Professional Documents
Culture Documents
DESIGN APPROACHES
Original sprinkler spacing, pipe size or water delivery capacity might not
control the new storage or layout.
In the design of wet type Automatic Fire Sprinkler System,
NFPA 13 identifies three (3) design approaches where
water demand requirement shall be determined
This is the most common design approach used in Automatic Fire Sprinkler
System. There are two ways to design a sprinkler system:
Pipe schedule method – uses tables that indicate that steel pipe of certain size
will supply a certain number of heads.
Therefore, pipe is sized to deliver the required flow and pressure each
head in the area of operation and size the pipe back to the system water
supply in order to deliver the demand for the area of operation.
Area of Operation – Hydraulic Calc. Method
This figure establishes the quantity of sprinklers required open to contain and
extinguish the fire within the area of operation. It also establishes the number
of heads to be hydraulically calculated.
The flow required from a sprinkler is determined by the area “covered by the
sprinkler multiplied by the desired density.
The product obtained means that all sprinklers in the design area must
discharge at least this amount of water flow calculated.
This design approach shall be applied for the protection of the following:
a. Plastic commodities
b. Commodities that are stored in Wooden or Plastic Pallets, Solid Piled,
Bin Boxes, Shelf and Multiple Racks storage
c. Plastic, Rubber Tires and Rolled Paper and related hazard commodities
(Class 1 to Class 4 commodities)
NFPA 13 Chap. 13 defines that Special Occupancy Design Approach shall only be
apply to meet the requirements of arrangements and commodities that includes:
a. Flammable and Combustible Liquids
b. Aerosol Products
c. Solvent Extraction Plants
d. Nitrate Film
e. Storage or vaults containing Pyroxylin Plastics
f. Laboratories Using Chemicals
g. Oxygen-Fuel Gas Systems for Welding, Cutting and Allied Processes
h. Acetylene Cylinder Charging Plants
i. Production, Storage and Handling of Liquefied Natural Gas
j. Electronic Computer Systems and Data Centers
k. Ventilation Control and Fire Protection of Commercial Cooking Operations
l. Piers, Terminals and Wharves
m. Aircraft Hangars
n. Storage of Organic Peroxides
The use of Wet Type Automatic Sprinklers has to be carefully studied since the
use of water in some of the above occupancies is not advisable.
The fire protection design for this should meet the requirement of separate NFPA
standards.
The use of Pipe Schedule is also a recognized method in
installing Automatic Fire Sprinkler System under the
Occupancy Hazard Fire Control Approach (NFPA 13, Chap. 11)
Pipe Schedule Method shall not be used, except in existing systems or extensions to
existing systems.
Pipe Schedule Method shall be permitted only for new installations of 5,000 ft 2 (465 m 2 )
or less or for additions or modifications to the existing pipe systems that is sized according
to Pipe Schedule.
Pipe Schedule Method shall be permitted for use in systems exceeding 5,000 ft 2 (465m 2)
where the flows required as specified in the table below are available at a minimum
residual pressure of 50 psi (3.4 bar) at the highest elevation of sprinkler.
The residual pressure requirement shall be met at the elevation of the highest sprinkler.
The lower duration value of the table shall be acceptable only where remote or central
station water flow alarm service is provided. If not, then use the higher value of duration.
The lower flow value shall be permitted only where the building is of non-combustible
construction or the potential areas of fire are limited by building size or compartmentation
such that no open areas exceeded 3000 ft 2 (279 m2) for light hazard or 4000 ft2 (372 m2)
for ordinary hazard.
The use of Pipe Schedule method is limited only for Light and Ordinary Hazard
occupancies.
Pressures and flow requirements for extra hazard occupancies shall be based on the
hydraulic calculation methods.
Sprinkler systems having sprinklers with K-factors other than 5.6 nominal, extra hazard
Groups 1 and 2 systems, and exposure protection systems shall be hydraulically
calculated.
In using the pipe schedule design method, the number of
sprinkler heads on a given pipe size on one floor shall not
exceed the number specified for each classification of
occupancies.
On Branchlines
Sprinkler heads for each branch line shall not exceed eight (8) on either
side of a cross main.
STEEL COPPER
SIZE NO. OF SPRINKLER SIZE NO. OF SPRINKLER
HEADS HEADS
1 in. 2 heads 1 in. 2 heads
1-1/4 in. 3 heads 1-1/4 in. 3 heads
1-1/2 in. 5 heads 1-1/2 in. 5 heads
2 in. 10 heads 2 in. 12 heads
2-1/2 in. 30 heads 2-1/2 in. 40 heads
3 in. 60 heads 3 in. 65 heads
3-1/2 in. 100 heads 3-1/2 in. 115 heads
4 in. See Section 8.2 4 in. See Section 8.2
STEEL COPPER
Total Combined
Occupancy Inside Hose Inside and Outside Duration
(gpm) Hose (gpm) (minutes)
• Add the hose demand for the highest hazard classification within
the system, or
• Where the higher classification only lies within single room less
than or equal to 400 ft2 (37.18 m2 ) in area with no such rooms
adjacent, add the hose demand for the principal occupancy for the
remainder of the system.
a. In using Room Design Method, the water supply requirements for sprinklers
(except for hose stream requirement) shall be based upon the room that
creates the greatest demand.
b. To utilize the room design method, all rooms shall be enclosed with walls
having a fire-resistance rating equal to 30 min for Light Hazard, 60 minutes for
Ordinary Hazard and 90 minutes for Extra Hazard.
RESIDENTIAL SPRINKLERS
a. The design area shall be the area that includes the four hydraulically most
demanding sprinklers.
NFPA 13, Chapter 8, Section 8.2 states that the maximum floor area on
any one floor to be protected by sprinklers supplied by any one sprinkler
system riser or combined system riser shall be as follows:
3. Extra hazard
a) Pipe schedule – 25,000 square feet (2,323 square meter)
b) Hydraulically calculated – 40,000 square feet (3,716 square meter)