Professional Documents
Culture Documents
Bigger Performance.
input #1 at www.csemag.com/information
Tyco SimplexGrinnell
is now Johnson Controls.
The combined strengths of two great companies are now under one great name. Making
Johnson Controls the world leader in fire protection, security, HVAC, building controls and
energy storage. Count on us for innovative solutions that lead to safer building environments
and better outcomes for customers. Like advanced Simplex TrueAlert ES solutions with
revolutionary notification system self-testing capabilities. Exactly what you’d expect from a leader.
input #2 at www.csemag.com/information
Packing more power into the
same flexible design.
Introducing 1200 Amp Starline Track Busway,
the newest addition to the T5 Series.
Starline’s newest addition to our line of track busway options delivers even more power,
without losing any of the flexibility that you’ve come to rely on from our T5 Series.
The 1200 amp busway still has our unique, modular, build-as-you-need design, and is
equipped for high-density electrical distribution under the most demanding conditions
in data center and mission critical environments. Best of all, the same plug-in units can
be used for all systems in the T5 series—from our 250 amp to the new 1200 amp. To
learn more about our newest and largest busway choice, visit StarlinePower.com.
input #3 at www.csemag.com/information
ON THE COVER:
The Vanderbilt Uni-
versity Engineering
and Science Build-
ing is a 230,000-sq-
ft interdisciplinary
research and JUNE 2017
teaching build-
ing in Nashville,
Tenn. The building
uses air-side heat FEATURES
recovery as one
of the elements 38 | Modernizing the Wrigley
to achieve 30% Field chilled-water system
energy-cost sav- Selecting and specifying the right chiller
ings compared to is generally dictated by capacity, and
ASHRAE Standard there are many philosophies on the
90.1-2007.
best way to control, operate, and calcu-
Courtesy: TLC Engi-
late system operational costs.
neering for Archi-
SUZAN SUN-YUAN, PE, CDT, LEED AP; and
tecture
CORY J. ABRAMOWICZ, PE, HBDP, LEED AP
COVER STORY
32 | Recovering waste heat in buildings 46 | Designing buildings
Waste-heat recovery systems are increasingly used in for the Internet of Things
buildings to move waste heat from laboratories, data
The networking of things within a
centers, or industrial activities to provide beneficial
building must be anticipated by
heating in other parts of the building.
building engineers.
CORY DUGGIN, PE, LEED AP BD+C, BEMP
TIM KUHLMAN, PE, RCDD
DEPARTMENTS
51 | Integrating BAS,
05 | Viewpoint 25 | Codes & Standards controls for smart buildings
How to educate a Applying NFPA 99 Technology integration between all
changing population to health care facilities engineering disciplines will create a
smart building that can enhance
07 | Research 77 | Digital Edition
building operations.
Electrical, power systems Exclusive
in data centers BRANDON McCARRON
The basics of daylighting
CONSULTING-SPECIFYING ENGINEER (ISSN 0892-5046, Vol. 54, No. 5, GST #123397457) is published 11x per year, monthly except in February, by CFE Media, LLC, 1111 W. 22nd Street, Suite
#250, Oak Brook, IL 60523. Jim Langhenry, Group Publisher /Co-Founder; Steve Rourke CEO/COO/Co-Founder. CONSULTING-SPECIFYING ENGINEER copyright 2017 by CFE Media, LLC. All rights reserved. CONSULTING-
SPECIFYING ENGINEER is a registered trademark of CFE Media, LLC used under license. Periodicals postage paid at Oak Brook, IL 60523 and additional mailing offices. Circulation records are maintained at CFE Media, LLC, 1111
W. 22nd Street, Suite #250, Oak Brook, IL 60523. E-mail: customerservice@cfemedia.com. Postmaster: send address changes to CONSULTING-SPECIFYING ENGINEER, 1111 W. 22nd Street, Suite #250,
Oak Brook, IL 60523. Publications Mail Agreement No. 40685520. Return undeliverable Canadian addresses to: 1111 W. 22nd Street, Suite #250, Oak Brook, IL 60523. Email: customerservice@
cfemedia.com. Rates for nonqualified subscriptions, including all issues: USA, $150/yr; Canada/Mexico, $180/yr (includes 7% GST, GST#123397457); International air delivery $325/yr. Except for special issues where price
changes are indicated, single copies are available for $30.00 US and $35.00 foreign. Please address all subscription mail to CONSULTING-SPECIFYING ENGINEER, 1111 W. 22nd Street, Suite #250, Oak Brook, IL 60523. Printed
in the USA. CFE Media, LLC does not assume and hereby disclaims any liability to any person for any loss or damage caused by errors or omissions in the material contained herein, regardless of whether such errors result from
negligence, accident or any other cause whatsoever.
TRENDview
SPACEview
www.reliablecontrols.com/MPV
Addressable lighting
systems
Not affected Very affected
18% 18%
30% 34%
research
2016 ELECTRICAL AND POWER STUDY
Somewhat
ff d
affected
Moderately
ff d
affected Electrical, power systems in data centers
T
he Consulting-Specifying Engi- 3. Specifications: Engineers are
Figure 1: Within the past 12 to 18
neer 2016 Electrical and Power most frequently issuing performance
months, more than half of engineers
Study indicated that 41% of electrical or power system specifica-
have been affected by the increased
engineers specify, design, or make tions (75%) for data center projects,
popularity of addressable lighting
product selections for data centers— closely followed by prescriptive spec-
systems among their clients. Source:
and seven in 10 of these engineers are ifications (71%).
Consulting-Specifying Engineer
responsible for researching and eval- 4. Challenges: When working on
2017 Lighting and Lighting Controls
uating the options for these projects. electrical or power systems for data
Study
Below are five electrical and power centers, engineers are having the
system findings as they relate to data most difficulty with insufficient bud-
center projects: gets for high-quality designs (80%)
62% of mechanical engineers
recommend the brand of HVAC
1. Revenue: The average firm
earns $3 million annually from elec-
and meeting a client’s expected deliv-
ery date (67%).
trical or power systems specified into 5. Comparing systems: Overall
systems, equipment, and controls
new and existing data centers, with quality is highly important when
being used in a project. Source:
33% bringing in more than $5 mil- selecting an electrical or power sys-
Consulting-Specifying Engineer 2015
lion each year from these projects. tem for a data center; engineers also
HVAC and Building Automation Sys-
2. Systems specified: The top five are looking for superior service sup-
tems Study
electrical or power systems or equip- port, a reputable manufacturer, and
ment being specified into data cen- energy-efficient capabilities for these
ters are circuit breakers, fuses, etc. systems.
50% of fire protection engi-
neers expect to specify or select
(83%); transfer switches, etc. (79%);
emergency and standby power (79%);
View more information at
www.csemag.com/2016ElectricalPower.
emergency communication or mass transformers (79%); and electrical Amanda Pelliccione is the research
notification systems within the next distribution (77%). director at CFE Media.
12 months. Source: Consulting-
Specifying Engineer 2016 Fire and
Most critical challenges in electrical,
Life Safety Study
power system design for data centers
26%
$2.9 million:
Budget, cost
Other 16%
More research
Consulting-Specifying Engineer cov- Figure 2: The lack of a skilled workforce leaves 18% of engineers concerned about electrical
ers several research topics each year. or power systems designed for future data center projects. Source: Consulting-Specifying
All reports are available at Engineer
www.csemag.com/research.
715.359.6171
greenheck.com
input #6 at www.csemag.com/information
Career Smart
DAVID KURTEN PE,
HDR Architecture Inc., Princeton, N.J.
Mentoring creates a
competitive advantage
Developing and maintaining a mentoring program within an
organization can help grow the bottom line.
T
he higher education system in the Friend—provides social and bureau- A successful mentoring program also
U.S. is only producing a small frac- cratic context relies on young professionals, them-
tion of the graduates needed to fill Intellectual guide—provides selves. The firm should seek entry-level
entry-level positions in the architectural constructive feedback in a peer candidates with a healthy thirst for
engineering industry, and that number relationship. knowledge and the industry and a clear
continues to decline. In 2015, only 717 understanding of the benefits that men-
students graduated from 23 architectural Each type of mentor plays an impor- tors provide. They need to be proactive
engineering programs accredited by the tant role in the development of young and have a desire to seek out wisdom
Accreditation Board for Engineering and professionals, and each will foster a dif- and expertise from their mentors. They
Technology Inc., down from a recent high ferent mentoring relationship. A firm also have a responsibility to pay it for-
of 921 graduates in 2012. The numbers needs to evaluate the types of mentors ward to the next generation, which will
suggest that the architectural engineering available within the organization and help ensure the long-term success of a
industry will continue to seek more entry- select the most appropriate for a given mentoring program.
level talent through engineering pro- young professional. In some cases, the Mentoring can benefit every aspect
grams that are not tailored to this specific young professional may select the indi- of an organization. Young professionals
industry. The result is an industry that is vidual through natural interaction with learn skill sets, get more visibility, feel
becoming more self-taught every year. departmental staff. In that case, the valued, and typically have higher earn-
Selecting the right mentors within an firm may need to augment a mentoring ings potential. Mentors have a higher
organization is critical. Simply possess- relationship with another individual in degree of job satisfaction, an increase
ing the technical knowledge of a specific a different category. Providing a second in generational awareness in the work-
discipline doesn’t always guarantee effec- mentor gives the young professional place, and renewed enthusiasm—and
tive mentoring. Successful mentors need well-balanced exposure. they may even relearn skills that have
to have a propensity for teaching and Companies need to encourage mentor- atrophied.
engaging young staff. They also need to be ing by ideally embedding professional The need to mentor young profes-
disciplined in their approach and willing development in the cultural fabric of the sionals in the industry is becoming
to facilitate the progression of young pro- organization. They should provide guid- more urgent. Those firms that embrace
fessionals through their firm. ance and direction to ensure consistency mentoring holistically and create a sym-
Typically, mentors fall within four in the outcomes as well as a degree of biotic relationship between their prac-
broad categories: flexibility that accommodates a variety of tice, mentors, and young professionals
personalities and department structures. will create a distinct competitive advan-
Career guide—counsels, promotes, The firm also needs to adopt a long-term tage in the marketplace.
and helps with long-term career perspective about professional develop-
development ment, recognizing that the return on the David Kurten is the vice president and
Information source—serves as a investment of time and resources will not director of engineering for HDR Archi-
technical resource be visible in the bottom line for years. tecture Inc.
High expectations
VP, Intelligent Building Group
Operation Director
Environmental Systems
Design
for high-performance
Chicago
buildings
Paul Erickson, High-performance buildings are intricate, complex projects that
LEED AP BD+C
Building Performance Practice require attention—qualified, expert consulting-specifying engineers
Leader
Affiliated Engineers apply their knowledge on such projects.
Madison, Wis.
CSE: What’s the No. 1 trend you see for smarter building systems or the interaction
today in the design of high-performance of the people that work in the building, there
buildings? is an expectation that the new technologies for
sharing data will be supported.
Dave Clute: The No. 1 trend we see in our A. Brian Lomel: I’m seeing wellness and
Richard Holzer, current projects is clients’ desire to deliver indoor air quality for enhanced productivity
EE, LEED AP economic, environmental, and experiential and better work environments as well as attrac-
Principal Engineer
outcomes that allow them to create a com- tion and retention of employees/occupants.
Southland Engineering
Portland, Ore. petitive advantage for their core businesses.
Economic performance to satisfy long-term CSE: What other trends should engi-
cost benefits is paramount. Environmental neers be on the lookout regarding such
performance and energy efficiency is a given. projects in the near future (1 to 3 years)?
Workspaces that provide a compelling experi-
ence to work, live, and play is also high on the Erickson: Considering the energy/water
list of desirable attributes. nexus in buildings and on campuses, respond-
Paul Erickson: Energy modeling seems to ing with holistic design solutions is a growing
Tim Kuhlman, be the most widespread trend that I am see- trend. More attention is being given to occu-
PE, RCDD, CDT ing in high-performance building projects. At pant experience, whether via rating systems
Associate Principal
the rate energy codes and standards are ramp- like Living Building Challenge and WELL or
TEECOM
Portland, Ore. ing up, prescriptive compliance is becoming via individual controllability tools like Comfy.
more challenging. This coupled with energy- Other trends we see are a bit more project-
savings targets for many institutions compels type-specific. Geoexchange systems (geother-
the need for using modeling tools to test con- mal to many) have found great success in the
cepts, shape design solutions, and evaluate the K-12 market and are increasingly part of the
overall project performance. puzzle for high-performance higher education
Richard Holzer: I’m seeing a shift in empha- and corporate buildings and campus planning.
sis from energy conservation to occupant With the confirmation of successful first appli-
A. Brian Lomel, PE, LEED health and wellness. Interestingly, the num- cations like Cone Health’s, active chilled beams
AP BD+C, CxA, WELL AP ber of projects seeking LEED certification is are the major trend in health care right now.
Director trending down. With updates a few years ago to ASHRAE Stan-
TLC Engineering for Archi-
tecture Tim Kuhlman: I see a trend to make build- dard 170: Ventilation of Health Care Facilities
Orlando, Fla. ings more “technology-ready.” Whether it is that opened up the opportunity to use chilled
beams for reducing air-change require- smartphones. Communication, collab- the HVAC industry. Norm Asbjornson,
ments, we are consistently seeing our oration, coordination, and innovation founder of AAON, made a significant
projects apply this solution for the same is how people want to work; anywhere donation to fund a new engineering
cost—or less—as traditional variable air and anytime. building on campus (Norm Asbjornson
volume (VAV) while gaining significant Hall) charged with embracing high-per-
energy savings as well. CSE: Please describe a recent formance design, even reaching toward
Kuhlman: Engineers should start get- high-performance building project net zero energy, to create a dynamic and
ting used to working with virtual reality you’ve worked on—share details interactive learning environment. AEI
(VR). I expect this to appear on two dif- about the project including location, and ZGF Architects partnered with Asso-
ferent fronts. The first is in how we design systems engineered, team involved, ciated Construction Engineering and
systems. VR will be able to help engi- etc. A&E Architects to design this leading-
neers to virtually interact with a system edge facility. Starting with early planning
to determine issues with access, mainte- Clute: The Zurich North America and study, we determined an energy-use
nance, and construction. The second is Headquarters project located in Scha- intensity (EUI) target that could be sup-
in the design of VR interaction rooms. umburg, Ill., was recently completed and ported by PV on the site, which included
These rooms can be thought of as very opened in October 2016. Certified as a new parking garage that is a part of the
high-end AV rooms where a client can LEED Platinum, the 783,800-sq-ft com- project. In conjunction with a vision held
project a virtual space to evaluate prod- plex reinforces Zurich’s commitment to by the assistant director of facilities ser-
ucts and have interactive training with environmental stewardship. A network of vices to interconnect multiple buildings
equipment and demonstrations. horizontal sunshades clad the perimeter on this south part of campus, we explored
Holzer: There is a greater focus on of the complex, with the sunshades vary- and implemented a geoexchange system
water conservation and reuse, particularly ing in depth depending on orientation, design. Using a mix of an AAON air han-
in the Western United States. while floor-to-ceiling glass offers exten- dling unit and local conditioning equip-
Lomel: Net zero water and energy, sive natural light for the shallow office ment that can be selected with geoex-
microgrids, and emphasis on resiliency plates. A soaring 3-story double wall faces change heat pump options, we were able
are some other trends. south toward the multilevel plazas, show- to provide a low-energy concept that can
Clute: The ability to offer the end casing an architecture that responds to the move heating and cooling energy between
users, tenants, visitors, and operators of changing Chicago climate. The building the spaces in the building, the building
a building a mobile, digital experience was designed by Goettsch Partners for the and the geofield, or even the building
is becoming increasingly more impor- base building and Cannon Design for the and the other nearby campus build-
tant. Millennials and next-generation interiors; Clayco Construction was the ings. To help meet the heavily domi-
employees want to be able to access a design-build contractor. nating heating loads, a transpired solar
building using digital credentials and Erickson: Montana State University wall system was employed, harnessing
modify the temperature and light lev- in Bozeman has an engineering student the extremely sunny Bozeman climate.
els of their workspace using handheld alum that’s made a name for himself in These and other systems allowed the
For more information about this newly expanded product line, visit
www.TNB.com/TBEXHazardous or contact your authorized distributor
or T&B/ABB representative.
tnb.com
input #9 at www.csemag.com/information
MEP Roundtable
THE NEW STANDARD FOR
CRITICAL ENVIRONMENTS.
can be a problem because they don’t recognize a UL list-
ing. Instead, I may be looking for the same product that
has a CE mark. Our clients want to move globally, but each
country is sovereign and has its own codes and standards.
Networking equipment is probably the most uniform from
country to country. All Ethernet ports look the same. The
same cannot be said for power outlets. Yet, even in building
networking components where there is such a high level of
Introducing the new Ruskin® critical uniformity, the building codes and listing requirements for
environment damper series: the model CD50CE
these products can be different in each country.
damper and thermally efficient model TED50CE
damper. Designed and manufactured to Holzer: Full integration of architectural, mechanical,
withstand the elements of coastal and corrosive plumbing, structural, and electrical design to achieve the
applications, these models combine the strength project performance goals is absolutely essential. Looking
of stainless steel and the protection of anodized for synergistic opportunities is critical—things like using a
aluminum to deliver lasting performance in
concrete structural system to increase the thermal capaci-
severe environments.
tance of the building, building-integrated photovoltaic sys-
For more information visit ruskin.com tems, and using solar panels as sun-shading devices.
input #10 at www.csemag.com/information Holzer: Codes restrict the amount of vision glazing,
design of wall/roof/floor assemblies, and rooftop space
allocations set aside for solar panels.
29CSEAd-A19a.indd 1 5/31/17 3:09 PM Clute: New codes, standards, and guidelines for energy
efficiency are making it easier for us to justify and build
compelling business cases for the design of high-perfor-
mance buildings. When the need to achieve higher levels
of performance are required by law, it makes the need to
comply much easier than if the choice was optional.
Lomel: The changes between the 2004 and 2007 editions
of ASHRAE 90.1 and between the 2006 and 2009 editions of
the International Energy Conservation Code (IECC), and
then the changes from ASHRAE 90.1-2010 and IECC 2012
to the latest editions, brought about a generation of chang-
es, bringing new requirements for air barriers, building-
pressurization testing, plug-load controls, commissioning,
decreased window-to-wall ratio, and more. It’s all catching
designers unaware and reinforces the need for educating
both design teams and owners to better understand the
code requirements and associated costs. The prescriptive
path for compliance has gotten so onerous and difficult
• ISO-9001 Certified • Available Certified IBC Seismic Compliance to adhere to that most of our projects are following the
• 70,000 ft2 of manufacturing space • Professional sales and engineering staff performance path.
• Strategically located for domestic and • High performance, maintenance free
worldwide markets materials
Read more at
• Over 65 years of experience • Unparalleled customer service www.csemag.com about:
• Turn-key systems available • Expertise in code compliance, extreme n Automation and controls
sound attenuation and challenging n Electrical/lighting/power
applications n Fire/life safety
n HVAC
n Sustainable buildings/energy efficiency.
Like Us
800.231.2258
BALTIMORE, MD WWW.PRITCHARDBROWN.COM
Up to
70%
of chiller
components to help
meet regulations
Benchmark
has gone Platinum.
N
FPA 99: Health Care Facilities Code and Vacuum Systems; Chapter 7: Information
applies to all health care facilities other Technology and Communications Systems; and Learning
than home care. The code is intended for Chapter 9: HVAC. Chapter 8: Plumbing, which objectives
professionals involved in the design, construc- was added in the 2012 edition of NFPA 99 with Identify major changes to
tion, maintenance, and inspection of health care the intent that it be used to support the local the 2015 edition of NFPA 99:
facilities in addition to the design, manufacture, plumbing codes for health care facilities, has not Health Care Facilities Code
and testing of appliances and equipment used in been modified in the 2015 edition. that impact mechanical
designers.
patient-care rooms of the health care facilities.
Learn to build upon the
NFPA 99-2015 continues to build upon the Chapter 5: Gas and vacuum systems
risk-based approach of NFPA
risk-based categories established in the 2012 edi- As in the 2012 edition, NFPA 99-2015 divides 99 when designing hospitals
tion. As many health care designers are aware, Chapter 5 into three sections corresponding to and health care facilities.
the 2012 edition of NFPA 99 experienced a Category 1, Category 2, and Category 3 systems.
major overhaul. The intent of the upgrade was Category 1 systems are the most critical and
to elevate NFPA 99-2012 from a standard to a are required to be available continuously for
code, allowing it to be incorporated into a local patient life support, even during the loss of nor-
jurisdiction’s code by itself instead of being ref- mal power sources or failure of other hospital
erenced from NFPA 101: Life Safety Code. systems. It is important to note that Chapter 5
The 2012 edition eliminated all previous occu- does not include a Category 4 system (no impact
pancy-based chapters and replaced them with on patients) because a failure of a gas and vac-
Chapter 4: Fundamentals, which established risk uum system would have at least some impact
categories 1 through 4. The change meant NFPA on the patient. The minimum risk level for a
99 would no longer be applied based upon the gas and vacuum system, therefore, is Category
name of an occupied space, but rather applied 3 (failure may cause discomfort).
based upon a risk category. Unchanged in the NFPA 99-2015 adds new criteria in Chapter 5
2015 edition, the risk category is determined to help define a Category 1, Category 2, and Cat-
by the impact of system failure on patients and egory 3 piped gas and vacuum system. The intent
caregivers within a facility space. The higher the of the change is to ensure that when a facility
risk to occupants in the event of system loss, the is performing a risk assessment as defined in
stricter the requirements to ensure the system Chapter 4, the risk assessment is not being used
is not lost. to lower the level of safety. For example, prior to
While the overall structure and majority of the 2015 edition, it may have been possible for a
the content remain the same between the 2012 facility performing a risk assessment to define a
and 2015 NFPA 99 editions, slight modifica- medical-gas system as Category 2 even though
tions have been made throughout the code in deep sedation was administered to the patient.
the latest version. The changes in the 2015 edi- Because of the changes to the 2015 code, this
tion that are of most importance to a health care situation would now be required to be classified
mechanical designer appear in Chapter 5: Gas as Category 1.
www.csemag.com Consulting-Specifying Engineer • JUNE 2017 19
Codes & Standards
of the emergency in Chapter 7, which was added in the
oxygen-supply con- 2012 edition and is divided into three
nection referenced risk categories.
in Section 5.1.3.5.15. The change alters restrictions for the
This section remains routing of utilities through a Category 1
unchanged from the telecom entrance facility (EF) and tech-
2012 edition. nology equipment room (TER). The 2015
edition eliminates the 2012 requirement
Figure 1: Section 5.1.3.5.7, Auxiliary Source Connec- that underground utilities, such as elec-
tion, states that all medical-gas source systems be pro-
trical, water, gas, and sewer, could not
vided with an auxiliary source connection point of the
be located below a Category 1 EF. As in
2012, however, Sections 7.3.1.2.1.4 and
same size as the main line, located on the patient side
7.3.1.2.2.4 of the 2015 edition continue
of the source valve. The section further stipulates that
to stipulate that mechanical equipment of
the connection consists of a tee and a normally closed
any kind that does not directly serve the
secured valve. All graphics courtesy: IMEG Corp.
TER or EF shall not be installed in, pass
The added language through, or enter the space. (This type
in Chapter 5 of the 2015 edition is to Section 5.1.9.2.3, Master Medical of restriction is similar to those found in
be used in addition to the risk-category Gas Alarm, was revised to differentiate the international codes for nonessential
definitions in Chapter 4 when conduct- between the wired and wireless com- utilities routed within egress stairwells or
ing the risk assessment of a facility’s gas munication between the two mandatory elevator machine rooms.)
and vacuum systems. master alarm panels and the initiating Chapter 7 also maintains the require-
Other updates in Chapter 5 affect stor- device. Under either wired or wireless ment that an EF or TER must have
age temperatures, auxiliary-source con- communication, the intent of the code a positive pressure differential with
nections, master medical-gas alarms, and remains unchanged: that should one of respect to surrounding areas. Under the
instrument air. the mandatory master alarm panels fail, “environmental requirements” in Sec-
For all three categories of medical-gas its failure does not disable any signal on tion 7.3.1.2.1.8, a designer must provide
systems under section 5.1.3.2.12, the the other mandatory master alarm panel. a means for maintaining a positive air
2015 code changed the maximum storage NFPA 99-2015 also has added a dedi- pressure relationship for the technology
temperature of gas cylinders from 130° cated section for instrument air under space. Attention must be paid to ensure
to 125°F to match the Compressed Gas Section 5.1.13, Category Support Gases. this pressure relationship is maintained
Association recommendations. Under This section was added to avoid the confu- when dedicated terminal heat-transfer
section 5.1.3.2.13, the 2015 edition also sion between nitrogen, which is a medical units are provided (see Figure 2).
has modified the minimum storage tem- gas, and instrument air, which is a support
perature for nitrous oxide and carbon gas. Instrument air is not mandated to be Chapter 9: HVAC
dioxide cylinders from -20° to 20°F. provided, but when it is provided, it shall Unlike chapters 5 and 7, the HVAC
Section 5.1.3.5.7, Auxiliary Source comply with the requirements of NFPA 99. section does not define systems based
Connection, was added in the 2015 edi- Furthermore, when support equip- upon a risk category. The section requires
tion for medical-gas systems. The section ment, such as operating room booms each facility to perform a risk assessment
states, “All source systems shall be pro- or control panels, require gas to oper- to assign a risk category in accordance
vided with an auxiliary source connec- ate, a facility has the option of providing with Sections 4.1 and 4.2. Similar to the
tion point of the same size as the main either instrument air or nitrogen. How- 2012 edition, NFPA 99-2015 is written
line, which shall be located immediately ever, because it is uncommon and usu- with the intent that the risk category
on the patient side of the source valve.” ally unnecessary for a facility to use both assigned to each HVAC system serving
The section further stipulates that the an instrument air system and a nitrogen a space is independent of the risk cat-
connection shall consist of a tee and system, NFPA 99 recommends a decision egory applied to other systems serving
a normally closed secured valve (see be made to use the one system that best the same space.
Figure 1). The intent of this addition meets the facility’s needs. For example, a central sterile supply
is to provide a facility with a simpler located at a health care facility in Dal-
and safer means to change out service Chapter 7: Information technology las may assign a risk category of 3 to the
equipment. It is important to note that and communications systems heating system serving the department,
this additional source requirement does NFPA 99-2015 introduces one change but assign a risk category of 2 to the cool-
not modify or remove the requirements of importance to mechanical designers ing system. Assigning Category 3 to the
Led by industry expert Bill Kosik, PE, CEM, LEED AP, the two on-demand online data centers
courses offer instructor-led discussions, videos, and high-quality presentations on an interactive
and intuitive platform. The courses are self-paced, accessible 24/7, and offer one (1) AIA CES
approved learning unit per course.
Check out the new course “Impacts of Climate and Cooling Technology on
Data Center Energy Use,” which covers:
✓ The importance of climate analysis
✓ Key drivers in reviewing different climate types
✓ Cooling system technologies
✓ Determining appropriateness of cooling systems based on climate and data center types
✓ Energy estimating techniques for data centers.
91 finalists in 16 categories
The 2017 Product of the Year results will appear in print and online September 2017
Codes & Standards
Applying NFPA 99
to health care facilities
The impact of applying NFPA 99: Health Care Facilities
Code to hospitals and health care facilities varies depending
on the level of care provided.
N
FPA 99: Health Care Facilities Code fire and life safety provisions of the final rule
identifies criteria applicable to health through Form 2786, with K-Tags (deficiency
Learning
care facilities including hospitals and number identifiers) starting with 900 being those
objectives
nursing homes. The impact of applying NFPA applicable to NFPA 99 requirements. Identify major changes to
99 to health care facilities varies depending on NFPA 99 consists of 15 chapters, from general the 2015 edition of NFPA 99:
the level of care provided. NFPA 99-2015 is the building requirements to criteria that affect the Health Care Facilities Code
that impact fire protection
latest edition, but there are few changes from the various building systems including fire protec- engineers.
2012 edition focused on fire protection other tion systems. CMS does not require compli-
Determine the impact of
than editorial revisions. NFPA 99-2012 is more ance with chapters 7 (information technology NFPA 99 on hospitals and
widely used due to its adoption by the Centers systems), 8 (plumbing systems), 12 (emergency health care facilities.
for Medicare & Medicaid Services (CMS). Edi- management), and 13 (security management), as Learn about NFPA 99’s
tions prior to the 2012 edition of NFPA 99 were these chapters were not adopted in the final rule. adoption by the Centers for
limited in their application since they were not CMS has enacted an emergency-preparedness Medicare & Medicaid Services
individually adopted by CMS. However, limited rule (CMS-3178-F) in lieu of adopting Chapter (CMS) and how it affects fire
and life safety requirements.
portions of NFPA 99-1999 were referenced by 12, whereby compliance with the emergency-
applicable CMS criteria. Changes to NFPA 99
from earlier editions to both the 2012 and 2015
editions will be discussed as they apply to fire NFPA 99 has taken on a new level of importance
protection and life safety, with changes specific
in the past year due to the CMS issuance of CMS-
to the 2015 edition identified in each section.
NFPA 99 has taken on a new level of impor- 3277-F, Medicare and Medicaid Programs; Fire Safety
tance in the past year due to the CMS issuance of
CMS-3277-F, Medicare and Medicaid Programs; Requirements for Certain Health Care Facilities.
Fire Safety Requirements for Certain Health Care
Facilities. The rule revised 42 CFR Parts 403, 416, preparedness rule is required by Nov. 16, 2017.
418, 460, 482, 483, and 485, which address pro- Where local jurisdictions do not require compli-
gram requirements for hospitals, long-term care ance with NFPA 99, the excluded chapters noted
facilities, ambulatory surgical centers, and others. provide pertinent information in regards to
The final rule became effective July 5, 2016, with designing and maintaining the building systems
enforcement beginning Nov. 1, 2016. As part of and could be used as a reference.
this rule, CMS adopted the 2012 editions of NFPA
99 and NFPA 101: Life Safety Code along with all The risk assessment in NFPA 99
associated tentative interim amendments (TIAs) One of the changes to NFPA 99-2012 and later
issued prior to April 16, 2014. CMS reviews the editions is the move to a risk-based approach
www.csemag.com Consulting-Specifying Engineer • JUNE 2017 25
Codes & Standards
for determining applicable requirements include cooling systems in the south- identified in Figure 1 is a qualitative
rather than the former prescriptive ern U.S., resident emergency-call sys- approach based on yes or no answers for
approach based on facility type. NFPA 99 tems, heating systems in the northern each building system’s impact. It does not
now requires a risk assessment to deter- U.S., and lighting or potable water in address the probability of failure similarly
mine the applicable risk category for each patient-care areas. Category 2 systems to that used in NFPA 551 nor require in-
building system. The risk category is then are likely to be found in general-care depth knowledge of the systems and pos-
applied to chapters 5 through 11 of NFPA rooms, such as inpatient bedrooms and sible failures. It is important that those
99 as appropriate for the system. The main dialysis rooms. performing the assessment are knowl-
focus is seen in Chapter 5 (gas and vac- Category 3—Systems in which fail- edgeable in the procedures, equipment,
uum systems) and Chapter 6 (electrical ure is unlikely to cause injury. Failure of and systems being evaluated. Appropriate
systems). Although this requirement has the system does not have an immediate personnel could include building engi-
caused concern, the process can be simple impact on patients or their safety. Exam- neers, caregivers, and administrators.
since the failure of the system is assumed ples might include cooling systems in the Documentation of the risk assessment
without human intervention. Each build- northern U.S., lighting and potable-water should include the risk assessment pro-
ing system is to be categorized into one of systems outside of patient-care areas and cess used, all participants of the assess-
the following four categories: plumbing/sanitary systems. Category 3 ment, and all systems with assigned risk
Category 1—Systems in which failure systems are likely to be found in basic-care categories. CMS does not require the
is likely to cause major injury or death. rooms, such as treatment or exam rooms. risk assessment to be submitted, but it
Systems are required to be available at all Category 4—Systems in which failure is required to be kept on-site and avail-
times to support patient needs. Examples has no impact on patient care. Examples able at the time of the survey. K-Tag 901
might include life-support ventilation might include lawn sprinklers, television is used to cite a missing risk assessment.
equipment, emergency power for oper- service, and the public-address system. NFPA 99-2015 notes that the risk assess-
ating rooms, and medical-gas systems in Category 4 systems are likely to be found ment does not have to be performed for
intensive care units. Category 1 systems in support rooms, such as waiting rooms any system assigned a Category 1 classifi-
are likely to be found in intensive care and lounges. cation. Category 1 systems have the most
units, operating rooms, delivery rooms, The risk assessment is required to be stringent requirements; therefore, docu-
and areas dealing with general anesthesia. performed by following and document- mentation is only required for those sys-
Category 2—Systems in which ing a defined process, as described in tems in lower-risk categories to show that
failure is likely to cause minor injury. NFPA 551: Guide for the Evaluation of those systems are appropriately assigned.
Systems are expected to provide a high Fire Risk Assessments or ISO/IEC 31010:
level of reliability; however, limited fail- Risk Management – Risk Assessment Existing facilities
ures can be tolerated without significant Techniques. The process can be as sim- Existing facilities will not see major
impact on patients. Examples might ple as depicted in Figure 1. The process changes with the application of NFPA
99-2015 with the exception of inspection,
testing, and maintenance (ITM) require-
Will major injury
Yes CATEGORY 1
ments. In general, existing building sys-
System loss
or death occur? tems are permitted to remain, even if they
are not in strict compliance with the code,
No unless the authority having jurisdiction
(AHJ) determines that their continued use
constitutes a distinct hazard to life. This
Will minor
Yes CATEGORY 2 allowance of existing systems provides a
injury occur?
basis that existing facilities do not have
to upgrade their medical-gas/vacuum,
No electrical, and HVAC systems, along with
other utility infrastructure, to meet the
Will discomfort
requirements of the new edition. The
CATEGORY 4 No Yes CATEGORY 3 wording of this requirement leaves the
occur?
AHJ with latitude to potentially require
updates to building systems, such that
Figure 1: This flowchart illustrates a simple qualitative risk assessment approach facilities should review the status of their
based on yes/no answers to the level of patient and caregiver impact. All graphics systems conservatively to ensure that
courtesy: JENSEN HUGHES no surprises occur during inspections.
POWER VTX
to new and existing facilities. Most of the
®
fire protection and life safety require-
ments are not specifically included in
CONDENSING WATER HEATER
this chapter, but references are made to
other NFPA codes including: ®
ENGINEERED DUPLEX ALLOY
Visit
AHR Booth
New!
10” x 1”
#C4710
8” x 1”
AP ARMAFLEX®
LARGE ID TUBES
Now offering large size tubes.
10” x 1.5” Saves Time 25/50
8” x 1.5”
Easy-to-install ASTM E 84 flame
tubes and smoke rated
Unrivaled.
Belimo Advanced
Butterfly Valve.
Belimo’s new butterfly valve assembly is the most
intelligent, energy efficient, and reliable high flow solution
NEAR FIELD for HVAC applications. With a smartphone, easily program,
COMMUNICATION
(NFC) ENABLED
commission, and troubleshoot the butterfly valve. NFC and
BACnet communication provide the data access you need
to ease installation and ensure optimal performance.
Belimo offers the highest quality products that are backed
by world-class service and support.
Google Play and the Google Play logo are trademarks of Google Inc.
S
pace heating is the single largest required to have an ERV in climate zones
Learning energy end use in most build- 1A, 2A, 3A, 4A, 5A, and 6A under the
objectives ing types. The surprising fact 2012 and 2015 IECC. (The 2015 IECC
Know the basics of waste-
is there is a lot of waste heat clarifies it further by separating systems
heat recovery. that goes unused. Hospitals that operate greater than and less than
Learn the codes, standards,
and laboratories are two of the high- 8,000 hours/year.)
and guidelines that provide est energy-use-intensity building types. ASHRAE 90.1’s ERV requirement is
engineers with guidance in Regardless as to whether a conventional similar but prescriptive, which means
designing waste-heat recov- hospital or lab is in Miami or New York the performance path allows the ERV
ery systems in buildings. City, the largest single energy consum- performance to be made up in other
Understand that recover- er is the heating plant. This is because systems. The other most common code-
ing waste heat becomes an the heating load in hospitals and labs is required heat recovery is a prescriptive
attractive option for facili-
ties working to achieve low
largely reheat, which is not a climate- requirement introduced in ASHRAE
energy use (such as in high- dependent load. Traditional, centralized 90.1-1999 and the 2003 IECC, which is
performance buildings) and HVAC systems with code-required air- applied for recovering condenser heat of
to reduce emissions. change rates typically use reheat to keep water-cooled systems to preheat service
the spaces comfortable. Any heat that can hot water in 24-hour facilities or provide
be recovered in these building types can reheat (via an exception). This require-
be used to reduce the heating energy. ment has remained in all subsequent ver-
For many engineers, their first foray sions of ASHRAE 90.1 and the IECC.
into heat-recovery comes as a result of The first step in any design process
5
a code requirement. ASHRAE Standard is to focus on reducing the load before
tips for using 90.1: Energy Standard for Buildings employing technologies to serve the load
energy recovery Except Low-Rise Residential Buildings or offset energy consumption. Reducing
Check what is required by code. and the International Energy Conser- the load saves on first cost and lifecycle
vation Code (IECC) both have require- cost, whereas systems used to just reduce
Specify a bypass with air-side energy
recovery. ments for heat recovery. The most strin- energy consumption add to the first cost
gent being the mandatory requirement while reducing lifecycle cost. Energy
Size heat-recovery chillers to run continu-
ously at full load. of energy-recovery ventilation (ERV) models may be used to compare load-
Zone variable refrigerant flow systems to
systems in the 2012 and 2015 versions reduction strategies early in design.
take maximum advantage of heat recovery. of the IECC.
Use energy models to determine the most
For example, a system with 35% out- Defining waste-heat recovery
efficient heat-recovery strategy. side air at maximum flow that has greater Waste-heat recovery is using any heat
than or equal to 5,500 cfm total supply is that would otherwise be wasted. There
T
he Vanderbilt University Engineering Science Building (VU ESB) contains Instead, the team elected to use a desiccant wheel in series with a CHW
dry and wet research labs, a clean room, and classrooms. The labs coil on the primary 42°F CHW loop. This allowed for the elimination of the
and clean room are the predominant building uses and most energy- dedicated glycol chiller and reduced the heating and cooling energy needed
intensive spaces. A primary goal established at the beginning of design was to maintain the clean room conditions.
to have a flexible HVAC system that would minimize reheat. The smaller classroom and gathering areas are served with a standard VAV
The base HVAC system used for comparison was a chilled-water (CHW) system with return air. The lab areas of the building are 100% OA with ACB.
variable air volume (VAV) system with hot-water (HW) reheat. Because the Since the need for reheat in the labs had already been minimized via system
labs had a minimum air-change requirement and the clean room had a mini- selection, the focus for employing waste-heat recovery moved to precooling/
mum air-recirculation requirement, fan energy was heating the large volume of required OA.
the highest energy end use rather than heating; When designing air-side When designing air-side heat-recovery systems
however, it was a close second. heat-recovery systems for labs and hospitals, there is always concern
An energy model was used to approximate the about what exhaust air is safe for heat recovery.
annual energy use of the building with the base
for labs and hospitals, In hospitals, there is potentially hazardous air from
VAV system and active chilled beams (ACB) for there is always concern about isolation rooms, soiled storage, and emergency
the labs. ACBs allow for zone heating and cooling what exhaust air is safe for waiting rooms, to name a few. No one wants
control, which reduces reheat. The only reheat that to potentially contaminate the OA by recovering
heat recovery.
occurs with an ACB is when the zone has no need heat and/or moisture from those spaces. In a lab
for cooling and the primary air must be reheated. This same approach is being building like the VU ESB, air from the exhaust hoods is the major airstream
applied in some health care facilities by reducing primary air-change rates. of concern. It was decided that the hood exhaust would not go through the
The clean room is served by a make-up air unit (MAU) dedicated to main- heat-recovery device. Beyond the fear of contamination, certain chemicals
taining strict humidity limits coupled with recirculation units to continuously could also damage the heat-recovery media.
filter the air. The MAU takes preconditioned outside air (OA) from the lab An enthalpy wheel was chosen for the main lab DOAS because of its ability
dedicated outside-air system (DOAS), lowers the dew point to 40°F, and to precool and dehumidify the OA in the summer months while preheating and
reheats it to 65°F. The typical brute-force method would require a dedicated humidifying the OA in the winter months, and any fume hood exhaust would
glycol chiller to produce extra-cold CHW to reduce the dew point and then not be available to the heat-recovery system. Being in Climate Zone 4A, the
reheat it with HW. enthalpy wheel would have a positive effect year-round. The main piece of
analysis was to determine whether a dual-wheel system would yield lower The other negative factor of a potential second wheel is it only
energy consumption than a single-wheel arrangement. provides benefit in cooling mode. The second wheel doesn’t turn when
ACB systems are often designed with the primary air delivered at a neutral the unit is in heating mode, but the pressure-drop penalty still exists. A
temperature, one that provides little heating or cooling effect because it is bypass could be incorporated to remove the wheel from the airstream to
close to the space’s set points. In cooling mode, a dual-wheel arrangement remove the pressure-drop penalty when the wheel wouldn’t be effective;
would allow the DOAS to reheat the primary air with recovered heat using a however, for large systems like those in the VU ESB, a bypass is very
second sensible-only wheel instead of HW. costly. Some smaller systems have bypasses as a standard feature,
The trade-off to adding an air-side heat-recovery device is always whether which can make the needed energy savings easier to achieve because
the amount of energy saved via preheating/cooling the fan penalty only has to be paid when energy
is enough to offset the increased fan energy that Energy codes are can be recovered.
results from the increased pressure drop, which hap- pushing more designs Even though the energy model showed
pens when moving the air through the heat-recovery lower energy consumption with the dual-wheel
to require waste-heat
equipment. An economizer bypass allows the air to arrangement supplying neutral air, the final
bypass the heat-recovery device when outdoor condi- recovery, whether it be via design used one wheel to assure there was
tions are suitable, which reduces wasted fan energy. air, water, or refrigerant. enough flexibility in the cooling capacity of the
The energy trade-off to make air-side heat recovery labs without increasing the number of ACB.
financially viable hinges on the utility rates. Where electricity rates are lower and The lab DOAS heat-recovery system resulted in an estimated savings of
gas rates are higher, the increase in fan energy due to the added static makes $47,200 and 7.85% energy per year as compared with the same system
less of a cost impact than the reduction in heating energy. The opposite is also without heat recovery. The clean room desiccant heat-recovery system also
true, especially when high-efficiency boiler systems are used. saved a substantial amount of energy, and its first cost was offset against
Through energy modeling, it was determined the single enthalpy wheel the cost of the now unnecessary glycol chiller.
energy savings were above and beyond the increase in fan energy. Interest- Waste-heat recovery systems may be incorporated in many ways. Energy
ingly, the determining factor as to whether the second sensible-only wheel codes are pushing more designs to require waste-heat recovery, whether it
would provide enough savings was the needed primary air temperature. The be via air, water, or refrigerant. At the end of the day, waste-heat recovery
second wheel would only provide benefit if cooling effect from the primary is effective because heat that would otherwise be squandered is being
air was not needed. used to reduce energy consumption.
“Critical Power: Hospital Electrical Systems” is a new CFE Edu online course
that has been developed specifically for engineers who design electrical systems for health care
facilities. This unique course with exclusive content features instructor-led discussions, videos,
and high-quality presentations on an interactive, on-demand platform. The course is self-paced,
accessible 24/7, and offers one (1) AIA CES approved learning unit and one (1) HSW credit.
Figure 2: The plate and frame heat exchangers in the Wrigley Field campus chilled-water plant allow for the chilled-water system
to operate in water-side economizer.
enticing option as it would be used more viding up to 100% of the expected system 90.1. To have an integrated control of a
frequently. cooling load at OA temperature of 50°F water-side economizer per Standard 90.1,
There are arguments that could be dry-bulb/45°F wet-bulb and below.” This the system is responsible for not only
made against water-side economizers typically requires the engineer to calcu- providing free cooling when the outdoor
due to their high use of make-up water. late the economizer capacity using the wet-bulb temperature is 45°F and below,
However, due to the low cost of water in load calculation with loads on the build- but also for prolonging the free cooling
Chicago as compared with the national ing broken down by OA temperature. period by precooling the condenser-
average, a water-side economizer for this One exception for this section involves water temperate and warming the return
application had a clear advantage. computer rooms; there is a table to evalu- chilled-water temperature.
A potential justification for designing ate the requirements based on the climate
a water-side economizer is if the OA and zone. The other exception for this sec- Cooling towers
exhaust louver locations established by tion includes dehumidification require- In some cases, the air-side economizer
the project are restrictive. Often for air- ments that cannot be met at a 50°F dry- option has been integrated into the sys-
side economizer projects, the AHU needs bulb/45°F wet-bulb outdoor condition tem design. Unlike data centers for an
to be near the exterior façade to enable and where the expected system cooling office building, hotel, or mixed-used
a short connection to the outdoors. This load at 45°F dry-bulb and 40°F wet-bulb complex commercial building (such as
often forfeits the sought-out perimeter is met by the water-cooled fluid econo- a high-rise), the variation between the
offices for executives. A water-side econo- mizers. Standard 90.1 also requires the summer load versus winter load can be
mizer minimizes this because, instead of fluid economizer to have integrated large—from 4:1 to as high as 10:1.
large ductwork resulting in lower ceilings economizer control. For most cooling tower manufactur-
or perimeter offices becoming mechani- When designing the water-side econo- ers, cooling towers or cooling tower cells
cal rooms with a view, the ductwork is mizer with plate and frame heat exchang- can be winterized by using weir dams or
sized for minimum OA and the econo- ers, there are two piping arrangements for maintaining 50% or more of peak summer
mizer requirement is met by the heat which the heat exchangers can be con- condenser flow at the nozzles to prevent
exchanger at the central cooling plant. figured in relation to the chillers: par- scaling during winter operation. Depend-
Per ASHRAE Standard 90.1-2016 Sec- allel (Figure 3) and series (Figure 4). If ing on specific cooling tower selections,
tion 6.5.1.2, Fluid Economizers, if the the building system only has the option some manufacturers can reduce winter
project team elects to design a water-side of a water-side economizer, then series condenser flow even more than 50%.
economizer, the cooling towers/fluid arrangement with integrated control is Therefore, when choosing cooling tow-
economizer needs to “be capable of pro- the only option when following Standard ers and chillers for the project, the main
and MS/TP
•Open drag and drop component
based programming language –
Sedona Framework™
•Unrestricted programming
tool – our free Sedona
Application Editor
input #21 at www.csemag.com/information
BAScontrol
Learn more at www.ccontrols.com/controllers
Additionally, the maximum load on
the water-side heat exchanger and cool-
ing tower cells also was assessed to
determine the heat-exchanger capac-
ity. Important criteria the design team
assessed when determining the maxi-
mum water-side cooling load, besides
the Standard 90.1 requirement, included
whether there would be a winter event at
the ballpark (i.e., outdoor hockey game),
occupancy loads and uses, refrigeration Figure 5: This view shows the secondary chilled-water pumps at the Wrigley Field
equipment usage, and computer room campus chilled-water plant.
cooling loads.
Among other cold-climate chilled- cooling tower basin, and variable-speed chillers of 400 to 600 tons required 0.560
water systems, careful consideration is condenser-water pumps. kW/ton at full load (FL) and 0.500 kW/ton
required to prevent continuous operation (integrated part-load value; IPLV) for Path
through the winter months to prevent Modified chiller efficiencies A. Additionally, Path B required 0.585 kW/
freezing. During the design of the Wrigley ASHRAE Standard 90.1-2013 Table ton (FL) and 0.380 kW/ton (IPLV) for the
Field Plaza Building, there were a number 6.8.1-3 dictates minimum efficiency same chiller type and load range.
of precautions taken. These included heat requirements for water-chilling pack- Both requirement paths are based on
tracing outdoor piping used in water-side ages that all projects are required to meet. AHRI Standard 550/590 testing crite-
economizer operation, isolation of valves Effective Jan. 1, 2015, the requirements ria. The difference is Path A is intended
not winterized for system drain-down, were further restricted where water- for applications where most of the load
condenser-water bypass through the cooled, electrically operated centrifugal is full load while Path B is intended for
The 2017 Lighting & Lighting Controls study was completed by Consulting-Specifying
Engineer to evaluate customer awareness, usage of, and preference for suppliers
of various types of lighting and lighting controls products and systems. Respondents
to the Consulting-Specifying Engineer 2017 Lighting and Lighting Controls
study identified six high-level findings.
According to the data in the Lighting & Lighting Controls report, when asked
to identify important features considered when selecting one lighting product
over another, 73% of respondents said the overall quality of the product is
highly important, and 61% said the same of the product’s energy efficiency
capabilities. Other valuable factors include the manufacturer’s reputation and
the initial product cost.
I
n the past few years, the term “Inter- ’90s, cell phones only handled telephone
Learning net of Things” (IoT) has become the calls. During this time, cell phones had
objectives favored buzzword to describe the next access to the telephone network but not
Understand the basics of stage of evolution of the information the internet.
Internet of Things (IoT) and age. This is an abstract term, which In the early ’90s, we saw the birth of
how its evolution will impact makes the concept more difficult to the web and smartphones. When phones
building systems. understand. How does this abstract term could be used to access data from external
Anticipate IoT’s influence affect building design? It would make data sources, they became an IoT device.
on building systems, infra-
more sense to use the term as a verb, such As an infant IoT device, cell phones could
structure, and the evolution
of design. as “the internetting of things,” or simpler be used for email and text messages. They
yet, “the networking of things.” eventually grew into web browsers. Cur-
What we are really talking about with rently, smartphones are only limited by
IoT is taking items or devices (things) and the applications loaded on them. Com-
connecting them to a network where the munications and access to data were key
items have access to information. The to cell phones becoming smartphones.
devices will use the information in dif- Today, cell phones have multiple wire-
ferenent ways. The simple devices will less modes (cellular, Wi-Fi, Bluetooth,
interpret and display information. More and others) that allow them to exchange
sophisticated devices will receive infor- data from the “cloud” and control other
mation from their environment and com- devices near and far.
municate it back through the network. The cell phone is just one example.
The most sophisiticated devices have Consider the following: We have cars
integrated logic or intelligence to per- that can communicate to a dealership
form control functions and to interact when they need service or if they are in
with other devices. How can we anticipate an accident, vending machines that tell
the impact and trends of IoT so we can the distributor when they are running
extrapolate its impact on infrastructure? low on product and allow payment via
Let’s start with an analysis of probably the credit card or mobile phone wallet, and
first IoT device, the cellular phone, to see televisions and DVRs that automatical-
how it evolved. ly check for software updates from the
The cell phone didn’t start as an IoT manufacturer.
device, but because of its access to the As architects and engineers, we need
cell phone wireless network, it was in to anticipate IoT trends as we design
the unique position to become an IoT facilities. IoT devices will continue to
device. From the early 1980s to the early become more popular for personal use,
Disparate lifespans
In considering a facility design that sup-
ports IoT, the challenge for the designer
is anticipating the technology trends for
key building components with different
lifespans. Cell phones as IoT devices do
not actually wear out in 18 months, but
they are driven to obsolescence by the
introduction of new technology and com-
petitive market forces. A cell phone battery
has an estimated life span of 2 years, but
when faced with the choice of replacing
the battery for 10% of the cost of a new
phone, often the choice is to replace the
phone to take advantage of the technol-
ogy improvements. Of all IoT devices, cell
phones probably have the shortest lifespan.
They also represent a new category of
devices in the workplace, often referred to
as “bring your own device” or BYOD. This
could apply to personal laptops, tablets, or
other electronic devices that are owned by
a person but used in a facility to conduct
business. Whereas a company may have
a corporate policy to replace an employee Figure 1: There are many different types of IoT devices depending on their function
laptop computer every 4 years, a person and how they interact with their environment. Some are designed to interact with
who brings their own laptop may decide people; many are designed to communicate with other devices or systems to auto-
to replace their laptop every 2 years. This mate our surroundins. All graphics courtesy: TEECOM
implies two things: The IT network must
be adaptable to newer technologies, and the device is used. The trend is for an source in the network room. Current
the IT department may not be in control increase in devices to be wireless. Wire- technology allows for a device with a
of their technology rollout. less allows for more flexibility for mobile single cable to communicate with video,
devices; for stationary devices, it elimi- data, control signal, and power just shy
Internet vs. intranet, nates the cabling. The biggest drawback of 100 W.
wired vs. wireless of wireless devices is the source of power. Related to IoT, another big user of
As the term implies, IoT devices are IoT devices are not inherently passive. wired devices is the wireless infrastruc-
connected to the internet. This is not They require power from a battery or an ture. To make wireless devices work, they
always true. This is another reason why external source. There are new devices, need to communicate with a cellular sys-
IoT devices should be considered the however, that have integrated photovol- tem or a Wi-Fi network. Within a facil-
“networking of things.” Besides access- taic cells to allow for recharging from ity, this will likely be through the building
ing data from across the internet, an IoT ambient light sources. Wi-Fi network. Each wireless access point
device may access data from a local net- Wired IoT devices in need of a power (essentially a radio) requires power and
work (intranet) or exchange data locally source can use the same data cable that data. The more devices communicating in
with a peer device. It depends on where is used to transmit and receive data. No one area, the greater the number of wire-
the device is and where the data is located. external power supply is necessary. This less access points needed to maintain a
IoT devices can be wired or wireless. uses a Power over Ethernet protocol or quality of service. The trend in wireless
This all depends on the device and how some other Class 2 or Class 3 power is for a higher density of wireless access
It’s so good at
cable management
you’ll expand technology.
Introducing Our New Under-Carpet Wireway
Available Now for Pre-Order
Connectrac ® wireways provide a proven power and IT alternative
to expensive and disruptive core drilling, trenching and unsightly
power poles. Our ultra-low profile wireway is so discreet it’s
barely noticeable as it elegantly blends in to any environment
while accommodating power and data.
Delivers Power + Data
®
S
mart buildings are made up of experts from the architecture, engineering,
complex systems containing and construction tiers focused on reducing Learning
equipment, control devices, and construction and lifecycle costs through a objectives
sensors managed with network- technology-focused approach. Learn how networking
ing infrastructure, processors, building infrastructure and
computers, and servers. The traditional Maximizing the sum of all parts systems can lead to a smart
construction approach to smart building A successfully integrated system will building.
infrastructure pushes down most imple- add greater value to the overall project as Plan for integrated building
mentation details and technology choices opposed to each individual design disci- technology with CSI Master-
Format Division 25.
to multiple levels of contractors. In turn, pline that uses embedded technologies to
these professionals design, procure, and monitor and control its respective systems.
implement infrastructure systems with- For example, lighting and HVAC have
out any collaboration of effort or choices many overlapping features, such as zone
across disciplines. occupancy sensors and schedules, front-
The resulting absence of a standardized end visualization software, tools for
network architecture, security scheme, and setup and configuration, Ethernet and
user interface for the entire facility creates fiber-optic cabling, and communication
a fragmented network of systems that protocols. These similarities present an
proves more difficult to operate, maintain, opportunity to remove duplications and
and expand over the building lifecycle. minimize the number of devices required
Although it is possible to manipulate to accomplish the same goal; automation
a smart building after construction is tasks also can be streamlined once the
complete, it comes at a cost. The tradi- systems are live. All of this adds up to
tional construction approach must rap- eliminated waste.
idly evolve, much like today’s operational In addition to lighting and HVAC,
technologies, to change the way that smart several other systems are responsible for
building technology is incorporated into maintaining any complex project includ-
new construction. Embracing this trans- ing access control, closed-circuit TV, life
formation will help building owners and safety, metering for utilities, and solar
operators avoid the sunk costs of meeting and energy storage. The importance of
specifications at minimum, as well as the eliminating inefficiencies and minimiz-
costs of integrating smart systems after the ing waste in any building is no longer a
building is occupied. Translating the idea value add. Today, it is a necessity for the
of integration to actuality requires upfront long-term lifecycle management of any
coordination and a collaborative team of smart building.
Figure 1: The West 2nd District project team that includes Envise is employing breakthrough strategies in design, engineering,
construction, and environmental systems to create a game-changing new cultural place. Courtesy: West 2nd District
Applying the CSI MasterFormat consequently, continuity did not exist in As emerging technology becomes
specification operational technology implementations viable, Division 25 serves as both a blue-
When planning for integrated tech- from one building to the next. print for upgrading existing technologies
nology upfront, consider using the Con- As rapid adoption of direct digital con- as they reach their end of life and as a
struction Specifications Institute (CSI) trol and networkable technology acceler- technology version-control system for
MasterFormat Division 25: Integrated ated, so did the need for data assimilation continuously improving and solving old
Automation specification as the coordi- in what used to be traditionally segmented problems with new, viable technology.
nation point between design, construc- systems within a building environment. As While the inclusion of Division 25 adds
tion, and service teams. This will enable a result, the MasterFormat was revised to sweat equity and coordination to the early
the project team to address technology address the growing need for governance development process, it is an essential
framework for addressing the long-term
sustainability of these facilities.
Implementing Division 25 as a coordination hub for Cost and quality remain at the top of
our industry’s priority list, and that will
design, construction, and service teams is critical. not change. However, our approach to
incorporating smart building technology
integration first and define goals and of all disciplines to converge the enormous into new construction must revolution-
requirements prior to construction. amount of technology being implemented. ize to more fully integrate project teams,
Introduced in 1963, the CSI Master- That revision is now known as Division which in turn, minimizes and even elimi-
Format specification for design coordina- 25: Integrated Automation. nates unnecessary and costly gaps. A true
tion and contract documentation for con- Implementing Division 25 as a coordi- champion of operational technology inte-
struction projects in the U.S. did not have nation hub for design, construction, and gration allows the appropriate accountabil-
a place, or need, for integrated technology. service teams is critical for addressing ity and responsibility of normalizing net-
Each division of the MasterFormat was commonalities between all the similar work architectures while creating criteria
covered under different disciplines, verti- technologies being applied to the same for standardizing operational technology
cals, and tiers within the new construction portfolios and new-construction oppor- software, hardware, and communications.
industry, with designers as experts in their tunities. Large campuses, hospital facili- The result is more efficiency, less waste,
respective field responsible for each piece ties, government agencies, data centers, and overall greater cost savings.
of the overall system. and other high-performing or complex
In essence, an architect responsible environments that have large operational Brandon McCarron is technology integra-
for converging systems was not part of requirements are especially prone to inef- tion engineer at Envise, a national build-
the design or construction process, and ficiencies without standardization. ing systems integrator.
That was over 30 years ago, and we’re still listening to customer input.
That is why Baldor-Reliance Stainless Steel motors and Dodge Ultra Kleen gear reducers are
engineered to meet the toughest demands of food production and processing. These products
have been designed, tested and certified to meet IP69K requirements for water protection, and
provide the necessary protection from severe washdown conditions without allowing caustic
chemicals or water to enter the product.
National Fire
[1]
Protection Association
(NFPA)
800.250.8552
info@cleaverbrooks.com
cleaverbrooks.com
input #29 at www.csemag.com/information
A DV E R T I S E M E N T
Connectrac’s latest cable installation process come with ramps and an array of
management solution – the core drilling, Connectrac is accessories and options.
Connectrac Under-Carpet efficient with the users’ time
Wireway— is now available and can be reconfigured as The Connectrac On-Floor
for purchase and shipping. This workspaces evolve. Wireway is Connectrac’s most
new wireway is the sleekest and flexible wireway, able to be
most low-profile design ever The Connectrac Under-Carpet installed on top of any flooring.
from Connectrac and looks to be Wireway elegantly accom- They lead the industry in both
an industry game-changer. modates power, data, and AV ease of installation and capacity
cabling and performs ideally for for telecom and A/V cables. The
Connectrac reduced the profile classroom lecterns, executive Connectrac On-Floor Wireway
of the wireway further to the offices, reception desks, and is the best wireway solution
point where any carpet can be much more! The low-profile when the speed of installation,
laid over the system, making it wireway used for the Under- flexibility, and value are critical.
virtually invisible. This factor Carpet system is also available
will take cable management in the Connectrac In-Carpet and With the Connectrac
out of sight and out of mind, On-Floor Wireway options. Under-Carpet, In-Carpet, and
blending in seamlessly with On-Floor Wireways, users can
any application design. The Connectrac In-Carpet deliver power, data, and A/V
Wireway offers discreet and connectivity to anywhere in
Now that carpeting completely elegant power and technology their interior application. The
covers the wireway, users can cable management, integrated three wireway options from
provide wireless aesthetics to into the carpeting with a Connectrac ensure it the most
their workspaces without the removable top cap for easy elegant and cost-efficient cable
hassles associated with cable and wiring access. It management solution over
alternatives like core drilling combines an extruded aluminum other alternatives such as
or trenching. While time central wireway flanked by core drilling, trenching, and
consuming and an arduous ultra-low sloping floor transition power poles.
Connectrac.com
info@connectrac.com | 1.877.480.5637
Firetrace International is the global leader in special hazard fire protection. The first to adapt to
new technologies, Firetrace supplies powerful, flexible fire management solutions worldwide.
Headquartered in Scottsdale, Arizona since its inception in 2000, Firetrace has expanded from
its initial 2,000sq ft (185sq m) facility to over 80,000sq ft (7,500sq m). Its European operations are
based just outside Gatwick Airport near London and, to ensure timely, effective support around the
world, it also maintains sales offices in Sydney, Singapore, New Delhi, Dubai and Johannesburg.
As one of the largest global installers of fire suppression systems, Firetrace has an established
product division. Skilled engineers in electrical, electronic and mechanical engineering are
dedicated to the ongoing research and development of all kinds of fire suppression systems.
Firetrace also sits on a range of different fire suppression committees that seek to determine and
promote best practice. This enables the business to not only remain compliant today, but also to
make accommodations for the future and ensure it continues at the forefront of any new learnings
or technologies.
It is this focus on innovation, flexibility and adaptability that sets Firetrace apart from its
competitors. If a customer comes to Firetrace with fire suppression needs that aren’t fulfilled – or
aren’t optimally fulfilled – by the company’s current range, the team works with them to make the
necessary changes.
A perfect example of Firetrace’s innovation is its E4 engineered clean agent
systems; the newest evolution in total flooding fire suppression. Firetrace E4
systems are shattering traditional design limitations using 500psi/35 bar
pressure in lower-cost, low pressure equipment, while achieving the
performance of more expensive high pressure or ‘nitrogen driver’ systems.
A further demonstration of Firetrace’s unique adaptability is its complete family
of UNECE (United Nations Economic Commission for Europe) R107 approved fire
suppression systems for buses. Firetrace is the only manufacturer to offer the
mass transit industry a wide choice of approved systems specifically designed
for their sector.
Mark Osborne
President, Firetrace International
www.firetrace.com | info@firetrace.com
+1 888 607 1218 (USA & Canada) +1 480 607 1218 (international enquiries)
input #31 at www.csemag.com/information
A DV E R T I S E M E N T
Intuitive Start-Up
Greenheck’s preconfigured and intuitive controls
Model RVE simplify start-up and reduce installation time. Control
sequences are optimized for Dedicated Outdoor Air
Systems and Variable Air Volume applications.
Model RV and Model RVE
• Up to 13,500 cfm
Greenheck Controller
• 2” Double Wall R13 Foam
• Cooling Options:
— Packaged DX
— Split DX
— Chilled Water
• Heating Options:
— Indirect Gas Furnace
— Electric Heater
— Hot Water
• Available with Modulating Hot Gas Reheat with
precise humidity control The controller is preprogrammed for the specific
job but parameters are easily adjustable in the
High Turndown Furnace field without additional programming devices or
An optional high turndown furnace can be specified factory technicians.
to provide up to 16:1 seamless turndown for more
precise temperature control and less furnace cycling. The microprocessor controller is capable of
This option is especially beneficial in variable air operating stand-alone or it can be integrated into
volume applications when decreased airflow causes a Building Management System (BMS) at any time
excessive cycling with lower turndown furnaces. through a protocol card using BACnet ® MS/TP or IP,
Higher turndown also improves occupant comfort on LonWorks ® or Modbus ® RTU protocols. Each unit is
part-load days or when the furnace is sized for a large factory-tested to ensure optimum performance
temperature rise. and quality.
715-359-6171 | greenheck.com
The Innovent Cx-Series provides streamlined Taking advantage of modern technologies creates a superior alternative
design and construction for today’s fast-paced to a welded floor.
environment. Applications include chilled and hot
water air handling needs in healthcare, hospitality, An innovative breakthrough in construction offers
education, commercial, industrial and laboratories. distinct advantages over a conventional welded
floor. A durable protective coating over a sheet
The Cx-Series offers metal floor creates a waterproof, non-slip surface
a wide range of throughout the unit. This 2” basin offers true wash
energy-efficiency down construction. Removable panels provide
options in a robust, easy upgrade of components enabling 30+ years of
foam-injected, service life.
variable-aspect ratio
casing. An online From configurable to custom, Unison® Air Handling
selection webpage has the right solution for your next project. Unison
enables Unison reps has earned a reputation for expertise in energy
to submit a unit recovery and refrigeration. With Valent configu-
selection and receive rable packaged rooftops and Innovent custom air
design documents in handling equipment, Unison has the products that
a matter of minutes. today’s energy-efficient buildings require.
“The Innovent Cx series bridges the gap between
custom units and configured products for fast-
track, cost-sensitive projects,” says Jennifer Schroer,
Vice President of Unison Air Handling.
Save 10-30%
HVAC system performance can begin to degrade within one year of
start-up. According to the 2015 ASHRAE Handbook—HVAC
Applications, UV-C reduces mold, biofilm and coil pressure drop, as
well as coil-cleaning. It further states that UV-C can increase airflow
and heat-transfer coefficients and reduce both fan- and refrigeration-
system energy use. Savings of 10-30% have been reported once
capacity is restored. And, UV-C equipment costs an average of less
than $0.15 per cfm.
Rapid Roi
For one commercial building owner, an independent audit
documented a 47% increase in airflow following the
installation of UV-C. The ultraviolet energy lowered energy
consumption enough for the project to pay for itself in just
three-months—an impressive 90-day ROI.
Although UV-C is a relatively simple technology, many engineers and building owners are amazed that
something so simple can yield such significant savings. Learn more today!
Call UV Resources at 877-884-4822 or visit www.uvresources.com
877-884-4822 | info@uvresources.com
www.UVResources.com
input #41 at www.csemag.com/information
A DV E R T I S E M E N T
901-748-8000
vpsales@vp.com
www.vp.com
input #42 at www.csemag.com/information
ADVERTISEMENT
Armaflex for Chilled Water Systems - AP Armaflex tubes, sheets and rolls are ideal for controlling conden-
sation and ensuring long lasting thermal efficiency for chilled water systems. The closed-cell nature of the
material provides a built-in water vapor barrier, so it won’t wick moisture, doesn’t require jacketing indoors
and surface punctures won’t affect its performance over time. AP Armaflex products are GREENGUARD Gold
certified and made with Microban® antimicrobial technology to resist the growth of mold in the insulation.
Support You Can Trust - Our Technical Managers can answer questions about products or performance. We
have a team of Specification Managers to help write specs as well as conduct educational Lunch & Learns
for continuing education credits.
About Armacell - Armacell operates six manufacturing facilities
in the US and one in Canada.
info.us@armacell.com | 800-866-5638 | www.armacell.us
input #43 at www.csemag.com/information
ADVERTISEMENT
• Delta T Optimization and Flow Setpoints provide recommendation which One Optimized Complete Solution –
can be updated remotely or automatically. Now Cloud Based.
• Performance Reporting graphically showing current and historical data of Discover all the advantages at
flow rates, energy usage, and Delta T. www.belimo.us or contact your
• Lifetime Data Access for future optimization. local Belimo Sales Engineer at
• Online Tech Support to assist you remotely. 800-543-9038.
• Software Updates provided for maximum productivity and reliability.
• Extended Warranty increased to 7-year with Belimo cloud connection.
ADVERTISEMENT
Learn more at
www.ccontrols.com/controllers
input #47 at www.csemag.com/information
ADVERTISEMENT
The design of many cooling towers creates pockets where water may stagnate, another condition
that can lead to microorganism development. The stagnant water areas are prime breeding
grounds for Legionella. To avoid such problems, Delta’s cooling tower designs feature
a sloped basin and/or basin sweeper system. A 20-year
factory warranty provides evidence of the durability of sales@deltacooling.com
these HDPE cooling towers. 973-586-2201
http://deltacooling.com
Features Include: Chilled, Hot, and Condenser Water System Applications for:
• Multiple Outputs, Flow Meter and • Central plant monitoring, campus energy monitoring and cost allocation
Temperature Sensor Options • Performance/efficiency evaluations
• Auxiliary Pulse Inputs • AHU and CRAC units for commercial office tenant billing
• Built-in Interval Data Logger • Solar, geothermal and ground-source
• Suitable for Water and Water/Glycol Solutions energy monitoring
• User-Friendly Interface Display
FLOW AND ENERGY MEASUREMENT
www.onicon.com | sales@onicon.com | 727-447-6140
input #49 at www.csemag.com/information
ADVERTISEMENT
800-784-8326 | www.PVI.com
The FR-PANL™ has no screws through the panel joints, eliminating the
possibility of air and noise leaks while also reducing installation costs.
Available in a 4-inch thickness, these panels protect equipment inside
the enclosure from surrounding fires and also prevent fire spread to
surrounding environments when originating inside the enclosure.
ADVERTISEMENT
BY ALEXANDER SASSOON, EIT, LEED AP BD+C, WELL AP, P2S, Long Beach, Calif.
E
ffective daylight design in tasks and limit glare. Luminance is the
Learning buildings creates a comfort- measurement of task lighting, and Illu-
objectives able and productive environ- minance is a measurement of direct
How to identify successful ment for occupants. Effec- glare. The unit of measurement for
daylighting design. tive daylighting can reduce luminance is a footcandle (fc), or lux,
Explore the elements of energy use, but also must limit HVAC and the unit for illuminance is candelas
daylighting. loads. The U.S Green Building Council’s per square meter (cd/m2). Uniformity
Learn how to integrate day- LEED rating system and the Interna- glare is also important, which is the ratio
lighting and lighting control tional WELL Building Institute’s WELL of luminances in adjacent spaces.
systems. Building Standard are two well-known People need between 5 and 10 fc for
rating systems that reward outstanding circulation and orientation in a space,
daylighting design. between 30 and 50 fc to perform most
visual tasks, and between 50 and 100
Daylighting design fc to perform difficult tasks involving
It’s important to first identify the ele- low contrast or high accuracy. People
ments of successful daylighting design. also need uniform light. The differ-
Buildings that are daylit provide ade- ence between lighting in task areas and
quate lighting to perform most visual adjacent areas (uniformity glare ratio)
should be close to 3:1, and the unifor-
mity glare ratio between task areas and
remote areas should be close to 5:1. At
no point should the brightest spot be
more than 10 times brighter than the
darkest spot, or it will become a source
of indirect glare.
There are two ways to bring daylight
into a building: from the walls or from
the ceiling. Once daylight is brought
into a building, it’s important to make
sure that glare wasn’t introduced.
Sidelighting refers to daylighting
from windows. Windows can bring
twice as much daylight into a space.
Figure 1: A closed-loop photosensor measures both natural and artificial light in the For example, if the top of the window
space. All graphics courtesy: P2S Engineering Inc. is 10 ft above the floor, daylight will
MOTOR
WattNode® Meter
Module for HVAC
PLUGS
Load Measurement
NEW
QUICKLY CONNECT
& DISCONNECT POWER
OFF
Button
Multi-measurement energy
metering on a single board
RS485 communications
Externally (instrument) powered Safety Shutter
For all (120-600 Vac) Services (on receptacle)
Single or three-phase
Designed for -30C to +80C Rated up to 200A, 75hp
Options for interface and
mounting, including DIN
4 Connector + Switch in 1 device
4 Maximizes Arc Flash Protection
1-888-928-8663 4 Minimizes PPE Requirements
sales@ctlsys.com meltric.com
www.ctlsys.com
800.433.7642 A company of MARECHAL ELECTRIC GROUP
New E-Newsletters!
Providing helpful and specific information that’s
Why Should You directly applicable to your career
increases the water pressure drop through the heat NewsWatch: Hospitals
This newsletter focuses on hospitals and health care facilities,
exchanger and pipes. In fact, one study has shown including codes and standards, electrical/power, HVAC, fire and
that .002" fouling will increase pumping needs by 20%. life safety, and other engineering topics.
T
he exponential growth of com- Technology is already employed Assuming the former can be over-
puting power, increasingly in less complex service businesses come, engineering firms should
innovative software applica- to reduce manually intensive tasks, understand that a different set of com-
tions, and a relentless pursuit of automate easily defined transactions, petencies is needed to make the latter
streamlined project delivery has led and facilitate reuse of similar historic successful.
many engineering firms from the solutions. At the farthest end of the These firms need a dedicated staff
world of T squares and slide rules to technology spectrum, artificial intel- whose only job is to build, maintain,
suddenly resembling Silicon Valley ligence is seeking to replace human and sell the software. They also need
startups. Customers are constantly recollection, judgment, and estimation to have an appetite for a different
demanding better, faster, and cheaper in a scalable manner that delivers either business model that involves building
projects. As a result, engineering firms comparable or better results derived prototypes, piloting, gaining traction
have looked to software and intellectu- from highly trained people. The pri- through marketing, and then waiting
al property (IP) to gain a leg up. These mary advantage technology-based solu- for revenue to come in. There is little to
innovations, if properly harnessed, tions have over human capital is scale. no immediate value creation in a soft-
should lead to an increase in value if Delivery methods like virtual design ware-as-a-service business model, but
one of the below paths are followed. and construction will soon become the it is incredibly scalable and can add a
new norm for projects of all sizes, so high-margin, recurring revenue stream
Third-party applications or IP firms will need to adapt their methods to the typical project-based business
The first, and more traditional, route and become fluent in the processes and model of an engineering firm.
is leveraging a third-party application or tools necessary to compete. Tools like The takeaway is that firms that believe
internally developed IP to improve effi- Revit, coupled with contract structures IP has value beyond internal use will
ciency. If a firm can employ technology that enable and incentivize efficiency, need to think differently about their
to do their work better-faster-cheaper, can be tremendous value-creation approach. Software and IP should be
profit margins should improve. In the methods for firms in the industry. more than just a way to get projects out
If an engineer can produce two sets of the door.
plans in the same amount of time it used Monetizing proprietary software
to take to produce one, the firm’s profit The second, and less traveled, route Neil Churman is a director at 7 Mile
and loss statement should benefit. This, is to monetize a proprietary software or Advisors, where he advises architecture,
of course, is under the assumption that application externally by marketing it engineering, and construction industry
the revenue generated by each project to other industry partners. Many firms firms.
is constant, regardless of the amount of that have developed IP have struggled
time or cost to produce them. to find ways to monetize it, either Andy Johnston is a founding partner
Firms that work on a lump-sum or because they feared they’d lose the of 7 Mile Advisors. The investment
fixed-fee basis stand to gain the most advantage it afforded them to compete banking firm focuses on working with
from the improved efficiencies technol- for projects or because they lacked the providers of consulting and professional
ogy and IP can provide. ability to effectively market it. services.
Low Harmonics
IEEE519-1992 Compliant
Power Factor
0.98 or higher
OR HERE OR HERE
REDUCED
HIGHEST
FOOTPRINT
TIERED
AVAILABLE PERFORMANCE
EFFICIENCY
Introducing the all-new AquaForce® 30XV from Carrier – the air-cooled screw chiller
that’s designed for tomorrow and fit for today.
Today’s cooling systems face a multitude of demands and limited spaces – and the same old
solutions just can’t cut it. That’s why Carrier developed the new 30XV with a range of available
benefits, tiered performance, innovative features and more. Plus, with industry-leading efficiency,
quieter operation, a wide operating range and quick restart capability it all adds up to the
versatility you need to meet almost any cooling demand, in any type of building, anywhere.