Data sheet

Automatically balanced combination valves


AB-QM

Description

AB-QM valve is an automatic balancing valve AB-QM valve equipped with an actuator is a
- flow limiter. control valve with full authority and automatic
Typical applications are: Automatic (adjustable) balancing valve - flow limiter.
flow limitation on terminal units (fan-coils, chilled Typical applications are: Temperature control and
ceilings, Air-handling units..) or branches. It is permanent automatic balancing on terminal units
recommended to be used in constant flow systems. (fan-coils, chilled ceilings, Air-handling units..).

Benefits  “Plug and Play” even when installation is


 The AB-QM is able to control the temperature not yet completely finished. For example
at low loads and is equally stable all through when some floors are already occupied
the range. while construction is still going on at other
 All changes in the available differential floors, the occupied floors are already fully
pressure are corrected by the pressure functional and balanced.
controller. Therefore, less disturbances
for temperature control and further less Simplifications
movements from actuator.  Flow limitation is achieved by setting the valve
 AB-QM offers full flexibility of adjustment
to required flow - Set & Forget.
 Flow is the only parameter to be considered,
– AB-QM valves can be set to a precise design
value – they allow full control over the real so easy and fast valve selection.
 Maximal setting of AB-QM corresponds
conditions in the system.
 Due to the membrane design the valves are
with the maximal flowspeed through that
pipe dimension according to international
not susceptible to blockage.
 Always the right flow, so no complaints from
standards.
 Easy troubleshooting
endusers or excessive energy consumption
 No control ratio calculation
 Because the AB valve covers two functions
 No authority calculation
– Balancing & Control - the installment costs
 Commissioning is a matter of adjusting the
are halved
 Measuring nipples (optional) allow
valve without using specialised equipment or
highly educated staff.
optimisation of the pump’s energy
 Compact design allows instalment where
consumption.
 100% built in control valve authority allows
only limited space is available, for example in
standalone fan-coils.
lower pump head than traditional setup, thus
minimizing energy consumption.
 Because of the automatic flow limiting
function, commissioning costs are
nonexistent.
 Easy adjustability allows late change of design
flows without high costs.

SIBC VD.A2.W4.02 © Danfoss 10/2005 1


Data sheet Automatically balanced combination valves AB

Applications - variable flow systems

Air handling unit (AHU) / fan coil (FCU)

An AB-QM with an actuator can be used as a not influencing each other. The flow setting is
combined flow limiter and control valve with very simple. Just set the required flow for the
full authority for an AHU (Air Handling Unit). The AHU direct at the AB-QM. There is no special
AB-QM ensures the required flow on every AHU method needed for balancing the whole
and simplifies the hydronic balancing of the systems. This means a lot of savings in working
system. Because of the integrated differential hours. Not to forget the combination of several
pressure controller the control valve always has functions in one valve body means less valves
100% authority which means that partial load and installation work. For temperature control
in the system has no influence on temperature AB-QM can be equipped with different actuators
regulation as it will have with normal control (on/off, 3-point, 0 -10Volt) as required.
valves. By installing AB-QM the whole system
is divided in independent control loop zones

Chilled ceiling

AB-QM in systems with chilled ceilings are used


to achieve the required flow in the system and to
control the temperature. An AB-QM is installed
at every chilled ceiling limiting the flow. The
integrated control valve is used for temperature
control by mounting an actuator. Different types
of actuators can be used.

2 VD.A2.W4.02 © Danfoss 10/2005 SIBC


Data sheet Automatically balanced combination valves AB

Applications
- constant flow systems

AB-QM can be used as an automatic flow Alternatively the system can be changed into a
controller if a system with an AHU/fan coil is run system with variable flow because AB-QM is also
with constant flow (system with 3-way valve). able to work as a control valve with full authority
There is no special balancing method needed. which means no problems with partial load.
The flow can be set directly at the AB-QM.

In a one pipe heating system the AB-QM can be


installed as an automatic flow controller in every
riser. The AB-QM limits the flow to the set value,
thus automatically achieving hydronic balance in
the system.

There are numerous applications in which AB-QM can be used. In principle every time you need an automatic
flow controller or a control valve with full authority it can be used. For example systems with heating/cooling
with concrete core activation or small substations.

SIBC VD.A2.W4.02 © Danfoss 10/2005 3


Data sheet Automatically balanced combination valves AB

Ordering AB-QM
Qmax. External External
AB-QM DN Code No. AB-QM Code No.
(l/h) thread thread
10 LF 150 003Z0251 003Z0261
G½A G½A
10 275 003Z0201 003Z0211
15 LF 275 003Z0252 003Z0262
G¾A G¾A
15 450 003Z0202 003Z0212
20 900 G1A 003Z0203 G1A 003Z0213
25 1700 G 1¼ A 003Z0204 G 1¼ A 003Z0214
AB-QM can not be upgraded to AB-QM
with nipples! 32 3200 G 1½ A 003Z0205 G 1½ A 003Z0215

Set-pack (one MSV-M and one AB-QM without nipples)


External thread
Type DN Qmax. (l/h) Code No.
ISO 228/1
10 275 G½A 003Z0241*
15 450 G¾A 003Z0242
20 900 G1A 003Z0243

* Includes MSV-M DN15 with external


25 1700 G 1¼ A 003Z0244
thread G ¾A 32 3200 G 1½ A 003Z0245

Accessories & spare parts


Comments
Type Code No.
To pipe To valve
Union connection R 3/8 DN 10 003Z0231
(1 pcs.)
R 1/2 DN 15 003Z0232
R 3/4 DN 20 003Z0233
R1 DN 25 003Z0234
R 1 1/4 DN 32 003Z0235
Welded nipple Weld. DN 15 003N5090
(2 pcs.)
Weld. DN 20 003N5091
Weld. DN 25 003N5092
Weld. DN 32 003N5093
Tailpieces for soldering 12x1 mm DN 10 065Z7016
(2 nuts, 2 gaskets,
2 soldering nipples 15x1 mm DN 15 065Z7017

Locking ring 003Z0236


Shut-off & protection piece (max. closing pressure 16 bar) 003Z0230
Shut-off - plastic (max. closing pressure 1 bar) 003Z0240

Combinations AB-QM with electrical actuators


Valve type Stroke TWA-Z** ABNM-Z AMV(E)-H 01/02
(mm)
Recommended ordering code numbers
(for details refer to data sheets for these actuators)
082F1226 082F1094 082H8001
10.4 ±0.3

NC, 230 V Thermal actuator AMV 01/24 V,24 s/mm,


24 V (0 - 10 V) 3-point control
082F1072 082H8003
Adapter for AB-QM AME 01/24 V,24 s/mm,
(M30 x 1.5) 0 - 10 V
Closing point (measure)
AB-QM DN 10 - 20 2.25   
AB-QM DN 25 - 32 4.50 * * 
* up to 60 % of Q max
** Please be aware that only this type of TWA actuator is to be used with AB-QM

Closing pressure for all actuators: 6 bar.

4 VD.A2.W4.02 © Danfoss 10/2005 SIBC


Data sheet Automatically balanced combination valves AB

Technical data 10 15
Nominal diameter DN 10 15 20 25 32
Low Flow Low Flow
Qmin (20%) 30 55 55 90 180 340 640
Ranges l/h
Qmax (100%) 150 275 275 450 900 1700 3200
Diff. pressure (p₁ - p₃) 0.16 - 4.0 bar; (16 - 400 kPa) 0.2 - 4.0 bar
Pressure stage PN 16
Control range > 1:50
Control valve’s characteristic Linear
Leakage acc. to standard IEC 534 max.0.01 % of k v at 250 N

Flow medium Water and water mixtures with secondary coolants (like glycols)*
for closed heating and cooling systems
Medium temperature °C -10 ... +120
Stroke mm 2.25 4.5
Connection external thread (ISO 228/1) G ½” G ½” G ¾” G ¾” G 1” G 1¼” G 1½”
actuator M30 x 1.5
Material In the water Valve bodies Brass (CuZn40Pb2 - CW 617N)
Membranes and O - rings EPDM
Springs W.Nr. 1.4568,W.Nr. 1.4310
Cone (Pc) W.Nr. 1.4305
Seat (Pc) EPDM
Cone (Cv) CuZn40Pb3 - CW 614N
Seat (Cv) CuZn40Pb2 - CW 617N
Screw Stainless Steel (A2)
Flat gasket NBR
Sealing agent Dimethacrylate Ester
(only for valves with measuring nipples)
Out of the water Plastic parts POM
Insert parts and outer screws CuZn39Pb3 - CW 614N;
W.Nr. 1.4310; W.Nr. 1.4401
* according suitability and usage especially in not oxygen tight systems please mind the instructions given by the coolant
producer

Operation principle The AB-QM is a control valve combined with a


differential pressure controller. The differential
pressure controller maintains a constant pressure
over the control valve independent of varying STROKE
conditions in the installation. Because of this 100%
construction the flow is automatically limited to
a specified value and the control valve has an 80%
authority of 100%.
Q=kv[%]* P2 P3
Flow limitation 50%
If you have a constant differential pressure across
an orifice with a known resistance (kv value) you
can determine the flow with the formula:
Q � kv � �p
Because the AB-QM limits the differential Q,Kv
pressure (Δp) across the control valve to a 50% 80% 100%
constant level it follows that the flow through
the AB-QM is also limited.To function properly
the AB-QM needs a pressure difference of at
least 16 kPa. By limiting the stroke of the control
valve, the maximal flow through the valve can be
adjusted.
If the kv-value of the control valve is halved, the
flow is also halved. Because the AB-QM has a
nearly linear chracteristic to have half the flow
you need half the stroke (see figure 1).

SIBC VD.A2.W4.02 © Danfoss 10/2005 5


Data sheet Automatically balanced combination valves AB

Operation principle Authority As an example we take two valves in a


(continued) The valve authority can be defined as: The normal HVAC system, one close to the pump
resistance across the fully opened control valve, (position 1) and the most distant valve (position
divided by the total resistance in the system 2). Both valves have the same differential
(valve, pipes, heat exchanger etc.). pressure potential (the pump head) but the
pressure drops between:
Rvalve - Control valve (abrivated as CV),
A�
Rvalve � Rsystem - balancing valve (abrivated as BV) and
- other elements (abrivated as OT; such as pipe,
Usually the authority should be 0,3 (30%) as terminal units ect.)
high as possible to guarantee sufficient control are distributed differently. With the valve closer
quality. The resistance in the sytem is variable to the pump the pressure drop in the pipes
because it depends on the flow. If the flow (OT) is much smaller. The differential pressure
is reduced, the resistance in the system also controller (BV) ensures however that the working
drops. Normally the control valve would have to conditions for both control valves (CV) are the
compensate for this by closing even further, thus same.
causing a distortion in the valve characteristic.
Because the AB-QM has a built in differential If we look at a situation where we need only
pressure controller that keeps the differential 20% , can see that the pressure drop in the
pressure across the control valve constant, the pipes (OT) becomes smaller when the flow is
effect of this decrease is compensated. It is decreasing.This effect is much bigger for the
therefore possible to assume that Rsystem is distant valve because the pressure drop in
zero. The formula then becomes: the pipes (OT) is bigger to begin with. The
differential pressure controller (BV) compensates
Rvalve
A� � 1 �100% � for the difference and ensures identical working
Rvalve conditions for both control valves across the
total range. If you compare that with a situation
The AB-QM therefore always automatically with traditional balancing valves you can see
ensures 100% authority which provides stable that, because the balancing valve is static and
control and therefore increase confort and saves doesn’t react to the system conditions, the
time consuming calculations to check the valve pressure drop across the control valve increases
authority. significantly which puts the control valve (CV)
to a challenge to provide comfort and stable
temperature control.

position 2

P P
CV CV
BV

BV
position 1 OT

OT
Q Q

P P P P
position 1 position 2 position 1 position 2
CV CV
CV CV
BV
BV

BV
BV
OT OT

OT OT
Q Q Q Q
20% of Design 20% of Design 20% of Design 20% of Design
design flow flow design flow flow design flow flow design flow flow
P P
pressure drop in a system with AB-QM pressure drop in a system with traditional valve set
CV CV
(manual balancing valve + control valve)
BV

BV
OT
6 VD.A2.W4.02 © Danfoss 10/2005 SIBC
OT
Q Q
Data sheet Automatically balanced combination valves AB

Design

5 2
3

6 4

1. Stuffing box
2. Spindle
3. Plastic ring
4. Control valve’s cone
5. Membrane
6. Main spring
P2 P3
7. Hollow cone
(pressure controller)
P1
8. Vulcanized seat
(pressure controller)

P2-P3
P1-P3

Function: 1. Differential pressure controller BV 2. Control valve CV


The AB-QM valve consists of The differential pressure controller maintains a The control valve has a linear characteristic. It
two parts: constant differential pressure across the features a stroke limitation function that
1. Differential pressure control valve.The pressure difference (p2-p3) allows adjustment of the Kv value. The
controller on the membrane is balanced with the force percentage marked on the scale equals the
2. Control valve of the spring. Whenever the differential pressure percentage of 100% flow marked on the pointer.
across the control valve changes (due to a Changing the stroke limitation is done by lifting
change in available pressure, or movement of the blocking mechanism and turning the top of
the control valve) the hollow cone is displaced to the valve to the desired position, showed on the
a new position which brings a new equilibrium scale as a percentage. A blocking mechanism
and therefore keeps the differential pressure at a automatically prevents unwanted changing of
constant level. the setting.

SIBC VD.A2.W4.02 © Danfoss 10/2005 7


Data sheet Automatically balanced combination valves AB

Sizing Example 1: Variable flow system Example 3: Sizing AB-QM according pipe
dimension
Given:
Cool requirement per unit : 1000 W Given:
Flow temperature in the system: 6 °C Flow in system 1, 4 m3/h (1400 l/h = 0,38l/s),
Return temperature in the system:12 °C pipe dimension DN 25 mm

Required - control and balancing valves: Required - automatic flow limiter:


AB-QM and actuators type for BMS system. AB-QM and presetting.

Solution: Solution:
Flow in the system: Q (l/h) In this case we can selected AB-QM DN 25 mm
Q = 0,86 x 1000 / ( 12-6 ) = 143 l/h with Qmax = 1700 l/h

Selected: In this case it will be recommended to check


AB-QM DN 10 mm with Qmax = 275 l/h the maximum velocity in the pipe. For this we
presetting on 143 / 275 = 0,52 = 52 % of calculate velocity in the pipe for condition:
maximum opening. DN 25 mm – Di 27,2 mm
Actuators: AMV 01 - 24 V
Dimension and condition acceptable, veloscity
Remarks: below 1,0 m/s.
required minimum differential pressure across
the AB-QM DN 10 - 16 kPa. Preseting on the valve AB-QM DN 25 mm
1400 / 1700 = 0,82 = 82 % of maximum opening.

Example 2: Constant flow system Remarks:


required minimum differential pressure across
Given: the AB-QM DN 25 - 16 kPa.
Cool requirement per unit : 4000 W
Flow temperature in the system : 6 °C
Return temperature in the system : 12 °C
Q[l/h]
Required - automatic flow limiter: 3500
AB-QM and presetting.
3200
Solution:
Flow in the system : Q (l/h)
3000
Q = 0,86 x 4000 / ( 12-6 ) = 573 l/h

Selected:
AB-QM DN 20 mm with Qmax = 900 l/h
2500
presetting on 573 / 900 = 0,64 = 64 % of
maximum opening.

Remarks:
required minimum differential pressure across 2000
the AB-QM DN 20 - 16 kPa.
1700

1500

1000
900

640
500 450

275 340
150
180
55 90
0 30
DN10LF DN10 DN15 DN20 DN25 DN32
DN15LF

8 VD.A2.W4.02 © Danfoss 10/2005 SIBC


Data sheet Automatically balanced combination valves AB

Pump optimising / Trouble


shooting

Blue

Red

P2-P3

Pump optimization
Q Q=const. Q=const.

P2-P3

P2 P3
P1

P2-P3
P1-P3

P1-P3
16kPa 400kPa
(20kPa)

The AB-QM features measuring nipples It can also be used to optimize the pump head.
that allow measuring of the pressure difference The pump head can be decreased until no more
(p2-p3) across the control valve. If the pressure than the minimal required pressure (7-14 kPa)
difference exceeds certain value (7-14 kPa) it is available on the most distant valve (in terms
means the differential pressure controller is of hydronic). This optimal point is to be found
operational and the flow limitation is achieved. when proportionality between pump head and
The measuring function can be used to verify if measured differential pressure cease to exist.
enough pressure difference is available and thus Verifying the pressure can be done by using a
verify the flow. Danfoss PFM 3000 for example (for more details
please refer to AB-QM Tech Notes VN.A3.N1.02).

Presetting The calculated flow can be adjusted easily


without using special tools. 100% 10%

To change the presetting: 50 60 50 60

70
70

40
40

- Remove the blue protective cap or the


80
80

30
30

mounted actuator. 90 90
)
)

(%
(%

0 0
100 2 100 2
- Raise the grey plastic ring and turn to the new Red
presetting.
- Release the white plastic ring and the
presetting is locked.

The presetting scale indicates a values from


100% flow to 0% closed.

Counter clock wise turning would increase the


flow value while clock wise would decrease it.

When valve is set to 80% or more the red ring


(below “DN max flow “ sign) becomes visible.

If the valve is a DN 15 then the max flow


= 450 l/h =100% presetting. To set a flow of 270
l/h you have to set: 270/450 = 60%.

Danfoss recomends a presetting/flow from 20%


to 100%. Factory presetting is 100%.

SIBC VD.A2.W4.02 © Danfoss 10/2005 9


Data sheet Automatically balanced combination valves AB

Service The valve features a service function that allows Unwanted change of the setting is provided by
changing of the “stuffing box (code 065F0006)” locking ring (code 003Z0236) which is inserted
under water pressure. in the groove below the scale. The locking ring
Valves are equipped with plastic shut-off would not allow one to lift the grey plastic ring
mechanism that is to be used for isolating thus no change of the setting is possible.
function up to 1 bar differential pressure. When
closing against higher differential pressure
please use accessory - shut-off & protection
piece (003Z0230) or set the value to 0%.

Installing AB-QM valve is mono-directional meaning that


the valve operates when arrow on the valve body
is aligned with flow direction. When this rule is
disobeyed the valve acts like variable orifice that
cause water hammer at sudden closing when
available pressure has increased or valve have
been set to lower value.

In case when system condition allows backflows


it is strongly recommended to use backflow
preventer in order to avoid possible water
hammer that can damage the valve as well as
other elements in the system.

10 VD.A2.W4.02 © Danfoss 10/2005 SIBC


Data sheet Automatically balanced combination valves AB

Dimensions
TWA-Z AMV / AME

L1 L2 L3 H1 H2 H3 H4 b Weight
Type mm mm mm mm mm mm mm ISO 228/1 kg
AB-QM DN 10 53 36 79 20 73 105 140 G½A 0.38
AB-QM DN 15 65 45 79 25 75 110 145 G ¾A 0.48
AB-QM DN 20 82 56 79 33 77 115 150 G1A 0.65
AB-QM DN 25 104 71 79 42 88 130 165 G 1¼ A 1.45
AB-QM DN 32 130 90 79 50 102 145 180 G 1½ A 2.21

SIBC VD.A2.W4.02 © Danfoss 10/2005 11


Data sheet Automatically balanced combination valves AB

Danfoss A/S Danfoss Trata d.o.o.


Comfort Division Jožeta Jame 16, P.O.B. 4820
Hårupvænget 11 1210 Ljubljana - Šentvid
Hårup Slovenia
DK-8600 Silkeborg Tel.: +386 1/58 20 200
Denmark Fax: + 386 1/51 99 824
Tel.: +45 74 88 80 00
Fax: +45 74 88 81 00
http://www.hydronicbalancing.com http://www.danfoss-trata.si