Data sheet

ECA 87
RS 232 remote control and data log for ECL Comfort 200/300

Application The ECA 87 RS 232 remote control and data


log module provides the user with a protected
gateway for the ECL Comfort 200/300,
accessible via modem connection or directly.

The ECA 87 module enables:


- Remote monitoring and control via RS 232
communication.
- Data logging.
- Alarm notification of external recipients, if
supported by the ECL Comfort application*.

* Alarm monitoring is only possible with ECL Comfort 300


version 1.08 and later versions.

Principle of operation The ECA 87 module enhances remote access The data logging capability of the ECA 87
to the ECL Comfort by adding an RS 232 module allows logging of:
connection, making it possible to monitor - ECL Comfort parameters.
and control the ECL Comfort 200/300 from - The state of all relay outputs.
an external device. When the ECA 87 module
is installed, other modules cannot use the The maximum number of parameters that can
rear slot, and the existing RS 232 port on the be logged is 15.
controller's front panel cannot be used.
The sampling time can be set in fixed inter-
The ECA 87 module uses a character-based vals between 5 seconds and 2 hours**.
interface allowing it to communicate with Values in the data log memory are preserved
any terminal emulation program, e.g. Hyper- during reset and power-down operations. The
Terminal. The interface comprises two ECA 87 will restart the data log after reset and
communication protocols, one interactive and power-down operations, recording the time
one CRC (cyclic redundancy check) encoded. and date of the restart.
In addition to the two protocols, there are
two response formats, a standard and a short When the ECA 87 module is used with an ECL
format. The standard format includes "human Comfort 300, version 1.08 or later versions, it
readable" text strings, e.g. Done. The short can be set to report alarms, provided that this
format uses numerical return codes, e.g. #0100. is supported by the application. The ECA 87 can
establish a dial-up connection to a user-defined
By default, the ECA 87 module supports the telephone number of an alarm recipient. The
LASAT Safire 560 Voice modem. However, it is alarm message can include an ID number
possible to change the modem initialisa-tion showing the identity of the calling ECL Comfort.
strings. This makes it possible to use other
Hayes compatible modems, including GSM ** With a sampling interval of 5 seconds, a maximum of 5
parameters can be logged.
modems.

Monitoring and control via RS 232 communi-


cation allows a remote user to check and
change the performance of the ECL Comfort.
Thus it becomes possible to monitor and
control multiple ECL Comforts individually,
from one location.

DH-SMT/DK VD.BB.E1.02 © Danfoss 12/2007 


Data sheet ECA 87, RS 232 remote control and data log for ECL Comfort 200/300

Ordering Type Description Code No.


ECA 87*** RS 232 remote control and data log 087B1160
Modem cable RS 232 PC modem cable 1.5 m 087B1171
PC cable RS 232 PC cable 1.5 m 087B1172

*** Note that code no. 087B1160 does not include a PC cable
or modem cable

Technical data Storage temperature -40 oC - 70 oC


Ambient temperature 0 - 50 oC
Installation Rear slot of ECL Comfort controller
Module weigth 12 g
ECA 87 connection type JST S10B-PHDSS
PC cable length maximum / type 1.5 m max. / DB-9 female
Modem cable length maximum / type 1.5 m max. / DB-25 male
Communication set-up 9600 baud, 8 data bits, 1 stop bit, even parity
Default modem LASAT Safire 560 Voice
Modem initialisation strings 2 x 24 characters
Alarm telephone number 24 characters
Alarm ID number 15 characters
Data log memory 130,000 data values
Data log sample time / accuracy 5 seconds - 2 hours / ± 2%
Maximum log parameters 15 parameters

Pin connection JST connector Description - input / output


Pin 1 TX - output
Pin 2 GND - ground
Pin 3 RTS - output
Pin 4 DTR - output
Pin 5 RX - input
Pin 6 DCD -input
Pin 7 RI - input
Pin 8 DSR - input
Pin 9 No connection
Pin 10 CTS - input

Supported ECL Comfort ECL Comfort Remote control + data logging Remote control + data logging + alarm notification
controllers ECL Comfort 200 As of version 1.04 None
ECL Comfort 300 As of version 1.04 As of version 1.08

 VD.BB.E1.02 © Danfoss 12/2007 DH-SMT/DK