You are on page 1of 1

[APPLICABLE MODEL FROM COMPUTER]

AIR-COOLED TYPE WATER CHILLER-Screw Type-H Series Heat Recovery


MODEL NUMBER RCUG200AHYZ1-HR
Nominal cooling capacity kW 544(12/7 & DB35)
Cooling capacity(design) kW 544
Standard heat recovery capacity kW 108 (12/7&DB35&30/55)
Heat Recovery capacity (design) kW 108
Hot water flow rate(design) m3/h 3.7 (25Deg.Ctemp.diff)
EVAPORATOR
Type Shell-and-Tube, Dry Expansion Type
Material shell/tube Steel/Copper
Insulation Polyethylene(25mm)
Chilled water temperature(outlet/inlet) Deg.C 7/12
Chilled water flow rate m3/h 93.6
Evaporator pressure drop kPa 80
Specific Fouling Factor m2.Deg.C/kW 0.018
CONDENSER
Type(Material) Cross Fin Type(Aluminium/Copper)
Condenser air inlet temperature Deg.C 35
CONDENSER FAN
Type(Material) Direct drive Propeller Fan(Aluminium Alloy)
Quantity 12
Revolutions 50Hz-r/min. 960
FAN MOTOR
Type Drip-Proof Enclosure
Quantity 12
Starting method Direct-On-Line Starting
Number of poles 6
Insulation class E
Input power(motor) kW 1.1
COMPRESSOR
Type Semi-Hermetic Screw Type
Model ASCCW-60Z
Quantity 3
Revolutions 50Hz-r/min. 2880
Circuits 3
Refrigerant R407C
Capacity control 100~15(5),0
%
Motor type Three-Phase asynchronism
Starting method Star Delta
Number of poles 2
Insulation class F
Output power(motor) kW 45
ELECTRICAL DATA
Power supply V/Phase/Hz 380/3/50
Unit voltage(Max/Min) V 418/342
Maximum unit current A 543
Starting current(Comp.No.1-) A 178/178/178
Running current(Comp.) A 321
Input power(Comp.+fan) kW 192.3
DIMENSIONS AND WEIGHT
Depth/Width/Height mm 6,590/2057/2170
Net weight kg 4990
NOISE
The measuring point is 1 m from the centre of the machine's surface and 1.5 m from floor level.
Octave band (Hz) 45-90 90-180 180-35 355-71 710-140 1400-280 2800-560 5600-1120
dB(A) 72.7 53.1 57.7 66.7 67.6 68.8 67.5 47.2 42.6
OPERATING SPACE
Front/rear side of unit(with electric box side) mm 900
Right,left and back of unit(without electric box side) mm 1200,1200&100

* The heat recovery capacity shown above is based on:hot water inlet/outlet
temperature 30Deg.C/55Deg.C;
* Hot water outlet temperature range:30Deg.C to 55Deg.C(max.60Deg.C);
* The unit shall be tested in the factory before shipment.

Note:Specifications in this sheet are just for reference only.Hitachi shall


reserve right to change specification in this sheet without any notice.