person may well not assist another. The coloured wall can be a glare source
following notes are offered as a general whereas a traditional ‘blackboard’ would
guide and should help in the majority of not. Similarly, a view of a daylit scene
cases. through a window can be a disabling
glare source.
Visual impairment can be put into two
broad classifications. Both loss of field and loss of acuity can
occur together and, the particular
difficulties which people with visual

23
Section 4 : Lighting

impairment experience, and their luminance and not just colour. For
responses to light and other example, pale green and pale cream may
environmental features, can vary widely. be clearly distinguished by the normally
sighted but be seen as a single shade of
The use of higher than normal task grey even by some pupils where an
illuminances can be of help to those impairment has not been identified.
whose acuity can be improved by the
contraction of the iris, producing a Contrast in the decor should be used to
greater depth of field. In some cases, aid orientation within a space. For
however, such as those with central instance, using a darker colour for the
cornea opacities, the iris needs to be architrave around a door will aid location
dilated so that the student sees ‘around’ of the door and a handle which clearly
the opacity. In such a case more light will contrasts with the surface of the door will
aggravate, not relieve, the condition. indicate which way it swings.

While in some spaces orientation may be


Positioning established by the furniture arrangement
or by windows during daylight hours, in
Students with visual impairment should
others it can be aided by making one wall
be seated where they can best see the
distinctly different, perhaps by the
work in progress. This may mean a
addition of a large clock or a change in
position outside the normal arrangement,
colour. Whatever method is used, it is
eg immediately in front of the teacher or
best adhered to throughout the building,
board.
ie, the different wall is always to the same
side of the main exit from the space.
It is also important that any visual aids are
readily available for use. These may range
High gloss finishes should be used with
from hand-held or stand mounted optical
care as they can appear as glare sources
magnifiers to CCTV magnifiers. Local
when they reflect bright lights such as
task lighting may also be used as an aid.
sunlight. In general, eggshell finishes are
It may be necessary to allow the student
to be preferred as some directional
to change position within the teaching
reflection is desirable rather than dead
space to accommodate access to an
matt surfaces which may be difficult to
electrical supply, cope with excess
place precisely.
daylight or use any other aid that is
available.
Changes in the tactile qualities of surfaces
can also be useful to reinforce visual
contrasts. They are most important in
Use of colour schools for the blind.
Colour and contrast are particulary
important to the visually impaired and the
hearing impaired[Ref.21]. For example, ICT and display equipment
downlighters in reception or teaching
areas produce harsh shadows which The use of ICT by the visually impaired
obstruct lip reading. can be made easier or more difficult by
the choice of font and background
Careful use of the colour scheme can help colours, screen brightness, font size and
pupils recognise and identify a location. It style, the type and level of room lighting,
can be more important than an elaborate and the control of solar glare [Ref. 22].
lighting installation.
Individual display screens also provide the
Some visual impairments involve a degree opportunity to set up a work space and
of colour blindness and it is important display screen to cater for an individual’s
that contrast should be introduced in particular needs. It can take a

24
Section 4 : Lighting

considerable amount of effort to set up a conventionally ballasted lamps can


display screen but research is going on demostrate at the end of their life. If high
into ways of automating at least part of frequency ballasts are used, consideration
the set up process for example the choice should be given to using a regulated
of font and background colour. version which can be dimmed to allow
the illuminance level to be adjusted to
Daylight suit the individual as well as to save
energy. The additional cost for this is
Generally schools should be designed
usually modest.
with daylight as the principal light source.
The window wall should be light in
It is not normally economic to install
colour, to reduce contrast with the
more than the recommended
outdoor scene, and window reveals may
illuminances on the off-chance that they
be splayed to increase the apparent size of
will be useful some day to a hypothetical
the glazing.
visually impaired student. Additional
illuminance can often be readily supplied
Sunlight can be either a help or a
when the need arises from local task
hindrance, depending on the type of
lights.
visual impairment, and some means of
controlling the quantity should be
Escape routes should be clearly identified
provided. Traditionally this has been by
and alarm systems (visual and acoustic)
means of blinds. The design of
should be adequate.
fenestration in circulation spaces should
minimise glare hazards.

Large areas of glazing can be hazardous Summary of main points on


to the visually impaired unless they can be lighting for pupils with
clearly seen. To avoid accidents they can
be marked with a contrasting feature at visual impairments
eye level. This should be visible in low
• Provide contrast in the decor to aid
light levels.
the location of doors and their
handles, switches and socket outlets,
In the UK the greatest problems, both
changes in direction in corridors,
visual and thermal, are caused by low
changes in floor level, stairs and
altitude sunlight at either end of the
steps.
school day. Any solar shading devices,
including those for rooflights must, • Avoid glare from windows,
therefore, be readily adjustable to cater rooflights and luminaires; either
for a range of conditions. Adjustment of distant or immediately overhead.
solar shading should preferably be at the
• Provide facilities for the use of any
discretion of the students and not the
visual aids, eg magnifiers, telescopes,
teaching staff who may not fully
display screens, etc.
appreciate the visual difficulties of the
students. • Provide additional illumination by
adjustable local task lighting as
Electric light needed.

The control of glare from overhead


lighting is particularly important to
students with a visual impairment.

High frequency electronic ballasts for


fluorescent lamps are to be preferred as
they avoid subliminal flicker and also the
annoying visible flicker that

25
Section 5 : Hot and cold water supplies

The School Premises Regulations

Water Supplies (3) The temperature of hot water


(1) A school shall have a wholesome supplies to baths and showers
supply of water for domestic shall not exceed 43oC. Note 1
purposes including a supply of
drinking water. Drainage
(1) A school shall be provided with an
(2) Water closets and urinals shall adequate drainage system for
have an adequate supply of cold hygienic purposes and the general
water and washbasins, sinks, disposal of waste water and
baths and showers shall have an surface water.
adequate supply of hot and cold
water.

Main summary of standards recommended that hot water supplies to


and regulations washbasins in nursery and primary
schools are limited to 43oC. Particular
Water storage is not a mandatory attention should be given to the
requirement of schools and need not be provision of facilities to ensure the
incorporated where mains pressures can effective maintenance of systems.Ref: 24&25
normally be maintained throughout the
occupied period sufficient to supply all Unvented hot water storage systems
outlets. However, where storage is not should comply with Building Regulation
installed the School Authorities should be Approved Document G3, 1992.
reminded that the affected building
should cease to operate in periods of Drainage and waste disposal should
mains failure unless satisfactory sanitary comply with Building Regulation
facilities can be provided in adjacent Approved Document H, 2000 (2002
buildings. Edition).Note 2

Cold water storage capacity in day schools


should not exceed 25 litres per occupant. Cold water storage
If water is stored, the cold water storage
All water fittings and installations should cistern capacity should be designed with
comply with The Water Supply (Water consideration towards providing the
Fittings) Regulations 1999.Ref: 23 minimum amount of storage sufficient to
enable the school to function during an
Where a temperature regime is used to interruption to the water supply. In day
reduce the risk of legionellosis hot water schools it should not be necessary to
storage temperatures should not be lower exceed 25 litres per pupil. The
than 60oC. However for occupant safety, minimum recommendedRef. 26 & 27 storage
Notes to reduce the risk of scalding, The School capacities per pupil for 24 hour storage
1 In the TMV2 scheme 46 oC Premises Regulations require that the for different types of school are shown in
is appropriate for showers
temperature at point of use should not be Table 3.
and baths.
above 43oC for baths and showers and
2 In Scotland and Northern
where occupants are severely disabled.
Ireland other regulations This may be achieved by thermostatic
apply. mixing at the point of use. It is also

26
Section 5 : Hot and cold water supplies

Table 3 Remote metering allowing easy, possibly


real-time monitoring of water
Day schools
consumption is now a cost effective
Nursery and primary 15 litres per pupil possibility. Sub-metering can be included
as appropriate, for example for
Secondary and technical 20 litres per pupil independent facilities such as, kitchens
Boarding school 90 litres per pupil run by outside caterers, swimming pools,
sports facilities and nurseries.
Reference BS 6700: 1998Ref. 26
By monitoring actual consumption on
site, storage cistern and meter sizes can
These figures assume that meals are
often be further reduced. Observations
provided on site. In many schools this is
of the meter readings can be made over a
not the case. In practice 8 hours storage
period of time or electronic dataloggers
is more realistic and 4 hours should be
can be used but note that consumption is
sufficient in most cases. The water
usually less in winter. Water companies
supplier should be consulted before
may help to conduct a water audit and
finalising cold water storage cistern
establish peak demand flows for accurate
capacities.
sizing. Notes
3 This may fluctuate during
In mainland Europe it is normal practice
the day due to the draw
not to provide any water storage in off pattern of the supply
schools. This is often possible in English Drinking Water network. Compensation
schools. The installation will depend on Health and safety legislation and the can usually be claimed
the supply pressure available from the from the water supplier if
School Premises Regulations require that water pressure drops to
water supply company. Where the supply adequate supplies of wholesome drinking 70% of the minimum level
pressure is low, a storage vessel with a water are accessible to staff and pupils of service, ie 0.7 bar.
booster pump may be required. Water throughout the school day.Ref: 28 All water
supply pressures vary with location, outlets should be labelled as ‘Drinking’ or 4 Within public buildings it is
however water supply companies must often not possible to
‘Not for drinking’.Note 4
provide a minimum level of service of determine whether taps
are connected to the
1 bar (10 metres head) at 12 litres/ Water fountains are quite often used to supply main or to storage
minute. Generally a pressure of 1.5 bar supply drinking water but can be prone to cisterns and it is possible
is set as a minimum standard with a vandalism unless they are located in areas that the microbiological
normal operational pressure of 2 bar such as corridors that are easily observed quality of the water in
(20 metres head).Note 3 storage may deteriorate.
by staff. Therefore, unless the tap
is clearly labelled as
The size of water meter should be as Fountains that discharge water suitable for drinking, it
small as possible, as typically standing downwards are more hygienic than those should not be assumed
charges increase with the meter size. that discharge upwards. Fountains can that the water from any
As a rule of thumb it should be possible tap is safe to drink. The
also be fitted with in-line water filters to
to down size existing older type meters to 1998 Drinking Water
remove chlorine, etc and a facility for Directive contained new
one size smaller than the diameter of the cooling water. Water coolers, including provisions to ensure that
supply pipe to the premises. However, those plumbed directly to the water the water supply within
although water for fire fighting purposes supply may also be considered for public buildings remains
is supplied free of charge, some schools drinking water purposes, however wholesome and is not
may have a fire hose reel fed by the adversely affected by the
consideration should be given to domestic plumbing
metered supply. In these cases, or if in maintenance and the number of pupils system. The various
doubt, the local fire officer should be using the facility. elements of the Directive
consulted if a reduction in the water are due to be implemented
meter size is considered. before the end of 2003.

27
Section 5 : Hot and cold water supplies

Disposable paper cups can be provided at These temperatures can be achieved in


drinking water outlets, to make them practice but require all cisterns to be fully
more comfortable to use, but have insulated and will require the ventilation
hygiene and maintenance consequences. of roofs or other spaces containing,
Where Local Authorities remove cisterns, which are subject to solar gain.
fountains they must ensure that there is a
suitable alternative source of drinking Good practice requires that the water
water for pupils. should not remain static for a long
period. Automatic flushing urinals and
Drinking water taps and fountains in caretaker use in holidays is usually
toilet facilities are not recommended in sufficient to ensure this and preclude the
new facilities but do exist in some schools need for annual draining and cleaning,
and should always be clearly labelled. which is a difficult procedure and best
It is quite acceptable to supply drinking avoided if at all possible. If this cannot
water from a “well managed” cistern be achieved then the cistern should be
supply, installed to the standards of the cleaned, and disinfected annually as
Water Regulations 1999; previously called recommended. Cleaning is very
a “Water Byelaw 30 tank”, when the important in order to remove even
Water Byelaws were in force. This is inorganic debris which could provide a
common practice in schools and habitat for bacteria, including legionella;
recommended by water supply and the cistern must be periodically
companies. sampled to ensure that too many bacteria
are not present (depending on
However these cisterns need to be circumstances, between two and four
designed and maintained correctly. times a year is normally advised).
Key elements to ensure the preservation
of water quality are:- Some Local Authorities do however
routinely carry out annual draining and
• cleanliness
cleaning of their water cisterns.
• maintenance of cool conditions
• the regular use of water to prevent The difficulty of meeting all the
stagnation conditions for water quality in a school
situation means that it is preferable if
• system design; and drinking water supplies in schools can be
• materials used in the construction of connected directly to the cold water main
the cistern should not contaminate the wherever possible.
stored water (eg materials listed in the
Water Fittings and Materials Directory, An alternative is to use bottled water
published by the Water Regulations supplies, as are often used in offices.
Advisory Scheme (WRAS)). However the cost will usually be
prohibitive for school use and bacterial
counts in bottled water are often higher
The water inside the cold water storage
than in mains cold water, because bottled
cisterns should be kept as cool as possible.
water is not chlorinated. Also it is
To minimise the risk of proliferation of
possible to supply a mains fed water
bacteria, cold water temperatures should
cooler which does not require a bottled
be maintained below 20oC. If the
water supply.
temperature is between 20oC and 25oC,
then caution should be exercised. If the
Water cisterns that are not up to the
temperature is above 25oC, action should
standard of the Water Regulations; ie,
be taken to lower the temperature as
without tight-fitting lids, uninsulated or
bacteria will multiply.
without insect screens on the vent and
overflow pipes, do exist in some schools
and drinking water should not be

28
Section 5 : Hot and cold water supplies

supplied from them. They should be In accordance with the HSC Approved
upgraded as soon as possible even if they Code of PracticeRef : 29, risk assessments
do not supply drinking water outlets as are required for certain water systems.
there is no guarantee in the school Where a reasonable foreseeable risk is
environment that children will not drink assessed, management plans should be
from any available cold water tap. Note 5 drawn up and maintained to minimise the
risk by regular inspection, maintenance,
cleaning and treatment procedures.
Hot water
The use of a decentralised hot water
system may help to reduce energy Hot and cold water services
wastage. Wherever possible a separate Whilst surveys have shown legionella to
boiler, hot water generator or point of be present in quite large numbers of
use water heater should be used to water systems such as those found in
provide hot water. Plant sizing curves for hospitals, schools and office blocks, only
hot water in schools are given in Section rarely do these appear to give rise to
2 of the CIBSE Guide, Public Health infection. It is generally not possible to
Engineering. Ref : 27 completely and permanently eradicate the
bacteria. Therefore, in practice, the risk
The minimum numbers of sanitary of infection is addressed by the
appliances for different types of schools application of good engineering practice
are given in The School Premises to ensure the bacteria are prevented from
Regulations, 1999. proliferating. A considerable amount of
guidance has been issued on the risks.
Consideration should be given to the Compliance with the HSC Approved
problem of build up of limescale on heat Code of PracticeRef :29 is a minimum
exchanger surfaces in hard water areas. requirement. Good practical guidance
This can especially be a problem for direct on procedures is also available.Ref : 24 & 25
systems and maintenance issues need to
be considered. Also, the use of water Hot and cold water systems of all sizes are
softeners has on-going consumable costs. covered by the ACoP. Steps should be
taken to minimise the opportunity for
growth of legionella. It multiplies in
Legionellosis (including warm water (approximately 20oC to
45oC) and will thrive in the presence of
legionnaires’ disease) biofilms, scale or debris. The
Inhalation of the legionella bacteria can temperature at cold water outlets should
give rise to legionellosis, but the risk of be not more than 3oC higher than the
infection is low in children unless they are cold water storage temperature, which
immuno-compromised or have respiratory can be as high as 25oC, the highest
problems, eg smoking. Aerosols temperature at which the water
produced by water services such as companies can supply water.
showers and spray taps are potential Consequently quick water turnover in
routes of infection. storage tanks is crucial in preventing the
proliferation of legionella. Features of Note
Although there have been no known cistern fed hot water systems which 5 If lawfully installed before
cases of legionnaires’ disease in schools influence the risk of exposure to the 1 July 1999 water
this is no reason for complacency. legionella include having open cisterns cisterns are not required
Schools need to be aware of the dangers to meet the Water
and larger than required cistern capacities.
and their responsibility to maintain water Regulations requirements.
These risk features can be removed by However, such tanks
systems properly. replacing such hot water systems with should not supply drinking
direct feed water systems using unvented water outlets.

29
Section 5 : Hot and cold water supplies

hot water storage. Other problems such Research on silver/copper ionisation water
as maintaining distribution temperatures treatment has shown that this can be useful
throughout the system can be reduced in the control of legionellosis.Ref: 30
through the installation of instantaneous The research has also established that
hot water heaters. copper pipework is naturally biocidal
particularly at slightly acid pH values.
Where a temperature regime is relied However acidic water is uncommon.
upon to control legionella hot water Copper can inhibit the formation of
should be stored at a temperature of biofilms which are the breeding ground
60oC or above and distributed at a for legionella and other bacteria.
minimum temperature of 50oC. Copper pipework must have water
However for occupant safety, to reduce passing through it in the first few months
the risk of scalding, The School Premises for the natural inhibition to take place. It
Regulations require that the temperature should not be left empty for long periods.
at point of use should not be above
43oC for baths and showers and where Past outbreaks of legionnaires’ disease
occupants are severely disabled. This may have usually been associated with systems
be achieved by thermostatic mixing at the that have been neglected, or where the
point of use. It is also recommended that routine operation has changed. Frequent
hot water supplies to washbasins in monitoring of the operation of the system
nursery and primary schools are limited and factors encouraging rapid
to 43oC. This may be achieved by multiplication of bacteria are therefore
installing a thermostatic mixing valve vital control measures. Excessive periods
(TMV) close to the terminal fitting. of stagnation (in tanks or ‘dead legs’)
Valves meeting the requirements of the should be avoided, and storage tanks
Buildcert TMV scheme give assured levels must be maintained in a clean condition.
of scalding protection to either TMV2 Water cisterns should comply with
or TMV3 standards. The Water Supply (Water Fittings)
Regulations.Ref. 23
Because the organism thrives in warm
(but not hot) water, the length of piping GRP tanks usually contain biofilms
carrying hot and cold water (eg, after a therefore annual chlorination followed by
thermostatic mixing valve) must be kept cleaning is recommended. Chlorination
to an absolute minimum, certainly less of copper pipework should be avoided as
than 2 metres where possible. Where the it strips off the natural protection of the
final pipework supplying shower heads is pipe and can cause corrosion.
longer than this it should be regularly
pasteurised as a precautionary measure. Chlorination of hot and cold water
It is recommended that this is done every services should be done in accordance
time the showers are out of use for more with the concentrations and chlorination
than 5 days. Self draining shower heads times recommended in the ACOP.Ref: 29
can also be fitted as a precautionary
measure. Similarly, the length of pipes As sampling for legionella will often yield
feeding washbasin hot taps should be positive results, it is not advocated as a
minimised, especially with spray head routine measure because it can cause
taps which could generate an aerosol either unnecessary alarm and anxiety
containing legionella; point of use water to all concerned, or complacency and
heaters may be preferable to centralised relaxation of standards. Sampling is
hot water systems. expensive, and since no firm conclusions
can be drawn from the results, the
random sampling for legionella does not

30
Section 5 : Hot and cold water supplies

represent good value for money. The European Drinking Water Directive
CIBSE Technical Memorandum TM 13 came into force in December 1998.
recommends that a thermal pasteurisation Most of the new standards must be
regime is the most appropriate form of implemented by the end of 2003. Water
legionella control for hot and cold water within buildings is the responsibility of
systems.Ref : 24 On the other hand, the owner. The new maximum lead level
monitoring general water quality can of 10 microgrammes/litre is expressed in
provide a fair indication of system terms of an average weekly consumption.
conditions. This, together with a package
of other routine measures recommended Currently, there is no practical way of
by HSE, will draw attention to potential measuring this except through laboratory
problems as they develop. analysis. Monitoring of water supplies at
the dietetic tap will be required in schools
to demonstrate compliance with the
Directive. Further guidance is awaited.
Water Pollution
The Control of Pollution (Oil Storage) Up till around 1975 lead-based solders
(England) Regulations 2001 administered were used on copper pipework for
by the Environment Agency control drinking water supplies. This can lead to
secondary containment of oil storage breaches of the 10 microgrammes/litre
tanks dependant on a risk analysis. level therefore testing of copper systems
Bulk storage tanks greater than 200 litres of this age will be necessary in some areas.
supplying a generator or “day tank”
come within the scope of the Oil Storage The Drinking Water Inspectorate (DWI)
Regulations as the oil is being stored recommends the replacement of lead
)not used. pipes however if this is not feasible DWI
recommends that if water is left standing
in lead pipework for an extended duration
Lead Pipework that a volume is drawn off (for a non-
drinking or food preparation purpose)
Lead pipework for drinking water supplies
before consumption. Guidance can be
is a hazard. This is increased in areas with
found on the DWI website
plumbosolvent water, ie soft water,
(www.dwi.gov.uk).
particularly where the water is acidic.
In schools built before the early 1950s,
where there is a likelihood of the presence
of lead pipework, its extent should be
assessed and a programme drawn up for
its removal.

31
The School Premises Regulations Summary Sheet

These are the minimum environmental standards that (3) Each room or other space which has a heating
apply to all school buildings, both new and existing. system shall, if the temperature during any period
during which it is occupied would otherwise be
Acoustics
below that appropriate to its normal use, be
Each room or other space in a school building shall
heated to a temperature which is so appropriate.
have the acoustic conditions and the insulation against
disturbance by noise appropriate to its normal use. (4) In a special school, nursery school or teaching
accommodation used by a nursery class in a
school the surface temperature of any radiator,
Lighting including exposed pipework, which is in a
(1) Each room or other space in a school building - position where it may be touched by a pupil shall
not exceed 43 oC.
(a) shall have lighting appropriate to its normal
use; and
(b) shall satisfy the requirements of paragraphs Ventilation
(2) to (4). (1) All occupied areas in a school building shall have
(2) Subject to paragraph (3), the maintained controllable ventilation at a minimum rate of 3
illuminance of teaching accommodation shall be litres of fresh air per second for each of the
not less than 300 lux on the working plane. maximum number of persons the area will
accommodate.
(3) In teaching accommodation where visually
demanding tasks are carried out, provision shall (2) All teaching accommodation, medical
be made for a maintained illuminance of not less examination or treatment rooms, sick rooms,
than 500 lux on the working plane. isolation rooms, sleeping and living
accommodation shall also be capable of being
(4) The Glare Index shall be limited to no more than ventilated at a minimum rate of 8 litre of fresh air
19. per second for each of the usual number of people
Heating in those areas when such areas are occupied.

(1) Each room or other space in a school building (3) All washrooms shall also be capable of being
shall have such system of heating, if any, as is ventilated at a rate of at least six air changes an
appropriate to its normal use. hour.

(2) Any such heating system shall be capable of (4) Adequate measures shall be taken to prevent
maintaining the air temperature, at a height of condensation in, and remove noxious fumes from,
0.5 m above floor level, at the specified level, in every kitchen and other room in which there may
the areas set out in the Table below, when the be steam or fumes.
external air temperature is –1oC: Water supplies
Area Temperature oC (1) A school shall have a wholesome supply of water
for domestic purposes including a supply of
Areas where there is the normal level drinking water.
of physical activity associated with 18
teaching, private study or examinations (2) Water closets and urinals shall have an adequate
supply of cold water and washbasins, sinks, baths
Areas where there is a lower than and showers shall have an adequate supply of hot
normal level of physical activity because and cold water.
of sickness or physical disability 21
including sick rooms and isolation (3) The temperature of hot water supplies to baths
rooms but not other sleeping and showers shall not exceed 43oC.
accommodation
Drainage
Areas where there is a higher than (1) A school shall be provided with an adequate
normal level of physical activity (for
15 drainage system for hygienic purposes and the
example arising out of physical
general disposal of waste water and surface water.
education) and washrooms, sleeping
accommodation and circulation
spaces.

32
Standards for environmental conditions and energy conservation for new
school buildings summary sheet

The main provisions of BB87 (2003) to be used in A maintained illuminance at floor level in the range
conjunction with Approved Document Part L2, in 80 - 120 lux is recommended for stairs and corridors.
support of the Building Regulations, or quoted by Entrance halls, stairs, lobbies and waiting rooms
DfES as constructional standards are given below. require a higher illuminance in the range 175 - 250
lux on the appropriate plane.

The type of luminaires should be chosen to give an


Conservation of Fuel and Power
average initial circuit luminous efficacy of 65 lumens/
Energy efficiency rating circuit watt for the fixed lighting equipment within the
The designer of a school has three options in the building, excluding track-mounted luminaires and
design of a new school building. emergency lighting.

1. To use the elemental method as described in


In all other respects the lighting efficiency and controls
Section 1 of ADL2 2002 of the Building
should comply with ADL2 in support of the Building
Regulations, together with the advice contained
Regulations.
in the revised BB87.
2. To use the Whole Building Method described in External Lighting
BB87 (2003) to estimate the total energy It is recommended that all external lighting is provided
consumption of the building and achieve a carbon with lamps having an efficacy of at least 65 lumens per
performance rating of better than 5 kgC/m2 per circuit watt that are fitted with both time control and
year. daylight level photocell control.
3. To use the carbon emission calculation method as
described in ADL2 2002. This technique is Heating
advised for innovative or passive designs that will The heating system should be capable of maintaining
benefit from detailed whole building simulation the minimum air temperatures quoted in the School
procedures. Premises Regulations. The heating system should be
provided with frost protection.
Acoustics
See Building Bulletin 93 Section 1, which is quoted by Central heating systems should have appropriate
Approved Document Part E in support of Building controls complying with the requirements in ADL2
Regulations as a means of compliance for schools with 2002, in support of the Building Regulations.
Requirement E4 of the Building Regulations.
The air supply to and discharge of products of
combustion from heat producing appliances and the
Lighting
protection of the building from the appliances and
Where possible, priority should be given to design for their flue pipes and chimneys should comply with
daylight as the main source of light in working areas. Building Regulations, Part J, 2002.

The uniformity ratio (minimum/average daylight


Thermal performance
factor) of the daylight should be in the range 0.3 to
0.4 for side-lit rooms. Where spaces are top-lit, eg The fabric insulation should comply with the
atria, then higher uniformities should be expected recommended maximum values given in the
of the order of 0.7. ‘Elemental Method’ in Table 1 of section 1 of ADL2
2002 in support of the Building Regulations, 2002.
The uniformity ratio (minimum/average maintained
illuminance) of the electric lighting in teaching areas Vertical glazed areas (including clerestory or monitor
should be not less than 0.8 over the task area. lights) should not normally exceed an average of 40%
of the internal elevation of the external wall. However,
Teaching spaces should have views out except in where a passive or daylight design strategy has been
special circumstances. A minimum glazed area of adopted the percentage glazing may exceed 40%,
20% of the internal elevation of the exterior wall is provided the insulation of the rest of the building
recommended to provide adequate views out. fabric is increased to compensate for the increased heat
loss through the glazing or the heating plant carbon
intensity is traded up accordingly.

33
Standards for environmental conditions and energy conservation for new school buildings summary sheet

Horizontal or near horizontal glazing should not Hot and cold water
normally exceed 20% of the roof area. Cold water storage capacity in schools should not
exceed 25 litres per occupant.
Ventilation
It is recommended that in classrooms, ventilation All water fittings should be of a type approved by a
systems, whether natural or mechanical, are capable of WRC (Water Research Centre), and all installations
providing approximately 8 litres per second of fresh air should comply with the Water Supply (Water Fittings)
per person. Regulations 1999.

Spaces where noxious fumes or dust are generated may Where a temperature regime is used to reduce the risk
need additional ventilation. Laboratories may require of legionellosis, hot water storage temperatures should
the use of fume cupboards, which should be designed not be lower than 60oC. However, for occupant
in accordance with DfES Building Bulletin 88. Design safety, to reduce the risk of scalding, The School
technology areas may require local exhaust ventilation. Premises Regulations require that the temperature at
point of use should not be above 43oC for baths and
All washrooms in which at least 6 air changes per hour showers and where occupants are severely disabled.
cannot be achieved on average by natural means This may be achieved by thermostatic mixing at the
should be mechanically ventilated and the air expelled point of use. It is also recommended that hot water
from the building. Heat recovery fans can be used. supplies to washbasins in nursery and primary schools
are limited to 43oC.
During the summer, when the heating system is not
in operation, the recommended design temperature Particular attention should be given to the provision
for all spaces should be 24 oC with a swing of not of facilities to ensure the effective maintenance
more than +/- 4 oC. It is undesirable for peak air of systems.
temperatures to exceed 28 oC during normal working
hours but a higher temperature for 80 hours during Unvented hot water storage systems should comply
the summer term is acceptable. with Building Regulations Part G3, 1992.

34
References

1. See the Regulatory Information section of the 12. CIBSE Applications Manual AM10: Natural
Department for Education and Skills’, Schools Ventilation in Non-Domestic Buildings, 1997,
Buildings and Design Unit’s website at ISBN 0 900953 77 2, £45.
www.teachernet.gov.uk/schoolbuildings for
copies of The School Premises Regulations, and 13. BS 5925: 1991 Code of Practice for Ventilation,
the Constructional Standards for Schools (to be Principles and designing for natural ventilation.
revised) and guidance on their application.
14. CIBSE Code for Lighting, 2002,
2. Approved Document F (Ventilation) in support of ISBN 1 903287 22 7, available on CD-Rom or as
the Building Regulations, printed version, see www.cibse.org
Department of the Environment and Welsh
Office, 1994, ISBN 0 11 752932 X, £4.50. 15. DfEE Building Bulletin 90,
Lighting Design for Schools,
3. Approved Document L2 (Conservation of fuel ISBN 0 11 271041 7,
and power) in support of the Building The Stationery Office, 1999, £22.95.
Regulations, Department of the Environment and
Welsh Office, 2002, ISBN 0 11 753610 5, £15. 16. BRE Information Paper IP6/96, People and
lighting controls.
4. The Education (School Premises) Regulations
1999, SI 1999 No. 2, The Stationery Office, 17. See www.serraglaze.redbus.co.uk
1999, ISBN 0 11 080331 0, £3 and on website
www.legislation.hmso.gov.uk/si/si1999/ 18. The Institution of Lighting Engineers, Guidance
19990002.htm notes for the reduction of light pollution,
1994, available from ILE,
5. Building Bulletin 93, Acoustic Design of Schools, Lennox House,
DfES, The Stationery Office, 9 Lawford Road,
ISBN 0 11 271105 7, to be published in 2003 Rugby,
and availble as a download from Warwickshire, CV21 2DZ.
www.teachernet.gov.uk/acoustics
19. RNIB/GBDA Joint Mobility Unit,
6. CIBSE Guide J : Weather, solar and illuminance 224 Great Portland Street,
data (CD-Rom), 2002, £176.25, London,
see www.cibse.org W1N 6AA,
Tel: 0171 388 1266,
7. CIBSE Guide B18 - Installation and Equipment Fax: 0171 388 3160.
Data, 1988, see www.cibse.org
20. The Partially Sighted Society,
8. CIBSE Guide A - Environmental Design, 1999, 62 Salusbury Road,
see www.cibse.org London,
NW6 6NS,
Tel: 0171 372 1551.
9. Department for Education, Building Bulletin 73,
A guide to energy efficient refurbishment,
21. Building Sight, Peter Barker, Jon Barrick,
HMSO, 1991, ISBN 0 11 270772 6, £8.50.
Rod Wilson, RNIB, ISBN 011 701 993 3,
HMSO, 1995, £35.
10. DfEE, Building Bulletin 88, Fume Cupboards in
Schools, ISBN 0 11 271027,
The Stationery Office, 1998, £14.95. 22. The visual environmeent for display screen use,
LG03: 1996 and addendum 2001,
11. CIBSE Technical Memorandum 23: Testing ISBN 0 900953 71 3.
buildings for air leakage, 2000, £30,
see www.cibse.org

35
References

23. The Water Supply (Water Fittings) 27. CIBSE Guide Public Health Engineering,
Regulations 1999 Section 2: ISBN 0 900953 87 X.
Schedule 1: Fluid Categories
Schedule 2: Approved Document.
28. Workplace (Health, Safety and Welfare)
See also the Water Regulations Advisory Scheme
Regulations 1992, Guidance for the Education
publication, The Water Fittings and Materials
Sector, Leaflet IAC(L)97, HSE Books.
Directory available from the Water Regulations
Advisory Scheme, ISSN 0954-3643.
29. Health and Safety Executive, HSC Approved code
of practice and guidance, L8, Legionnaires’
24. Chartered Institution of Building Services
disease - The control of legionella bacteria in
Engineers (CIBSE), Technical Memorandum 13,
water systems, HSE Books, 2000.
2002, Minimising the risk of Legionnaires disease,
ISBN 1 903287 23 5.
30. Ionisation water treatment for hot and cold water
services, BSRIA Technical Note TN 6/96,
25. Guide to Legionellosis, Temperature
N.L.Pavey,
measurements for hot and cold water services,
ISBN 0 86022 438 4.
BSRIA Application Guide AG4/94, N.L. Pavey,
ISBN 0 86022 3. Legionella and Building Services,
G.W.Brundrett,
Buttersworth Heinemann,
26. BS 6700: 1997, British Standard Specification for ISBN 0 7506 1528 1.
Design, installation, testing and maintenance of
services supplying water for domestic use within
buildings and their curtillages,
ISBN 0 580 26817 9.

36
Bibliography – further reading

Building Bulletin 83, Schools BRE Digest 457,


Environmental Assessment Method The Carbon Performance
(SEAM), The Stationery Office, 1996, Rating for Offices.
ISBN 0 11 27099206, £14.95.
DfEE Building Bulletin 77, Designing for
Building Bulletin 90. Lighting Design pupils with special educational needs:
for Schools. ISBN 0 11 2710417, special schools, HMSO 1992,
TSO 1999, £22.95 ISBN 0 11 270796 3, £14.95

CIBSE Lighting Guides: BRE Report BR262 Thermal Insulation:


The visual environment in lecture, Avoiding risks, Building Research
teaching and conference rooms, Establishment, 1994,
LG05:1991. ISBN 0 11 701792 2, £16.50.

The outdoor environment, Water Regulations Advisory


LG06: 1992, ISBN 0 900953 53 5. Scheme publications:

The Water Fittings and Materials


Daylighting and window Design,
Directory.1
LG10:1999,
ISBN 0 900953 98 5. • Reclaimed Water Systems, Information
about installing, modifying or
Energy efficient lighting in schools, maintaining reclaimed water systems,
BRECSU-OPET, Building Research Information and Guidance Note
Establishment. 9-02-04, 1999.
• Precautions against freezing of water in
Department for Education, Building
plumbing systems, Information and
Bulletin 79, Passive Solar Schools, a
Guidance Note 9-02-02, 1998.
design guide, HMSO 1994,
ISBN 0 11 270876 5, £19.95. • Conservation of Water an IGN for
Architects, Designers and Installers,
Good Practice Guide 16 - Guide for Information and Guidance Note
installers of Condensing Boilers in 9-02-03, 1999.
Commercial Buildings - Energy Efficiency
Office Best Practice Programme, 1990. The Water Regulations Advisory
Scheme,
BRE IP 12/94, Thermal Bridges, Fern Close,
Assessing condensation risk and heat Pen-y-Fan Industrial Estate,
loss at thermal bridges around openings, Oakdale,
Building Research Establishment. Gwent, NP11 3EH
Tel: 01495 248454
BS 6880: 1988 Code of practice for low
Fax: 01495 249234
temperature hot water heating systems
of output greater than 45 kW. E-mail: wrcetc@wrcplc.co.uk
Note
Website: www.wras.co.uk 1 WRAS are producing a
CIBSE Applications Manual AM1:1985, water supply industry
Automatic controls and their implications plumbing installations
for systems design. guide for schools,
colleges & further and
higher education premises
BRE Digest 399 Natural Ventilation on the design and
non-domestic buildings, 1994, management of water
ISBN 0 85125 645 7. supplies in schools.

37

You might also like