DESIGN BASE SHEAR COMPUTATIONS

WEIGHT OF SUPERIMPOSED DEAD LOADS WEIGHT OF COLUMNS PER FLOOR

DEAD
UNIFORM LOAD(Kn/m^3 NUMBER OF
FLOOR FLOOR AREA(sqm) LOAD (kPa) WEIGHT(kN) FLOOR ) AREA HEIGHT WEIGHT COLUMNS TOTAL
1 240 3.8 912 1 23.6 0.25 3 17.7 20 354
2 240 3.8 912 2 23.6 0.25 3 17.7 20 354
3 240 3.8 912 3 23.6 0.25 3 17.7 20 354
4 240 3.8 912 4 23.6 0.25 3 17.7 20 354
DECK 240 3.8 912
WEIGHT OF SLAB
WEIGHT OF STAIRS

DEAD
LOAD(Kn/m^3
FOR WEIGHT OF LIVE LOAD FLOOR ) AREA THICKNESS WEIGHT
FLOOR LIVE LOAD (kPa) AREA WEIGHT(kN) 1 23.6 240 0.3 1699.2
1 4.8 0.95 4.56 2 23.6 240 0.3 1699.2
2 4.8 0.95 4.56 3 23.6 240 0.3 1699.2
3 4.8 0.95 4.56 4 23.6 240 0.3 1699.2
4 4.8 0.95 4.56 DECK 23.6 240 0.3 1699.2
DECK 4.8 0.95 4.56
BEAM SELF WEIGHT = 0.885 kN/m
WEIGHT OF DEAD LOAD
FOR TOTAL BEAM WEIGHT PER FLOOR
AREA OF STAIRS = 9 sqm NUMBER OF 4m BEAMS = 15
NUMBER OF 5m BEAMS = 16
DEAD
FLOOR LOAD(Kn/m^3) AREA STAIR HEIGHT WEIGHT(kN)
1 23.6 9 3 637.2 FLOOR WEIGHT TOTAL WEIGHT PER FLOOR
2 23.6 9 3 637.2 1 647.466
3 23.6 9 3 637.2 2 647.466 FLOOR TOTAL W
4 23.6 9 3 637.2 3 647.466 1 4254.426
DECK 23.6 9 3 637.2 4 647.466 2 4254.426
DECK 647.466 3 4254.426
4 4254.426
DECK 3900.426
20918.13
w=3900.526

3m
w=4254.426

3m
w=4254.426

3m
w=4254.426

TOTAL WEIGHT= 20918.13

3m
PARAMETERS
STANDARD OCCUPANCY: COMMERCIAL Fx= (V-Ft)(WxHx) V= 2953.006588
SOIL TYPE: Sc WiHi
5 km AWAY FROM FAULT
SMRF, R=8.5
IMPORTANCE FACTOR, I=1 FLOOR Wx Hx WxHx Fx
ZONE 4,Z=0.4 2 4254.426 3 12763.278 305.46455941
SEISMIC SOURCE TYPE, A 3 4254.426 6 25526.556 610.92911883
4 4254.426 9 38289.834 916.39367824
NEAR SOURCE FACTOR FOR T: DECK 3900.526 12 46806.312 1120.2192315
Na= 1.2 T= Ct(Hn)^0.75
Nv= 1.6 T= 0.5499648911 WiHi= 123385.98
Ca=0.4(1.2) T is less than 0.7
Ca=0.48 therfore, Ft=0
Cv=0.56(1.6)
Cv=0.896
Ct= 0.0853
CONDITIONS
1 V= CvIW/RT 4009.3777499279
2 V=2.5CaI/R 2953.0065882353 4009.38<2953.01
THERFORE, USE 2953.01 Kn