You are on page 1of 4

FOR

AUTO
OMATIC VOLTAGE CONTROLLER
AVC63-12 AND AVC125-10

INTRODUCTION F
Frequency Compensation Storage: 0 to 70°C (–40 to 158°F)
–40
The AVC63-12 and AVC125-10 regulate the O
One or two jumper-selectable V/Hz curves Max. Humidity: 95%
%, non-condensing
level of excitation supplied to the field of a w
with knee frequency adjustable from 45 to Weight: 1.1 kg (2.5 lb)
conventional, brushless, synchronous gene- 65 Hz (50/60 Hz units) or 300 to 430 Hz
INSTALLATION
rator. (4
400 Hz units). Refer to Figure 1 (60 Hz) and
F
Figure 2 (400 Hz) for sensing models. Regulators are co ontained in an encapsu-
Regulation is achieved by sensing the gene-
lated plastic case and may be mounted in
rator output voltage, converting it to a dc E
EMI Suppression any convenient pos sition. A regulator may be
signal, and comparing the signal to a refer- nternal filter. (See CE Conformity)
In mounted directly onn a genset using UNF ¼-
ence voltage. An error signal is developed 20 or equivalent haardware. Hardware selec-
V
Voltage Buildup
and used to control the dc field power in tion should be base ed on any expected ship-
order to maintain a constant generator out- A
Automatic voltage buildup occurs from resi-
dual generator voltage as low as 6 Vac ping/transportation and operating conditions.
put. The torque applied d to the mounting hard-
(A
AVC63-12) or 12 Vac (AVC125-10).
Each regulator includes frequency compen- ware should not exc ceed 65 in-lb (7.34 N•m).
sation with selectable slope, inverse-time O
Overexcitation Shutdown See Figure 5 for reggulator dimensions.
overexcitation shutdown, buildup circuitry, O
Overexcitation shutdown protection reduces
single- or three-phase voltage sensing, sin- th
he output voltage to zero in the times CONNECTIONS
gle- or three-phase shunt or permanent shhown below for the listed voltages. Other Before connecting the voltage regulator into
magnet generator (PMG) power input, paral- vooltages and times are based on the inverse your system, revie ew the terminal descrip-
lel droop compensation, and an accessory me characteristic curves of Figures 3 and 4
tim tions listed in Table 1 and the connection
input. The accessory input provides compa- A
AVC63-12 diagrams in Figures s 6 through 8.
tibility with devices such as var/power factor 1225 Vdc, ±10% in approximately 10 s Table 1. Terrminal Descriptions
controllers or excitation limiters. 210 Vdc, ±10% in approximately 1 s or less Term # Description
SPECIFICATIONS A
AVC125-10 CH GND Cha assis ground connection
Power Input ∗ 250 Vdc, ±10% in approximately 10 s 2 Aux xiliary input from SCP250
Configuration: 1-phase or 3-phase 370 Vdc, ±10% in approximately 1 s or less andd/or EL 200 (See Fig. 7)
3
Frequency: 50 to 400 Hz D
Droop/Line Drop Compensation
4 Inte
ernal voltage adjust: con-
Voltage Range <10 VA adjustable from 0 to 10% of rated necct to 7. External voltage
AVC63-12: 90 TO 153 Vac in
nput current at 0.8 power factor. (LDC com- adjust: no connection

Upper Terminal Strip


AVC125-10: 180 to 264 Vac pensates only for voltage drop due to line
re
eactance and reactive components of the 5 1 A current transformer (CT)
Maximum Continuous Burden
lo
oad current.) 5a 5 A CT
AVC63-12: 1,092 VA
AVC125-10: 1,750 VA A
Agency Approvals 6 CT common connection
∗ See Options for Inrush Current Reduction U
UL Recognition 6a Commmon connection for
Module information. S
Standard 508, File E97035 seleectable features
Sensing Input C
CSA Certification 7 Inte
ernal voltage adjust: con-
Configuration: 1-phase or 3-phase S
Standard CAN/CSA-C22.2 No. 14-95, necct to 4. External voltage
Burden: <1 VA per phase F
File LR 23131 adjust: connect to 6a
Voltage Range C
CE Conformity 8 Connnect to 6a to select 1
Option A: 90 to 139 Vac R
Radiated Emissions V/H
Hz underfrequency slope
Option B: 180 to 264 Vac EN50081-2 9 Connnect to 6a to select
Nominal Frequency C
Conducted Emissions 3-p
phase sensing
EN50081-2 (EN55011, Class A) 20 C-pphase sensing input
Option 1: 50 or 60 Hz
C
Conducted Emissions
Option 2: 400 Hz 22 A-pphase sensing input
Lower Term. Strip

EN50081-2 (EN55011, Class A)


(See Table 2 for style/option information.) E
ESD Immunity 24 B-pphase sensing input
Accessory Input EN50082-2 (4 kV contact, 8 kV air) 26 1- or
o 3-phase power input
Voltage Range: ±3 Vdc E
EFT Immunity
28 3-p
phase power input
EN50082-2 (2 kV coupling clamp)
Power Output M
Magnetic Immunity 30 1- or
o 3-phase power input
Maximum Continuous Output EN50082-2 (30 Arms, 50 Hz) F1 Field + connection
AVC63-12: 12 Adc at 63 Vdc S
Safety
F2 Field – connection
AVC125-10: 10 Adc at 125 Vdc EN61010-1
10 Second Forcing Output R
Radiated Immunity ADJUSTMENTS
AVC63-12: 24 Adc at 125 Vdc Electric Field: EN61000-4-3 (10 V/m)
AVC63-12 and AVC C125-10 adjustments are
AVC125-10: 20 Adc at 250 Vdc Conducted: EN61000-4-6 (10 Vrms)
described in the folllowing paragraphs.
Minimum Field Resistance T
Type Tests
Field Flashing
AVC63-12: 5.25 Ω S
Shock
AVC125-10: 12.5 Ω When the regulato or is operated with the
W
Withstands 20 G in each of 3 mutually per- generator for the first time, the residual
Regulation Accuracy pendicular planes. magnetism may no ot be of sufficient magni-
±0.5% of voltage setpoint, average response V
Vibration tude or the correct polarity. If the generator
Voltage Drift W
Withstands 4.5 G at 18 to 2,000 Hz residual voltage is less than 6 Vac for the
±0.5% variation for a 40°C (104°F) change P
Physical AVC63-12 or 12 Vac for the AVC125-10 at
terminals 26, 28 and/or 30, shut down the
Response Time T
Temperature
prime mover and proceed
p with the following
<4 ms O
Operating: –40 to 70°C (–40 to 158°F) steps.

Publication Revision g: 06/01


First Printing Copyright
9337200991 E Revised: 08/110 2010
CAUTION To allow operation of an external voltage 5. Check regulation under normal operat-
Do not flash the field when the genera- adjust control, remove the jumper between ing conditions.
tor is in motion. Regulator damage may terminals 4 and 7 and connect a 10 kΩ, If the regulation is poor:
result. external potentiometer across terminals 6a a. Check that the prime mover is up
and 7. The front-panel VLT ADJ control to rated speed.
1. With the prime mover at rest, apply an should be set fully clockwise for proper op-
ungrounded dc source of not more than eration of the external adjustment. Note that b. Check that the voltmeter is con-
24 Vdc to terminals F1 (+) and F2 (–) in as the external potentiometer resistance nected at the same point as the
series with a limiting resistor. Use 1 Ω increases, generator voltage also increases. regulator sensing.
of resistance for each volt applied. The c. Use an average-sensing voltmeter
power source should have a rating of at Factory Calibration (FAC CAL)
(not an rms-sensing voltmeter).
least 1 W/Ω. CAUTION 6. Reduce the generator frequency. The
EXAMPLE: If using a 24 Vdc source, The FAC CAL control is intended for use generator output should decrease from
use a 24 Ω, 24 W resistor. during factory calibration only. The fol- this point.
2. Allow the field to be flashed for approx- lowing procedure can be used if the fac- If the generator output voltage does not
imately 10 seconds before removing tory calibration has been disturbed. decrease at the desired frequency:
the dc source. 1. With the regulator operating on a gene- a. Check that all wiring is in accor-
3. If voltage buildup does not occur after rator, adjust the FAC CAL control fully dance with the connection dia-
performing steps 1 and 2, verify the po- counterclockwise and the external vol- grams provided in this instruction
larity of the dc source and repeat steps tage adjust control fully clockwise. sheet.
1 and 2. 2. Adjust the FAC CAL control clockwise b. Adjust the UF KNEE control.
Frequency Roll-Off (UF KNEE) until the generator voltage reaches the
OPTIONS
The underfrequency knee (roll-off) is typical- desired maximum voltage setting. The
regulator is calibrated and the FAC The AVC63-12 and AVC125-10 may be
ly set below the nominal system frequency. equipped with the following options to en-
When the generator speed falls below the CAL control can be sealed.
hance operation.
knee setpoint of the regulator, generator Parallel Droop Compensation
voltage is reduced proportionally to the Variable parallel droop compensation levels Remote Voltage Adjust
speed of the machine. To adjust the under- can be obtained by adjusting the DRP con- Connect a 10 kΩ, 2 W potentiometer across
frequency knee, perform the following steps. trol. Clockwise rotation increases the terminals 6a and 7, remove the jumper from
1. Adjust the generator frequency at the amount of droop for a given condition. terminals 4 and 7, and adjust the front panel
nominal level (50, 60, or 400 Hz). VLT ADJ control fully clockwise to enable
Line Drop Compensation remote adjustment of the voltage setpoint.
2. Adjust the UF KNEE control counter- When the sensing input CT connections are
clockwise. reversed to provide line drop compensation, Inrush Current Reduction Module
3. Adjust the VLT ADJ control for nominal the droop adjustment become the line drop A Basler ICRM-15 is required when energiz-
generator voltage. compensation adjustment. ing the AVC63-12 or AVC125-10 from a
4. Adjust the UF KNEE control clockwise source that is already at the regulator input
until the voltage begins to decrease. STARTUP power rating. The ICRM-15 minimizes the
Startup and troubleshooting procedures for amount of inrush current that could be seen
5. Adjust the UF KNEE counterclockwise
the AVC63-12 and AVC125-10 are listed in when power is applied.
until the voltage just returns to the val-
ue set in step 3. the following procedure. Symptoms of star- Excitation Disable
tup problems stemming from improper regu- This option disables excitation by removing
The underfrequency knee is now set just lator adjustments and certain generator
below the nominal operating frequency. power from the regulator. A switch removing
system problems that resemble faulty regu- voltage from terminals 26, 28 and/or 30 will
Further rotation in the counterclockwise lation are listed with possible solutions. Sim-
direction will lower the knee frequency set- remove regulator power.
plifying the system by eliminating compo-
point at which underfrequency compensa- nents, such as remote adjustment potenti- Excitation Limiter
tion just begins. ometers and other nonessential items, can The Basler EL 200 provides an initial, fast-
Connecting a jumper from terminal 8 to 6a be helpful in the troubleshooting process. acting limit of the field current at a user-
will provide an underfrequency slope of Adjustments, options, and an operational defined level. Once the field current has
1 PU V/Hz. No connection to terminal 8 will test are included in the paragraphs following changed to the selected level, the EL 200
result in an underfrequency slope of 2 PU the procedure. provides a signal to the regulator to change
V/Hz. The slope can also be selected on the 1. Ensure that the regulator has been the excitation level.
400 Hz models. However, the actual V/Hz installed in accordance with the Instal-
curve is approximately 1 PU or 2 PU, de- Var/Power Factor Control
lation and Connections paragraphs be- This option enables the AVC63-12 and
pending if terminal 8 is jumpered to 6a. fore proceeding with system startup. AVC125-10 to regulate the var and power
Stability (STB) 2. Start the prime mover and bring it up to factor while the generator is connected to an
An oscilloscope or other voltage recording rated speed. infinite or utility bus. The Basler SCP 250
device should be used in an optimal stability If the voltage does not build up: supplies a dc signal into terminals 2 and 3 of
setting is desired. Adjust the stability setting a. Flash the field. the regulator to correct for vars or power
with the generator at no load. factor. Figure 7 illustrates regulator and SCP
b. Remove power for one minute to
Clockwise rotation of the STB control will 250 interconnection.
reset the overexcitation circuit.
slow response time. Counterclockwise rota- Current Boost System
tion will speed response time. If rotated too 3. Slowly adjust the VOLT potentiometer
far counterclockwise, the generator voltage or external, voltage adjust rheostat until With the CBS 212 option, if the generator
may oscillate (hunt). the voltage reaches nominal. output voltage decreases below the preset
If the voltage will not build up to rated: operating point due to a short or large motor
To obtain good response, rotate the STB starting, the CBS 212 provides full current
control counterclockwise until the system Check the generator output for a
boost to the generator exciter until the vol-
just begins to oscillate. Then, rotate the shorted or excessive load.
tage returns to a level just above the operat-
control clockwise just past the point where 4. Apply and remove the generator load ing point.
oscillation occurred. Apply various amounts to check stability.
of load to determine proper stability perfor- Manual Voltage Control
If the generator response is too slow or
mance. is hunting (oscillating): The Basler MVC-112 provides a method for
Voltage (VLT ADJ) manually controlling the generator output
a. Check the generator output for a
during generator startup and commissioning
Installation of a jumper across terminals 4 shorted or excessive load. Adjust
or in the unlikely event of a regulator failure.
and 7 enables the front-panel VLT ADJ the STB potentiometer with no
Model MVC-112 is suitable for use with
control to vary the generator nominal voltage load applied.
either the AVC63-12 or AVC125-10 voltage
over the operating range. b. Check stability of the governor. regulator.
OPERATIONAL TEST To test regulator operation, perform the MAINTENANCE
This test verifies the operation of all eight following steps. A periodic inspection of the regulator should
models of the AVC63-12 and AVC125-10. 1. Connect the regulator according to be made to ensure that it is clean and free
Table 2 lists each regulator model and the Figure 9 and apply the appropriate vol- from accumulations of dust and moisture.
corresponding test voltage and frequency. tages. Ensure that all connections are clean and
Table 2. Testing Parameters 2. Adjust the VLT ADJ control fully coun- tight.
Input terclockwise. TROUBLESHOOTING
Observe that the lamp is off. In case of regulator failure or defective op-
Sensing
Power 3. Adjust the VLT ADJ control clockwise. eration, simplifying the system by eliminating
Model Vac Hz
Observe that the lamp turns on. components such as remote adjust potenti-
AVC63-12A1 120 120 50/60 ometers and other non-essential items can
4. Adjust the VLT ADJ control until the
AVC63-12A2 120 120 400 lamp just turns off. be helpful in the troubleshooting process.
AVC63-12B1 120 240 50/60 Regulator operation is satisfactory if the
AVC63-12B2 120 240 400 above results are obtained. However, stabili-
AVC125-10A1 240 120 50/60 ty must be tested with the generator and
regulator in operation.
AVC125-10A2 240 120 400
AVC125-10B1 240 240 50/60
100
AVC125-10B2 240 240 400

Time In Seconds
Shutdown Region
250 10
Terminal Voltage

200
150 Ideal 1 PU/Hz

1
100
Ideal 2 PU/Hz 210 230 250 270 290 310 330 350
50
DC Output Voltage
0
20 25 30 35 40 45 50 55 60 65 Figure 4. AVC12510 Overexcitation Shutdown Characteristics
Frequency In Hertz

Figure 1. 60 Hz Frequency Compensation

250
Terminal Voltage in Volts

200
Ideal 1 PU/Hz
150

100
Ideal 2 PU/Hz

50

0
150 200 250 300 350 400 450
Frequency in Hertz

Figure 2. 400 Hz Frequency Compensation

100
Time In Seconds

Shutdown Region
10

1
70 90 110 130 150 170 190 210 230
DC Output Voltage

Figure 3. AVC63-12 Overexcitation Shutdown Characteristics Figure 5. Outline Drawing


Part of 3 L
AVC63-12 Part of
2 C
or P0009-25 EL200
AVC125-10 08-15-05

AVC units may be connected to either the


EL 200 or the SCP 250 using the
A
terminals as shown in place of this series
interconnection. See the unit instruction C Part of
manuals for more information. SCP250
When the AVC receives a positive voltage
(terminal 2 positive, terminal 3 negative)
at the Accessory input, the setpoint
decreases. A negative voltage (terminal 2
negative, terminal 3 positive) at the
Accessory input increases the setpoint.

Figure 7. AVC Interconnection Diagram


CT
GEN 1
52 1

0.1
6
AVC 52b 1
5 or 5A
CCC
0.1 ENABLE
6
CONTACT
AVC 52b 2
5 or 5A
LOAD

GEN 2
CT 52 2
0.1
6
AVC 52b 3

P0009-26.vsd
5 or 5A

08-10-01
52 3
GEN 3
CT

Figure 8. Cross-Current Compensation

100 W
Lamp
Input Sensing
Power Voltage
10 20
ohms ohms

F1 F2 26 28 30 20 22 24

AVC63-12 or AVC125-10
D2590-33
03-24-06

CH
GND
2 3 4 5 5a 6 6a 7 8 9
Figure 6. Typical Interconnection Diagram

1 A wire-wound resistor with a minimum


power rating of 15 W should be used.

Figure 9. Operational Test Setup

You might also like