BILLS OF QUANTITIES

SUMMARY

BILL DESCRIPTION AMOUNT (excl. VAT)

SECTION A - CIVIL WORKS

A1 PREAMBLES
A2 CONCRETE WORKS
A3 CONCRETE REINFORCEMENT
A4 MASONRY AND BRICKWORK
A5 ROOFING WORKS, WATER AND DAMP PROOFING
A6 ALUMINIUM WORK
A7 METAL WORKS
A8 FINISHES TO WALLS AND CEILINGS
A9 FLOOR FINISHES
A10 JOINERY AND SUSPENDED CEILING WORKS
A11 SANITARY FITTINGS
A12 DAYWORKS
SUB TOTAL FOR CIVIL WORKS

SECTION B - MECHANICAL WORKS

B1 EXTRACTOR FAN
B2 VRV TYPE AIR CONDITIONING SYTEM
B3 VENTILATION SYSTEM HEAT RECOVERY UNITS
B4 HOT AND COLD WATER SERVICES
SUB TOTAL FOR MECHANICAL WORKS

SECTION C - ELECTRICAL AND EXTRA LOW VOLTAGE SERVICES

C1 ELECTRICAL INSTALLATION
C2 EXTRA LOW VOLTAGE SERVICES

SUB TOTAL FOR ELECTRICAL WORKS

TOTAL EXCLUDING VAT

VAT AT 18%

241
TOTAL VALUE OF THE WORKS INCLUDING VAT

242
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A1 Preambles

1.01 Site visit to familiarise with site conditions and limitations

1.02 Allow of the temporary replacement of all services at roof level 1 Sum

1.03 Allow for all the required testing by an independent laboratory 1 Sum
in accordance with specifications.

1.04 Manufacture, supply and erect where indicated a weather proof 1 Sum
project sign boards, measuring a minimum 1200mm high x
2400mm wide, Contractor is responsible for all permits
required.

1.05 Care is to be taken during demolition works to minimize


disturbance to remaining buildings and to protect existing
services, floor/wall finishes and apertures.

1.06 In case of damage to items in 1.04 above, Contractor is to


make good for all such damage immediately. In case of failure
to do so, Client will commission the required repairs and back
charge Contractor for the costs.

1.07 All rates are to include double handling where this is the case,
no claims will be accepted for double handling of material
and/or supplies.

1.08 Provision for insurance (CAR - contractor all risk) during the
progress of works, and for a period of 15 years after
completion.

1.09 Removal of existing membrane at roof level and cart away 732 m2

1.10 Removal of existing 'kontrabejt' at roof level and cart away 560 m2

1.11 Removal of existing 'apromorta' at roof level and cart away 130 m2

Total for Bill A1 : Preambles

242
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A2 Concrete Works

All rates for concrete are to include for the supply placement
and all the required testing by an independent laboratory in
accordance with specifications.

Rates for all concrete items requiring formwork are to


include for all the necessary formwork, and scaffolding and
other tools as may be required.

All steel reinforcement shall be measured and paid for


separately (except for precast concrete elements).

All rates for reinforcement are to include for the supply,


cutting, bending, fixing, placing in position and testing in
accordance with specifications.

All rates for steel reinforcement are to include for the


preparation and submission for approval of bar bending
schedules in accordance with specifications.

Concrete grade C20 in:

2.01 In cavities of 230mm thick hollow concrete block walls (area 50.00 m2
of walls measured).

2.02 Between skins of walls max. thickness 150mm. rate only m3

Concrete grade 25 in:


Suspended slabs:
2.03 150mm thick. 115.00 m2
2.04 200mm thick. 85.00 m2
2.05 250mm thick 120.00 m2
2.06 300mm thick 335.00 m2

Concrete grade 30 in:


2.07 Suspended beams and lintols (stem only measured) 25.00 m3
(sectional area 0.10 - 0.25m2).

Extra over for:


2.08 Using concrete grade 30 instead of Grade 25. Rate only m2

Sika 1/ Plastocrete N additive waterproofer or approved


equal in:

2.09 Concrete Grade C30 Rate only m3

2.10 Concrete Grade C25 Rate only m3

243
Total for Bill A2 : Concrete Works

244
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A3 Concrete Reinforcement

Bending of reinforcement shall conform with Eurocode 2.

Steel mesh fabric reinforcement shall confirm with Eurocode 2


or latest update. It shall have a minimum specified
characteristic strength of 460N/sq.mm.

The Contractor is to provide all necessary mild and high yield


steel and is also to supply:

Manufacturer's name;

Manufacturer's routine work certificate

The ladle analysIs for all reinforcement supplied when


required to do so by the Architect.

High Yield Steel Bar Reinforcement including supply, cut,


bend and fix
3.01 32mm diameter 250 kg

3.02 25mm diameter 2,000 kg

3.03 20mm diameter 1,000 kg


3.04 16mm diameter 750 kg

3.05 12mm diameter in stirrups 650 kg

Steel Mesh Fabric Reinforcement

Supply and lay in position steel mesh fabric


reinforcement to Eurocode 2. Measured net rate to
include for lapping and wastage.

3.06 Type A98 Rate m2


only
3.07 Type C503 1,270 m2

Total for Bill A3 : Concrete Reinforcement

244
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A4 Masonry and Blockwork

(i) Masonry and Blockwork walls shall be measured in


square metres, stating the thickness of the overall section.

(ii) Projecting features on walls exceeding 25mm are to be


measured separately in linear meters.

Soft stone walls fair faced both sides bedded and


jointed in accordance with specifications.

4.01 350mm thick wall 2 No. 175mm skins 350 m2

4.02 230mm thick wall rate only m2

4.03 150/175mm thick wall rate only m2

Precast hollow concrete blocks in:

230mm thick hollow concrete block walls, bedded and


jointed according to specifications.
4.04 Double density blocks 500 m2
4.05 Single density blocks 30 m2

4.06 150/175mm thick hollow concrete block walls, bedded and 30 m2


jointed according to specifications.

Extra over for:


4.07 Chamfer not exceeding 50mm wide. rate only m
4.08 Squint angle "Skwerra Falza". rate only no.
4.09 Plain projected bans ("faxex u membri") 75 m
4.10 Pointing '"fuq il-fil" finish 200 m2

4.11 Moulded string course 273mm high and 150mm projection 50 m


straight or curved (tlibbisa).
4.12 Voussoirs (Sammrotti) in flat arches rate only no.

4.13 Sleeves inserted in Concrete Blockwork for wiring services. 7 no.


Plastic sleeves to be approx. 60mm diameter.

Softstone Coping

4.14 230m wide x 170mm high with weathered top, set on 125 m
parapet wall.

245
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

Total for Bill A4 : Masonry and Blockwork

246
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A5 Roofing Works, Water & Damp Proofing

5.01 Remove existing concrete screed (kontrabejt), membrane, 650 m2


torba, and any other insulating materials on existing roof. Rate
to include for carting away to an approved site.

5.02 Remove existing floor tiles in existing room at roof structure 60 m2

5.03 Import and spread out torba over proposed concrete roof. 90 m3
Rate to include for levelling due to different slab depths

5.04 Horizontal damp proofing course HiLoad DPC or approved 50 m2


equal.

5.05 Supply and apply as per manufacturer's instructions, as and 700 m2


when directed, one coat of a minimum 500g/m2 solvent based
primer coat. Primer is not to be applied to wet ot water logged
areas.

5.06 Supply and lay 4kg/m2 polyester reinforced bituminous, torch 1,050 m2
welded water proofing membrane, with 300mm turnups to
vertical surfaces. To horizontal surfaces. PROVISIONAL

5.07 Extra over waterproof membrane for working over expansion rate m
joint. only

5.08 Construct cement sand triangular fillet 125 m

5.09 75mm thick concrete screed ("kontrabejt"), Grade C20 with 650 m2
10mm diameter chippings, laid to falls and current with a
power float finish, cast in appropriate bays, separated by
expansion joints (included)

5.10 Expanded Polystyrene sheets, laid directly on waterproofed 650 m2


concrete roof, 100mm thick, density 15kg/m3

Total for Bill A5 : Roofing Works, Water & Damp Proofing

246
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT (excl.


ITEM DESCRIPTION QTY UNIT
VAT) VAT)

A6 Aluminium Work

Preamble

Notes Refer to Drawings.


a) The Tenderer shall ascertain the actual dimensions of the
aperture openings on site prior to the submission of the Tender.

b) All rates shall mean to include all costs, both direct and
indirect, in connection with the manufacture, transport, placing,
alignment, fixing and sealing of all Aluminium works in this Bill
of Quantities.

c) All rates shall mean to include all costs, both direct and
indirect for the cleaning of all floors, fittings, windows, doors,
glazing, casements and accessories from shavings, dust, finger
marks and carting away of waste material.

Doors and Windows


Double-glazing shall consist of two sheets (6mm thick external
sheet and 6mm internal sheet) laminated glass with 12mm gap
with partial vacuum.

The glazing shall be hermetically sealed with aluminium


spacers set in EPDM gaskets, the gaskets shall be continuous
along the whole of the perimeter of the glazing panes to which
they are applied.

The glazed aluminium units shall be hinged and shall have an


outward opening mechanism. Aluminium Units are to be
installed on the inner face of the external wall. Design is to
ensure that all external faces of the glass can be cleaned
safely; supplied with detachable opening devices, and restrictor
stays fitted to ensure that the opening complies with the
necessary health and safety requirements unless otherwise
indicated. Top hung sections shall have a side hanging
mechanism.

The apertures shall have lever type of handles. All hardware


and its fastenings shall be of suitable material resistant to
atmospheric corrosion.

Apertures shall be supplied complete with all ironmongery.

All apertures shall be lockable.

247
The aluminium frame system shall be capable of absorbing
thermal movements. The frame shall be using compatible and
suitably sized adjustable frame screws and plastic spacers.
The gaps between the frame and the stone/concrete shall be
sealed with mineral wool to prevent any air movement.

The aluminium units shall be black anodised finish


mechanically treated as per specifications with minimum
coating of 15 microns. The surface shall have a matt texture.

Double glazed window units shall be manufactured from 3-


compartment extruded aluminium sections. The windows shall
be supplied complete with all ironmongery.

Rates are to include for all aluminium sections to be in black


finish. Rates for doors and windows are to include for all
necessary glazing, ironmongery and for sealing with weather
proof sealant both internally and externally.

Windows

6.01 Windows type A measuring 1900mm wide by 1500mm high. 5 no.


Glazing in double glazing

6.02 Windows type B measuring 1900mm wide by 1000mm high. 9 no.


Glazing in double glazing

6.03 Windows type C measuring 1100mm wide by 1100mm high. 1 no.


Glazing in double glazing

6.04 Windows type D measuring 750mm wide by 1100mm high. 2 no.


Glazing in double glazing

6.05 Windows type E measuring 1250mm wide by 1100mm high. 17 no.


Glazing in double glazing

6.06 Windows type G measuring 6500mm wide by 1350mm high. 1 no.


Glazing in double glazing

6.07 Windows type H measuring 1880mm wide by 1350mm high. 3 no.


Glazing in double glazing

6.08 Windows type I measuring 1670mm wide by 1350mm high. 3 no.


Glazing in double glazing

Doors
6.09 Door type B measuring 1000mm wide by 2200mm high. 1 no.
Glazing to be in laminated glass

248
6.10 Door type C measuring 1000mm wide by 2200mm high. 1 no.

Total for Bill A6 : Aluminium Work

249
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A7 Metal Works

Externally

7.01 Manufacture, supply and install galvanised steel fire 1 no.


escape as per existing structure. Rate is to include for
any supports and making good of existing structure.
Extension to include two floors

Total for Bill A7 : Metal Works

249
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A8 Finishes to Walls and Ceilings

Rendering

8.01 Render surfaces of concrete/brick walls internally in one coat 6mm 550 m2
thick in a gypsum based coat.

8.02 Render surfaces of concrete ceilings/beams internally in one coat 300 m2


limewash

8.03 Render surface of brick walls externally (in shafts, parapet walls, etc.) 225 m2
in two coats 6mm base coat in cement and sand (1:3) and 3mm
setting coat on cement:lime:sand (1:1:6) including two coats "xahx" or
limewash as directed by the Architect-in-charge

Pointing
8.04 Clean down, scrape where required, rake out joints and point with 500 m2
lime mortar surfaces of stone walls internally area only, including two
coats of limewash.

8.05 Clean down, scrape where required, rake out joints and point with 250 m2
lime mortar surfaces of stone walls externally, as directed by the
Architect in charge.

Sundries
8.06 Apply 1 mist coat and 2 full coats of water emulsion paint to all walls. 1,350 m2

8.07 Apply two coats of approved water based coloured sand paint on 225 m2
rendered surfaces externally as directed.

Supply and install, approved plastic ventilating holes covers and


fixed where directed.
8.08 a) internal type 22 no.

8.09 b) external type 22 no.

Total for Bill A8 : Finishes to Walls and Ceilings

250
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A9 Floor Finishes

Preamble

All work shall be measured net as laid. Rates are to include for
all waste and straight or raked cutting.

Beds

9.01 Bed of torba 100mm (average) thick, spread and levelled to 660 m2
receive tiles.

Tiles

9.02 Supply and lay internal type, first quality, ceramic gres floor tiles 660 m2
450mm x 450mm medium size, including for laying and
grouting

9.03 Supply, lay and grout internal type, first quality, glazed ceramic 50 m2
wall tiles, 200mm x 200mm to include for 1 in no. 400mm high
base border and 200mm high upper border having a different
colour.

9.04 Supply and lay best quality 200mm x 200mm ceramic floor tiles 120 m2
(minimum 6mm thickness) in bathrooms and laboratories
including laying and grouting. Colour, size and/or pattern, if
any, to be decided by the Architect in charge upon submission
of samples by contractor.

9.05 Provide and lay resin skirting 175mm high x 18mm thick with 300 m
chamfer edge. Rate is to include fixing with adhesive and
grouting of joints.

Total for Bill A9 - Floor Finishes

251
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT (excl.


ITEM DESCRIPTION QTY UNIT
VAT) VAT)

A10 Joinery and Suspended Ceiling Works

Preamble
i) Rates for internal joinery are to include for the manufacture
and fixing in white deal of doors and other fittings inclusive of
all necessary frames/linings, architrave's, glazing,
ironmongery, and finishing where necessary.

Doors Internally
10.01 Door type A,1200mm x 2300mm, in Door Schedules Booklet 7 no.
and fixing (class-room door - White deal).

10.02 Bathroom door measuring 1000mm x 2200mm - 2 no.


specifications as per Door A above

10.03 Bathroom door measuring 800mm x 2200mm - specifications 1 no.


as per Door A above

Suspended Ceilings
10.04 Supply, transport, assemble and fix suspended ceiling 660 m2
consisting of 600mm x 600mm tiles, supported by a ceiling
hung frame structure. Rate is to include all required
bulheads around the stair well

Total for Bill A10 : Joinery and Suspended Ceiling Works

252
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A11 Sanitary Fittings

11.01 Supply and fix close coupled water closet (WC) in white 2 no.
vitreous china, complete with wall enchased flushing
including heavy duty toilet cover. Rate to include all
necessary connections

11.02 Suppply and fix wash hand basin in white vitreous china 2 no.
approx. 450mmx300mm complete with pedestal, including
monoblock basin mixer and pop-up waste. Rate to include
all necessary connections

11.03 Supply and install stainless steel floor drain. Rate is to 2 no.
include connection to sewer gully.

11.04 Supply and fix automated electric hand drier 1 no.

11.05 Supply and fix toilet paper holder 2 no.

11.06 Supply and fix 25ltr water heater 1 no.

Total for Bill A11 : Sanitary Works

253
SECTION A - CIVIL WORKS

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

A12 Dayworks

Preamble
i) Dayworks will only be payable when expressly ordered in
writing by the Architect.

ii) For labour the man-hour rate shall cover all other charges
of every description, including bonus, incentives,
superintendent, foremen, administrative staff, timekeeper,
insurances, pensions, holidays with pay, use of small tools
(including sharpening), appliances and plant (not included in
‘plant’ below), establishment charges profit and VAT.

iii) The rate shall cover all costs including driver/attendant,


fuel, establishment charges, profit in connection with the use
of plant on daywork and VAT.

Labour
12.01 Provide for stone-masons 300 h

12.02 Provide for shutterers 100 h

12.03 Provide for concreters 200 h

Plant
12.04 Provide for 15 tonne rubber tyred crane 100 h

12.05 Provide for 10 tonne lorry tipper 100 h

Material
12.06 Provide the sum of €16,310 for the net cost of materials 1 L.S.
expended on dayworks.

12.07 Add to the above the cost of delivery, unloading, unpacking, 1 L.S.
storing, protecting, hoisting, distributing on site, and profit.

Total for Bill A12 : Dayworks

254
SECTION B - MECHANICAL WORKS

RATE (excl. AMOUNT (excl.


ITEM DESCRIPTION QTY UNIT VAT) VAT)

B1 Extractor Fan

Other Ventilation Systems


Supply, install and commissioning the following items
as specified in the tender documents:

Ventilation System - Type EF1


1.01 Low noise centrifugal extract fan acoustically lined 1 no.
with sound absorbing insulation c/w mounting
hardware, flexible duct connectors and suitable for an
electric supply of 230V/1/50Hz.

1.02 Ceiling mounted type movement detector c/w delay 1 no.


timer, first fix, wiring and connecting up.

1.03 Internal back-draught shutter 1 no.

1.04 Pre-insulated aluminium ductwork c/w fittings, 3 m²


supports and proprietary bracketing as specified.

1.05 Plain ducted sleeves as specified. L.S. L.S.

1.06 Acoustically lined flexible duct including supports and


proprietary bracketing with the following nominal bore:

1.07 100mm diameter 3 m

1.08 Aluminium tap-in collars c/w steel clamp strips for the
following flexible duct diameters.

1.09 100mm diameter 3 no.

1.10 Exhaust valves, made of steel with white electrostatic


powder coating with adjustable core and fixing steel
galvanized frame suitable for the following flexible
duct diameters.

1.11 125 mm diameter 3 no.

1.12 Volume control damopers c/w indication and lockable


handles as specified - pvc

1.13 100 mm diameter 3 no.

1.14 Aluminium weather louver c/w screens with the


following dimensions as specified:

255
1.15 250mm wide x 250mm high 1 no.

1.16 Labelling of all ductwork as specified. L.S. L.S.

1.17 Ceiling mounted type movement detector c/w delay 1 no.


timer, first fix, wiring and connecting up.

Builder’ s work for ventilation systems. This shall


include all the penetrations and chasing in walls,
making good for rain water ingress and plastering
around hole.

1.18 250mm high x 250mm wide 1 no.

1.19 Door transfer grills in to cater for flow of EF1 1 no.

Ventilation System - Type EF2


1.20 Low noise centrifugal extract fan acoustically lined 1 no.
with sound absorbing insulation c/w mounting
hardware, flexible duct connectors and suitable for an
electric supply of 230V/1/50Hz.

1.21 Thermostat to control EF2 in comms room. Including 1 no.


connecting up

1.22 Duct work for respective fan EF2 to be installed in L.S. L.S.
comms room including outside weather grill and return
interanl grill in comms room two way. The ine

1.23 Door transfer grill to cater for the flow of EF2 L.S. L.S.

1.24 Testing, commissioning and handing over of L.S. L.S.


ventilation system.

1.25 Maintenance agreement for a period of three (3) L.S. L.S.


years from date of commissioning for the above
ventilation systems, including consumables

1.26 3 sets of installation, operation and maintenance L.S. L.S.


manuals

1.27 As fitted drawings:

1.28 3 copies in electronic format L.S. L.S.

1.29 3 hard copies L.S. L.S.

256
Total for Bill B1 : Extractor Fan

257
SECTION B - MECHANICAL WORKS

RATE (excl.
ITEM DESCRIPTION QTY UNIT
VAT)

B2 VRV Type Air Conditioning System

Supply, install and commissioning the following items


as specified in the tender documents:

2.01 OU-01 & OU-02 2 no.


Variable refrigerant flow/volume, inverter heat pump type
outdoor unit - 75.0kW cooling capacity as specified.

Indoor units each c/w an wired LCD remote controller


installed as specified and as indicated in drawing
with the following cooling duties:
2.02 Indoor Units VRV IU1 - 12 KW 1 no.

2.03 Indoor Units VRV IU2 -14 KW 1 no.

2.04 Indoor Units VRV IU3 - 15KW 1 no.

2.05 Indoor Units VRV IU4 - 12.5 KW 1 no.

2.06 Indoor Units VRV IU5 - 12.5KW 1 no.

2.07 Indoor Units VRV IU6 - 12KW 1 no.

2.08 Indoor Units VRV IU7 - 12KW 1 no.

2.09 Indoor Units VRV IU8 - 8KW 1 no.

2.10 Indoor Units VRV IU9 -8KW 1 no.

2.11 Indoor Units VRV IU8 - 8KW 1 no.

2.12 Indoor Units VRV IU9 -8KW 1 no.

2.13 Outdoor Unit Located on roof. L.S. L.S.


Insulated refrigerant copper pipework (suction &
discharge) complete with branches, support, insulation
blocks bracketing etc. connected between outdoor units
and indoor units as specified. Outdoor refrigerant
pipework (horizontal and vertical runs) to be aluminium
cladded.

2.14 Insulated PP condensate pipework including support and L.S. L.S.


bracketing from indoor unit to drain point as specified.
Separate drain vertical pipe to be installed for condensate
drain.

257
2.15 Control and power wiring including first fix, fittings, and L.S. L.S.
any other accessories between indoor units, controllers,
and outdoor units. Wiring between double pole switch
and indoor units and isolator and outdoor unit to be
carried out by the Air Conditioning Contractor.

2.16 Centralized remote control, schedule timer and unified L.S L.S.
ON/OFF control. These shall connect and control
individually the outdoor units in the respective zone as
shown in drawings.

2.17 Concrete plinth on upper roof, 100mm thick and vibration L.S. L.S.
isolation pads each not less than 20mm thickness.

2.18 Labeling of indoor, outdoor unitsand oipework as L.S. L.S.


specified.

2.19 Testing, commissioning and handing over of air L.S. L.S.


conditioning system as specified.

2.20 Maintenance agreement for a period of three (3) years L.S. L.S.
from date of commissioning for air conditioning system,
including consumables

2.21 Documentation: 3 sets of installation, service, engineering L.S. L.S.


data and operational manuals.

2.22 As fitted drawings

2.23 3 hard copies L.S. L.S.

2.24 3 electronic format L.S. L.S.

Total for Bill B2 : VRV Type Air Conditioning System

258
AMOUNT (excl.
VAT)

259
260
SECTION B - MECHANICAL WORKS

RATE (excl.
ITEM DESCRIPTION QTY UNIT
VAT)

B3 Ventilation System Heat Recovery Units

Supply, install and commissioning the following items as


specified in the tender documents:

3.01 Energy recovery unit HRU c/w accessories with an air volume 1 no.
flow rate of 1400l/s. The fan should have a speed controller
three stage.

3.02 Remote controller for heat recovery unit including first fix- 1 no.
vertical drops buried in wall chase while horizontal runs clipped
conduit clipped to ceiling and wiring as specified. It should have
motorised dampers that closes when switched off.

3.03 Attenuators 2 no.

3.04 Back-draught shutter 2 no.

Supply and Return Ductwork


Supply and install the following ductwork complete with
fittings, supports, etc all as specified.

3.05 Pre-insulated aluminum ductwork c/w fittings, supports and 310 m²


proprietary bracketing as specified. (20mm thickness)
For supply and return ductwork installed inside

3.06 Pre-insulated aluminum ductwork c/w fittings, supports and 54 m²


proprietary bracketing as specified. (20mm thickness)
For supply and return ductwork installed outside.

3.07 Plain ducted sleeves in each penetration as specified. L.S. L.S.

Acoustically lined flexible duct including supports and


proprietary bracketing with the following nominal bore:

3.08 250 mm diameter. 22 m²

3.09 Aluminium tap-in collars c/w steel clamp strips for the following
flexible duct diameters:

3.10 250 mm diameter. 28 no.

259
Supply Diffusers
Supply, install and commission the following louvered face
diffusers complete with insulated plenum box to deal with
the indicated volume flow rate as described in the
specifications. All air supply diffusers shall be complete
with volume control dampers and white in colour.

3.11 SD 1 - 3-way 100l/s 1 no.

3.12 SD 2 to SD 5 - 2-way 100l/s 4 no.

3.13 SD 6 - 3-way 100l/s 1 no.

3.14 SD 7 to SD 14 - 2-way 100l/s 8 no.

Return Grilles
Supply, install and commission the following egg-crate
type grilles complete with insulated plenum box to deal
with the indicated volume flow rate as described in the
specifications. All air return grilles shall be complete with
volume control dampers and white in colour.

3.15 RG 1 to RG 14 -100l/s No. 14

Builder’ s work for ventilation systems. This shall include


all the penetrations and chasing in walls, making good for
rain water ingress and plastering around hole. Even
penetrations in building walls, are to be well plasters
around sleeves.

3.16 390mm x 340mm high No. 7

3.17 440mm x 340mm high No. 4

3.18 640mm x 290mm high No. 1

3.19 790mm x 340mm high No. 4

3.20 390mm x 290mm high No. 1

3.21 490mm x 390mm high No. 1

Volume Control Dampers c/w indication and lockable


handles as specified.
3.22 750mm x 250mm No. 2

3.23 600mm x 250mm No. 1

3.24 450mm x 300mm No. 1

260
3.25 400mm x 300mm No. 3

3.26 350mm x 250mm No. 2

Fire damper for 750mm x 350mm duct. Outside.

3.27 Duct inspection covers No. 2


approx. dimension 300mm x 200mm
3.28 Concrete plinth and vibration isolation pads each not less than L.S. L.S.
20mm thickness.

3.29 Test points on main supply and return duct work on roof 25mm No. 8
diameter with tap.

3.3 Duct thermometers dial type No. 2

3.31 Labeling of all ductwork and units as specified. L.S. L.S.

3.32 Electrical interconnection of HRU to fire detection system. L.S. L.S.

3.33 Wiring of supply cable between the HRU and isolator installed L.S. L.S.
by others. To be installed on galvanised cable tray with the
necessary support.

3.34 Supply and connecting up of HRU to the centralized control. L.S. L.S.
Wiring including first fix, fittings, and any other accessories
between centralized controller and HRU. All wiring to be
installed inside conduit/ flexible conduit adequately sized.

3.35 Testing, commissioning and handing over of ventilation system. L.S. L.S.

3.36 Maintenance agreement for a period of three (3) years from L.S. L.S.
date of commissioning for ventilation system, including
consumables

3.37 3 sets of installation, operation and maintenance manuals L.S. L.S.

As fitted drawings:

3.38 3 copies in electronic format L.S. L.S.

3.39 3 hard copies L.S. L.S.

261
Total for Bill B3 : Ventilation System Heat Recovery Units

262
AMOUNT
(excl. VAT)

263
264
265
266
SECTION B - MECHANICAL WORKS

RATE (excl.
ITEM DESCRIPTION QTY UNIT
VAT)

B4 Hot & Cold Water Services

Supply, install and commission the following items


as specified in the tender specifications and
drawings:

Transfering of exisitng water tank. Any pipe work to


be coated with two coats of paints against UV c/w
bracketing.

4.01 Removing of exisitng water tank on present roof, L.S. L.S.


including relaive pipe work.

4.02 Installing of water tank (removed previously) and L.S. L.S.


connecting up to water system.
It is to be included the additional pipe work and fittings
such as brackets, ancharing etc…
4.03 Concrete plinthpipe
Any additional on upper roof, PP-R
work type 100mm thick.
and fittings required L.S. L.S.
cost is to be included in this item.

Water pipe work c/w fittings and bracketing, as


specified. Pipework installed outside to be UV
protected as specified. Dark UV coating shall be
painted by two coats of light colour paint. All
penetrations through walls shall be sleeved and
making good for any cleqarance between sleve and
walls.

Cold Water Pipework

4.04 DN 25mm PP-R 80, PN 20 fusion weld pipe work 21 m

4.05 DN 20mm PP-R 80, PN 20 fusion weld pipe work 31 m

4.06 DN 15mm PP-R 80, PN 20 fusion weld pipe work 15 m

Hot Water Supply System complete with fittings and


bracketing as specified. All penetrations through
walls shall be sleeved. Pipework installed outside to
be UV protected as specified. Dark UV coating shall
be painted by two coats of light colour paint.

4.07 20mm PP-R 80 PN 20 fusion weld pipe work c/w 19mm 30 m


thick closed cell rubber insulation DHWS & R

262
4.08 15mm PP-R 80 PN 20 fusion weld pipe work c/w 19mm 12 m
thick closed cell rubber insulation DHWS & R

Pipework Accessories for Hot & Cold Water Services

Ball valves provided with the necessary


accessories for dismantling without the need to cut
pipes. Valves to be supplied from the same
manufacturer of the pipes.

4.09 DN 25mm bronze quarter turn ball valves 2 no.

4.10 DN 20mm bronze quarter turn ball valves 3 no.

4.11 DN 15mm bronze quarter turn ball valves 4 no.

Lockable bib cocks c/w pad lock.

4.12 Lockable bib cocks c/w pad lock DN 15mm bronze 1 no.
quarter turn ball valves.

Ball float valves c/w float and y strainer.

4.13 DN 25mm 1 no.

Wall plate elbows Copper x BSP parallel female


thread

4.14 15mm x 1/2"f 8 no.

4.15 20mm x 1/2"f 8 no.

Chrome angle valves:


4.16 Ø 15 mm 12 no.

4.17 Air vent DN 25 1 no.

4.18 Solid chrome plated flexible connection to connect 12 no.


between sanitary ware and angle valves.

4.19 Geyser 12lt 1 no.

4.20 Labelling of pipes, commissioning L.S. L.S.

4.21 Dimantling extisting drainage pipe work, extending as L.S. L.S.


necessary and connecting up to the new floor that is to
be build above. This should include any gullys, bends,
eye rods as the trade demands etc…

263
4.22 Dimantling extisting sink drains, and connected to the L.S. L.S.
erected drainage system of the new sinks that are to be
installed in the floor above. Any bends, tees, eye rods
etc.. Are the trade demands are to be included in the
item. Allowance for two sinks is to be included.

4.23 Dismantling, extending to floor above and reconnect rain L.S. L.S.
water pipes with the roof above. This should inlcude any
connections and grills on roof levels as necessary. (4
connection to be included)
4.24 Floor drain c/w stainless steel grill including water seal. L.S. L.S.
Pipe work, Ǿ 50 PP material and any other fittings
required to terminate in gully as trade demands. Anchors
and other fixtures are to be included in item.

4.25 Builder's Works to allow pipes to pass through walls and LS L.S.
making good to avoid water ingress.

4.26 Testing, commissioning and handing over of Plant L.S. L.S.


System (as specified) including commissioning reports
and test certificates signed by a warranted engineer
responsible for the supervision of works.

4.27 Maintenance agreement for a period of three (3) years L.S. L.S.
from date of commissioning covering all the systems
described above, including consumables.

4.28 3 sets of installation, operation and maintenance LS. L.S.


manuals in English language.

As fitted drawings:

4.29 3 copies in electronic format L.S. L.S.

4.30 3 hard copies L.S. L.S.

Total for Bill B4 : Hot & Cold Water Services

264
AMOUNT
(excl. VAT)

265
266
267
SECTION C - ELECTRICAL & EXTRA LOW VOLTAGE SERVICES

RATE (excl. AMOUNT (excl.


ITEM DESCRIPTION QTY UNIT
VAT) VAT)

C1 ELECTRICAL INSTALLATION

Distribution Boards
1.01 Supply, install and connect-up Distribution Board DB-3 in 1 L.S.
Utility Room at Level 3, 315 Amps, 12 Way, TP+N
comprising of:

Incomer: MCCB 4P 250 Amps


Busbars: 315 Amp TP+N+E
Outgoing: 11 x 10 Amp SP+N RCBOs
1 x 20 Amp SP+N RCBO
7 x 25 Amp SP+N RCBOs
2 x 40 Amp SP MCBs
5 x Spare TP Ways

1.02 Supply, install and connect-up Distribution Board DB-AC 1 L.S.


at Roof Level, IP65 Enclosure, 200 Amps, 6 Way, TP+N
comprising of:

Incomer: MCCB TP 160 Amp


Busbars: 200 Amp TP+N+E
Outgoing: 2 x 16 Amp SP+N RCBOs
1 x 20 Amp SP+N RCBO
1 x 32 Amp TP MCCB
2 x 80 Amp TP MCCBs
2 x Spare TP Ways

1.03 Supply, install and connect-up Consumer Unit CU-3A in 1 L.S.


Lab 'A' at Level 3, 60 Amp, 8 way, SP+N, comprising of:

Incomer: MCB DP 40Amp


Busbars: 60Amp SP+N+E
Outgoing: 2 x 10Amp SP+N RCBOs
6 x 25Amps SP+N RCBOs

1.04 Supply, install and connect-up Consumer Unit CU-3B in 1 L.S.


Lab 'B' at Level 3, 60 Amps, 8 way, SP+N, comprising of:

Incomer: MCB DP 40Amp


Busbars: 60 Amps SP+N+E
Outgoing: 2 x 10Amp SP+N RCBOs
5 x 25Amp SP+N RCBOs
1 x Spare SP Way

Provision of Cable Feeders in single core cables run in


galvanised trunking or multicore armoured cables run on
cable tray:
1.05 From MDB to DB-3 in 4 core 95mm.sq. cable 28 m
XLPE/PVC/SWA/PVC
1.06 From MDB to DB-AC in 4 core 70mm.sq. cable 36 m
XLPE/PVC/SWA/PVC

265
1.07 From DB-AC to VRF1 in 4 core 16mm.sq. cable 11 m
XLPE/PVC/SWA/PVC
1.08 From DB-AC to VRF2 in 4 core 16mm.sq. cable 11 m
XLPE/PVC/SWA/PVC
1.09 From DB-AC to HRU1 in 4 core 6mm.sq. cable 8 m
XLPE/PVC/SWA/PVC
1.10 From DB-3 to CU-3A in 3 x 10mm.sq. cable PVC 15 m

1.11 From DB-3 to CU-3B in 3 x 10mm.sq. cable PVC 27 m

Armoured Cable Terminations


Termination of Armoured Cable Feeders utilising
Brass Cable Glands, gland kits and compression
terminals
Indoor Type Termination (BW)
1.12 Cable Size 4 core 95mm.sq. 2 no.
1.13 Cable Size 4 core 70mm.sq. 1 no.

Outdoor Type Termination (CW)


1.14 Cable Size 4 core 70mm.sq. 1 no.
1.15 Cable Size 4 core 16mm.sq. 4 no.
1.16 Cable Size 4 core 6mm.sq. 2 no.

Supply and fix Galvanised Sheet Steel Cable Trunking


complete with galvanised brackets, fixing
accessories, earthing bonding, and cover sheets

1.17 Size 2" x 2" 69 m


1.18 Size 3" x 2" 54 m
1.19 Size 3" x 3" 25 m

Provision of Perforated Galvanised Sheet Steel Cable


Tray complete with brackets for suspension from
ceiling, wall penetrations, couplings, bends, etc., as
per the following:-

1.20 Cable Tray Size 100mm x 30mm 30 m

Provision of PVC Trunking complete with cover, end


caps, corners, couplings, as per the following:-

1.21 Size 100mm x 50mm (at 900mm FFL) 98 m

Provision of the following Lighting Points wired in 3 x


1.5mm.sq. PVC insulated Cables, run in PVC conduit,
chased in walls, in trunking and under floor screed, as
necessary:-

DB-3
1.22 One lighting point controlled by one switch 8 no.
1.23 Two lighting points controlled by one switch 11 no.
1.24 Three lighting points controlled by one switch 2 no.

266
1.25 Eight lighting points controlled by one switch 1 no.
1.26 Two lighting points controlled by 2 x 2way switches 1 no.
1.27 Five lighting points controlled by 2 x 2way switches 2 no.
1.28 Six lighting points controlled by 2 x 2way swithces and 3 in 1 no.
1.29 Two lighting points and one extractor fan point controlled by 1 no.
1.30 Emergency lighting fixtures 10 no.

CU-3A
1.31 One lighting point controlled by one switch 1 no.
1.32 Four lighting points controlled by one switch 2 no.

CU-3B
1.33 One lighting point controlled by one switch 1 no.
1.34 Four lighting points controlled by one switch 2 no.

DB-AC
1.35 Three lighting points controlled by one weatherproof 1 no.
switch

Provision for dismantling of the following Existing


Lighting Fixtures and re-fixing after new installation:

1.36 400W Metal Halide Floodlight 6 no.

Supply, assemble, install and connect the following


Fixtures:
1.37 Type 'A': 4 x 24W T5 Recessed Fluorescent Light Fixture 38 no.

1.38 Type 'Am': 4 x 24W T5 Recessed Maintained Fluorescent 7 no.


Light Fixture

1.39 Type 'B': 1 x 35W T5 Soffit Recessed assymetric 7 no.


Fluorescent Light Fixture

1.40 Type 'C': 2 x 26W CFL Soffit Recessed Round Downlighter 14 no.

1.41 Type 'Cm': 2 x 26W Soffit CFL Recessed Round 5 no.


Maintained Downlighter

1.42 Type 'D' - 2 x 18W CFL Soffit Recessed Light Fixutre 3 no.

1.43 Type 'E1' - 1 x 8W T5 Non-Maintained Emergency Lighting 4 no.


Fixture

1.44 Type 'E2' - 1 x 8W T5 Maintained Emergency Lighting 6 no.


Fixutre c/w Directional Pictogram

1.45 Type 'F' - 2 x 18W CFL IP55 Bulkhead Fixture 7 no.

1.46 Type 'G' - 1 x 35W T5 Wall/Ceiling Mounted Fluorescent 1 no.


Light Fixture

1.47 120º PIR Detector 1 no.

267
1.48 Ceiling Mount Occupancy Sensor c/w the necessary 10 no.
accessories to turn on light when light is only needed
when a person is present.

Provision of the following Power Points wired in 3 x


4.0mm.sq. PVC insulated cables, Radial Circuits, run
through PVC conduit, chased in walls, in trunking and
under floor screed and multicore cables run on cable
tray

DB-3
1.49 Twin 13Amp Switched Socket outlets 34 no.
1.50 13 Amp DP fused switch for AC Indoor Unit 5 no.
1.51 13Amp DP fused switch c/w flex outlet for Overhead Project 5 no.
1.52 13Amp DP fused switch for Overhead projector screen 5 no.
1.53 13Amp DP fused switch and flex outlet for Hand Dryer 2 no.
1.54 13Amp DP fused switch for Water Heater 1 no.

CU-3A
1.55 Twin 13Amp Switched Socket outlets 23 no.
1.56 13 Amp DP fused switch for AC Indoor Unit 2 no.

CU-3B
1.57 Twin 13Amp Switched Socket outlets 18 no.
1.58 13 Amp DP fused switch for AC Indoor Unit 2 no.

DB-AC
1.59 Single 13Amp Weatherproof socket outlet 1 no.

1.60 80Amp TP+N IP55 Isolator for VRF1 and VRF 2 2 no.
1.61 32Amp TP+N IP55 Isolator for HRU1 1 no.

Other Services
1.62 Testing and Certification of the complete Electrical 1 L.S.
Installations covered by the Scope of this Tender

1.63 Provision of One Set "As-Fitted" Drawings in Electronic 1 L.S.


Format (in ACAD Version 2005 or better) and three (3)
sets of copies

1.64 Allow for all Builders' Work necessary for the above listed 1 L.S.
installation, including wall and ceiling slab penetrations

268
1.65 Provision of FULL Documentation and Technical 1 L.S.
Literature covering ALL Electrical Services Installations

1.66 Provision of Durable Labels and labelling on all items of 1 L.S.


equipment and fix connecting schedules etc..
Designations to match those on 'As-Fitted' Drawings

Total for Bill C1 : ELECTRICAL INSTALLATION

269
SECTION C - ELECTRICAL & EXTRA LOW VOLTAGE SERVICES

RATE (excl. AMOUNT


ITEM DESCRIPTION QTY UNIT
VAT) (excl. VAT)

C2 EXTRA LOW VOLTAGE SERVICES

Fire Alarm Services

Provision of PVC conduit chased in walls and


under floor screed, including draw-in wire for the
following services:

2.01 Manual Call points in 25mmØ conduit 3 no.


2.02 Fire Internal Sounders in 25mmØ conduit 2 no.

Supply, fix, connect up and set to work the


following fire detection and alarm devices, to be
connected to the existing Fire Alarm Panel,
servicing the lower levels of the building

2.03 Smoke Detector Unit 14 no.

2.04 Manual Call Point 3 no.

2.05 Internal Fire Alarm Sounder 2 no.

2.06 Provision of Fire Alarm Cable, in accordance and to 200 m


complement the existing system

Voice and Data Communication System

2.07 Supply, assemble, fix and connect-up Patch Panel PP- 1 no.
LA, 24U, wall mounted in Lab 'A', third floor, as
specified, allowing extra space for Cable Management,
patch leads, etc., (Power Supply included in Electrical
Section)
2.08 Supply, assemble, fix and connect-up Patch Panel PP- 1 no.
LB, 24U, wall mounted in Lab 'B', third floor, as
specified, allowing extra space for Cable Management,
patch leads, etc., (Power Supply included in Electrical
Section)
2.09 Wiring of Voice and Data Communication Points in 2 38 no.
x 4 Pair CAT 5E Cable per outlet, on Cable Tray,
through chased 25mm dia. PVC Conduit and Trunking,
complete with dual RJ45 outlets, as specified (Trunking
and Cable Tray included in another BOQ Item)

2.10 Supply, fix and connect up 24 RJ45 Port, 2 Giga Bits 1 no.
per second data transfer rate, Ethernet 1000Base-T, 19
inch rack mounting to IEEE 802.3.

269
2.11 2x4 Pair UTP Cat 5e cable + 50 pair voice cable from 25 m
PP-LA to PP-LB
2.12 100mm x 100mm PVC Box chased in wall for 14 no.
connection of wiring above soffit to the ceiling mounted
overhead projector

Cable Management System

Provision of PVC Trunking complete with cover,


end caps, corners and couplings, for Low Voltage
Services, as per the following:

2.13 Size 100mm x 50mm (at 300mm FFL) 78 m

Provision of Perforated Galvanised Sheet Steel


Cable Tray complete with brackets for suspension
from ceiling, wall penetrations, couplings, bends,
etc., as per the following:

2.14 Cable Tray Size 100mm x 30mm 78 m

2.15 Cable Tray Size 200mm x 30mm 25 m

2.16 Labelling of All Structured Cable Network, Cables and 1 L.S.


Port Outlets

2.17 Test and commission the complete Voice and Data 1 L.S.
Network, including Submission of Test Results

Other Services
2.18 Testing and Certification of the complete Low Voltage 1 L.S.
Services Installations covered by the scope of this
tender

2.19 Provision of one set of 'As-Fitted' Drawings in 1 L.S.


Electronic Format (in ACAD Version 2005 or better) and
three sets of copies

2.20 Allow for all Builder's Work necessary for the above 1 L.S.
listed installation, including wall and ceiling slab
penetrations

2.21 Provision of Full Documentation and Technical 1 L.S.


Literature covering all Low Voltage Services
Installations

270
Total for Bill C2 : EXTRA LOW VOLTAGE SERVICES

271