You are on page 1of 226

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3300 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 2378.08 Sq.mm.


REQD. CONCRETE AREA 247621.9 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4234.68 Muz1 272.61 Muy1 272.61

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 1 Puz 4247.21 Muz 275.98
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2202.96 Sq.mm.


REQD. CONCRETE AREA 247797.1 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4171.37 Muz1 313.65 Muy1 313.65

INTERACTRATIO 0.99 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 2 Puz 4192.69 Muz 317.33
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2111.57 Sq.mm.


REQD. CONCRETE AREA 247888.4 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4138.33 Muz1 286.57 Muy1 286.57

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 3 Puz 4192.69 Muz 296.66
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 2240.26 Sq.mm.


REQD. CONCRETE AREA 247759.7 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4184.85 Muz1 274.03 Muy1 274.03

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 4 Puz 4192.69 Muz 275.54
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 2421.38 Sq.mm.


REQD. CONCRETE AREA 247578.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4250.33 Muz1 296.95 Muy1 296.95

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 5 Puz 4283.55 Muz 311.79
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT


REQD. STEEL AREA 2268.38 Sq.mm.
REQD. CONCRETE AREA 247731.6 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4195.02 Muz1 296.84 Muy1 296.84

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 6 Puz 4247.21 Muz 308.46
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2263.55 Sq.mm.


REQD. CONCRETE AREA 247736.5 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4193.27 Muz1 300.12 Muy1 300.12

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 7 Puz 4247.21 Muz 311.97
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 2347.43 Sq.mm.


REQD. CONCRETE AREA 247652.6 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4223.6 Muz1 325.42 Muy1 325.42

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 8 Puz 4247.21 Muz 330.14
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2735.21 Sq.mm.


REQD. CONCRETE AREA 247264.8 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4363.78 Muz1 290.22 Muy1 290.22

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 9 Puz 4519.77 Muz 320.65
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2341.18 Sq.mm.


REQD. CONCRETE AREA 247658.8 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4221.34 Muz1 308.54 Muy1 308.54

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 10 Puz 4247.21 Muz 315.41
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2679.56 Sq.mm.


REQD. CONCRETE AREA 247320.4 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4343.66 Muz1 333.48 Muy1 333.48

INTERACTRATIO 0.99 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 11 Puz 4356.23 Muz 335.92
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2396.79 Sq.mm.


REQD. CONCRETE AREA 247603.2 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4241.44 Muz1 292.03 Muy1 292.03

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 12 Puz 4247.21 Muz 294.66
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2452.73 Sq.mm.


REQD. CONCRETE AREA 247547.3 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4261.66 Muz1 286.42 Muy1 286.42

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 13 Puz 4283.55 Muz 301.2
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2472.91 Sq.mm.


REQD. CONCRETE AREA 247527.1 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4268.96 Muz1 318 Muy1 318

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 14 Puz 4283.55 Muz 322.26
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT


REQD. STEEL AREA 2829.7 Sq.mm.
REQD. CONCRETE AREA 247170.3 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4397.94 Muz1 296.59 Muy1 296.59

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 15 Puz 4519.77 Muz 320.32
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2479.35 Sq.mm.


REQD. CONCRETE AREA 247520.7 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4271.28 Muz1 316.41 Muy1 316.41

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 16 Puz 4283.55 Muz 323.84
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2687.78 Sq.mm.


REQD. CONCRETE AREA 247312.2 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4346.63 Muz1 340.72 Muy1 340.72

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 17 Puz 4356.23 Muz 342.54
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2475.78 Sq.mm.


REQD. CONCRETE AREA 247524.2 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4269.99 Muz1 327.66 Muy1 327.66

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 18 Puz 4283.55 Muz 334.93
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2565.23 Sq.mm.


REQD. CONCRETE AREA 247434.8 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4302.33 Muz1 332.79 Muy1 332.79

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 19 Puz 4356.23 Muz 342.29
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2728.03 Sq.mm.


REQD. CONCRETE AREA 247272 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4361.18 Muz1 340.73 Muy1 340.73

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 20 Puz 4519.77 Muz 368.46
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2728.08 Sq.mm.


REQD. CONCRETE AREA 247271.9 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4361.2 Muz1 345.13 Muy1 345.13

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 21 Puz 4519.77 Muz 372.57
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 305 END JOINT

REQD. STEEL AREA 3651.09 Sq.mm.


REQD. CONCRETE AREA 246348.9 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4694.87 Muz1 374.43 Muy1 374.43

INTERACTRATIO 0.98 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 22 Puz 4737.82 Muz 381
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 END JOINT

REQD. STEEL AREA 3584.49 Sq.mm.


REQD. CONCRETE AREA 246415.5 Sq.mm.
MAIN REINFORCEMENT Provide 32 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4670.79 Muz1 377.72 Muy1 377.72

INTERACTRATIO 0.98 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 23 Puz 4683.31 Muz 380.05
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT


REQD. STEEL AREA 2853.55 Sq.mm.
REQD. CONCRETE AREA 247146.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4406.56 Muz1 327.78 Muy1 327.78

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 24 Puz 4519.77 Muz 348.49
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2420.72 Sq.mm.


REQD. CONCRETE AREA 247579.3 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4250.09 Muz1 269.2 Muy1 269.2

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 25 Puz 4283.55 Muz 284.92
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2459.13 Sq.mm.


REQD. CONCRETE AREA 247540.9 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4263.98 Muz1 290.93 Muy1 290.93

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 26 Puz 4283.55 Muz 305.18
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2785.69 Sq.mm.


REQD. CONCRETE AREA 247214.3 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4382.03 Muz1 310.99 Muy1 310.99

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 27 Puz 4519.77 Muz 337.06
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 2842.49 Sq.mm.


REQD. CONCRETE AREA 247157.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4402.56 Muz1 358.47 Muy1 358.47

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 28 Puz 4519.77 Muz 354.45
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2447.77 Sq.mm.


REQD. CONCRETE AREA 247552.2 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4259.87 Muz1 321.37 Muy1 321.37

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 29 Puz 4283.55 Muz 330.6
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2549.27 Sq.mm.


REQD. CONCRETE AREA 247450.7 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4296.56 Muz1 315.37 Muy1 315.37

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 30 Puz 4356.23 Muz 325.75
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 301 END JOINT

REQD. STEEL AREA 1589.05 Sq.mm.


REQD. CONCRETE AREA 198631.1 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 3949.44 Muz1 216.19 Muy1 216.19

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 301
END JOINT 31 Puz 3956.47 Muz 223.24
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 306 END JOINT

REQD. STEEL AREA 991.28 Sq.mm.


REQD. CONCRETE AREA 123910.5 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3733.35 Muz1 184.49 Muy1 184.49

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 32 Puz 3865.62 Muz 212.65
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 306 END JOINT


REQD. STEEL AREA 1647.26 Sq.mm.
REQD. CONCRETE AREA 205907.2 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3970.48 Muz1 235.25 Muy1 235.25

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 33 Puz 4029.16 Muz 247.58
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 1053.52 Sq.mm.


REQD. CONCRETE AREA 131689.6 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3755.85 Muz1 178.32 Muy1 178.32

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 34 Puz 3865.62 Muz 202.54
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 1913.01 Sq.mm.


REQD. CONCRETE AREA 248087 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4066.55 Muz1 254.68 Muy1 254.68

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 307
END JOINT 35 Puz 4192.69 Muz 279.17
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 306 END JOINT

REQD. STEEL AREA 2104.9 Sq.mm.


REQD. CONCRETE AREA 247895.1 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4135.92 Muz1 251.55 Muy1 251.55

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 36 Puz 4192.69 Muz 263.02
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 317 END JOINT

REQD. STEEL AREA 3146.44 Sq.mm.


REQD. CONCRETE AREA 246853.6 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4512.44 Muz1 331.88 Muy1 331.88

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 317
END JOINT 37 Puz 4519.77 Muz 333.37
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1045.22 Sq.mm.


REQD. CONCRETE AREA 130652.7 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3752.85 Muz1 188.16 Muy1 188.16

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 38 Puz 3865.62 Muz 212.27
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 5000 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 311 BRACED LONG

REQD. STEEL AREA 5284.62 Sq.mm.


REQD. CONCRETE AREA 244715.4 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 5285.39 Muz1 490.52 Muy1 490.52

INTERACTRATIO 1 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1623.9 Sq.mm.


REQD. CONCRETE AREA 202987.3 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3962.04 Muz1 215.8 Muy1 215.8
INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 41 Puz 4029.16 Muz 229.69
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 308 END JOINT

REQD. STEEL AREA 3015.81 Sq.mm.


REQD. CONCRETE AREA 246984.2 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4465.22 Muz1 326.73 Muy1 326.73

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 317
END JOINT 42 Puz 4519.77 Muz 337.02
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 318 END JOINT

REQD. STEEL AREA 1549.01 Sq.mm.


REQD. CONCRETE AREA 193625.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3934.97 Muz1 210.78 Muy1 210.78

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 309
END JOINT 43 Puz 3956.47 Muz 220.57
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 5000 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 303 BRACED LONG

REQD. STEEL AREA 5103.26 Sq.mm.


REQD. CONCRETE AREA 244896.7 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 5219.83 Muz1 478.24 Muy1 478.24

INTERACTRATIO 1 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 5000 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 BRACED LONG

REQD. STEEL AREA 5333.52 Sq.mm.


REQD. CONCRETE AREA 244666.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 5303.07 Muz1 492.55 Muy1 492.55

INTERACTRATIO 1 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1900.04 Sq.mm.


REQD. CONCRETE AREA 248100 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4061.86 Muz1 235.81 Muy1 235.81

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 47 Puz 4192.69 Muz 291.44
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 318 END JOINT


REQD. STEEL AREA 2840.29 Sq.mm.
REQD. CONCRETE AREA 247159.7 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4401.76 Muz1 314.64 Muy1 314.64

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 318
END JOINT 48 Puz 4519.77 Muz 337
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 309 END JOINT

REQD. STEEL AREA 1926.15 Sq.mm.


REQD. CONCRETE AREA 248073.8 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4071.3 Muz1 261.45 Muy1 261.45

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 309
END JOINT 49 Puz 4192.69 Muz 284.76
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 1030.53 Sq.mm.


REQD. CONCRETE AREA 128815.7 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3747.54 Muz1 173.44 Muy1 173.44

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 50 Puz 3865.62 Muz 200.26
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 308 END JOINT

REQD. STEEL AREA 1833.94 Sq.mm.


REQD. CONCRETE AREA 248166.1 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4037.97 Muz1 273.27 Muy1 273.27

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 308
END JOINT 51 Puz 4192.69 Muz 301.77
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 1491.13 Sq.mm.


REQD. CONCRETE AREA 186391.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3914.04 Muz1 211.85 Muy1 211.85

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 52 Puz 3956.47 Muz 226.53
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 316 END JOINT

REQD. STEEL AREA 2199.75 Sq.mm.


REQD. CONCRETE AREA 247800.3 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4170.21 Muz1 292.66 Muy1 292.66

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 316
END JOINT 53 Puz 4192.69 Muz 296.82
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 317 END JOINT

REQD. STEEL AREA 3340.5 Sq.mm.


REQD. CONCRETE AREA 246659.5 Sq.mm.
MAIN REINFORCEMENT Provide 32 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4582.59 Muz1 351.45 Muy1 351.45

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 317
END JOINT 54 Puz 4683.31 Muz 370.13
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 1194.77 Sq.mm.


REQD. CONCRETE AREA 149346.5 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 3806.91 Muz1 189.96 Muy1 189.96

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 316
END JOINT 55 Puz 3865.62 Muz 203.49
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1146.05 Sq.mm.


REQD. CONCRETE AREA 143256.4 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3789.3 Muz1 163.96 Muy1 163.96

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 56 Puz 3865.62 Muz 182.78
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 END JOINT


REQD. STEEL AREA 2111.42 Sq.mm.
REQD. CONCRETE AREA 247888.6 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4138.28 Muz1 255.18 Muy1 255.18

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 57 Puz 4192.69 Muz 265.89
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1720 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 310 END JOINT

REQD. STEEL AREA 470.14 Sq.mm.


REQD. CONCRETE AREA 58767.32 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3544.96 Muz1 183.08 Muy1 183.08

INTERACTRATIO 0.53 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 58 Puz 3702.08 Muz 215.84
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 2666.3 Sq.mm.


REQD. CONCRETE AREA 247333.7 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4338.87 Muz1 307.75 Muy1 307.75

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 307
END JOINT 59 Puz 4356.23 Muz 311.23
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 315 END JOINT

REQD. STEEL AREA 2797.5 Sq.mm.


REQD. CONCRETE AREA 247202.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4386.3 Muz1 300.12 Muy1 300.12

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 315
END JOINT 60 Puz 4519.77 Muz 325.77
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2900 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 305 END JOINT

REQD. STEEL AREA 1104.52 Sq.mm.


REQD. CONCRETE AREA 138065.1 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3774.28 Muz1 126.01 Muy1 126.01

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 311 Puz 3865.62 Muz 147.78
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 160 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 311 END JOINT

REQD. STEEL AREA 1278.63 Sq.mm.


REQD. CONCRETE AREA 159829.3 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3837.23 Muz1 173.07 Muy1 173.07

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 311
END JOINT 334 Puz 3865.62 Muz 181.31
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 309 END JOINT

REQD. STEEL AREA 1944.77 Sq.mm.


REQD. CONCRETE AREA 248055.2 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4078.04 Muz1 278.28 Muy1 278.28

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 309
END JOINT 31 Puz 4192.69 Muz 299.53
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 174 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 1709.53 Sq.mm.


REQD. CONCRETE AREA 213691.3 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 3993 Muz1 250.05 Muy1 250.05

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 32 Puz 4029.16 Muz 258.05
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 1677.56 Sq.mm.


REQD. CONCRETE AREA 209695.1 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3981.44 Muz1 238.56 Muy1 238.56

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 33 Puz 4029.16 Muz 248.77
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT


REQD. STEEL AREA 1734.09 Sq.mm.
REQD. CONCRETE AREA 216761.5 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4001.87 Muz1 235.12 Muy1 235.12

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 34 Puz 4029.16 Muz 240.84
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2285.42 Sq.mm.


REQD. CONCRETE AREA 247714.6 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4201.18 Muz1 288.75 Muy1 288.75

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 35 Puz 4247.21 Muz 298.97
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 306 END JOINT

REQD. STEEL AREA 2611.1 Sq.mm.


REQD. CONCRETE AREA 247388.9 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4318.91 Muz1 327.7 Muy1 327.7

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 36 Puz 4356.23 Muz 334.33
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 317 END JOINT

REQD. STEEL AREA 2479.41 Sq.mm.


REQD. CONCRETE AREA 247520.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4271.31 Muz1 334.3 Muy1 334.3

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 317
END JOINT 37 Puz 4283.55 Muz 341.86
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 2018.41 Sq.mm.


REQD. CONCRETE AREA 247981.6 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4104.65 Muz1 294.94 Muy1 294.94

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 38 Puz 4192.69 Muz 310.47
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 3046.55 Sq.mm.


REQD. CONCRETE AREA 246953.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4476.33 Muz1 301.29 Muy1 301.29

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 39 Puz 4519.77 Muz 309.59
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 1950.74 Sq.mm.


REQD. CONCRETE AREA 248049.3 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4080.19 Muz1 278.9 Muy1 278.9

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 40 Puz 4192.69 Muz 299.73
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 2368.75 Sq.mm.


REQD. CONCRETE AREA 247631.3 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4231.3 Muz1 308.68 Muy1 308.68

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 41 Puz 4247.21 Muz 313.68
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 317 END JOINT

REQD. STEEL AREA 3052.21 Sq.mm.


REQD. CONCRETE AREA 246947.8 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4478.37 Muz1 372.56 Muy1 372.56

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 317
END JOINT 42 Puz 4519.77 Muz 379.21
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT


REQD. STEEL AREA 2381.93 Sq.mm.
REQD. CONCRETE AREA 247618.1 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4236.07 Muz1 279.92 Muy1 279.92

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 43 Puz 4247.21 Muz 283.4
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2195.98 Sq.mm.


REQD. CONCRETE AREA 247804 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4168.85 Muz1 292.29 Muy1 292.29

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 44 Puz 4192.69 Muz 296.71
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 3160.82 Sq.mm.


REQD. CONCRETE AREA 246839.2 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4517.64 Muz1 309.1 Muy1 309.1

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 45 Puz 4519.77 Muz 309.14
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 1850.18 Sq.mm.


REQD. CONCRETE AREA 248149.8 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4043.84 Muz1 269.98 Muy1 269.98

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 46 Puz 4192.69 Muz 297.69
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2399.68 Sq.mm.


REQD. CONCRETE AREA 247600.3 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4242.49 Muz1 309.27 Muy1 309.27

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 47 Puz 4247.21 Muz 312.12
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 318 END JOINT

REQD. STEEL AREA 3060 Sq.mm.


REQD. CONCRETE AREA 246940 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4481.19 Muz1 372.46 Muy1 372.46

INTERACTRATIO 0.99 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 309
END JOINT 48 Puz 4519.77 Muz 378.64
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 2482.71 Sq.mm.


REQD. CONCRETE AREA 247517.3 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4272.5 Muz1 297.61 Muy1 297.61

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 49 Puz 4283.55 Muz 334.66
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2068.19 Sq.mm.


REQD. CONCRETE AREA 247931.8 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4122.65 Muz1 287.88 Muy1 287.88

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 50 Puz 4192.69 Muz 300.72
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2198.59 Sq.mm.


REQD. CONCRETE AREA 247801.4 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4169.79 Muz1 296.48 Muy1 296.48

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 51 Puz 4192.69 Muz 300.68
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT


REQD. STEEL AREA 2086.78 Sq.mm.
REQD. CONCRETE AREA 247913.2 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4129.37 Muz1 304.72 Muy1 304.72

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 52 Puz 4192.69 Muz 315.81
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 3424.24 Sq.mm.


REQD. CONCRETE AREA 246575.8 Sq.mm.
MAIN REINFORCEMENT Provide 32 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4612.86 Muz1 362 Muy1 362

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 316
END JOINT 53 Puz 4683.31 Muz 372.26
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 315 END JOINT

REQD. STEEL AREA 4251.59 Sq.mm.


REQD. CONCRETE AREA 245748.4 Sq.mm.
MAIN REINFORCEMENT Provide 40 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4911.95 Muz1 439.26 Muy1 439.26

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 54 Puz 5010.39 Muz 456.73
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 1810.59 Sq.mm.


REQD. CONCRETE AREA 248189.4 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4029.53 Muz1 264.12 Muy1 264.12

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 55 Puz 4192.69 Muz 294.79
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 1799.58 Sq.mm.


REQD. CONCRETE AREA 224947.4 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4025.55 Muz1 243.93 Muy1 243.93

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 56 Puz 4029.16 Muz 245.3
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2580.99 Sq.mm.


REQD. CONCRETE AREA 247419 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4308.03 Muz1 279.69 Muy1 279.69

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 57 Puz 4356.23 Muz 288.7
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1667 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1458.66 Sq.mm.


REQD. CONCRETE AREA 182332 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3902.3 Muz1 224.44 Muy1 224.44

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 58 Puz 3956.47 Muz 274.7
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 2432 Sq.mm.


REQD. CONCRETE AREA 247568 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4254.17 Muz1 335.11 Muy1 335.11

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 307
END JOINT 59 Puz 4283.55 Muz 345.85
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 315 END JOINT

REQD. STEEL AREA 2879.51 Sq.mm.


REQD. CONCRETE AREA 247120.5 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4415.94 Muz1 348.13 Muy1 348.13

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 315
END JOINT 60 Puz 4519.77 Muz 366.36
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 305 END JOINT


REQD. STEEL AREA 2414.43 Sq.mm.
REQD. CONCRETE AREA 247585.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4247.82 Muz1 252.96 Muy1 252.96

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 61 Puz 4283.55 Muz 267.29
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 END JOINT

REQD. STEEL AREA 1601.93 Sq.mm.


REQD. CONCRETE AREA 200241.9 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3954.1 Muz1 208.12 Muy1 208.12

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 62 Puz 3956.47 Muz 213.15
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 END JOINT

REQD. STEEL AREA 4299.46 Sq.mm.


REQD. CONCRETE AREA 245700.5 Sq.mm.
MAIN REINFORCEMENT Provide 40 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4929.26 Muz1 405.37 Muy1 405.37

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 63 Puz 5010.39 Muz 421.15
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 302 END JOINT

REQD. STEEL AREA 1643.62 Sq.mm.


REQD. CONCRETE AREA 205452.1 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3969.17 Muz1 205.19 Muy1 205.19

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 64 Puz 4029.16 Muz 217.99
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 303 END JOINT

REQD. STEEL AREA 2247.92 Sq.mm.


REQD. CONCRETE AREA 247752.1 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4187.62 Muz1 259.11 Muy1 259.11

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 65 Puz 4192.69 Muz 260.13
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 305 END JOINT

REQD. STEEL AREA 2978.96 Sq.mm.


REQD. CONCRETE AREA 247021 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4451.89 Muz1 298.4 Muy1 298.4

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 66 Puz 4519.77 Muz 311.62
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 307 END JOINT

REQD. STEEL AREA 3192.39 Sq.mm.


REQD. CONCRETE AREA 246807.6 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4529.05 Muz1 317.01 Muy1 317.01

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 307
END JOINT 85 Puz 4537.94 Muz 319.33
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 315 END JOINT

REQD. STEEL AREA 2141.22 Sq.mm.


REQD. CONCRETE AREA 247858.8 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4149.05 Muz1 268.4 Muy1 268.4

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 315
END JOINT 86 Puz 4192.69 Muz 276.84
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 306 END JOINT

REQD. STEEL AREA 2419.78 Sq.mm.


REQD. CONCRETE AREA 247580.2 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4249.75 Muz1 262.77 Muy1 262.77

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 306
END JOINT 87 Puz 4283.55 Muz 277.84
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 303 END JOINT


REQD. STEEL AREA 2070.73 Sq.mm.
REQD. CONCRETE AREA 247929.3 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4123.57 Muz1 251.16 Muy1 251.16

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 88 Puz 4192.69 Muz 264.94
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 303 END JOINT

REQD. STEEL AREA 2529.62 Sq.mm.


REQD. CONCRETE AREA 247470.4 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4289.46 Muz1 280.53 Muy1 280.53

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 312
END JOINT 89 Puz 4356.23 Muz 293.41
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 311 END JOINT

REQD. STEEL AREA 3181.04 Sq.mm.


REQD. CONCRETE AREA 246819 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4524.95 Muz1 311.38 Muy1 311.38

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 302
END JOINT 90 Puz 4537.94 Muz 313.9
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 1485.91 Sq.mm.


REQD. CONCRETE AREA 185739.3 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3912.16 Muz1 188.52 Muy1 188.52

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 67 Puz 3956.47 Muz 201.93
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 314 END JOINT

REQD. STEEL AREA 1710.63 Sq.mm.


REQD. CONCRETE AREA 213828.9 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3993.39 Muz1 205.11 Muy1 205.11

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 314
END JOINT 73 Puz 4029.16 Muz 212.84
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 309 END JOINT

REQD. STEEL AREA 3218.02 Sq.mm.


REQD. CONCRETE AREA 246782 Sq.mm.
MAIN REINFORCEMENT Provide 32 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4538.32 Muz1 331.23 Muy1 331.23

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 309
END JOINT 79 Puz 4683.31 Muz 359.17
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 304 END JOINT

REQD. STEEL AREA 2908.65 Sq.mm.


REQD. CONCRETE AREA 247091.3 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4426.48 Muz1 306.83 Muy1 306.83

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 72 Puz 4519.77 Muz 324.76
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 311 END JOINT

REQD. STEEL AREA 2849.1 Sq.mm.


REQD. CONCRETE AREA 247150.9 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 4404.95 Muz1 303.81 Muy1 303.81

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 311
END JOINT 78 Puz 4519.77 Muz 325.86
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 314 END JOINT

REQD. STEEL AREA 2903.42 Sq.mm.


REQD. CONCRETE AREA 247096.6 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4424.59 Muz1 305.76 Muy1 305.76

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 314
END JOINT 84 Puz 4519.77 Muz 324.06
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT


REQD. STEEL AREA 5537.93 Sq.mm.
REQD. CONCRETE AREA 244462.1 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 5376.96 Muz1 506.14 Muy1 506.14

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 68 Puz 5410.15 Muz 513.24
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 1635.22 Sq.mm.


REQD. CONCRETE AREA 204403.1 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3966.13 Muz1 205.23 Muy1 205.23

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 80 Puz 4029.16 Muz 218.66
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 304 END JOINT

REQD. STEEL AREA 4209.47 Sq.mm.


REQD. CONCRETE AREA 245790.5 Sq.mm.
MAIN REINFORCEMENT Provide 40 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4896.72 Muz1 409.12 Muy1 409.12

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 304
END JOINT 81 Puz 5010.39 Muz 430.39
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 1603 Sq.mm.


REQD. CONCRETE AREA 200374.5 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3954.48 Muz1 200.45 Muy1 200.45

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 82 Puz 3956.47 Muz 204.89
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 1741.95 Sq.mm.


REQD. CONCRETE AREA 217744.1 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4004.72 Muz1 213.98 Muy1 213.98

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 83 Puz 4029.16 Muz 219.07
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 312 END JOINT

REQD. STEEL AREA 2617.72 Sq.mm.


REQD. CONCRETE AREA 247382.3 Sq.mm.
MAIN REINFORCEMENT Provide 24 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4321.31 Muz1 299.54 Muy1 299.54

INTERACTRATIO 1 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 71 Puz 4356.23 Muz 306.57
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 312 END JOINT

REQD. STEEL AREA 2896.17 Sq.mm.


REQD. CONCRETE AREA 247103.8 Sq.mm.
MAIN REINFORCEMENT Provide 28 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 4421.96 Muz1 315.46 Muy1 315.46

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 77 Puz 4519.77 Muz 334.1
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 BRACED LONG(Z)

REQD. STEEL AREA 2492.14 Sq.mm.


REQD. CONCRETE AREA 147507.9 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 2925.91 Muz1 136.3 Muy1 259.14

INTERACTRATIO 0.99 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1720 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 1091.73 Sq.mm.


REQD. CONCRETE AREA 148908.3 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2419.66 Muz1 70.37 Muy1 126.13

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 315 Puz 2515.62 Muz 80.97
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 160 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 314 END JOINT

REQD. STEEL AREA 632.27 Sq.mm.


REQD. CONCRETE AREA 79033.82 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2253.57 Muz1 49.53 Muy1 86.49

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 314
END JOINT 335 Puz 2352.08 Muz 61.72
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1667 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 352 END JOINT

REQD. STEEL AREA 2323.64 Sq.mm.


REQD. CONCRETE AREA 147676.4 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2865 Muz1 118.07 Muy1 221.03

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 352
END JOINT 315 Puz 2897.21 Muz 120.98
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm


** GUIDING LOAD CASE 304 END JOINT

REQD. STEEL AREA 1081.12 Sq.mm.


REQD. CONCRETE AREA 148918.9 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2415.83 Muz1 79.88 Muy1 143.59

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 304
END JOINT 316 Puz 2515.62 Muz 90.05
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3750 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 304 BRACED LONG(Z)

REQD. STEEL AREA 2417.3 Sq.mm.


REQD. CONCRETE AREA 147582.7 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2898.85 Muz1 138.01 Muy1 257.6

INTERACTRATIO 1 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)


LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 304 END JOINT

REQD. STEEL AREA 1762.02 Sq.mm.


REQD. CONCRETE AREA 148238 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2661.97 Muz1 109.79 Muy1 201.43

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 304
END JOINT 324 Puz 2679.16 Muz 111.09
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2900 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 348.33 Sq.mm.


REQD. CONCRETE AREA 43541.06 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2150.92 Muz1 27.51 Muy1 46.67

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 311
END JOINT 326 Puz 2352.08 Muz 61.25
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3550 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 304 BRACED LONG(Z)

REQD. STEEL AREA 2453.29 Sq.mm.


REQD. CONCRETE AREA 147546.7 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 20 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2911.87 Muz1 136.02 Muy1 253.93

INTERACTRATIO 0.99 (as per Cl. 39.6

============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2500 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 353 END JOINT

REQD. STEEL AREA 1613.98 Sq.mm.


REQD. CONCRETE AREA 148386 Sq.mm.
MAIN REINFORCEMENT Provide 16 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2608.45 Muz1 91.73 Muy1 168.59

INTERACTRATIO 1 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 353
END JOINT 326 Puz 2679.16 Muz 98.99
============================================================================
============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1883 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 1050.31 Sq.mm.


REQD. CONCRETE AREA 131288.5 Sq.mm.
MAIN REINFORCEMENT Provide 12 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3754.69 Muz1 253.15 Muy1 253.15

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 304
END JOINT 499 Puz 3865.62 Muz 272.39
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 1883 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 2057.53 Sq.mm.


REQD. CONCRETE AREA 147942.5 Sq.mm.
MAIN REINFORCEMENT Provide 20 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2768.8 Muz1 116.46 Muy1 215.76

INTERACTRATIO 0.99 (as per Cl. 39.6


SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)
----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 508 Puz 2842.69 Muz 123.13
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 780 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 354 END JOINT

REQD. STEEL AREA 503.44 Sq.mm.


REQD. CONCRETE AREA 62929.61 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2206.99 Muz1 34.65 Muy1 59.63

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 354
END JOINT 523 Puz 2352.08 Muz 53.14
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 780 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 403.19 Sq.mm.


REQD. CONCRETE AREA 50398.29 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular
SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)
----------------------------------------------------------
Puz 3520.75 Muz1 164.18 Muy1 164.18

INTERACTRATIO 0.29 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 533 Puz 3702.08 Muz 204.27
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2740 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 313 END JOINT

REQD. STEEL AREA 865.77 Sq.mm.


REQD. CONCRETE AREA 108221 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3687.98 Muz1 103.43 Muy1 103.43

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 313
END JOINT 313 Puz 3702.08 Muz 106.57
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 2740 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 303 END JOINT


REQD. STEEL AREA 574.71 Sq.mm.
REQD. CONCRETE AREA 71839.29 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 2232.76 Muz1 39.22 Muy1 67.99

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 303
END JOINT 335 Puz 2352.08 Muz 54.23
============================================================================

============================================================================

C O L U M N N

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 3376 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 351 END JOINT

REQD. STEEL AREA 1457.26 Sq.mm.


REQD. CONCRETE AREA 182157.6 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 16 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3901.8 Muz1 232.4 Muy1 232.4

INTERACTRATIO 0.99 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 351
END JOINT 520 Puz 3956.47 Muz 250.28
============================================================================

============================================================================

C O L U M N N
M30 Fe500 (Main) Fe500 (Sec.)

LENGTH 450 mm CROSS SECTION 500 mm

** GUIDING LOAD CASE 301 END JOINT

REQD. STEEL AREA 609.33 Sq.mm.


REQD. CONCRETE AREA 76166.8 Sq.mm.
MAIN REINFORCEMENT Provide 8 - 12 dia.
(Equally distributed)
TIE REINFORCEMENT Provide 8 mm dia. rectangular

SECTION CAPACITY BASED ON REINFOR REQUIRED(KNS-MET)


----------------------------------------------------------
Puz 3595.27 Muz1 215.39 Muy1 215.39

INTERACTRATIO 0.24 (as per Cl. 39.6

SECTION CAPACITY BASED ON REINFOR PROVIDED(KNS-MET)


----------------------------------------------------------
WORST LOAD CASE 305
END JOINT 513 Puz 3702.08 Muz 230.3
============================================================================
================

O. 1 D E S I G N R

X 500 mm COVER 40 mm

1 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 275.98 IR 0.98


================

================

O. 2 D E S I G N R

X 500 mm COVER 40 mm

2 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 317.33 IR 0.98
================

================

O. 3 D E S I G N R

X 500 mm COVER 40 mm

3 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 296.66 IR 0.96


================

================

O. 4 D E S I G N R

X 500 mm COVER 40 mm

4 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 275.54 IR 0.99


================

================

O. 5 D E S I G N R

X 500 mm COVER 40 mm

5 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 311.79 IR 0.95


================

================

O. 6 D E S I G N R

X 500 mm COVER 40 mm

6 SHORT COLUMN
(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 308.46 IR 0.96


================

================

O. 7 D E S I G N R

X 500 mm COVER 40 mm

7 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 311.97 IR 0.96


================

================

O. 8 D E S I G N R
X 500 mm COVER 40 mm

8 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 330.14 IR 0.98


================

================

O. 9 D E S I G N R

X 500 mm COVER 40 mm

9 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 320.65 IR 0.9


================
================

O. 10 D E S I G N R

X 500 mm COVER 40 mm

10 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 315.41 IR 0.97


================

================

O. 11 D E S I G N R

X 500 mm COVER 40 mm

11 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 335.92 IR 0.99
================

================

O. 12 D E S I G N R

X 500 mm COVER 40 mm

12 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 294.66 IR 0.99


================

================

O. 13 D E S I G N R

X 500 mm COVER 40 mm

13 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c


IS456 2000)

Muy 301.2 IR 0.95


================

================

O. 14 D E S I G N R

X 500 mm COVER 40 mm

14 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 322.26 IR 0.97


================

================

O. 15 D E S I G N R

X 500 mm COVER 40 mm

15 SHORT COLUMN
(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 320.32 IR 0.92


================

================

O. 16 D E S I G N R

X 500 mm COVER 40 mm

16 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 323.84 IR 0.97


================

================

O. 17 D E S I G N R
X 500 mm COVER 40 mm

17 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 342.54 IR 0.99


================

================

O. 18 D E S I G N R

X 500 mm COVER 40 mm

18 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 334.93 IR 0.97


================
================

O. 19 D E S I G N R

X 500 mm COVER 40 mm

19 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 342.29 IR 0.97


================

================

O. 20 D E S I G N R

X 500 mm COVER 40 mm

20 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 368.46 IR 0.92
================

================

O. 21 D E S I G N R

X 500 mm COVER 40 mm

21 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 372.57 IR 0.92


================

================

O. 22 D E S I G N R

X 500 mm COVER 40 mm

22 SHORT COLUMN

(1.51% 3769.91 Sq.mm.)

ties @ 300 mm c/c


IS456 2000)

Muy 381 IR 0.96


================

================

O. 23 D E S I G N R

X 500 mm COVER 40 mm

23 SHORT COLUMN

(1.45% 3619.11 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 380.05 IR 0.97


================

================

O. 24 D E S I G N R

X 500 mm COVER 40 mm

24 SHORT COLUMN
(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 348.49 IR 0.94


================

================

O. 25 D E S I G N R

X 500 mm COVER 40 mm

25 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 284.92 IR 0.94


================

================

O. 26 D E S I G N R
X 500 mm COVER 40 mm

26 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 305.18 IR 0.95


================

================

O. 27 D E S I G N R

X 500 mm COVER 40 mm

27 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 337.06 IR 0.92


================
================

O. 28 D E S I G N R

X 500 mm COVER 40 mm

28 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 354.45 IR 0.94


================

================

O. 29 D E S I G N R

X 500 mm COVER 40 mm

29 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)
Muy 330.6 IR 0.97
================

================

O. 30 D E S I G N R

X 500 mm COVER 40 mm

30 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 325.75 IR 0.96


================

================

O. 80 D E S I G N R

X 500 mm COVER 40 mm

31 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c


IS456 2000)

Muy 223.24 IR 0.97


================

================

O. 81 D E S I G N R

X 500 mm COVER 40 mm

32 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 212.65 IR 0.86


================

================

O. 82 D E S I G N R

X 500 mm COVER 40 mm

33 SHORT COLUMN
(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 247.58 IR 0.94


================

================

O. 83 D E S I G N R

X 500 mm COVER 40 mm

34 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 202.54 IR 0.87


================

================

O. 84 D E S I G N R
X 500 mm COVER 40 mm

35 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 279.17 IR 0.9


================

================

O. 85 D E S I G N R

X 500 mm COVER 40 mm

36 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 263.02 IR 0.95


================
================

O. 86 D E S I G N R

X 500 mm COVER 40 mm

37 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 333.37 IR 0.99


================

================

O. 87 D E S I G N R

X 500 mm COVER 40 mm

38 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 212.27 IR 0.88
================

================

O. 89 D E S I G N R

X 500 mm COVER 40 mm

COLUMN

(2.25% 5629.73 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

================

================

O. 90 D E S I G N R

X 500 mm COVER 40 mm

41 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 229.69 IR 0.94


================

================

O. 91 D E S I G N R

X 500 mm COVER 40 mm

42 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 337.02 IR 0.96


================

================

O. 92 D E S I G N R

X 500 mm COVER 40 mm

43 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)


ties @ 255 mm c/c

IS456 2000)

Muy 220.57 IR 0.95


================

================

O. 93 D E S I G N R

X 500 mm COVER 40 mm

COLUMN

(2.25% 5629.73 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

================

================

O. 95 D E S I G N R

X 500 mm COVER 40 mm

COLUMN
(2.25% 5629.73 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

================

================

O. 96 D E S I G N R

X 500 mm COVER 40 mm

47 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 291.44 IR 0.91


================

================

O. 97 D E S I G N R

X 500 mm COVER 40 mm

48 SHORT COLUMN
(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 337 IR 0.93


================

================

O. 98 D E S I G N R

X 500 mm COVER 40 mm

49 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 284.76 IR 0.91


================

================

O. 99 D E S I G N R
X 500 mm COVER 40 mm

50 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 200.26 IR 0.86


================

================

O. 100 D E S I G N R

X 500 mm COVER 40 mm

51 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 301.77 IR 0.9


================
================

O. 101 D E S I G N R

X 500 mm COVER 40 mm

52 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 226.53 IR 0.93


================

================

O. 102 D E S I G N R

X 500 mm COVER 40 mm

53 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 296.82 IR 0.98
================

================

O. 103 D E S I G N R

X 500 mm COVER 40 mm

54 SHORT COLUMN

(1.45% 3619.11 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 370.13 IR 0.95


================

================

O. 104 D E S I G N R

X 500 mm COVER 40 mm

55 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 203.49 IR 0.93


================

================

O. 105 D E S I G N R

X 500 mm COVER 40 mm

56 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 182.78 IR 0.89


================

================

O. 106 D E S I G N R

X 500 mm COVER 40 mm

57 SHORT COLUMN
(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 265.89 IR 0.95


================

================

O. 107 D E S I G N R

X 500 mm COVER 40 mm

58 SHORT COLUMN

(0.36% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 215.84 IR 0.77


================

================

O. 108 D E S I G N R
X 500 mm COVER 40 mm

59 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 311.23 IR 0.98


================

================

O. 109 D E S I G N R

X 500 mm COVER 40 mm

60 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 325.77 IR 0.92


================
================

O. 196 D E S I G N R

X 500 mm COVER 40 mm

311 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 147.78 IR 0.84


================

================

O. 198 D E S I G N R

X 500 mm COVER 40 mm

334 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 181.31 IR 0.95
================

================

O. 203 D E S I G N R

X 500 mm COVER 40 mm

31 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 299.53 IR 0.93


================

================

O. 204 D E S I G N R

X 500 mm COVER 40 mm

32 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 258.05 IR 0.96


================

================

O. 206 D E S I G N R

X 500 mm COVER 40 mm

33 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 248.77 IR 0.95


================

================

O. 208 D E S I G N R

X 500 mm COVER 40 mm

34 SHORT COLUMN
(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 240.84 IR 0.98


================

================

O. 210 D E S I G N R

X 500 mm COVER 40 mm

35 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 298.97 IR 0.96


================

================

O. 212 D E S I G N R
X 500 mm COVER 40 mm

36 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 334.33 IR 0.97


================

================

O. 214 D E S I G N R

X 500 mm COVER 40 mm

37 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 341.86 IR 0.97


================
================

O. 215 D E S I G N R

X 500 mm COVER 40 mm

38 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 310.47 IR 0.95


================

================

O. 217 D E S I G N R

X 500 mm COVER 40 mm

39 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 309.59 IR 0.97
================

================

O. 219 D E S I G N R

X 500 mm COVER 40 mm

40 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 299.73 IR 0.93


================

================

O. 221 D E S I G N R

X 500 mm COVER 40 mm

41 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c


IS456 2000)

Muy 313.68 IR 0.98


================

================

O. 223 D E S I G N R

X 500 mm COVER 40 mm

42 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 379.21 IR 0.97


================

================

O. 225 D E S I G N R

X 500 mm COVER 40 mm

43 SHORT COLUMN
(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 283.4 IR 0.99


================

================

O. 226 D E S I G N R

X 500 mm COVER 40 mm

44 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 296.71 IR 0.98


================

================

O. 228 D E S I G N R
X 500 mm COVER 40 mm

45 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 309.14 IR 1
================

================

O. 230 D E S I G N R

X 500 mm COVER 40 mm

46 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 297.69 IR 0.9


================
================

O. 232 D E S I G N R

X 500 mm COVER 40 mm

47 SHORT COLUMN

(0.97% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 312.12 IR 0.99


================

================

O. 234 D E S I G N R

X 500 mm COVER 40 mm

48 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 378.64 IR 0.98
================

================

O. 236 D E S I G N R

X 500 mm COVER 40 mm

49 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 334.66 IR 0.98


================

================

O. 237 D E S I G N R

X 500 mm COVER 40 mm

50 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 300.72 IR 0.96


================

================

O. 239 D E S I G N R

X 500 mm COVER 40 mm

51 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 300.68 IR 0.98


================

================

O. 241 D E S I G N R

X 500 mm COVER 40 mm

52 SHORT COLUMN
(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 315.81 IR 0.96


================

================

O. 243 D E S I G N R

X 500 mm COVER 40 mm

53 SHORT COLUMN

(1.45% 3619.11 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 372.26 IR 0.96


================

================

O. 245 D E S I G N R
X 500 mm COVER 40 mm

54 SHORT COLUMN

(1.81% 4523.89 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 456.73 IR 0.96


================

================

O. 247 D E S I G N R

X 500 mm COVER 40 mm

55 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 294.79 IR 0.89


================
================

O. 248 D E S I G N R

X 500 mm COVER 40 mm

56 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 245.3 IR 0.99


================

================

O. 250 D E S I G N R

X 500 mm COVER 40 mm

57 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 288.7 IR 0.97
================

================

O. 252 D E S I G N R

X 500 mm COVER 40 mm

58 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 274.7 IR 0.95


================

================

O. 254 D E S I G N R

X 500 mm COVER 40 mm

59 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c


IS456 2000)

Muy 345.85 IR 0.96


================

================

O. 256 D E S I G N R

X 500 mm COVER 40 mm

60 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 366.36 IR 0.95


================

================

O. 548 D E S I G N R

X 500 mm COVER 40 mm

61 SHORT COLUMN
(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 267.29 IR 0.95


================

================

O. 549 D E S I G N R

X 500 mm COVER 40 mm

62 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 213.15 IR 0.97


================

================

O. 550 D E S I G N R
X 500 mm COVER 40 mm

63 SHORT COLUMN

(1.81% 4523.89 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 421.15 IR 0.96


================

================

O. 551 D E S I G N R

X 500 mm COVER 40 mm

64 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 217.99 IR 0.94


================
================

O. 552 D E S I G N R

X 500 mm COVER 40 mm

65 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 260.13 IR 1
================

================

O. 553 D E S I G N R

X 500 mm COVER 40 mm

66 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 311.62 IR 0.95
================

================

O. 554 D E S I G N R

X 500 mm COVER 40 mm

85 SHORT COLUMN

(1.29% 3216.99 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 319.33 IR 0.99


================

================

O. 555 D E S I G N R

X 500 mm COVER 40 mm

86 SHORT COLUMN

(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 276.84 IR 0.96


================

================

O. 556 D E S I G N R

X 500 mm COVER 40 mm

87 SHORT COLUMN

(1.01% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

Muy 277.84 IR 0.95


================

================

O. 557 D E S I G N R

X 500 mm COVER 40 mm

88 SHORT COLUMN
(0.90% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 264.94 IR 0.95


================

================

O. 558 D E S I G N R

X 500 mm COVER 40 mm

89 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 293.41 IR 0.95


================

================

O. 559 D E S I G N R
X 500 mm COVER 40 mm

90 SHORT COLUMN

(1.29% 3216.99 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 313.9 IR 0.99


================

================

O. 560 D E S I G N R

X 500 mm COVER 40 mm

67 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 201.93 IR 0.93


================
================

O. 561 D E S I G N R

X 500 mm COVER 40 mm

73 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 212.84 IR 0.96


================

================

O. 562 D E S I G N R

X 500 mm COVER 40 mm

79 SHORT COLUMN

(1.45% 3619.11 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 359.17 IR 0.92
================

================

O. 563 D E S I G N R

X 500 mm COVER 40 mm

72 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 324.76 IR 0.94


================

================

O. 564 D E S I G N R

X 500 mm COVER 40 mm

78 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 325.86 IR 0.93


================

================

O. 565 D E S I G N R

X 500 mm COVER 40 mm

84 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 324.06 IR 0.94


================

================

O. 566 D E S I G N R

X 500 mm COVER 40 mm

68 SHORT COLUMN
(2.25% 5629.73 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 513.24 IR 0.98


================

================

O. 567 D E S I G N R

X 500 mm COVER 40 mm

80 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 218.66 IR 0.94


================

================

O. 568 D E S I G N R
X 500 mm COVER 40 mm

81 SHORT COLUMN

(1.81% 4523.89 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 430.39 IR 0.95


================

================

O. 569 D E S I G N R

X 500 mm COVER 40 mm

82 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 204.89 IR 0.97


================
================

O. 570 D E S I G N R

X 500 mm COVER 40 mm

83 SHORT COLUMN

(0.72% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 219.07 IR 0.97


================

================

O. 571 D E S I G N R

X 500 mm COVER 40 mm

71 SHORT COLUMN

(1.09% 2714.34 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 306.57 IR 0.98
================

================

O. 572 D E S I G N R

X 500 mm COVER 40 mm

77 SHORT COLUMN

(1.27% 3166.73 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 334.1 IR 0.94


================

================

O. 579 D E S I G N R

X 300 mm COVER 40 mm

/SHORT(Y)

(1.68% 2513.27 Sq.mm.)

ties @ 300 mm c/c


IS456 2000)

================

================

O. 581 D E S I G N R

X 300 mm COVER 40 mm

315 SHORT COLUMN

(0.90% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 148.55 IR 0.86


================

================

O. 584 D E S I G N R

X 300 mm COVER 40 mm

335 SHORT COLUMN

(0.60% 904.78 Sq.mm.)


ties @ 190 mm c/c

IS456 2000)

Muy 110.38 IR 0.79


================

================

O. 585 D E S I G N R

X 300 mm COVER 40 mm

315 SHORT COLUMN

(1.61% 2412.74 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 228.71 IR 0.97


================

================

O. 586 D E S I G N R

X 300 mm COVER 40 mm
316 SHORT COLUMN

(0.90% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 164.26 IR 0.87


================

================

O. 591 D E S I G N R

X 300 mm COVER 40 mm

/SHORT(Y)

(1.68% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

================

================

O. 594 D E S I G N R
X 300 mm COVER 40 mm

324 SHORT COLUMN

(1.21% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 204.74 IR 0.98


================

================

O. 597 D E S I G N R

X 300 mm COVER 40 mm

327 SHORT COLUMN

(0.60% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 109.54 IR 0.54


================
================

O. 598 D E S I G N R

X 300 mm COVER 40 mm

/SHORT(Y)

(1.68% 2513.27 Sq.mm.)

ties @ 300 mm c/c

IS456 2000)

================

================

O. 599 D E S I G N R

X 300 mm COVER 40 mm

326 SHORT COLUMN

(1.21% 1809.56 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 183.04 IR 0.92


================
================

O. 600 D E S I G N R

X 500 mm COVER 40 mm

499 SHORT COLUMN

(0.54% 1357.17 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 272.39 IR 0.92


================

================

O. 601 D E S I G N R

X 300 mm COVER 40 mm

508 SHORT COLUMN

(1.51% 2261.95 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)
Muy 229.49 IR 0.94
================

================

O. 602 D E S I G N R

X 300 mm COVER 40 mm

523 SHORT COLUMN

(0.60% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 94.63 IR 0.63


================

================

O. 603 D E S I G N R

X 500 mm COVER 40 mm

333 SHORT COLUMN

(0.36% 904.78 Sq.mm.)

ties @ 190 mm c/c


IS456 2000)

Muy 204.27 IR 0.61


================

================

O. 604 D E S I G N R

X 500 mm COVER 40 mm

313 SHORT COLUMN

(0.36% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 106.57 IR 0.96


================

================

O. 605 D E S I G N R

X 300 mm COVER 40 mm

335 SHORT COLUMN


(0.60% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 96.64 IR 0.72


================

================

O. 1025 D E S I G N R

X 500 mm COVER 40 mm

520 SHORT COLUMN

(0.64% 1608.5 Sq.mm.)

ties @ 255 mm c/c

IS456 2000)

Muy 250.28 IR 0.92


================

================

O. 1026 D E S I G N R
X 500 mm COVER 40 mm

521 SHORT COLUMN

(0.36% 904.78 Sq.mm.)

ties @ 190 mm c/c

IS456 2000)

Muy 230.3 IR 0.48


================
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
E S U L T S

E S U L T S
APPDCL 2X800 MW SDSTPS Switchyard Control Room-
TATA Projects Limited
KRISHNAPATNAM Analysis Design

C.3 COLUMN DESIGN SUMMARY

CORNER MIDDLE
Column Required Provided
Ast REIN. REIN. Ast
Sl Column Member WIDTH DEPTH Steel Steel
required percentage provided Percentage CHECK
No Mark No. (B) (D) Dia Dia
(mm2) Ptreq Nos Nos (mm 2
) Ptprovd
(STAAD) (mm) (mm)
1 A1 1 500 500 2378 0.95 4 20 4 20 2513 1.01 SAFE
1026 500 500 609 0.24 4 20 4 20 2513 1.01 SAFE
203 500 500 1945 0.78 4 20 4 20 2513 1.01 SAFE
80 500 500 1589 0.64 4 20 4 20 2513 1.01 SAFE
548 500 500 2414 0.97 4 20 4 20 2513 1.01 SAFE

2 A2 2 500 500 2203 0.88 4 20 4 20 2513 1.01 SAFE


1025 500 500 1457 0.58 4 20 4 20 2513 1.01 SAFE
204 500 500 1710 0.68 4 20 4 20 2513 1.01 SAFE
81 500 500 991 0.40 4 20 4 20 2513 1.01 SAFE
549 500 500 1602 0.64 4 20 4 20 2513 1.01 SAFE

3 A3 3 500 500 2112 0.84 4 28 4 25 4427 1.77 SAFE


206 500 500 1678 0.67 4 28 4 25 4427 1.77 SAFE
82 500 500 1647 0.66 4 28 4 25 4427 1.77 SAFE
550 500 500 4299 1.72 4 28 4 25 4427 1.77 SAFE

4 A4 4 500 500 2240 0.90 4 20 4 20 2513 1.01 SAFE


208 500 500 1734 0.69 4 20 4 20 2513 1.01 SAFE
83 500 500 1054 0.42 4 20 4 20 2513 1.01 SAFE
551 500 500 1644 0.66 4 20 4 20 2513 1.01 SAFE

5 A5 5 500 500 2421 0.97 4 20 4 20 2513 1.01 SAFE


210 500 500 2285 0.91 4 20 4 20 2513 1.01 SAFE
84 500 500 1913 0.77 4 20 4 20 2513 1.01 SAFE
552 500 500 2248 0.90 4 20 4 20 2513 1.01 SAFE

6 A6 6 500 500 2268 0.91 4 25 4 20 3220 1.29 SAFE


212 500 500 2611 1.04 4 25 4 20 3220 1.29 SAFE
85 500 500 2105 0.84 4 25 4 20 3220 1.29 SAFE
553 500 500 2979 1.19 4 25 4 20 3220 1.29 SAFE

7 B1 7 500 500 2264 0.91 4 25 4 20 3220 1.29 SAFE


214 500 500 2479 0.99 4 25 4 20 3220 1.29 SAFE
86 500 500 3146 1.26 4 25 4 20 3220 1.29 SAFE
560 500 500 1486 0.59 4 25 4 20 3220 1.29 SAFE

8 B2 8 500 500 2347 0.94 4 25 8 25 5890 2.36 SAFE


215 500 500 2018 0.81 4 25 8 25 5890 2.36 SAFE
87 500 500 1045 0.42 4 25 8 25 5890 2.36 SAFE
566 500 500 5538 2.22 4 25 8 25 5890 2.36 SAFE

9 B3 9 500 500 2735 1.09 4 25 4 20 3220 1.29 SAFE


217 500 500 3047 1.22 4 25 4 20 3220 1.29 SAFE

10 B4 10 500 500 2341 0.94 4 25 8 25 5890 2.36 SAFE


219 500 500 1951 0.78 4 25 8 25 5890 2.36 SAFE
89 500 500 5285 2.11 4 25 8 25 5890 2.36 SAFE

11 B5 11 500 500 2680 1.07 4 25 4 20 3220 1.29 SAFE


221 500 500 2369 0.95 4 25 4 20 3220 1.29 SAFE
90 500 500 1624 0.65 4 25 4 20 3220 1.29 SAFE
571 500 500 2618 1.05 4 25 4 20 3220 1.29 SAFE

12 B6 12 500 500 2397 0.96 4 25 4 20 3220 1.29 SAFE


223 500 500 3052 1.22 4 25 4 20 3220 1.29 SAFE
91 500 500 3016 1.21 4 25 4 20 3220 1.29 SAFE
563 500 500 2909 1.16 4 25 4 20 3220 1.29 SAFE

Doc. No. TPL-069-CAL-C-7885, Rev. P0-A FICHTNER INDIA


APPDCL 2X800 MW SDSTPS Switchyard Control Room-
TATA Projects Limited
KRISHNAPATNAM Analysis Design

CORNER MIDDLE
Column Required Provided
Ast REIN. REIN. Ast
Sl Column Member WIDTH DEPTH Steel Steel
required percentage provided Percentage CHECK
No Mark No. (B) (D) Dia Dia
(mm2) Ptreq Nos Nos (mm2) Ptprovd
(STAAD) (mm) (mm)

13 C1 13 500 500 2453 0.98 4 20 4 20 2513 1.01 SAFE


225 500 500 2382 0.95 4 20 4 20 2513 1.01 SAFE
92 500 500 1549 0.62 4 20 4 20 2513 1.01 SAFE
561 500 500 1711 0.68 4 20 4 20 2513 1.01 SAFE

14 C2 14 500 500 2473 0.99 4 25 8 25 5890 2.36 SAFE


226 500 500 2196 0.88 4 25 8 25 5890 2.36 SAFE
93 500 500 5103 2.04 4 25 8 25 5890 2.36 SAFE

15 C3 15 500 500 2830 1.13 4 25 4 20 3220 1.29 SAFE


228 500 500 3161 1.26 4 25 4 20 3220 1.29 SAFE

16 C4 16 500 500 2479 0.99 4 25 8 25 5890 2.36 SAFE


230 500 500 1850 0.74 4 25 8 25 5890 2.36 SAFE
95 500 500 5334 2.13 4 25 8 25 5890 2.36 SAFE

17 C5 17 500 500 2688 1.08 4 25 4 20 3220 1.29 SAFE


232 500 500 2400 0.96 4 25 4 20 3220 1.29 SAFE
96 500 500 1900 0.76 4 25 4 20 3220 1.29 SAFE
572 500 500 2896 1.16 4 25 4 20 3220 1.29 SAFE

18 C6 18 500 500 2476 0.99 4 25 4 20 3220 1.29 SAFE


234 500 500 3060 1.22 4 25 4 20 3220 1.29 SAFE
97 500 500 2840 1.14 4 25 4 20 3220 1.29 SAFE
564 500 500 2849 1.14 4 25 4 20 3220 1.29 SAFE

19 D1 19 500 500 2565 1.03 4 25 4 25 3927 1.57 SAFE


236 500 500 2483 0.99 4 25 4 25 3927 1.57 SAFE
98 500 500 1926 0.77 4 25 4 25 3927 1.57 SAFE
562 500 500 3218 1.29 4 25 4 25 3927 1.57 SAFE

20 D2 20 500 500 2728 1.09 4 25 4 20 3220 1.29 SAFE


237 500 500 2068 0.83 4 25 4 20 3220 1.29 SAFE
99 500 500 1031 0.41 4 25 4 20 3220 1.29 SAFE
567 500 500 1635 0.65 4 25 4 20 3220 1.29 SAFE

21 D3 21 500 500 2728 1.09 4 28 4 25 4427 1.77 SAFE


239 500 500 2199 0.88 4 28 4 25 4427 1.77 SAFE
100 500 500 1834 0.73 4 28 4 25 4427 1.77 SAFE
568 500 500 4209 1.68 4 28 4 25 4427 1.77 SAFE

22 D4 22 500 500 3651 1.46 4 25 4 25 3927 1.57 SAFE


241 500 500 2087 0.83 4 25 4 25 3927 1.57 SAFE
101 500 500 1491 0.60 4 25 4 25 3927 1.57 SAFE
569 500 500 1603 0.64 4 25 4 25 3927 1.57 SAFE
196 500 500 1105 0.44 4 25 4 25 3927 1.57 SAFE

23 D5 23 500 500 3584 1.43 4 25 4 25 3927 1.57 SAFE


243 500 500 3424 1.37 4 25 4 25 3927 1.57 SAFE
102 500 500 2200 0.88 4 25 4 25 3927 1.57 SAFE
570 500 500 1742 0.70 4 25 4 25 3927 1.57 SAFE

24 D6 24 500 500 2854 1.14 4 28 4 25 4427 1.77 SAFE


245 500 500 4252 1.70 4 28 4 25 4427 1.77 SAFE
103 500 500 3341 1.34 4 28 4 25 4427 1.77 SAFE
565 500 500 2903 1.16 4 28 4 25 4427 1.77 SAFE

25 D'3' 591 500 300 2417 1.61 4 25 4 20 3220 2.15 SAFE


598 500 300 2453 1.64 4 25 4 20 3220 2.15 SAFE
594 500 300 1762 1.17 4 25 4 20 3220 2.15 SAFE
599 500 300 1614 1.08 4 25 4 20 3220 2.15 SAFE

Doc. No. TPL-069-CAL-C-7885, Rev. P0-A FICHTNER INDIA


APPDCL 2X800 MW SDSTPS Switchyard Control Room-
TATA Projects Limited
KRISHNAPATNAM Analysis Design

CORNER MIDDLE
Column Required Provided
Ast REIN. REIN. Ast
Sl Column Member WIDTH DEPTH Steel Steel
required percentage provided Percentage CHECK
No Mark No. (B) (D) Dia Dia
(mm2) Ptreq Nos Nos (mm2) Ptprovd
(STAAD) (mm) (mm)
597 500 300 348 0.23 4 25 4 20 3220 2.15 SAFE

Doc. No. TPL-069-CAL-C-7885, Rev. P0-A FICHTNER INDIA


APPDCL 2X800 MW SDSTPS Switchyard Control Room-
TATA Projects Limited
KRISHNAPATNAM Analysis Design

CORNER MIDDLE
Column Required Provided
Ast REIN. REIN. Ast
Sl Column Member WIDTH DEPTH Steel Steel
required percentage provided Percentage CHECK
No Mark No. (B) (D) Dia Dia
(mm2) Ptreq Nos Nos (mm2) Ptprovd
(STAAD) (mm) (mm)

26 E1 25 500 500 2421 0.97 4 25 4 20 3220 1.29 SAFE


247 500 500 1811 0.72 4 25 4 20 3220 1.29 SAFE
104 500 500 1195 0.48 4 25 4 20 3220 1.29 SAFE
554 500 500 3192 1.28 4 25 4 20 3220 1.29 SAFE

27 E2 26 500 500 2459 0.98 4 20 4 20 2513 1.01 SAFE


248 500 500 1800 0.72 4 20 4 20 2513 1.01 SAFE
105 500 500 1146 0.46 4 20 4 20 2513 1.01 SAFE
555 500 500 2141 0.86 4 20 4 20 2513 1.01 SAFE

28 E3 27 500 500 2786 1.11 4 25 4 20 3220 1.29 SAFE


250 500 500 2581 1.03 4 25 4 20 3220 1.29 SAFE
106 500 500 2111 0.84 4 25 4 20 3220 1.29 SAFE
556 500 500 2420 0.97 4 25 4 20 3220 1.29 SAFE

29 E3' 579 500 300 2492 1.66 4 25 4 20 3220 2.15 SAFE


601 500 300 2058 1.37 4 25 4 20 3220 2.15 SAFE
585 500 300 2324 1.55 4 25 4 20 3220 2.15 SAFE
581 500 300 1092 0.73 4 25 4 20 3220 2.15 SAFE
602 500 300 503 0.34 4 25 4 20 3220 2.15 SAFE
586 500 300 1081 0.72 4 25 4 20 3220 2.15 SAFE
584 500 300 632 0.42 4 25 4 20 3220 2.15 SAFE
605 500 300 575 0.38 4 25 4 20 3220 2.15 SAFE

30 E4 28 500 500 2842 1.14 4 25 4 20 3220 1.29 SAFE


600 500 500 1050 0.42 4 25 4 20 3220 1.29 SAFE
252 500 500 1459 0.58 4 25 4 20 3220 1.29 SAFE
107 500 500 470 0.19 4 25 4 20 3220 1.29 SAFE
603 500 500 403 0.16 4 25 4 20 3220 1.29 SAFE
557 500 500 2071 0.83 4 25 4 20 3220 1.29 SAFE
198 500 500 1279 0.51 4 25 4 20 3220 1.29 SAFE
604 500 500 866 0.35 4 25 4 20 3220 1.29 SAFE

31 E5 29 500 500 2448 0.98 4 25 4 20 3220 1.29 SAFE


254 500 500 2432 0.97 4 25 4 20 3220 1.29 SAFE
108 500 500 2666 1.07 4 25 4 20 3220 1.29 SAFE
558 500 500 2530 1.01 4 25 4 20 3220 1.29 SAFE

32 E6 30 500 500 2549 1.02 4 25 4 20 3220 1.29 SAFE


256 500 500 2880 1.15 4 25 4 20 3220 1.29 SAFE
109 500 500 2798 1.12 4 25 4 20 3220 1.29 SAFE
559 500 500 3181 1.27 4 25 4 20 3220 1.29 SAFE

Doc. No. TPL-069-CAL-C-7885, Rev. P0-A FICHTNER INDIA


APPDCL 2X800 MW SDSTPS
Switchyard Control Room-
KRISHNAPATNAM TATA Projects Limited Analysis Design

ABSTRACT OF COLUMN DESIGN

Column B D Nos. Required Provided Provided Provided Tie Tie


Mark mm mm reinf. mm2 rebar reinf. mm2 % reinf. Reinf. Reqd. Reinf. Prvd.
4 Y 25 dia +
C1 500 300 2 2492 3220 2.15 8 dia @ 190c/c 8 dia @150c/c
4 Y 20dia

4 Y 20 dia +
C2 500 500 6 2414 2513 1.01 8 dia @ 190c/c 8 dia @150c/c
4 Y 20 dia

4 Y 25dia +
C3 500 500 11 3192 3220 1.29 8 dia @ 190c/c 8 dia @150c/c
4 Y 20 dia

4 Y 25dia +
C4 500 500 2 3161 3220 1.29 8 dia @ 190c/c 8 dia @150c/c
4 Y 20 dia

4 Y 25dia +
C5 500 500 2 3584 3927 1.57 8 dia @ 190c/c 8 dia @150c/c
4 Y 25 dia

Doc. No. TPL-069-CAL-C-7885, Rev. P0-A FICHTNER INDIA 03/22/2018