You are on page 1of 4

D.C.

Resistance
CENELEC CLC/TR 50480

The d.c. resistance of cables can be estimated in accordance with CENELC technical report
CLC/TR 50480 "Determination of cross-sectional area of conductors and selection of protective
devices", dated February 2011.

For a conductor:

R=ρ20S
where R = d.c. resistance of the cable Ω.m-1
ρ20 = electrical resistivity of conductor material at 20 °C, Ω.m
S = cross sectional area of conductor, m2 [or 1e-6 mm2]

An alternative to calculating the d.c. resistance is given by IEC 60228 "Conductor of insulated
cables". The standard has tables of maximum allowable resistance for various copper and
aluminium cables. For more details see IEC 60228 DC Resistance

Typical resistivities can be found in the Useful Tables part of the Knowledge Base.

IEC 60228 and IEC 60909-2

The standard IEC 60228 'Conductors of Insulated Cables' specifies the maximum allowable
resistance for conductors. Values given in the IEC 60228 standard are used within
myCableEngineering.com. For situations and cables not covered by IEC 60228, then resistance
values are calculated using the CENELEC formulae.

Resistance calculated above, is valid for unscreened cables. For screened (or any type of
magnetic shield) cables, with the metallic screen earthed at both ends, the resistance increases as
depicted in IEC 60909-9 'Short-circuit currents in three-phase a.c. systems - Part 2: Data of
electrical equipment for short-circuit current calculations' table 7. See Impedance for more
details.

A.C. Resistance
The ac resistance of a conductor is always larger than the dc resistance. The primary reasons for
this are 'skin effect' and 'proximity effect', both of which are discussed in more detail
below. Calculation of the a.c. resistance is derived from equations given in IEC 60287
"Electric cables - Calculation of the current rating".

Skin and proximity effects into account with the following formulae:

Rac=R[1+γs+γp]
where
Rac = the ac resistance of the conductor
R = the dc resistance of the conductor
ys = a skin effect factor
yp = a proximity effect factor

While the above formulae is pretty straight forward, working out the skin and proximity effect
factors is a little more involved, but still not too difficult.

Skin Effect

As the frequency of current increases, the flow of electricity tends to become more concentrated
around the outside of a conductor. At very high frequencies, often hollow conductors are used
primarily for this reason. At power frequencies (typically 50 or 60 Hz), while less pronounced
the change in resistance due to skin effect is still noticeable.

The skin effect factor ys is given by:

γs=X4S192+0.8X4S

with X2s=8πfR10−7ks
where:
f = supply frequency, Hz
ks = skin effect coefficient from the table below

Proximity Effect

Proximity effect is associated with the magnetic fields of conductors which are close together.
The distribution of the magnetic field is not even, but depends on the physical arrangement of the
conductors. With the flux cutting the conductors not being even, this forces the current
distribution throughout the conduit to be uneven and alters the resistance.

The formulae for the proximity effect factor differs dependant on wether we are talking about
two or three cores.

γp=Xp4192+0.8Xp4(dcS)2×2.9

- two core cables or two single core cables

γp=Xp4192+0.8Xp4(dcs)2×⎛⎝⎜0.312(dcs)2+1.18Xp4192+0.8X4p+0.27⎞⎠⎟
- for three core cables or three single core cables
where (for both cases):

X2p=8πfR10−7kp
dc = diameter of the conductor (mm)
s = distance between conductor axis (mm)
kp = proximity effect coefficient from the table below

Note:
1. for three single core with uneven spacing, s = √(s1 x s2)
2. for shaped conductors, yp is two-thirds the value calculated above, with
dc = dx = diameter of equivalent circular conductor of same cross-sectional area (mm)
s = (dx + t), where t is the thickness of insulation between conductors (mm)

* for s, we can gain some advantage by using the geometric spacing. See: Geometric Mean
Distance .

Coefficient ks and kp

ks
kp
Round stranded or solid 1 1
Copper Round segmental 0.435 0.37
Sector-shaped 1 1
Round stranded or solid 1 1
Round 4 segment 0.28 0.37
Aluminium
Round 5 segment 0.19 0.37
Round 6 segment 0.12 0.37

Temperature Adjustment
The d.c. resistance of a conductor is dependent on temperature:

Rt=R20[1+α20(t−20)]
where Rt = resistance of conductor at t °C
R20 = resistance of conductor at 20 °C
t = conductor temperature, °C
α20 = temperature coefficient of resistance of material at 20 °C

Typical temperature coefficients can be found in the Useful Tables part of the Knowledge Base.

CABLE OPERATING TEMPERATURE


At zero current the cable conductor temperature will be the same as the ambient temperature. At
the the maximum sustained current rating the cable will be at the insulation limiting temperature
(typically 70 °C for thermoplastic insulation and 90 °C for thermosetting insulation). At a
current ratings between these extremes the cable temperature will be at a value between ambient
and the limiting temperature.

The cable operating temperature can be found from:

t=(IbIz)2×(Tc−Ta)+Ta
where Ib = cable design current, A
Iz = sustained current rating of cable, A
Ta = ambient temperature, °C
Tc = conductor [insulation] limiting temperature, °C