Professional Documents
Culture Documents
1. A single circuit 50 Hz, 3-phase transmission line has the following parameters per km:
R=0.2 ohm, L=1.3mH and C=0.01 µ F. The voltage at the receiving end is 132 KV. If
the line is open at the receiving end, find the rms value and phase angle of the following:
(a) The incident voltage to neutral at the receiving end (reference) .
(b) The reflec ted voltage to neutral at the recei ving end.
(c) The incident and reflected voltages to neutral at 120 km from the receiving end.
132 × 1000
The receiving end line to neutral voltage V = √3 = 76200 volts
r
Vr + I r Zc
2
Since, it is no load condition, Ir = 0
Vr 76200
Incident voltage = = = 38100 volts
2 2
(b) Similarly, the reflected voltage to neutral at the receiving end
Vr −I Z r c Vr
= = 38100 volts
2 2
(c) The incident voltage at a distance of 120 km from the receiving end
Vr+ = V r exp(αx)exp(jβx)
Vr+ = 76.2exp(0.2712 120 10−3 exp(j 1.69 120
× × × × 10 −3
) = 78 .7̸ 8.02
The incident voltage at a distance of 120 km from the receiving end
78.7
= ̸ 8.02 = 39 .35̸ 8.02
2
2. Determine the efficiency of the line in the above problem if the line is 120 km long and
delivers 40 MW at 132 KV and 0.8 p.f. lagging.
Solution:
Vr Vr
+ Ir Ir
−
Zc Zc
Is = exp(αx)exp(jβ x) − exp( αx)exp( jβ x)
− −
2 2
V + Vs−
Is = s − = 200 .39̸ 29.9 −
Zc Zc
P ower at the sending end = 3 Vs Is cosφs = 3 86.26 200.39cos33.72 = 43 .132M W
×| || | × ×
40
% Ef f iciency = 43.132 100 = 92 .7%
×
3. Determine the ABCD parameters of the line of above problem and verify the sending
end quantities found in the above problem.
Solution:
−3
γl = (0.2712 + j 1.169)120 × 10 = 0.03254 + j 0.1402
A = cosh l= cosh(0.03245 + j 0.1402)
A = cosh0.03254cos0.1402 + jsinh 0.03254sin0.1402 = 0 .99 + j 0.004435 = 0 .99̸ 0.26
B = Z c sinh l
4. A three phas e 50 Hz transmission line is 400 km long. The voltage at the sendin g end
is 220 KV. The line parameters are r=0.0125 ohm/km, x=0.4 ohm/km and y = 2.8 ×
10−6 mho/km. Find the following:
(a) The maximum permissible line length if the receiving end no-load vo ltage is not to
exceed 235 KV.
(b) For part (a), the maximum permissible line frequency , if the no-load voltage is not
to exceed 250 KV.
Vs 220
|A| = | V | = 235 = 0.936
r
Now,
|A| = 1 + Y2Z
2 −6
|A| = 1 + l × j 2.8 × 10 2× (0.125 + j 0.4) = (1 − 0.56 × 10 −6 2
l ) + j 0.175 × 10 −6 2
l
Since, the imaginary part will be less than 1 /10th of real part, A can be approxi- | |
mated as
A = (1 0.56 10−6 l2 ) = 0.936
| | − ×
1 0.936
−
l2 =
0.56 10−6
×
l=338 km.
(b)
|A| = | VV | = 220
s
r 250
= 0.88
A = 1+
| | 1
2
j 1.12 10−3
× × × 50f (50 + j 160 × 50f )
Neglecting the imaginary part, we can write
2
|A| = 1 − 12 × 1.12 × 1.12 × 10 × 160 50f −3
2
= 0.88
5. A 275 KV transmission line has the following line constraints: A=0.85 ̸ 5; B=200 ̸ 75
(a) Determine the power at unity pow er factor that can be received if the voltage profil e
at each end is to be maintained at 275 KV.
(b) What type and rating of compensation equip ment would be required if the load is
150 MW at unity power factor with the same voltage profile as in part (a).
(c) With the load as in part (b), what woul d be the recei ving end voltage if the com-
pensation equipment is not installed.
Figure 1:
×
275 275 .85
150 =
200
cos(75 − δ) − 0200 2
× (275) cos(75 − 5) = 227 .6 − 109.9 = 117 .7M W
150 = 378 cos(75 − δ ) − 110
δ = 28.46
Qr = 275 275 cos(75 28.46) 0.85 (275)2 cos(75 5) = 274 .46 302 =
× − − × − − −27.56MVAR
200 200
Thus, in order to maintain 275 KV at the receiving end, Q r = -27.56 MVAR must be
drawn along with the real power of Pr = 150MW. The load being 150 MW at unity
power factor, i.e., Q D =0, compensation equipment must be installed at the receiving
end.
-27.56 + QC = 0
QC = 27.56 MVAR
i.e., the compensation equipment must feed positive VARs into the line.
(c) Since, no compensation equipment is provided
Pr = 150MW; Qr = 0
Now, Vs = 275 KV, Vr = ?
| |
Figure 5 | |
Substituting this data in Pr and Qr , we have
275 Vr
×| | 0.85 2
150 = cos(75 δ ) − − × |V | cos70
r (1)
200 200
275 Vr
×| | 0.85 2
0= sin(75 δ )− − × |V | sin70
r (2)
200 200
From, Eq. (2), we get
sin(75 − δ) = 0.0029|V | r (3)
√
cos(75 − δ ) = (1 − 0.0029 |V | ) 2
r
2
(4)
150 = 1 .375 Vr
| |
√(1 − 0.0029 |V | ) − 0.00145|V |
2
r
2
r
2
(5)
|V | = 244.9 KV.
r
6. Input to a single-phas e short line shown in below Figu re is 2000 KW at 0.8 lagging power
factor. The line has a series impedance of (0.4+j0.4) ohms. If the load voltage is 3KV,
find the load and receiving end power factor. Also find the supply voltage.
Figure 2:
|I | = 725amps (16)