You are on page 1of 1

Minimum width 900 See detail

below
Fabric reinforcement I / I~
Dowel bar ~ l~~-~~-' / -1 \
Concrete slab
Reinstated slab
J
~
150 min. I
Subbase )
0.125 Thick ~ .. . Compacted .~ "--. /
polythene
sheeting
. backfill· .. ~Granularl
Extent of" trench lean concrete
subbase 150

EXISTING CONSTRUCTION PERMANENT REINSTATEMENT


sow cut
Nomlnal5mm'I 'lEdge E

Cover 60:1:10 I ~ll~proved sealing strip

r:: Holes drilled to receive


J

2fI rI j
~
dowel bars at 600 centres
-~-1--~-~--125±
at mid-depth

I I I ~

Concrete slob I ! 325 \ 325 I Epoxy resin

-----------1--- \ ~ 75
.'c=

I.
Granular 1 tight fitting
lean concrete 150 _I PVC anti-corrosive
subbase co
min. sleeve or PVC tape
'"
Dowel bar at ri'ght an~l~ ~ ""
to cut face

Extent of trench ~
DETAIL OF CONSTRUCTION JOINT
Notes
I. The subbase to be put back shall be of granular material 6. The reinstatement area shall be of sufficient width to
(or lean concrete if the existing construction is of the enable dowel holes to be drilled subject to a minimum
same material), and shall be of the same thickness as of 900.
the adjoining pavement subject to a minimum of 150. 7. Refer to Drg. No. H1125 for limit of reinstatement
2. The concrete road slab to be put back shall be of Grade 8. Existing slab to be thoroughly moistened with water
40/20 concrete and shall be of the same thickness as before concreting.
the adjoining pavement. 9. All dimensions are in millimetres.
3. Fabric reinforcement shall be C503 long mesh or of the
existing type whichever is heavier and shall be laid
with the main bars parallel to the longer dimension
of the reinstatement area.
4. Dowel bars shall be mild steel bars of diameter 25.
dowel bars shall be provided on all sides of the
C Joint groove details revised. June 05
reinstatement area except where it abuts a transv erse
B Joint groove details revised Nov 96
joint or longitudinal joint.
5. All transverse joints and longitudinal joints removed or A Minimum distance from trench revised Sept 96
damaged by the works shall be reinstated to the some Former Drg. No. H1018/2A with
general revision June 94
type and alignment. Refer to Drg. No. Hl126 for details.
REF. REVIS I ON SIGNATURE DATE

PERMANENT REINSTATEMENT HIGHWAYS DEPARTMENT


OF PAVEMENT - REFERENCE DRAWING No. I CAD
CONCRETE CARRIAGEWAY SCALE H 1124C
(SHEET 1 OF 2) N. T. S.