The number of counts, associated with corona discharges In Fig. 4 the count number values gathered from all performed
occurring on the long rod insulator was registered, while the trails are presented in dependence from the supply voltage value.
supply voltage value was decreased. The performed analyses One can recognize a characteristic exponential growth of the cont
consider estimation of dependency of the voltage value on the number with accordance to rising voltage value. This dependence
number of discharges, generated on the object. A single was confirmed by regression analysis using Gauss-type model
measurement, for each voltage value, lasted for 3 minutes. given by eq. (1). In Fig. 4 we can also recognize two outliers: one
in the positive and the other in the negative direction. These values
were taken in the analysis, but had not a significant impact on the
achieved result.
The applied Gauss-type model is given by eq. (1). The estimates
were calculated using a data set containing arithmetical means
over all data samples gathered for each voltage value. The
gathered result is depicted in Fig. 5.
2
tB
C
GaussModel (t ) A exp (1)
Fig. 1. The object under study and UV camera for measurement of optical signals
R2 1 0.9986 despite good correlated trend (Fig. 5), not always are the particular
t yt yt
2
data samples normally distributed (using Normal Distribution).
RMSE t yt ~
yt / n m
2
619
Fig. 6. Example graph showing histogram and estimated probability distribution over
dataset recorded during trail by constant supply voltage equal to 16.8 kV
Fig. 5. The measurement data in form of arithmetical mean values and the estimated
Gauss-type model
1
A B C 2
2π
The goodness of the applied model was evaluated using the square
of the correlation coefficient r, the so called determination
coefficient (2).
2
r
i yi y ~yi ~y
, (2)
y y 2 ~
i i
~
i yi y
2