You are on page 1of 88

Smaller Footprint.

Bigger Performance.

The new Baldor•Dodge® Vertical Gearmotor offers • Higher Efficiency


a high efficiency solution to low speed, high volume
pumping applications. Designed and built on a
standard low pole count motor platform and integrating
our proven planetary gear technology, our Vertical
Gearmotors provide optimum performance in a smaller
• Cost Effective
envelope.

With available power ratings from 750 Hp to 25,000 Hp,


you can be certain the new Baldor•Dodge Vertical • Smaller Footprint
Gearmotor will give you the highest efficiency, best
power factor in a smaller, lighter package.

baldor.com 479-646-4711 • Optimal Shaft Speed

©2017 Baldor Electric Company

input #1 at www.csemag.com/information
Tyco SimplexGrinnell
is now Johnson Controls.
The combined strengths of two great companies are now under one great name. Making
Johnson Controls the world leader in fire protection, security, HVAC, building controls and
energy storage. Count on us for innovative solutions that lead to safer building environments
and better outcomes for customers. Like advanced Simplex TrueAlert ES solutions with
revolutionary notification system self-testing capabilities. Exactly what you’d expect from a leader.

Discover the Addressable Self-Testing Difference


at tycosimplexgrinnell.com/selftest.

input #2 at www.csemag.com/information
Packing more power into the
same flexible design.
Introducing 1200 Amp Starline Track Busway,
the newest addition to the T5 Series.

Starline’s newest addition to our line of track busway options delivers even more power,
without losing any of the flexibility that you’ve come to rely on from our T5 Series.
The 1200 amp busway still has our unique, modular, build-as-you-need design, and is
equipped for high-density electrical distribution under the most demanding conditions
in data center and mission critical environments. Best of all, the same plug-in units can
be used for all systems in the T5 series—from our 250 amp to the new 1200 amp. To
learn more about our newest and largest busway choice, visit StarlinePower.com.

250 amp 400 amp 800 amp 1200 amp

input #3 at www.csemag.com/information
ON THE COVER:
The Vanderbilt Uni-
versity Engineering
and Science Build-
ing is a 230,000-sq-
ft interdisciplinary
research and JUNE 2017
teaching build-
ing in Nashville,
Tenn. The building
uses air-side heat FEATURES
recovery as one
of the elements 38 | Modernizing the Wrigley
to achieve 30% Field chilled-water system
energy-cost sav- Selecting and specifying the right chiller
ings compared to is generally dictated by capacity, and
ASHRAE Standard there are many philosophies on the
90.1-2007.
best way to control, operate, and calcu-
Courtesy: TLC Engi-
late system operational costs.
neering for Archi-
SUZAN SUN-YUAN, PE, CDT, LEED AP; and
tecture
CORY J. ABRAMOWICZ, PE, HBDP, LEED AP

COVER STORY
32 | Recovering waste heat in buildings 46 | Designing buildings
Waste-heat recovery systems are increasingly used in for the Internet of Things
buildings to move waste heat from laboratories, data
The networking of things within a
centers, or industrial activities to provide beneficial
building must be anticipated by
heating in other parts of the building.
building engineers.
CORY DUGGIN, PE, LEED AP BD+C, BEMP
TIM KUHLMAN, PE, RCDD

DEPARTMENTS
51 | Integrating BAS,
05 | Viewpoint 25 | Codes & Standards controls for smart buildings
How to educate a Applying NFPA 99 Technology integration between all
changing population to health care facilities engineering disciplines will create a
smart building that can enhance
07 | Research 77 | Digital Edition
building operations.
Electrical, power systems Exclusive
in data centers BRANDON McCARRON
The basics of daylighting

09 | Career Smart 79 | Advertiser Index


Mentoring creates a
competitive advantage 80 | Future of
Engineering ENGINEERING DISCIPLINES
10 | MEP Roundtable How engineering firms Use the icons to identify topics of interest.
High expectations for can enhance value with AUTOMATION & CONTROLS HVAC
high-performance buildings software and intellectual
COMMUNICATIONS LIGHTING
property
19 | Codes & Standards ELECTRICAL PLUMBING
How NFPA 99-2015 changes FIRE, SECURITY & LIFE SAFETY
affect mechanical design

CONSULTING-SPECIFYING ENGINEER (ISSN 0892-5046, Vol. 54, No. 5, GST #123397457) is published 11x per year, monthly except in February, by CFE Media, LLC, 1111 W. 22nd Street, Suite
#250, Oak Brook, IL 60523. Jim Langhenry, Group Publisher /Co-Founder; Steve Rourke CEO/COO/Co-Founder. CONSULTING-SPECIFYING ENGINEER copyright 2017 by CFE Media, LLC. All rights reserved. CONSULTING-
SPECIFYING ENGINEER is a registered trademark of CFE Media, LLC used under license. Periodicals postage paid at Oak Brook, IL 60523 and additional mailing offices. Circulation records are maintained at CFE Media, LLC, 1111
W. 22nd Street, Suite #250, Oak Brook, IL 60523. E-mail: customerservice@cfemedia.com. Postmaster: send address changes to CONSULTING-SPECIFYING ENGINEER, 1111 W. 22nd Street, Suite #250,
Oak Brook, IL 60523. Publications Mail Agreement No. 40685520. Return undeliverable Canadian addresses to: 1111 W. 22nd Street, Suite #250, Oak Brook, IL 60523. Email: customerservice@
cfemedia.com. Rates for nonqualified subscriptions, including all issues: USA, $150/yr; Canada/Mexico, $180/yr (includes 7% GST, GST#123397457); International air delivery $325/yr. Except for special issues where price
changes are indicated, single copies are available for $30.00 US and $35.00 foreign. Please address all subscription mail to CONSULTING-SPECIFYING ENGINEER, 1111 W. 22nd Street, Suite #250, Oak Brook, IL 60523. Printed
in the USA. CFE Media, LLC does not assume and hereby disclaims any liability to any person for any loss or damage caused by errors or omissions in the material contained herein, regardless of whether such errors result from
negligence, accident or any other cause whatsoever.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 3


WHATEVER THE HAZARD,
WE’VE GOT YOU COVERED

PRE-ENGINEERED SYSTEMS ENGINEERED SYSTEMS


FOR SMALL SPACES: FOR LARGE SPACES:
Detect and suppress fires automatically High-pressure performance in a low pressure system
Reacts 10x faster than conventional systems Unparalleled flexibility in system design and placement
Compatible with most extinguishing agents Cylinder sizes ranging from 35lbs to an industry leading
1300lbs using 3M™ Novec™1230
Listings and approvals vary by agent and system type

LEARN MORE AT:^^^MPYL[YHJLJVT

FIRETRACE INTERNATIONAL - WORLD HEADQUARTERS FIRETRACE INTERNATIONAL LTD - EMEA OFFICE


8435 N. 90th St., Suite 2, Scottsdale, AZ 85258, USA. Unit 11, IO Centre, Salbrook Road, Salfords, Surrey, RH1 5DY, UK.
Tel: +1 480 607 1218 •,THPS!PUMV'ÄYL[YHJLJVT Tel: +44 (0) 1293 780 390 •,THPS!PUMV'ÄYL[YHJLJVT
input #4 at www.csemag.com/information
Editor’s Viewpoint
CONTENT SPECIALISTS/EDITORIAL
AMARA ROZGUS, Editor-in-Chief/Content Manager
630-571-4070 x2211, ARozgus@CFEMedia.com
EMILY GUENTHER, Associate Content Manager
630-571-4070 x2220, EGuenther@CFEMedia.com
AMANDA PELLICCIONE, Director of Research
APelliccione@CFEMedia.com
MICHAEL SMITH, Creative Director
630-779-8910, MSmith@CFEmedia.com
ELISA GEISHEIMER, Production Coordinator
630-571-4070 x2213, EGeisheimer@CFEMedia.com
Amara Rozgus,
Editor-in-Chief
EDITORIAL ADVISORY BOARD
CORY J. ABRAMOWICZ, PE, LEED AP,
Associate, Environmental Systems Design Inc., Chicago
PETER ALSPACH, PE, LEED AP BD+C,
Principal, Mechanical Engineer, Arup, Seattle
JERRY BAUERS, PE,
How to educate a
Vice President, NV5, Kansas City, Mo.
MICHAEL CHOW, PE, LEED AP BD+C,
Principal, Metro CD Engineering LLC, Columbus, Ohio
changing population
T
TOM DIVINE, PE,
Senior Electrical Engineer,
Smith Seckman Reid Inc., Houston
he population of the United schools in many ways. Private schools
CORY DUGGIN, PE, LEED AP BD+C, BEMP, States ebbs and flows as the often rely on endowments or dona-
Energy Modeling Wizard, TLC Engineering for Architecture Inc.,
Brentwood, Tenn.
birthrate changes and the death tions from generous benefactors to
ROBERT J. GARRA JR., PE, CDT, rate fluctuates. According to the build new programs or facilities.
Vice President, Electrical Engineer,
CannonDesign, Grand Island, N.Y.
World Bank and other sources, the The cost of education continues to
JASON GERKE, PE, LEED AP BD+C, C X A, United States birthrate has held about rise, changing the dynamics of how
Mechanical Engineer, GRAEF, Milwaukee
even over the past 20 years, with 1.8 students earn a degree. The number of
JOSHUA D. GREENE, PE,
Vice President, Jensen Hughes, Framingham, Mass. births per woman (the most recent enrollees in 2-year schools saw a surge
RAYMOND GRILL, PE, FSFPE, data is from 2015). From 1960 to 1995, between 2009 and 2012 (think Great
Principal, Arup, Washington, D.C.
DANNA JENSEN, PE, LEED AP BD+C,
however, the U.S. birthrate was on Recession) and part-time students
Senior Vice President, WSP, Dallas a downward trend; in 1960, the U.S. were at an all-time high in 2010. The
WILLIAM KOFFEL, PE, FSFPE,
President, Koffel Associates Inc., Columbia, Md.
birthrate was 3.7 births per woman. debate continues about whether a col-
WILLIAM KOSIK, PE, CEM, LEED AP BD+C, BEMP, Around the world, the birthrate cur- lege degree is really necessary. What
Senior Mechanical Engineer - Mission Critical,
exp US Services Inc., Chicago
rently is 2.45 births per woman, which are schools doing to stay ahead of their
KENNETH KUTSMEDA, PE, LEED AP, also reflects a downward trend (it was competition in a tight market?
Engineering Manager, Jacobs, Philadelphia double that number, at 4.98 births per Brick-and-mortar facilities are creat-
JULIANNE LAUE, PE, LEED AP BD+C, BEMP,
Senior MEP Engineer, Center for Sustainable Energy, woman, in 1960). ing top-notch facilities to educate stu-
Mortenson Construction, Minneapolis Several news outlets reported the dents in the most promising fields. The
DAVID LOWREY,
Chief Fire Marshal, Boulder (Colo.) Fire Rescue low birthrate in the U.S. as a “national article “Recovering waste heat in build-
BRIAN MARTIN, PE, emergency” and a “fertility crisis.” As ings” on page 32, for example, highlights
Senior Electrical Engineer, Buildings and Places,
AECOM, Portland, Ore. older citizens die, the country’s young a university that is upgrading its science
DWAYNE G. MILLER, PE, RCDD, AEE CPQ, population cannot yet contribute as labs, banking on the fact that science and
Chief Executive Officer, NV5, Las Vegas
much into the economy, the tax base, technology are promising fields for jobs.
RODNEY V. OATHOUT, PE, CEM, LEED AP,
Principal, Regional Engineering Leader, and a host of social programs. Online educators are reworking
DLR Group, Overland Park, Kan.
Colleges and universities—along the way they offer education, mak-
FREDDY PADILLA, PE, ATD,
Principal/Senior Electrical Engineer, Page, Austin, Texas with K-12 schools—follow the birth- ing it easy to learn from anywhere at
SYED PEERAN, PE, PhD, rate in the United States closely, as any time. CFEEdu.cfemedia.com, for
Senior Engineer, CDM Smith Inc., Boston
GREGORY QUINN, PE, NCEES, LEED AP,
it helps them plan for facility expan- instance, offers courses in varying
Principal, Health Care Market Leader, sion or student needs. Public schools’ lengths to help engineers better under-
Affiliated Engineers Inc., Madison, Wis.
BRIAN A. RENER, PE, LEED AP,
capital funding frequently is pushed stand a particular technical topic.
Associate, SmithGroupJJR, Chicago by government bonds or other public Schools as we know them will not
SUNONDO ROY, PE, LEED AP BD+C,
Vice President, CCJM Engineers Ltd., Chicago
funding factors. Illinois, for example, disappear anytime soon. They may,
RANDY SCHRECENGOST, PE, CEM, has operated without a state budget however, shift to stay in touch with
Austin Operations Group Manager and
Senior Mechanical Engineer,
for nearly 2 years; this has hurt public students’ needs.
Stanley Consultants, Austin, Texas
RICHARD VEDVIK, PE,
Senior Electrical Engineer and Acoustics Engineer,
IMEG Corp., Rock Island, Ill.
MIKE WALTERS, PE, LEED AP,
Campus Energy Market Leader, MEP Associates, Verona, Wis.
JOHN YOON, PE, LEED AP ID+C,
Lead Electrical Engineer, McGuire Engineers Inc., Chicago www.csemag.com Consulting-Specifying Engineer • JUNE 2017 5
MACH-ProView ™
LCD
NOW with TRENDview

TRENDview

SPACEview

Reliable Controls unveils the new MACH-ProView™ LCD with LISTview


TRENDview. This freely programmable, combination BACnet® Building
Controller (B-BC) and BACnet Operator Display (B-OD) resides on
Ethernet, Power over Ethernet, Wi-Fi or EIA-485 networks. Backed
by an industry-recognized 5 year warranty and a nation-wide network
of certified Authorized Dealers, the new MACH-ProView will
empower you to stay in touch with your building's performance.
STATview
input #5 at www.csemag.com/information

www.reliablecontrols.com/MPV
Addressable lighting
systems
Not affected Very affected

18% 18%

30% 34%
research
2016 ELECTRICAL AND POWER STUDY
Somewhat
ff d
affected
Moderately
ff d
affected Electrical, power systems in data centers

T
he Consulting-Specifying Engi- 3. Specifications: Engineers are
Figure 1: Within the past 12 to 18
neer 2016 Electrical and Power most frequently issuing performance
months, more than half of engineers
Study indicated that 41% of electrical or power system specifica-
have been affected by the increased
engineers specify, design, or make tions (75%) for data center projects,
popularity of addressable lighting
product selections for data centers— closely followed by prescriptive spec-
systems among their clients. Source:
and seven in 10 of these engineers are ifications (71%).
Consulting-Specifying Engineer
responsible for researching and eval- 4. Challenges: When working on
2017 Lighting and Lighting Controls
uating the options for these projects. electrical or power systems for data
Study
Below are five electrical and power centers, engineers are having the
system findings as they relate to data most difficulty with insufficient bud-
center projects: gets for high-quality designs (80%)
62% of mechanical engineers
recommend the brand of HVAC
1. Revenue: The average firm
earns $3 million annually from elec-
and meeting a client’s expected deliv-
ery date (67%).
trical or power systems specified into 5. Comparing systems: Overall
systems, equipment, and controls
new and existing data centers, with quality is highly important when
being used in a project. Source:
33% bringing in more than $5 mil- selecting an electrical or power sys-
Consulting-Specifying Engineer 2015
lion each year from these projects. tem for a data center; engineers also
HVAC and Building Automation Sys-
2. Systems specified: The top five are looking for superior service sup-
tems Study
electrical or power systems or equip- port, a reputable manufacturer, and
ment being specified into data cen- energy-efficient capabilities for these
ters are circuit breakers, fuses, etc. systems.
50% of fire protection engi-
neers expect to specify or select
(83%); transfer switches, etc. (79%);
emergency and standby power (79%);
View more information at
www.csemag.com/2016ElectricalPower.
emergency communication or mass transformers (79%); and electrical Amanda Pelliccione is the research
notification systems within the next distribution (77%). director at CFE Media.
12 months. Source: Consulting-
Specifying Engineer 2016 Fire and
Most critical challenges in electrical,
Life Safety Study
power system design for data centers

26%
$2.9 million:
Budget, cost

Lack of skilled workforce 18%


Average total annual dollar amount
of electrical or power systems New technologies 17%
specified for new and existing build-
ings. Source: Consulting-Specifying Energy efficiency 14%
Engineer 2016 Electrical and Power
Study Codes and standards 9%

Other 16%
More research
Consulting-Specifying Engineer cov- Figure 2: The lack of a skilled workforce leaves 18% of engineers concerned about electrical
ers several research topics each year. or power systems designed for future data center projects. Source: Consulting-Specifying
All reports are available at Engineer
www.csemag.com/research.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 7


Model RVE Model RV

optimized outdoor air


Gain more control over energy costs.
Greenheck’s packaged rooftop outdoor air units deliver heated,
MODEL RV/RVE cooled and dehumidified supply air with optimal energy efficiency.
FEATURES Featuring double-wall construction, 2-inch polyurethane foam
• Capacities to 13,500 cfm (R13 insulation value), direct drive airfoil plenum fans and factory-
• Up to 45 tons of cooling mounted VFDs, Models RV and RVE (with energy recovery) are
• Up to 800 mbh heating
• Preprogrammed ideal for buildings where energy savings are critical. User-friendly
controls for DOAS preprogrammed controls also ensure energy efficiency and
and VAV applications significantly reduce start-up time. All units are factory-tested, and
BENEFITS include low sound condenser fans that reduce sound up to 8dB.
• Superior energy Several other energy-saving options are available including
efficiency our new high turndown furnaces that provide up to
• Quiet operation
16:1 seamless turndown for more precise PREPRO
GRAM
• Preconditions up to FOR EA MED
100% outdoor air with temperature control. A 5,000 hour-rated START-U
SY
P!
energy recovery coating can be applied to resist corrosion
APPLICATIONS in salt spray or other severe environments.
• Schools
• Offices
• Condos Learn more at greenheck.com/4rv
• Hotels
• Government buildings Fans | Energy Recovery | Packaged Ventilation | Make-up Air
Kitchen Ventilation | Lab Exhaust | Dampers | Louvers | Coils
© 2017 Greenheck

715.359.6171
greenheck.com

input #6 at www.csemag.com/information
Career Smart
DAVID KURTEN PE,
HDR Architecture Inc., Princeton, N.J.

Mentoring creates a
competitive advantage
Developing and maintaining a mentoring program within an
organization can help grow the bottom line.

T
he higher education system in the  Friend—provides social and bureau- A successful mentoring program also
U.S. is only producing a small frac- cratic context relies on young professionals, them-
tion of the graduates needed to fill  Intellectual guide—provides selves. The firm should seek entry-level
entry-level positions in the architectural constructive feedback in a peer candidates with a healthy thirst for
engineering industry, and that number relationship. knowledge and the industry and a clear
continues to decline. In 2015, only 717 understanding of the benefits that men-
students graduated from 23 architectural Each type of mentor plays an impor- tors provide. They need to be proactive
engineering programs accredited by the tant role in the development of young and have a desire to seek out wisdom
Accreditation Board for Engineering and professionals, and each will foster a dif- and expertise from their mentors. They
Technology Inc., down from a recent high ferent mentoring relationship. A firm also have a responsibility to pay it for-
of 921 graduates in 2012. The numbers needs to evaluate the types of mentors ward to the next generation, which will
suggest that the architectural engineering available within the organization and help ensure the long-term success of a
industry will continue to seek more entry- select the most appropriate for a given mentoring program.
level talent through engineering pro- young professional. In some cases, the Mentoring can benefit every aspect
grams that are not tailored to this specific young professional may select the indi- of an organization. Young professionals
industry. The result is an industry that is vidual through natural interaction with learn skill sets, get more visibility, feel
becoming more self-taught every year. departmental staff. In that case, the valued, and typically have higher earn-
Selecting the right mentors within an firm may need to augment a mentoring ings potential. Mentors have a higher
organization is critical. Simply possess- relationship with another individual in degree of job satisfaction, an increase
ing the technical knowledge of a specific a different category. Providing a second in generational awareness in the work-
discipline doesn’t always guarantee effec- mentor gives the young professional place, and renewed enthusiasm—and
tive mentoring. Successful mentors need well-balanced exposure. they may even relearn skills that have
to have a propensity for teaching and Companies need to encourage mentor- atrophied.
engaging young staff. They also need to be ing by ideally embedding professional The need to mentor young profes-
disciplined in their approach and willing development in the cultural fabric of the sionals in the industry is becoming
to facilitate the progression of young pro- organization. They should provide guid- more urgent. Those firms that embrace
fessionals through their firm. ance and direction to ensure consistency mentoring holistically and create a sym-
Typically, mentors fall within four in the outcomes as well as a degree of biotic relationship between their prac-
broad categories: flexibility that accommodates a variety of tice, mentors, and young professionals
personalities and department structures. will create a distinct competitive advan-
 Career guide—counsels, promotes, The firm also needs to adopt a long-term tage in the marketplace.
and helps with long-term career perspective about professional develop-
development ment, recognizing that the return on the David Kurten is the vice president and
 Information source—serves as a investment of time and resources will not director of engineering for HDR Archi-
technical resource be visible in the bottom line for years. tecture Inc.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 9


MEP Roundtable
Dave Clute, NREL Energy
Executive, BOMI-HP

High expectations
VP, Intelligent Building Group
Operation Director
Environmental Systems
Design

for high-performance
Chicago

buildings
Paul Erickson, High-performance buildings are intricate, complex projects that
LEED AP BD+C
Building Performance Practice require attention—qualified, expert consulting-specifying engineers
Leader
Affiliated Engineers apply their knowledge on such projects.
Madison, Wis.

CSE: What’s the No. 1 trend you see for smarter building systems or the interaction
today in the design of high-performance of the people that work in the building, there
buildings? is an expectation that the new technologies for
sharing data will be supported.
Dave Clute: The No. 1 trend we see in our A. Brian Lomel: I’m seeing wellness and
Richard Holzer, current projects is clients’ desire to deliver indoor air quality for enhanced productivity
EE, LEED AP economic, environmental, and experiential and better work environments as well as attrac-
Principal Engineer
outcomes that allow them to create a com- tion and retention of employees/occupants.
Southland Engineering
Portland, Ore. petitive advantage for their core businesses.
Economic performance to satisfy long-term CSE: What other trends should engi-
cost benefits is paramount. Environmental neers be on the lookout regarding such
performance and energy efficiency is a given. projects in the near future (1 to 3 years)?
Workspaces that provide a compelling experi-
ence to work, live, and play is also high on the Erickson: Considering the energy/water
list of desirable attributes. nexus in buildings and on campuses, respond-
Paul Erickson: Energy modeling seems to ing with holistic design solutions is a growing
Tim Kuhlman, be the most widespread trend that I am see- trend. More attention is being given to occu-
PE, RCDD, CDT ing in high-performance building projects. At pant experience, whether via rating systems
Associate Principal
the rate energy codes and standards are ramp- like Living Building Challenge and WELL or
TEECOM
Portland, Ore. ing up, prescriptive compliance is becoming via individual controllability tools like Comfy.
more challenging. This coupled with energy- Other trends we see are a bit more project-
savings targets for many institutions compels type-specific. Geoexchange systems (geother-
the need for using modeling tools to test con- mal to many) have found great success in the
cepts, shape design solutions, and evaluate the K-12 market and are increasingly part of the
overall project performance. puzzle for high-performance higher education
Richard Holzer: I’m seeing a shift in empha- and corporate buildings and campus planning.
sis from energy conservation to occupant With the confirmation of successful first appli-
A. Brian Lomel, PE, LEED health and wellness. Interestingly, the num- cations like Cone Health’s, active chilled beams
AP BD+C, CxA, WELL AP ber of projects seeking LEED certification is are the major trend in health care right now.
Director trending down. With updates a few years ago to ASHRAE Stan-
TLC Engineering for Archi-
tecture Tim Kuhlman: I see a trend to make build- dard 170: Ventilation of Health Care Facilities
Orlando, Fla. ings more “technology-ready.” Whether it is that opened up the opportunity to use chilled

10 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Figure 1: Opened in October
2016, Zurich’s North America
headquarters in Schaumburg,
Ill., is a 783,000-sq-ft, LEED
Platinum complex. Features
include horizontal sunshades
covering the exterior and floor-
to-ceiling glass offering exten-
sive natural light. Courtesy:
Environmental Systems Design

beams for reducing air-change require- smartphones. Communication, collab- the HVAC industry. Norm Asbjornson,
ments, we are consistently seeing our oration, coordination, and innovation founder of AAON, made a significant
projects apply this solution for the same is how people want to work; anywhere donation to fund a new engineering
cost—or less—as traditional variable air and anytime. building on campus (Norm Asbjornson
volume (VAV) while gaining significant Hall) charged with embracing high-per-
energy savings as well. CSE: Please describe a recent formance design, even reaching toward
Kuhlman: Engineers should start get- high-performance building project net zero energy, to create a dynamic and
ting used to working with virtual reality you’ve worked on—share details interactive learning environment. AEI
(VR). I expect this to appear on two dif- about the project including location, and ZGF Architects partnered with Asso-
ferent fronts. The first is in how we design systems engineered, team involved, ciated Construction Engineering and
systems. VR will be able to help engi- etc. A&E Architects to design this leading-
neers to virtually interact with a system edge facility. Starting with early planning
to determine issues with access, mainte- Clute: The Zurich North America and study, we determined an energy-use
nance, and construction. The second is Headquarters project located in Scha- intensity (EUI) target that could be sup-
in the design of VR interaction rooms. umburg, Ill., was recently completed and ported by PV on the site, which included
These rooms can be thought of as very opened in October 2016. Certified as a new parking garage that is a part of the
high-end AV rooms where a client can LEED Platinum, the 783,800-sq-ft com- project. In conjunction with a vision held
project a virtual space to evaluate prod- plex reinforces Zurich’s commitment to by the assistant director of facilities ser-
ucts and have interactive training with environmental stewardship. A network of vices to interconnect multiple buildings
equipment and demonstrations. horizontal sunshades clad the perimeter on this south part of campus, we explored
Holzer: There is a greater focus on of the complex, with the sunshades vary- and implemented a geoexchange system
water conservation and reuse, particularly ing in depth depending on orientation, design. Using a mix of an AAON air han-
in the Western United States. while floor-to-ceiling glass offers exten- dling unit and local conditioning equip-
Lomel: Net zero water and energy, sive natural light for the shallow office ment that can be selected with geoex-
microgrids, and emphasis on resiliency plates. A soaring 3-story double wall faces change heat pump options, we were able
are some other trends. south toward the multilevel plazas, show- to provide a low-energy concept that can
Clute: The ability to offer the end casing an architecture that responds to the move heating and cooling energy between
users, tenants, visitors, and operators of changing Chicago climate. The building the spaces in the building, the building
a building a mobile, digital experience was designed by Goettsch Partners for the and the geofield, or even the building
is becoming increasingly more impor- base building and Cannon Design for the and the other nearby campus build-
tant. Millennials and next-generation interiors; Clayco Construction was the ings. To help meet the heavily domi-
employees want to be able to access a design-build contractor. nating heating loads, a transpired solar
building using digital credentials and Erickson: Montana State University wall system was employed, harnessing
modify the temperature and light lev- in Bozeman has an engineering student the extremely sunny Bozeman climate.
els of their workspace using handheld alum that’s made a name for himself in These and other systems allowed the

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 11


MEP Roundtable
EUI of the building to be reduced to manufacturing space to work as a high- deliver a project using the IPD method.
a very low number, often referred to tech laboratory. It was an interesting The use of BIM was a guiding principle
as near zero energy or net zero-ready. experience to have the general contractor that allowed the entire team to communi-
Once deployed, the PV and solar hot- and subcontractors involved in the early cate, coordinate, and collaborate to deliv-
water systems should allow for net zero part of the design. It was a new process er a world-class, award-winning result.
operation. and learning experience for the entire Erickson: The award-winning Wis-
Kuhlman: I am currently working team. IPD presents a definite advantage consin Institutes for Discovery building
on cloud-computing data centers for to a building owner. It minimizes changes on the University of Wisconsin campus
a confidential client. The servers are during construction by getting all parties in Madison has been in operation since
connected through a fabric network to agree to a solution early in the design 2011, but the lessons learned relative to
designed for high throughput and high process. I would say the most difficult IPD delivery of a large-scale high-per-
reliability. In addition to the technology issue to overcome was trust amongst the formance facility remain timely. Com-
that is implemented to make the data parties (architects, engineer, contractor, bining the programs of two biomedical
center function, the fabric network also and subcontractors). We all had years of research organizations with aggressive
implements technology to assist the experience in the design-bid-build pro- energy efficiency and flexibility strate-
data center operators to interact with cess, which places the engineer and con- gies in this 300,000-sq-ft building almost
the building systems. tractor in an adversarial role. It takes a lot demanded—and certainly greatly ben-
of trust amongst all parties to make IPD efited from—the collaborative practices
CSE: Have you designed any high- work. Overall, this project was successful characterizing IPD. Correctly identify-
performance building projects using because the owner believed in it and was ing and organizing the distinct represen-
the integrated project delivery (IPD) an active participant to make it work. tatives who will jointly deliver specific
method? Clute: The Zurich North America outcomes is essential to the efficiency of
Headquarters project is an excellent such collaboration.
Kuhlman: I worked on an IPD proj- example of how the owner, architects,
ect a few years ago in Oregon for a con- and contractor teams can work very CSE: What are the challenges
fidential client that was renovating a closely together from the outset to that you face when designing such
facilities that you don’t normally
face for other building projects?

Lomel: Working on high-perfor-


mance buildings is both exciting and
encouraging, as owners of such facilities
tend to be more engaged in the design
process. A challenge is that design team
members seldom have similar levels of
expertise in high-performance design.
Due to the integrated nature of high-
performance design, it’s crucial for the
team to be in sync to deliver a high-
performance building.
Erickson: What we see is that, to
meet the energy- and water-savings
targets set by states or the institutions
themselves, we are introducing technol-
ogies and systems that are new to many
of the operators. We now find ourselves
spending as much or more time on
stakeholder engagement and organiza-
Figure 2: The Center for Translational Research and Education, located in Loyola tional change as we do on the analysis to
University’s Health Sciences Campus in Maywood, Ill., is a $137 million research and identify the design solutions. I find this
education facility accommodating 500 scientists and staff collaborating on various to be an informal requirement, but one
projects geared toward improving human health. Courtesy: Dave Burk Photography that needs to be addressed so that our

12 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


high-performance designs will succeed Institute (CSI) Division 25 – , Integrated Kuhlman: Often, what we call BIM
in the long run under operation. Automation. This is where all the indi- on a project is not what BIM is being
Clute: The complexity of the contrac- vidual building subsystems come together sold as in the market. Every project I
tual relationships required to define, in one place to provide cross-functional have worked on for the past several
design, and deliver a high-performance coordination and system integration. years has had a BIM execution plan to
building requires a more sophisticated Kuhlman: The assumptions on how we communicate between the owner, archi-
understanding of the details involved would approach lighting systems, access tect, engineer, and contractor on how
across the entire lifecycle of the project. control, and network distribution are dif- to develop and organize the building
The roles and responsibilities of each ferent now then what they were 10 years CAD model. Most of this relates to the
party need to be clearly communicat- ago. For example, it is now possible to do level of detail that will be represented
ed and understood at all levels of the a complete lighting system with LED- in the 3-D CAD building model. What
owner, architect, and contractor entities based lights using Class 2 power-limited BIM is still lacking is the rich amount
delivering the project. cabling. For some LED lighting systems, of detailed information of each compo-
Kuhlman: High-performance build- this is the same type of cabling used for nent in the model. The issue has to do
ings tend to have more utilities and data networks. I see a similar trend for with the size of the model for a large,
require a higher level of integration security systems and control systems that high-performance building that has a
between the systems. For example, in are moving toward Ethernet networks and lot of building elements. During the
a large data center, the fabric network POE (power over Ethernet) devices. All of design and construction process where
consists of multiple networks connect- this adds up to placing more of a burden the model is being constantly manipu-
ed in parallel that require each to have on the telecom-network infrastructure lated, very large BIM models can be
separate cable routes to reduce the risk in a building. This implies larger telecom detrimental to CAD production. Add-
of network failure. This results in need- rooms that need more power, cooling, ing in all the rich equipment data can
ing to do more space coordination. In and cabling than what they required in explode the size of the model so that it
a high-performance building for manu- the past. becomes too big to work with. Often,
facturing facilities, control systems are Erickson: The building envelope and each engineering discipline works on
more sophisticated to provide the cor- floor-to-floor height often drive many their own model and then connects
rect environment control for the manu- of our design solutions when retrofitting with the others on the team to coordi-
facturing area. high-performance buildings. The two nate the design. If the models are too
can directly relate. As we move toward big to work with, it can negatively affect
CSE: What are some unique ele- hydronic, decoupled cooling strategies the design coordination.
ments/considerations to designing/ (i.e., chilled beams, chilled sails, radiant Clute: The Zurich North America
retrofitting high-performance build- cooling panels, etc.), cooling capacity for Headquarters project is also an exam-
ings? each varies, to the extent that an envelope ple of where BIM was used to design,
with poor solar-load control will reduce build, and deliver a high-performance
Holzer: With the increasing interest in the system types that can be used or even building. BIM was used from the
low-energy, zero net energy buildings, preclude their use. High infiltration rates beginning of the project in the early
there is increasing need to drive down can also limit or preclude use of these design stages to visualize the project,
electrical consumption from equipment cooling systems, as moisture levels in the and Clayco delivered a completed BIM
and appliances, which requires a change space can get too high and lead to con- model to the Zurich Corporate Real
to occupant expectations and behaviors. densation issues. Considering an enve- Estate and Facilities Management team
The change in expectations revolves lope retrofit that addresses one or both in upon completion for ongoing opera-
around interior temperature/occupant addition to improving overall insulation tions and maintenance functions.
comfort. Behavioral change is necessary value is highly recommended.
to alter how and when occupants use and CSE: What are the most chal-
turn off equipment and appliances. CSE: Is your team using BIM in lenging codes and standards for
Lomel: Glazing (orientation, amount, conjunction with the architects, such structures? What makes them
quality), the early energy model, ventila- trades, and owners to design a high- so challenging?
tion, lighting, and how they all interact. performance building? Describe
Clute: Perhaps the most important ele- an instance in which you’ve turned Lomel: The Living Building Chal-
ment to consider throughout the design over the BIM model to the owner for lenge (LBC) provides considerable chal-
and construction process is the impor- long-term operations and mainte- lenges in reducing water and energy,
tance of the Construction Specifications nance. while also focusing on the materials

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 13


MEP Roundtable
used in construction. Everything is an imperative; there
are no options, so an owner has to be ‘all in’ in order to
achieve full LBC certification.
Kuhlman: Every engineer designing a telecommunica-
tions data or phone network for a building needs to know
NFPA 70: National Electrical Code (NEC) or the version
of the electrical code adopted for their state. Power-limited
systems and nonpowered systems (fiber optics) are still
HPS Titan®
regulated by the NEC. For telecommunications and net-
HPS FortressTM
work cabling, look toward the Telecommunications Industry
Encapsulated Transformers for Harsh Association (TIA) suite of standards for commercial build-
Environments & Commercial Applications ings, such as ANSI/TIA/EIA-568: Commercial Building
Telecommunications Cabling Standards, ANSI/TIA 569:
HPS offers a complete line of encapsulated transformers for both Telecommunications Pathways and Spaces, ANSI/TIA-606:
harsh environments and commercial applications. The core and
coil is encapsulated which seals out environmental elements and Administration Standard for Telecommunications Infra-
allows operation in harsh and hazardous locations. structure, and ANSI/TIA-607: Generic Telecommunications
Bonding and Grounding (Earthing) for Customer Premises.
HPS Titan® - UL Listed for Class 1, Div. 2, Groups A, B, C, D
Hazardous locations, ABS Approval Manufacturers of network components and cabling-related
HPS FortressTM - Economical solution for commercial applications products design with these standards in mind to make sure
the network equipment works with the cabling equipment.
Therefore, the engineer needs to design to these standards
power to perform for the network building equipment.
Holzer: I find that the energy-performance goals of vari-
input #7 at www.csemag.com/information ous institutions can be very difficult to attain. For example,
the University of California requires new buildings to exceed
the state energy code—Title 24—by at least 20%. This is
extraordinarily challenging because Title 24 is becoming
increasingly stringent with each revision cycle, and compli-
ance is challenging even without the additional requirement
of beating it by a 20% margin.

CSE: What are some solutions/best practices to


ensure that the high-performance building will meet
or exceed codes and standards?

Clute: We believe the “Three E’s”—education, exposure,


and experience—are the best ways to help our staff, indus-
try colleagues, and clients understand the importance of
implementing business processes required to meet or exceed
CBEX Elite Boilers at Stanford University
codes and standards. We also have developed a comprehen-
sive business-process framework for intelligent buildings
LOCAL COLLEGES TO LARGE UNIVERSITIES across the lifecycle of the built environment. This process
COUNT ON CLEAVER-BROOKS BOILERS. framework provides a comprehensive set of core competen-
cies at Level 0, process categories at Level 1, and detailed
SEE HOW WE CAN INCREASE ENERGY business processes at Level 2 through 5 that help us navi-
EFFICIENCY AND LOWER EMISSIONS gate and comply with the vast range of codes and standards
ON YOUR CAMPUS. required.
Kuhlman: In the example of a high-performance data cen-
Visit cleaverbrooks.com/colleges to learn how Cleaver-Brooks is engineering inventive
solutions and driving down costs at colleges and universities across the country. ter, a client wants one design that they can implement all
around the world. Working across the U.S. is easy. A piece
of equipment I select with a UL listing can be installed in
©2017 Cleaver-Brooks, Inc. Visit cleaverbrooks.com/findarep or call (888) 570-1721
every state. Taking the same piece of equipment into Europe

input #8 at www.csemag.com/information 14 Consulting-Specifying Engineer • JUNE 2017


Complete system.
Complete protection.
Complete confidence.

Explosion-proof, hazardous location solutions and systems


from T&B and ABB.
With T&B EX™ enclosure solutions, Thomas & Betts now carries a full
line of explosion-proof enclosures for use in hazardous and adverse
environments. T&B EX™ hazardous location enclosures can be customized
with ABB innovative industrial controls and circuit protective devices to
meet your facility’s most demanding needs.
T&B EX™ enclosure solution systems include:
• Cast aluminum and stainless • Disconnect switches
steel enclosures • Control stations, pilot devices,
• Combination motor starters and accessories
• Magnetic motor starters • Panelboards
• Manual motor starters • Instrument housings
• Circuit breakers • Junction boxes

For more information about this newly expanded product line, visit
www.TNB.com/TBEXHazardous or contact your authorized distributor
or T&B/ABB representative.

tnb.com

© 2017 Thomas & Betts Corporation. All rights reserved.

input #9 at www.csemag.com/information
MEP Roundtable
THE NEW STANDARD FOR
CRITICAL ENVIRONMENTS.
can be a problem because they don’t recognize a UL list-
ing. Instead, I may be looking for the same product that
has a CE mark. Our clients want to move globally, but each
country is sovereign and has its own codes and standards.
Networking equipment is probably the most uniform from
country to country. All Ethernet ports look the same. The
same cannot be said for power outlets. Yet, even in building
networking components where there is such a high level of
Introducing the new Ruskin® critical uniformity, the building codes and listing requirements for
environment damper series: the model CD50CE
these products can be different in each country.
damper and thermally efficient model TED50CE
damper. Designed and manufactured to Holzer: Full integration of architectural, mechanical,
withstand the elements of coastal and corrosive plumbing, structural, and electrical design to achieve the
applications, these models combine the strength project performance goals is absolutely essential. Looking
of stainless steel and the protection of anodized for synergistic opportunities is critical—things like using a
aluminum to deliver lasting performance in
concrete structural system to increase the thermal capaci-
severe environments.
tance of the building, building-integrated photovoltaic sys-
For more information visit ruskin.com tems, and using solar panels as sun-shading devices.

CSE: How are codes, standards, or guidelines for


energy efficiency impacting the design of such build-
ings?

input #10 at www.csemag.com/information Holzer: Codes restrict the amount of vision glazing,
design of wall/roof/floor assemblies, and rooftop space
allocations set aside for solar panels.
29CSEAd-A19a.indd 1 5/31/17 3:09 PM Clute: New codes, standards, and guidelines for energy
efficiency are making it easier for us to justify and build
compelling business cases for the design of high-perfor-
mance buildings. When the need to achieve higher levels
of performance are required by law, it makes the need to
comply much easier than if the choice was optional.
Lomel: The changes between the 2004 and 2007 editions
of ASHRAE 90.1 and between the 2006 and 2009 editions of
the International Energy Conservation Code (IECC), and
then the changes from ASHRAE 90.1-2010 and IECC 2012
to the latest editions, brought about a generation of chang-
es, bringing new requirements for air barriers, building-
pressurization testing, plug-load controls, commissioning,
decreased window-to-wall ratio, and more. It’s all catching
designers unaware and reinforces the need for educating
both design teams and owners to better understand the
code requirements and associated costs. The prescriptive
path for compliance has gotten so onerous and difficult
• ISO-9001 Certified • Available Certified IBC Seismic Compliance to adhere to that most of our projects are following the
• 70,000 ft2 of manufacturing space • Professional sales and engineering staff performance path.
• Strategically located for domestic and • High performance, maintenance free
worldwide markets materials
Read more at
• Over 65 years of experience • Unparalleled customer service www.csemag.com about:
• Turn-key systems available • Expertise in code compliance, extreme n Automation and controls
sound attenuation and challenging n Electrical/lighting/power
applications n Fire/life safety
n HVAC
n Sustainable buildings/energy efficiency.
Like Us
800.231.2258
BALTIMORE, MD WWW.PRITCHARDBROWN.COM

input #11 at www.csemag.com/information 16 Consulting-Specifying Engineer • JUNE 2017


is building a higher standard
for energy efficiency
From hospitals and data centers to offices and apartments, Danfoss is helping to
develop energy-efficient cities — one building at a time. Providing the industry’s
broadest portfolio, Danfoss’ component innovations improve system efficiency,
reliability and performance, and enable chiller manufacturers to reduce total cost of
ownership and energy consumption for more efficiently cooled buildings. And with
unparalleled air-conditioning systems expertise, Danfoss comfortably helps you
exceed the most rigorous efficiency standards.

Discover how we’re Engineering Tomorrow at chillers.danfoss.com


input #12 at www.csemag.com/information

Up to

70%
of chiller
components to help
meet regulations
Benchmark
has gone Platinum.

Introducing AERCO’s most advanced boiler –


the Benchmark® Platinum. We’ve raised our gold
standard to an even higher level with a powerful
bundle that optimizes your system for maximum
efficiencies. You‘ll see exactly how your system
is working, know when you need to perform
maintenance and rejoice in how much you’re saving.

The Benchmark® Platinum. Performance that’s


©2017 AERCO

music to your ears.


input #13 at www.csemag.com/information
800.526.0288 | aerco.com
Codes & Standards

How NFPA 99-2015 changes


affect mechanical design
NFPA 99-2015 has a few changes that mechanical engineers
should pay close attention to.
BY MIKE ZORICH, PE, LEED AP; IMEG Corp., Rock Island, Ill.

N
FPA 99: Health Care Facilities Code and Vacuum Systems; Chapter 7: Information
applies to all health care facilities other Technology and Communications Systems; and Learning
than home care. The code is intended for Chapter 9: HVAC. Chapter 8: Plumbing, which objectives
professionals involved in the design, construc- was added in the 2012 edition of NFPA 99 with  Identify major changes to
tion, maintenance, and inspection of health care the intent that it be used to support the local the 2015 edition of NFPA 99:
facilities in addition to the design, manufacture, plumbing codes for health care facilities, has not Health Care Facilities Code
and testing of appliances and equipment used in been modified in the 2015 edition. that impact mechanical
designers.
patient-care rooms of the health care facilities.
 Learn to build upon the
NFPA 99-2015 continues to build upon the Chapter 5: Gas and vacuum systems
risk-based approach of NFPA
risk-based categories established in the 2012 edi- As in the 2012 edition, NFPA 99-2015 divides 99 when designing hospitals
tion. As many health care designers are aware, Chapter 5 into three sections corresponding to and health care facilities.
the 2012 edition of NFPA 99 experienced a Category 1, Category 2, and Category 3 systems.
major overhaul. The intent of the upgrade was Category 1 systems are the most critical and
to elevate NFPA 99-2012 from a standard to a are required to be available continuously for
code, allowing it to be incorporated into a local patient life support, even during the loss of nor-
jurisdiction’s code by itself instead of being ref- mal power sources or failure of other hospital
erenced from NFPA 101: Life Safety Code. systems. It is important to note that Chapter 5
The 2012 edition eliminated all previous occu- does not include a Category 4 system (no impact
pancy-based chapters and replaced them with on patients) because a failure of a gas and vac-
Chapter 4: Fundamentals, which established risk uum system would have at least some impact
categories 1 through 4. The change meant NFPA on the patient. The minimum risk level for a
99 would no longer be applied based upon the gas and vacuum system, therefore, is Category
name of an occupied space, but rather applied 3 (failure may cause discomfort).
based upon a risk category. Unchanged in the NFPA 99-2015 adds new criteria in Chapter 5
2015 edition, the risk category is determined to help define a Category 1, Category 2, and Cat-
by the impact of system failure on patients and egory 3 piped gas and vacuum system. The intent
caregivers within a facility space. The higher the of the change is to ensure that when a facility
risk to occupants in the event of system loss, the is performing a risk assessment as defined in
stricter the requirements to ensure the system Chapter 4, the risk assessment is not being used
is not lost. to lower the level of safety. For example, prior to
While the overall structure and majority of the 2015 edition, it may have been possible for a
the content remain the same between the 2012 facility performing a risk assessment to define a
and 2015 NFPA 99 editions, slight modifica- medical-gas system as Category 2 even though
tions have been made throughout the code in deep sedation was administered to the patient.
the latest version. The changes in the 2015 edi- Because of the changes to the 2015 code, this
tion that are of most importance to a health care situation would now be required to be classified
mechanical designer appear in Chapter 5: Gas as Category 1.
www.csemag.com Consulting-Specifying Engineer • JUNE 2017 19
Codes & Standards
of the emergency in Chapter 7, which was added in the
oxygen-supply con- 2012 edition and is divided into three
nection referenced risk categories.
in Section 5.1.3.5.15. The change alters restrictions for the
This section remains routing of utilities through a Category 1
unchanged from the telecom entrance facility (EF) and tech-
2012 edition. nology equipment room (TER). The 2015
edition eliminates the 2012 requirement
Figure 1: Section 5.1.3.5.7, Auxiliary Source Connec- that underground utilities, such as elec-
tion, states that all medical-gas source systems be pro-
trical, water, gas, and sewer, could not
vided with an auxiliary source connection point of the
be located below a Category 1 EF. As in
2012, however, Sections 7.3.1.2.1.4 and
same size as the main line, located on the patient side
7.3.1.2.2.4 of the 2015 edition continue
of the source valve. The section further stipulates that
to stipulate that mechanical equipment of
the connection consists of a tee and a normally closed
any kind that does not directly serve the
secured valve. All graphics courtesy: IMEG Corp.
TER or EF shall not be installed in, pass
The added language through, or enter the space. (This type
in Chapter 5 of the 2015 edition is to Section 5.1.9.2.3, Master Medical of restriction is similar to those found in
be used in addition to the risk-category Gas Alarm, was revised to differentiate the international codes for nonessential
definitions in Chapter 4 when conduct- between the wired and wireless com- utilities routed within egress stairwells or
ing the risk assessment of a facility’s gas munication between the two mandatory elevator machine rooms.)
and vacuum systems. master alarm panels and the initiating Chapter 7 also maintains the require-
Other updates in Chapter 5 affect stor- device. Under either wired or wireless ment that an EF or TER must have
age temperatures, auxiliary-source con- communication, the intent of the code a positive pressure differential with
nections, master medical-gas alarms, and remains unchanged: that should one of respect to surrounding areas. Under the
instrument air. the mandatory master alarm panels fail, “environmental requirements” in Sec-
For all three categories of medical-gas its failure does not disable any signal on tion 7.3.1.2.1.8, a designer must provide
systems under section 5.1.3.2.12, the the other mandatory master alarm panel. a means for maintaining a positive air
2015 code changed the maximum storage NFPA 99-2015 also has added a dedi- pressure relationship for the technology
temperature of gas cylinders from 130° cated section for instrument air under space. Attention must be paid to ensure
to 125°F to match the Compressed Gas Section 5.1.13, Category Support Gases. this pressure relationship is maintained
Association recommendations. Under This section was added to avoid the confu- when dedicated terminal heat-transfer
section 5.1.3.2.13, the 2015 edition also sion between nitrogen, which is a medical units are provided (see Figure 2).
has modified the minimum storage tem- gas, and instrument air, which is a support
perature for nitrous oxide and carbon gas. Instrument air is not mandated to be Chapter 9: HVAC
dioxide cylinders from -20° to 20°F. provided, but when it is provided, it shall Unlike chapters 5 and 7, the HVAC
Section 5.1.3.5.7, Auxiliary Source comply with the requirements of NFPA 99. section does not define systems based
Connection, was added in the 2015 edi- Furthermore, when support equip- upon a risk category. The section requires
tion for medical-gas systems. The section ment, such as operating room booms each facility to perform a risk assessment
states, “All source systems shall be pro- or control panels, require gas to oper- to assign a risk category in accordance
vided with an auxiliary source connec- ate, a facility has the option of providing with Sections 4.1 and 4.2. Similar to the
tion point of the same size as the main either instrument air or nitrogen. How- 2012 edition, NFPA 99-2015 is written
line, which shall be located immediately ever, because it is uncommon and usu- with the intent that the risk category
on the patient side of the source valve.” ally unnecessary for a facility to use both assigned to each HVAC system serving
The section further stipulates that the an instrument air system and a nitrogen a space is independent of the risk cat-
connection shall consist of a tee and system, NFPA 99 recommends a decision egory applied to other systems serving
a normally closed secured valve (see be made to use the one system that best the same space.
Figure 1). The intent of this addition meets the facility’s needs. For example, a central sterile supply
is to provide a facility with a simpler located at a health care facility in Dal-
and safer means to change out service Chapter 7: Information technology las may assign a risk category of 3 to the
equipment. It is important to note that and communications systems heating system serving the department,
this additional source requirement does NFPA 99-2015 introduces one change but assign a risk category of 2 to the cool-
not modify or remove the requirements of importance to mechanical designers ing system. Assigning Category 3 to the

20 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


heating system may be justified because, noted in Chapter 4, Section 4.2. The sec- that removes the requirement for smoke
while the failure of the heating system tion does not specify the type of assess- purge for HVAC systems in anesthetizing
may cause discomfort for the staff, its ment the facility should conduct, but locations.
failure is unlikely to cause injury. Assign- only states the assessment be a defined Prior to the 2012 edition, NFPA 99
ing Category 2 for the cooling system procedure that is documented. required that anesthetizing locations be
also would be reasonable because, should A major change in Section 9.3.1.3 of served by an HVAC system capable of
it fail, the inability to control humidity the 2015 edition is very clear language removing smoke from the room without
within the department may result in the
failure of sterile products, which could
cause minor injury to patients.
Chapter 5 points out that the facility
has the responsibility for developing the
risk assessment for its HVAC system.
This allows flexibility in assigning risk to
mechanical systems based on their spe-
cific equipment and their associated risk.
The code’s intent is to not burden facili-
ties with mandates on redundancy or
major equipment upgrades. The process
and the documentation for the HVAC
system must be done by the facility as

Figure 2: Chapter 7 of NFPA 99-2015


maintains the requirement that an
entrance facility or technology equip-
ment room must have a positive pres-
sure differential with respect to sur-
rounding areas. Attention must be paid
to ensure this pressure relationship is
maintained when a dedicated terminal
heat-transfer unit (at right) is provided.

JUNE 2017 21 input #14 at www.csemag.com/information


Codes & Standards
recirculating it through the system or return- While the 2012 edition of NFPA 99 states that all HVAC systems serving the
ing it to the room it serves. This requirement removed the requirement for smoke purge emergency power system room shall be
added extra cost and complexity as designers in anesthetizing locations, its deletion led compliant to NFPA 110.
specified smoke purge on any air-handling to confusion in the industry as designers The 2015 edition of NFPA 99 did not
system that served anesthetizing locations, debated whether the removal was intention- experience major structural or content
such as an operating room or catheteriza- al. The 2015 edition has ended the debate by changes, but has made modifications to
tion lab. The smoke-purge system control clarifying that smoke purge in anesthetizing build upon the risk-based approach estab-
sequence was such that if smoke was detect- locations is no longer required. The require- lished in the 2012 edition. Due to NFPA 99’s
ed within the anesthetizing location, the air- ment for smoke purge in anesthetizing application to a wide range of infrastruc-
handling system would go to 100% outside locations was established years ago when ture, equipment, and design approaches
air, therefore relieving all air to the exterior the use of flammable anesthetics was com- for a health care facility, it is, therefore,
and eliminating any opportunity for the mon in operating rooms and, therefore, the critical for mechanical engineers to review
smoke-filled air to be recirculated through fire hazard was much higher. With today’s the entire 2015 edition to have a complete
the system or returned to the room it serves. usage of nonflammable anesthetics, the understanding of the code’s latest require-
In northern climates, which commonly fire hazard has been reduced, resulting in ments.
experience below-freezing temperatures, the definitive removal of the smoke-purge
additional heating capacity is typically requirement in the 2015 edition. Mike Zorich is a client executive and leads
added to the air-handling system. Should Another change in Chapter 9 is the one of IMEG Corp.’s health care design
the air-handling system experience a consolidation of Section 9.3.9, Emergen- groups. He has served as a project man-
smoke-purge occurrence when outside-air cy Power System Room. The 2012 edition ager and lead mechanical engineer for a
temperatures are below freezing, the addi- included several paragraphs copied from wide variety of health care facilities and is
tional heating capacity is used to ensure NFPA 110: Standard for Emergency and adept at system concept and design for new
the cold air is not distributed through the Standby Power Systems. The 2015 edition greenfield hospitals, renovations, expan-
space and does not cause damage. has removed these paragraphs and simply sions, and infrastructure upgrades.

input #15 at www.csemag.com/information


Data center technology and design
requirements are changing fast. Are you
keeping up? CFE Edu Data Centers courses
have been developed and designed specifically
for engineers working on data center projects.

Led by industry expert Bill Kosik, PE, CEM, LEED AP, the two on-demand online data centers
courses offer instructor-led discussions, videos, and high-quality presentations on an interactive
and intuitive platform. The courses are self-paced, accessible 24/7, and offer one (1) AIA CES
approved learning unit per course.

Check out the new course “Impacts of Climate and Cooling Technology on
Data Center Energy Use,” which covers:
✓ The importance of climate analysis
✓ Key drivers in reviewing different climate types
✓ Cooling system technologies
✓ Determining appropriateness of cooling systems based on climate and data center types
✓ Energy estimating techniques for data centers.

What’s included in all CFE Edu courses:


✓ Exclusive content--not found anywhere else--that includes research and expert knowledge
from instructors working within the industry
✓ Interaction with course authors
✓ Videos, quizzes, and interactive content designed for a proven learning experience with
associated CEU credits
✓ Full access to your course 24/7 with a computer, tablet or smartphone
✓ Course cost is $49.99

Learn more and register at CFEedu.cfemedia.com


* Contact CFE Edu Manager, Emily Guenther, at eguenther@cfemedia.com for more information
or with any questions about CFE Edu.
2017 The finalists are
in... it’s time to
cast your vote!

Who will win gold in 2017?


Consulting-Specifying Engineer’s Product of the Year (POY) contest is the premier award
for new products in the HVAC, fire/life safety, electrical, and plumbing systems engineering
markets. The annual reader-choice program was created to provide Consulting-Specifying
Engineer’s readers with information about the top new product in their fields.

In 2017, companies submitted their new and improved products to be


judged for this distinguished honor.

91 finalists in 16 categories

Product Submission Categories:


✓ Air Movement, Dehumidificationm Humidifcation ✓ Fire, Life Safety, Mass Notification
✓ BAS, Controls, Energy Management ✓ HVAC
✓ Chillers ✓ Lighting & Luminaires
✓ Electrical: Cable, Wire, Components ✓ Lighting Controls
✓ Electrical Distribution ✓ Plumbing & Water Management
✓ Electrical: Fuses, Circuit Breakers, Safety ✓ Pumps, Pump Controls
✓ Emergency, On-Site, Standby Power ✓ Software: Design, Modeling, Analysis
✓ Equipment-Level Sensors & Controls ✓ Test Instruments, Meters, Data Loggers
Only qualified Consulting-Specifying Engineer subscribers are eligible to vote, and only one vote
Voting per qualified subscriber. If more than one ballot per qualified subscriber is submitted, none of
Rules the ballots from that subscriber will be counted. Product finalist manufacturers are not eligible to
vote. Votes received from non-qualified participants will not be counted.

Qualified subscribers, cast your vote now! www.csemag.com/votepoy


Voting for the 2017 Product of the Year will close on June 30, 2017.

The 2017 Product of the Year results will appear in print and online September 2017
Codes & Standards

Applying NFPA 99
to health care facilities
The impact of applying NFPA 99: Health Care Facilities
Code to hospitals and health care facilities varies depending
on the level of care provided.

BY CHRIS MORAN, PE; ERIC ROSENBAUM, PE; and


AJAY PRASAD, PE; JENSEN HUGHES, Baltimore

N
FPA 99: Health Care Facilities Code fire and life safety provisions of the final rule
identifies criteria applicable to health through Form 2786, with K-Tags (deficiency
Learning
care facilities including hospitals and number identifiers) starting with 900 being those
objectives
nursing homes. The impact of applying NFPA applicable to NFPA 99 requirements.  Identify major changes to
99 to health care facilities varies depending on NFPA 99 consists of 15 chapters, from general the 2015 edition of NFPA 99:
the level of care provided. NFPA 99-2015 is the building requirements to criteria that affect the Health Care Facilities Code
that impact fire protection
latest edition, but there are few changes from the various building systems including fire protec- engineers.
2012 edition focused on fire protection other tion systems. CMS does not require compli-
 Determine the impact of
than editorial revisions. NFPA 99-2012 is more ance with chapters 7 (information technology NFPA 99 on hospitals and
widely used due to its adoption by the Centers systems), 8 (plumbing systems), 12 (emergency health care facilities.
for Medicare & Medicaid Services (CMS). Edi- management), and 13 (security management), as  Learn about NFPA 99’s
tions prior to the 2012 edition of NFPA 99 were these chapters were not adopted in the final rule. adoption by the Centers for
limited in their application since they were not CMS has enacted an emergency-preparedness Medicare & Medicaid Services
individually adopted by CMS. However, limited rule (CMS-3178-F) in lieu of adopting Chapter (CMS) and how it affects fire
and life safety requirements.
portions of NFPA 99-1999 were referenced by 12, whereby compliance with the emergency-
applicable CMS criteria. Changes to NFPA 99
from earlier editions to both the 2012 and 2015
editions will be discussed as they apply to fire NFPA 99 has taken on a new level of importance
protection and life safety, with changes specific
in the past year due to the CMS issuance of CMS-
to the 2015 edition identified in each section.
NFPA 99 has taken on a new level of impor- 3277-F, Medicare and Medicaid Programs; Fire Safety
tance in the past year due to the CMS issuance of
CMS-3277-F, Medicare and Medicaid Programs; Requirements for Certain Health Care Facilities.
Fire Safety Requirements for Certain Health Care
Facilities. The rule revised 42 CFR Parts 403, 416, preparedness rule is required by Nov. 16, 2017.
418, 460, 482, 483, and 485, which address pro- Where local jurisdictions do not require compli-
gram requirements for hospitals, long-term care ance with NFPA 99, the excluded chapters noted
facilities, ambulatory surgical centers, and others. provide pertinent information in regards to
The final rule became effective July 5, 2016, with designing and maintaining the building systems
enforcement beginning Nov. 1, 2016. As part of and could be used as a reference.
this rule, CMS adopted the 2012 editions of NFPA
99 and NFPA 101: Life Safety Code along with all The risk assessment in NFPA 99
associated tentative interim amendments (TIAs) One of the changes to NFPA 99-2012 and later
issued prior to April 16, 2014. CMS reviews the editions is the move to a risk-based approach
www.csemag.com Consulting-Specifying Engineer • JUNE 2017 25
Codes & Standards
for determining applicable requirements include cooling systems in the south- identified in Figure 1 is a qualitative
rather than the former prescriptive ern U.S., resident emergency-call sys- approach based on yes or no answers for
approach based on facility type. NFPA 99 tems, heating systems in the northern each building system’s impact. It does not
now requires a risk assessment to deter- U.S., and lighting or potable water in address the probability of failure similarly
mine the applicable risk category for each patient-care areas. Category 2 systems to that used in NFPA 551 nor require in-
building system. The risk category is then are likely to be found in general-care depth knowledge of the systems and pos-
applied to chapters 5 through 11 of NFPA rooms, such as inpatient bedrooms and sible failures. It is important that those
99 as appropriate for the system. The main dialysis rooms. performing the assessment are knowl-
focus is seen in Chapter 5 (gas and vac-  Category 3—Systems in which fail- edgeable in the procedures, equipment,
uum systems) and Chapter 6 (electrical ure is unlikely to cause injury. Failure of and systems being evaluated. Appropriate
systems). Although this requirement has the system does not have an immediate personnel could include building engi-
caused concern, the process can be simple impact on patients or their safety. Exam- neers, caregivers, and administrators.
since the failure of the system is assumed ples might include cooling systems in the Documentation of the risk assessment
without human intervention. Each build- northern U.S., lighting and potable-water should include the risk assessment pro-
ing system is to be categorized into one of systems outside of patient-care areas and cess used, all participants of the assess-
the following four categories: plumbing/sanitary systems. Category 3 ment, and all systems with assigned risk
 Category 1—Systems in which failure systems are likely to be found in basic-care categories. CMS does not require the
is likely to cause major injury or death. rooms, such as treatment or exam rooms. risk assessment to be submitted, but it
Systems are required to be available at all  Category 4—Systems in which failure is required to be kept on-site and avail-
times to support patient needs. Examples has no impact on patient care. Examples able at the time of the survey. K-Tag 901
might include life-support ventilation might include lawn sprinklers, television is used to cite a missing risk assessment.
equipment, emergency power for oper- service, and the public-address system. NFPA 99-2015 notes that the risk assess-
ating rooms, and medical-gas systems in Category 4 systems are likely to be found ment does not have to be performed for
intensive care units. Category 1 systems in support rooms, such as waiting rooms any system assigned a Category 1 classifi-
are likely to be found in intensive care and lounges. cation. Category 1 systems have the most
units, operating rooms, delivery rooms, The risk assessment is required to be stringent requirements; therefore, docu-
and areas dealing with general anesthesia. performed by following and document- mentation is only required for those sys-
 Category 2—Systems in which ing a defined process, as described in tems in lower-risk categories to show that
failure is likely to cause minor injury. NFPA 551: Guide for the Evaluation of those systems are appropriately assigned.
Systems are expected to provide a high Fire Risk Assessments or ISO/IEC 31010:
level of reliability; however, limited fail- Risk Management – Risk Assessment Existing facilities
ures can be tolerated without significant Techniques. The process can be as sim- Existing facilities will not see major
impact on patients. Examples might ple as depicted in Figure 1. The process changes with the application of NFPA
99-2015 with the exception of inspection,
testing, and maintenance (ITM) require-
Will major injury
Yes CATEGORY 1
ments. In general, existing building sys-
System loss
or death occur? tems are permitted to remain, even if they
are not in strict compliance with the code,
No unless the authority having jurisdiction
(AHJ) determines that their continued use
constitutes a distinct hazard to life. This
Will minor
Yes CATEGORY 2 allowance of existing systems provides a
injury occur?
basis that existing facilities do not have
to upgrade their medical-gas/vacuum,
No electrical, and HVAC systems, along with
other utility infrastructure, to meet the
Will discomfort
requirements of the new edition. The
CATEGORY 4 No Yes CATEGORY 3 wording of this requirement leaves the
occur?
AHJ with latitude to potentially require
updates to building systems, such that
Figure 1: This flowchart illustrates a simple qualitative risk assessment approach facilities should review the status of their
based on yes/no answers to the level of patient and caregiver impact. All graphics systems conservatively to ensure that
courtesy: JENSEN HUGHES no surprises occur during inspections.

26 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


When systems are replaced, the systems manual pull station where the fire alarm NFPA 99-2015 states that in facilities
may need to meet the requirements for system monitors and activates automati- with a defend-in-place response to a fire,
new systems as noted in the applicable cally upon sprinkler waterflow or smoke the fire alarm and sprinkler zones should
code(s). At the beginning of several chap- detection. The local fire code may not coincide with the smoke compartments of
ters, including chapters 5 and 6, the code include this exception, and the more strin- the facility unless otherwise specified in the
specifies which criteria are applicable to gent approach should be applied between facility fire plan. Notification signals pro-
existing facilities. It is important that each the applicable codes. vided through the fire alarm system should
facility identify which requirements are
applicable, especially those relating to
ITM, to ensure compliance with the code.
Where a building has a mixture of new
and old systems due to alterations and More hot water
renovations, the determination of appli-
cable requirements becomes more com-
for less money
plex, and it is important that the basis for
the determination is well-documented.
for a very long time.
NFPA 99 requirements You might even call it “a perfect fusion
Chapter 15 of NFPA 99 contains the of heat transfer and corrosion engineering.”
fire protection requirements applicable

POWER VTX
to new and existing facilities. Most of the
®
fire protection and life safety require-
ments are not specifically included in
CONDENSING WATER HEATER
this chapter, but references are made to
other NFPA codes including: ®
ENGINEERED DUPLEX ALLOY

n Facilities that contain laboratories


using chemicals
n The storage and handling of
flammable and combustible liq-
uids or gases
n Elevators and emergency or
standby power systems. Tank and heat exchanger are
fabricated entirely of AquaPLEX
NFPA 99 also relies on NFPA 101, or 15-YEAR duplex stainless steel. Fully
the fire code enforced by the local AHJ, TANK and HEAT EXCHANGER pickle-passivated, it requires no
CORROSION WARRANTY linings or anodes of any type.
for building construction and com-
partmentation, fire alarm and smoke-
detection systems, and fire suppression
▪ 95.5% to 95.8% thermal efficiency
systems. This language was revised from
NFPA 99-2012 to state “applicable code” ▪ Full burner modulation enables precise temperature control
in lieu of listing the various building and under varying flow conditions and improves efficiency to 99%
fire code possibilities. ▪ 500,000 • 750,000 and 1,000,000 Btuh models
NFPA 99-2015 specifies additional cri-
teria for fire alarm systems in addition to ▪ Moderately sized tank provides hot water during low demand
with minimal burner cycling. Extremely low standby losses
those required by NFPA 101 or the local
fire code. The majority of requirements ▪ Electronic, touch-screen operating control with Modbus.
in Section 15.7 are referenced from NFPA Includes plain-text status, diagnostics, firing rate
101, and the requirements are reiterated indication and history. Protocol gateways available
for clarity. Each facility should confirm
that these requirements do not con- www.pvi.com
tradict those within the local fire code.
For example, NFPA 99 permits a single

JUNE 2017 27 input #16 at www.csemag.com/information


Codes & Standards
identify the floor and zone within the build- Signaling Code, is permitted within the occupants who are not responsible in the
ing so that it is clear where a staff response health care and ambulatory health care implementation of the fire safety plan.
is required to support patient evacuation. areas of the facility. In private operat- Additionally, critical care areas are per-
Zoning these systems together simplifies ing mode, audible and visible signals are mitted to have visible notification in lieu
the process of providing accurate informa- only required to notify those persons of audible notification based on patient
tion during a fire event. who implement the fire-safety plan. concerns. Similarly, visible signals are
Private operating mode, as defined Direct notification through the fire not required inside surgical operating
in NFPA 72: National Fire Alarm and alarm system is not required for building rooms, patient sleeping rooms, or psy-
chiatric-care areas where the flashing
Table 1: NFPA 72 ITM frequency changes could interfere with patient treatment.
Component NFPA 25, 2011 edition NFPA 25, 2014 edition Other areas are also permitted to remove
INSPEC TIONS strobe coverage where the facility fire
plan requires staff to respond.
Gauges
Weekly/monthly Weekly/quarterly Automatic sprinklers are typically
(dry/preaction/deluge)
Gauges (wet) Monthly Quarterly
required in all new health care occu-
pancies as defined by NFPA 101. NFPA
Heat trace None previously Per manufacturer
99-2015 permits sprinklers to be omit-
TESTING ted from certain closets in patient sleep-
Sprinklers (harsh ing rooms and in hospital areas that are
None previously 5 years
environments)
smaller than 6 sq ft. When introduced
Air leakage in prior editions of NFPA 99, this provi-
None previously 3 years
(preaction/dry)
sion was not yet recognized in NFPA 13:
Table 1. This table is a summary of NFPA 25 ITM frequency changes from the 2011 Standard for the Installation of Sprinkler
edition to the 2014 edition. Systems; however, this requirement has

Visit
AHR Booth
New!
10” x 1”
#C4710

8” x 1”
AP ARMAFLEX®
LARGE ID TUBES
Now offering large size tubes.
10” x 1.5” Saves Time 25/50
8” x 1.5”
Easy-to-install ASTM E 84 flame
tubes and smoke rated

Less Waste Condensation Control


Reduce scraps from Reduces the chance of
cutting sheet material corrosion (CUI)
10” x 2” 8” x 2”
100% Microban®
Antimicrobial Technology
Fiber free and GREENGUARD
non-particulating Gold Certified

INSTALL IT. TRUST IT.


© 2017 Armacell LLC. Made in USA. MICROBAN is a registered trademark of
Microban Products Company. Certified to GREENGUARD Gold standards for low www.armacell.us | 800.866.5638 | info.us@armacell.com
chemical emissions into indoor air during usage.

input #17 at www.csemag.com/information


Table 2. NFPA 72 ITM frequency changes
Component NFPA 72-2010 NFPA 72-2013
Inspec tIons
now been incorporated into the latest Fuses, LeDs, interfaced
equipment of control none previously Annually
editions of NFPA 13 and NFPA 101. This
equipment
exception is limited to hospitals due to
transmitters to
the relative light fuel load of their small supervising stations
semiannually Annually
closets and does not apply to other facili-
Voice/alarm equipment semiannually Annually
ties, such as nursing homes, due to the
Area of refuge two-way
much higher concentration of combus- none previously Annually
communication system
tibles typically found. NFPA 99 also per-
testIng
mits hose and hose outlets that are not
required by the applicable local building supervisory signal
Monthly/semiannually Annually
devices
and fire codes to be removed.
Rooms that contain compact, movable Table 2. This table is a summary of NFPA 72 ITM frequency changes from the 2010
storage units with an area greater than edition to the 2013 edition.
50 sq ft are required to be protected as
hazardous areas per NFPA 101. In addi- include training on fire hazards within ments have changed in NFPA 99-2015.
tion, NFPA 99 requires smoke detection the space, development of emergency Updates to NFPA 99 include refer-
and automatic sprinkler protection for procedures, and regular updates to the ences to other codes that incorporate
these rooms. Additional requirements procedures and plans in place. additional requirements. Section 15.12
are also provided for facilities with oper- states that NFPA 25: Standard for the
ating rooms. The primary takeaway of Inspection, testing, and maintenance Inspection, Testing, and Maintenance
requirements applicable to operating While most facilities have a pro- of Water-Based Fire Protection Sys-
rooms is that formal procedures and cedure in place to inspect, test, and tems is required to be followed for all
training need to be in place for all per- maintain their fire systems, be aware water-based fire protection systems
sonnel who work in the area. This would that the frequencies of these require- while non-water-based systems shall

input #18 at www.csemag.com/information


Codes & Standards
be maintained in accordance with the Many requirements have been updat- the latest edition referenced by NFPA
applicable standard. Inadequate mainte- ed in NFPA 25 from earlier editions, 99-2015. Relevant changes to health care
nance of fire protection systems, such as including several new additions to the facilities are identified in Table 2. The
fire alarms, fire extinguishers, and auto- 2014 edition (as referenced by NFPA general trend with these changes is that
matic sprinklers, is one of the most fre- 99-2015). Table 1 includes a summary of the frequency of inspections and testing
quent CMS-identified deficiency types. these changes with some specific exam- decreases, but additional requirements
Another common deficiency identified ples including heat-trace inspections and are added as technology changes or pre-
is lack of appropriate documentation air-leakage tests for dry systems. Addi- vious issues are identified.
that maintenance has been performed. tional changes were incorporated into Portable fire extinguishers are
These common deficiencies are eas- the 2011 edition of NFPA 99 and should required to be selected, installed, and
ily remedied but require the facility to be reviewed by facilities following CMS maintained in accordance with NFPA
understand the current requirements requirements. 10: Standard for Portable Fire Extin-
and responsibility to maintain proper The frequency of ITM requirements guishers, 2013 edition. This is consis-
documentation. for NFPA 72 have also changed in tent with NFPA 101 and typical fire
code requirements. No major changes
occurred in the ITM requirements for
Inadequate maintenance of fire protection portable fire extinguishers from the pre-
vious edition. The hazards of the facility
systems, such as fire alarms, fire extinguishers, should be evaluated when selecting fire
extinguishers. For example, a Class K
and automatic sprinklers, is one of the most extinguisher is required within 30 ft of
any commercial kitchen appliances that
frequent CMS-identified deficiency types. use combustible cooking media (oils and
fats). Additionally, spaces with MRI or

Unrivaled.
Belimo Advanced
Butterfly Valve.
Belimo’s new butterfly valve assembly is the most
intelligent, energy efficient, and reliable high flow solution
NEAR FIELD for HVAC applications. With a smartphone, easily program,
COMMUNICATION
(NFC) ENABLED
commission, and troubleshoot the butterfly valve. NFC and
BACnet communication provide the data access you need
to ease installation and ensure optimal performance.
Belimo offers the highest quality products that are backed
by world-class service and support.

Discover all the advantages at belimo.us

Belimo Assistant App

Google Play and the Google Play logo are trademarks of Google Inc.

input #19 at www.csemag.com/information


Cottonwood Filter Screens
similar equipment should be provided with nonferrous com-
ponents due to the nature of the equipment when operating.
& Hail Guards
Additional guidance can be found in annexes A and D of With the Powerful Magna-Track™
NFPA 10-2013.
Magnetic Mounting System.
Power taps
The presence of multiple outlet connections (power taps) is NO Drills / No Screws / No Problem!
a consistent life safety issue with facilities due to the variety of
interpretations from AHJs. The requirement to provide a means
to keep additional devices or nonmedical equipment from
being connected to multiple outlet extensions after leakage
currents have been verified was removed from NFPA 99-2015
via TIA 1. Additional requirements regarding the leakage
current and touch currents of fixed and portable equipment,
respectively, have been relocated out of the testing section
and into the performance section for clarity and would still be
applicable for power tap use. NFPA 70-2014: National Electri-
cal Code, Article 517, describes the requirements for recep-
tacles in health care areas. Generally, if a power tap is used for
medical equipment or is located in the patient-care vicinity, it
must be a special-purpose relocatable power tap and comply
with UL 1363A or UL 60601-1.
The fire protection requirements in NFPA 99-2015 have not
changed significantly from NFPA 99-2012, but the 2015 edi-
tion does offer significant differences from the 1999 edition, Cottonwood Filter Screens & Hail-Master Mesh is
portions of which were previously used by facilities that follow now available with the “game changing” Magna-Track
CMS guidelines. These differences are important to recognize Magnetic Mounting System which makes installing
due to the regular surveys that occur. The two most notable Cottonwood Filter Screens and Hail-Master Mesh
fire and life safety differences apply to the requirement of a easier than ever before. Powerful Neodymium Rare
risk assessment and the changes in ITM requirements for the Earth Magnets, let you install filters and hail mesh in a
building and fire protection systems. matter of minutes without fear of drilling into
condenser coils or other sensitive components.
Chris Moran is a fire protection engineer at JENSEN HUGHES Mounting track is available in either PVC or Anodized
with 10 years of experience providing code-related consulting Aluminum and both include quick release twist-lock
support for health care clients’ life safety and fire protection
fasteners for easy removal of filter screens.
issues—including compliance with NFPA 101 and NFPA 99
as adopted by the Centers for Medicare & Medicaid Services. Cottonwood Filter Screens with their non-stick
coating, protects condenser coils by stopping airborne
Eric Rosenbaum is vice president at JENSEN HUGHES debris before it reaches the coils so they stay clean all-
with over 30 years of experience in fire safety. Rosenbaum season long. Cleaning Cottonwood Filter Screens
is also a fellow of the Society of Fire Protection Engineers instead of the condenser coils reduces wear and tear
and a member of NFPA’s Board of Directors. As a member
and risk of coil damage. Cleaning the filter screens is as
of the NFPA, he chaired NFPA 101’s technical committee on
easy as sweeping with a broom, brush, shop vacuum
fire protection features for 9 years. He is also on the NFPA
or garden hose – even the rain will rinse them clean.
technical committee for health care occupancies and techni-
cal correlating committee for NFPA 101, and member of the For More Information or, to Locate a Distributor Contact:
technical committee for board and care facilities for NFPA 101. input #20 at www.csemag.com/information

Ajay Prasad is a director for fire/life safety and accessibility


consulting services for JENSEN HUGHES in the Mid-Atlantic
region. He has 23 years of experience in providing code con-
sulting services to health care clients including architects, engi- Toll Free -800-819-2869
neers, owners, facility managers and facility planners. www.airsolutioncompany.com
United States and Foreign Patents Granted – Protected under one or more of the following
U.S. and foreign patents:
ϱ͕ϯϳϬ͕ϳϮϮභϱ͕ϱϮϵ͕ϱϵϯභϲ͕ϭϵϳ͕ϬϳϳϭභϮϭϳϬϮϰϰභϵϱϵϬϰϭϴϱ͘ϲ-Ϯϭϭϯභϳ͕ϯϮϯ͕ϬϮϴϮභϳ͕ϰϭϲ͕ϱϳϳϮ
$POTVMUJOH4QFDJGZJOH&OHJOFFSt+6/& 31 භ ϳ͕ϴϰϮ͕ϭϭϲϮ භ 'ϮϱϭϬϳϴϲභϳ͕ϴϰϮ͕ϭϭϲභϴ͕ϳϮϲ͕ϵϱϰභ Other Patents Pending.
Recovering waste
heat in buildings
Waste-heat recovery systems are increasingly used in buildings to move
waste heat from laboratories, data centers, or industrial activities to provide
beneficial heating in other parts of the building.
BY CORY DUGGIN, PE, LEED AP BD+C, BEMP; TLC Engineering for Architecture, Brentwood, Tenn.

S
pace heating is the single largest required to have an ERV in climate zones
Learning energy end use in most build- 1A, 2A, 3A, 4A, 5A, and 6A under the
objectives ing types. The surprising fact 2012 and 2015 IECC. (The 2015 IECC
 Know the basics of waste-
is there is a lot of waste heat clarifies it further by separating systems
heat recovery. that goes unused. Hospitals that operate greater than and less than
 Learn the codes, standards,
and laboratories are two of the high- 8,000 hours/year.)
and guidelines that provide est energy-use-intensity building types. ASHRAE 90.1’s ERV requirement is
engineers with guidance in Regardless as to whether a conventional similar but prescriptive, which means
designing waste-heat recov- hospital or lab is in Miami or New York the performance path allows the ERV
ery systems in buildings. City, the largest single energy consum- performance to be made up in other
 Understand that recover- er is the heating plant. This is because systems. The other most common code-
ing waste heat becomes an the heating load in hospitals and labs is required heat recovery is a prescriptive
attractive option for facili-
ties working to achieve low
largely reheat, which is not a climate- requirement introduced in ASHRAE
energy use (such as in high- dependent load. Traditional, centralized 90.1-1999 and the 2003 IECC, which is
performance buildings) and HVAC systems with code-required air- applied for recovering condenser heat of
to reduce emissions. change rates typically use reheat to keep water-cooled systems to preheat service
the spaces comfortable. Any heat that can hot water in 24-hour facilities or provide
be recovered in these building types can reheat (via an exception). This require-
be used to reduce the heating energy. ment has remained in all subsequent ver-
For many engineers, their first foray sions of ASHRAE 90.1 and the IECC.
into heat-recovery comes as a result of The first step in any design process

5
a code requirement. ASHRAE Standard is to focus on reducing the load before
tips for using 90.1: Energy Standard for Buildings employing technologies to serve the load
energy recovery Except Low-Rise Residential Buildings or offset energy consumption. Reducing
 Check what is required by code. and the International Energy Conser- the load saves on first cost and lifecycle
vation Code (IECC) both have require- cost, whereas systems used to just reduce
 Specify a bypass with air-side energy
recovery. ments for heat recovery. The most strin- energy consumption add to the first cost
gent being the mandatory requirement while reducing lifecycle cost. Energy
 Size heat-recovery chillers to run continu-
ously at full load. of energy-recovery ventilation (ERV) models may be used to compare load-
 Zone variable refrigerant flow systems to
systems in the 2012 and 2015 versions reduction strategies early in design.
take maximum advantage of heat recovery. of the IECC.
 Use energy models to determine the most
For example, a system with 35% out- Defining waste-heat recovery
efficient heat-recovery strategy. side air at maximum flow that has greater Waste-heat recovery is using any heat
than or equal to 5,500 cfm total supply is that would otherwise be wasted. There

32 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Figure 1: The Vanderbilt University Engineering and Science Building is a 230,000-sq-ft
interdisciplinary research and teaching building in Nashville, Tenn., that houses
research labs, a clean room, classrooms, and the Wond’ry, Vanderbilt’s new
innovation center. The building uses air-side heat recovery as one of the
elements to achieve 30% energy-cost savings compared to ASHRAE
Standard 90.1-2007. It has been designed to achieve Gold
certification under LEED-NC v2009. All graphics
courtesy: TLC Engineering for Architecture

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 33


Recovering waste heat in buildings
are several media within building sys- supply air by removing moisture and mates. Another advantage specific to
tems from which heat can be recovered: heating it. They are made of a hygroscop- the run-around coil is it allows the two
ic material, such as silica gel or lithium airstreams to be much farther apart, but
 Air chloride, that adsorbs moisture from the pumping energy is required and results
 Water supply airstream and rejects the moisture in piping heat loss. Newer versions of
 Refrigerant. via a hot regeneration airstream to the run-around loops that integrate the
ambient. Cross-flow heat-recovery cores heating- and cooling-water systems and
Air heat-recovery systems are most often work similar to enthalpy wheels, but the sophisticated controls have improved
employed to preheat and/or precool ven- airstreams flow in an X pattern separated the performance of run-around loops.
tilation air to reduce the load. Some heat- by static plates of heat-transfer media. Heat pipes work similar to run-
recovery ventilators, often also referred to Static cores can be enthalpy or sensible- around coils, but use refrigerant as the
as ERVs, have wheels that spin between two only depending on the heat-transfer heat-transfer medium. This allows the
airstreams to transfer heat. Others have media used for the plates. pumping energy to be eliminated by the
cross-flow static cores. The three main Mechanical codes don’t allow heat phase change of the refrigerant. Heat
types of wheels are enthalpy (also known as recovery from exhaust that is considered pipes are more limited in their arrange-
total energy), sensible-only, and desiccant. hazardous. Run-around coils and heat ment as compared with run-around
Enthalpy wheels transfer both sensible and pipes can both be used to recover heat coils, though. All of these air-side heat-
latent heat between the airstreams. These from contaminated airstreams because recovery technologies can be used in
often use the building exhaust air as the both allow for completely separate air- multiple configurations. For instance,
second airstream. Sensible-only wheels streams without the possibility of any a heat pipe or run-around coil can be
preheat/cool but don’t provide any transfer cross-contamination. A run-around coil set up to precool air before it enters
of moisture between airstreams. uses two coils connected by pipe with a the cooling coil and transfer that heat
The primary purpose of desiccant pump to circulate a heat-transfer fluid, to after the cooling coil for free reheat.
wheels is to reduce the dew point of the which is often a glycol brine in cold cli- Some units even have two wheels, where

CASE STUDY: University heat-recovery system

T
he Vanderbilt University Engineering Science Building (VU ESB) contains Instead, the team elected to use a desiccant wheel in series with a CHW
dry and wet research labs, a clean room, and classrooms. The labs coil on the primary 42°F CHW loop. This allowed for the elimination of the
and clean room are the predominant building uses and most energy- dedicated glycol chiller and reduced the heating and cooling energy needed
intensive spaces. A primary goal established at the beginning of design was to maintain the clean room conditions.
to have a flexible HVAC system that would minimize reheat. The smaller classroom and gathering areas are served with a standard VAV
The base HVAC system used for comparison was a chilled-water (CHW) system with return air. The lab areas of the building are 100% OA with ACB.
variable air volume (VAV) system with hot-water (HW) reheat. Because the Since the need for reheat in the labs had already been minimized via system
labs had a minimum air-change requirement and the clean room had a mini- selection, the focus for employing waste-heat recovery moved to precooling/
mum air-recirculation requirement, fan energy was heating the large volume of required OA.
the highest energy end use rather than heating; When designing air-side When designing air-side heat-recovery systems
however, it was a close second. heat-recovery systems for labs and hospitals, there is always concern
An energy model was used to approximate the about what exhaust air is safe for heat recovery.
annual energy use of the building with the base
for labs and hospitals, In hospitals, there is potentially hazardous air from
VAV system and active chilled beams (ACB) for there is always concern about isolation rooms, soiled storage, and emergency
the labs. ACBs allow for zone heating and cooling what exhaust air is safe for waiting rooms, to name a few. No one wants
control, which reduces reheat. The only reheat that to potentially contaminate the OA by recovering
heat recovery.
occurs with an ACB is when the zone has no need heat and/or moisture from those spaces. In a lab
for cooling and the primary air must be reheated. This same approach is being building like the VU ESB, air from the exhaust hoods is the major airstream
applied in some health care facilities by reducing primary air-change rates. of concern. It was decided that the hood exhaust would not go through the
The clean room is served by a make-up air unit (MAU) dedicated to main- heat-recovery device. Beyond the fear of contamination, certain chemicals
taining strict humidity limits coupled with recirculation units to continuously could also damage the heat-recovery media.
filter the air. The MAU takes preconditioned outside air (OA) from the lab An enthalpy wheel was chosen for the main lab DOAS because of its ability
dedicated outside-air system (DOAS), lowers the dew point to 40°F, and to precool and dehumidify the OA in the summer months while preheating and
reheats it to 65°F. The typical brute-force method would require a dedicated humidifying the OA in the winter months, and any fume hood exhaust would
glycol chiller to produce extra-cold CHW to reduce the dew point and then not be available to the heat-recovery system. Being in Climate Zone 4A, the
reheat it with HW. enthalpy wheel would have a positive effect year-round. The main piece of

34 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Heat exchanger
Outside air

an enthalpy wheel is used to precool and


dehumidify the air before the cooling
coil and a sensible-only wheel is used to
Exhaust air
reheat the air after the cooling coil but
before any heating coils.
The sensible-only wheel could be
used second in sequence with a supply- Figure 2: The most common air-side heat-recovery arrangement is a single wheel
air temperature (SAT) reset to reduce between outside air and exhaust air.
reheat. SAT resets are required by code
but often aren’t effective in labs and hos-
pitals because a critical zone forces the Cooling coil
system to stay at the minimum SAT.
Water or hydronic heat-recovery sys- Outside air
tems reuse heat produced by the cooling
process that would be rejected by a cool-
ing tower or condenser. Depending on the
building systems and their relative loads,
the recovered heat could be used to pre-
heat a low-temperature heating hot-water
Exhaust air
loop or a service hot-water loop. Not only
does this reduce the heating energy need- Enthalpy Sensible
ed, but it also reduces the cooling tower
fan energy used to reject the heat as well Figure 3: When neutral supply air is desired, dual-wheel air-side heat recovery can be
as condenser pump energy. implemented, which uses a second sensible-only wheel for reheat.

analysis was to determine whether a dual-wheel system would yield lower The other negative factor of a potential second wheel is it only
energy consumption than a single-wheel arrangement. provides benefit in cooling mode. The second wheel doesn’t turn when
ACB systems are often designed with the primary air delivered at a neutral the unit is in heating mode, but the pressure-drop penalty still exists. A
temperature, one that provides little heating or cooling effect because it is bypass could be incorporated to remove the wheel from the airstream to
close to the space’s set points. In cooling mode, a dual-wheel arrangement remove the pressure-drop penalty when the wheel wouldn’t be effective;
would allow the DOAS to reheat the primary air with recovered heat using a however, for large systems like those in the VU ESB, a bypass is very
second sensible-only wheel instead of HW. costly. Some smaller systems have bypasses as a standard feature,
The trade-off to adding an air-side heat-recovery device is always whether which can make the needed energy savings easier to achieve because
the amount of energy saved via preheating/cooling the fan penalty only has to be paid when energy
is enough to offset the increased fan energy that Energy codes are can be recovered.
results from the increased pressure drop, which hap- pushing more designs Even though the energy model showed
pens when moving the air through the heat-recovery lower energy consumption with the dual-wheel
to require waste-heat
equipment. An economizer bypass allows the air to arrangement supplying neutral air, the final
bypass the heat-recovery device when outdoor condi- recovery, whether it be via design used one wheel to assure there was
tions are suitable, which reduces wasted fan energy. air, water, or refrigerant. enough flexibility in the cooling capacity of the
The energy trade-off to make air-side heat recovery labs without increasing the number of ACB.
financially viable hinges on the utility rates. Where electricity rates are lower and The lab DOAS heat-recovery system resulted in an estimated savings of
gas rates are higher, the increase in fan energy due to the added static makes $47,200 and 7.85% energy per year as compared with the same system
less of a cost impact than the reduction in heating energy. The opposite is also without heat recovery. The clean room desiccant heat-recovery system also
true, especially when high-efficiency boiler systems are used. saved a substantial amount of energy, and its first cost was offset against
Through energy modeling, it was determined the single enthalpy wheel the cost of the now unnecessary glycol chiller.
energy savings were above and beyond the increase in fan energy. Interest- Waste-heat recovery systems may be incorporated in many ways. Energy
ingly, the determining factor as to whether the second sensible-only wheel codes are pushing more designs to require waste-heat recovery, whether it
would provide enough savings was the needed primary air temperature. The be via air, water, or refrigerant. At the end of the day, waste-heat recovery
second wheel would only provide benefit if cooling effect from the primary is effective because heat that would otherwise be squandered is being
air was not needed. used to reduce energy consumption.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 35


Recovering waste heat in buildings
Heat-recovery chillers are designed to energy simulation is the only way to get loop while others receive heat from the
produce chilled water (CHW) and hot a full picture of how the building reacts condenser-water loop, so the WSHPs in
(HW). They can even be set in heating to its internal loads and environment. heating mode are essentially receiving
mode to maintain a certain leaving HW Heat-recovery chillers can even be cou- heat from the cooling mode.
temperature while letting the leaving pled with thermal storage to expand the Refrigerant system heat recovery is
similar to hydronic systems. Hot-gas
reheat is a common type of heat recovery
Heat-recovery chillers are designed to produce often employed in dedicated outside-air
systems (DOAS). The hot gas from the
chilled water (CHW) and hot (HW). outlet of the direct-expansion cooling
coil bypasses the condenser and is used
as free reheat to both decrease the rela-
CHW temperature float based on load. hours of useful heat recovery in building tive humidity (RH) of the supply air (SA)
Heat-recovery chillers give the most ben- types with fewer hours of coincident heat- and reduce the possibility of overcooling
efit when they can run continuously at ing and cooling loads. when in dehumidification mode. Hot-
full load to maximize the heat-recovery Hydronic heat recovery can be used gas reheat is an efficient strategy anytime
hours, such as when they have been sized with most water-cooled equipment. dehumidification is dominant or a neutral
for the constant minimum-cooling load Air-cooled chillers can even have a to warm SA temperature is desired, such
in a hospital. hydronic heat-recovery bundle added. as in natatoriums where there is a con-
Energy models are useful for deter- Water-source heat pumps (WSHPs) use stant dehumidification load and the space
mining the diversified minimum build- an hydronic condenser loop, but heat set point is around 80°F. Specialized pool
ing load for heat-recovery chiller sizing; recovery works a little differently. One dehumidification units can also use the
otherwise, they can be oversized due to condenser-water loop can have multiple recovered heat for pool heating.
exaggerated process loads or lack of con- WSHPs in heating or cooling mode. Variable refrigerant flow (VRF) sys-
sideration for diversity. A whole-building Some reject heat to the condenser-water tems come in two types, heat-recovery
and heat pump. Only heat-recovery VRF
systems allow for simultaneous heating
Traditional all-air HVAC system is heat and cooling on the same refrigerant loop.
The simultaneous heating and cooling
Pump energy 1% feature is possible by using recovered
Heat rejection fans/ heat based on the predominant mode of
pump energy 2% operation (heating or cooling). As with
a WSHP, the VRF fan coil units (FCUs)
Interior fans 5% in cooling mode reject heat, in the form
Interior lighting 7% of hot vaporized refrigerant, back to the
common loop, but heat-recovery VRF
systems allow that hot gas to first be used
Cooling 9% by any FCU calling for heat. The opposite
occurs when heating is the predominant
mode. Even though heat recovery works
similarly between hydronic and refriger-
Receptacle 11% ant systems, refrigerant systems have the
equipment advantage of not needing pumps.

Cory Duggin is the energy-modeling wiz-


ard at TLC Engineering for Architecture
Inc., providing building-performance sim-
Heating (fossil fuel) 65%
ulation efforts across the 375-plus-person
firm through both direct project involve-
ment and by supporting project teams on
specific and unique modeling issues. He is
Figure 4: The highest energy end use for a lab building with a traditional all-air HVAC a member of the Consulting-Specifying
system is heat. Waste heat can be recovered to reduce the heating energy. Engineer editorial advisory board.

36 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Lives are at risk in the event of a utility
outage at a hospital. It is critical to maintain
power and communication systems through
emergency power-generation systems to avoid
loss of life.

“Critical Power: Hospital Electrical Systems” is a new CFE Edu online course
that has been developed specifically for engineers who design electrical systems for health care
facilities. This unique course with exclusive content features instructor-led discussions, videos,
and high-quality presentations on an interactive, on-demand platform. The course is self-paced,
accessible 24/7, and offers one (1) AIA CES approved learning unit and one (1) HSW credit.

Among other content areas, this course:


✓ Explains the applicable codes and standards: NFPA 70 National Electrical Code, Article 517;
NFPA 99: Health Care Facilities Code; NFPA 110: Standard for Emergency and Standby
Power Systems; and various hospital accrediting agencies.
✓ Assess the unique electrical system requirements of hospitals including those for patient care
and nonpatient areas.
✓ Analyzes and compares the differences between emergency and essential power, connected
load and demand load, the branches of the emergency power supply system (EPSS), and the
types of equipment associated with each branch.

What’s included in all CFE Edu courses:


✓ Exclusive content--not found anywhere else--that includes research and expert knowledge
from instructors working within the industry
✓ Interaction with course authors
✓ Videos, quizzes, and interactive content designed for a proven learning experience with
associated CEU credits
✓ Full access to your course 24/7 with a computer, tablet or smartphone
✓ Course cost is $49.99

Learn more and register at CFEedu.cfemedia.com


* Contact CFE Edu Manager, Emily Guenther, at eguenther@cfemedia.com for more information
or with any questions about CFE Edu.
Learning
objectives
 Review methods to spec-
ify an air-side economizer,
water-side economizer, and
modified chiller efficiencies.
 Understand the control sys-
tems that are part of chilled-
water systems.
 Assess a case study in
which a chilled-water system
was implemented.

Modernizing the Wrigley


Field chilled-water system
W
Selecting and specifying the right chiller is ith Wrigley Field
reaching 100 years
generally dictated by capacity, and there are many old, the Chicago
Cubs Baseball Orga-
philosophies on the best way to control, operate, nization embarked
on a number of HVAC improvements
and calculate system operational costs. inside and outside the historic ballpark.
Throughout the Wrigley Field rede-
velopment design, the project team took
BY SUZAN SUN-YUAN, PE, CDT, LEED AP; and steps to incorporate energy-efficient mea-
CORY J. ABRAMOWICZ, PE, HBDP, LEED AP; sures while meeting the client needs and
Environmental Systems Design Inc., Chicago
overcoming all challenges. Three strate-
gies—an air-side economizer, water-side
economizer, and modified chiller effi-
ciencies—are worth highlighting.

38 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Figure 1: This photo shows the centrifu- occupancy. To prevent short cycling of temperature. Whichever control type is
gal chiller in the Wrigley Field campus the economizer, a time duration for all decided for the project, sensor accura-
chilled-water plant. All graphics cour- control types is usually implemented into cy and reliability can have a significant
tesy: Environmental Systems Design the AHU economizer-controls sequence. impact on long-term operation. As the
Differential dry-bulb temperature high-limit variable of an economizer
Air-side economizer options control is still simple to implement and determines if the economizer is enabled
According to the Pacific Northwest operate, but it requires additional con- or disabled, this sensor can increase cost
National Laboratory, “An air-side econo- trols programming from the fixed dry- and energy consumption if not selected
mizer is a duct/damper arrangement in bulb temperature control. To operate the properly.
an air handling unit (AHU) along with economizer using this type of control, the Designing a system with air-side econ-
automatic controls that allow an AHU AHU compares the OA temperature with omizer to comply with energy code can
to use outdoor air to reduce or elimi- the RA temperature being sensed by the present several challenges depending on
nate the need for mechanical cooling.” RA temperature sensor. If the OA tem- the building occupancy type and pro-
Certain outdoor-air (OA) and build- perature is less than the RA temperature, gram requirements. Often, the most dif-
ing cooling-load conditions justify the the economizer is enabled; if the OA tem- ficult design conditions are when there
use of the AHU being put into air-side perature is more than the RA tempera- are high airflow requirements, such as
economizer mode. Generally, this would ture, the economizer is disabled. in commercial kitchens, and/or narrow
be when the outdoor dry-bulb air tem- While both fixed and differential dry- humidity control, such as in laboratories.
perature is less than the return-air (RA) bulb temperature control methods are For these types of building occupancies,
temperature; however, depending on the simple to implement and operate, neither a water-side economizer may be the opti-
OA humidity for the region, this may incorporates the OA humidity into oper- mal solution.
create humidity-control issues. ating the air-side economizer. During the design of the Wrigley Field
There are four common control types Fixed enthalpy with dry-bulb tem- Plaza Building, a robust central cooling
for air-side economizers, with each pre- perature control introduces a new OA plant with a water-side economizer was
senting various advantages and disad- condition to be met to enable the econo- planned and, therefore, an air-side econo-
vantages: mizer. Controlling the economizer based mizer was not required. Due to the prox-
on the enthalpy in addition to the dry- imity of the two 50,000-cfm base-build-
n Fixed dry-bulb temperature control bulb temperature further limits the usage ing AHUs located on the seventh-level
n Differential dry-bulb temperature of the economizer, but allows for better mechanical penthouse to the outdoors,
control control of the system. By using fixed outdoor- and exhaust-air ductwork was
n Fixed enthalpy with fixed dry-bulb enthalpy with dry-bulb temperature con- routed through the roof and an air-side
temperature control trol, the AHU control system assesses the economizer was implemented for these
n Differential enthalpy with fixed OA enthalpy and dry-bulb temperature AHUs. All other systems in the building
dry-bulb temperature control. against the high-limit shutoff setpoints rely on the water-side economizer.
and disables if setpoints are exceeded.
Fixed dry-bulb temperature con- The differential enthalpy with fixed Water-side economizer options
trol is the least complex control type dry-bulb temperature control operates When evaluating whether a water-
to implement and operate. A high-limit with the strictest requirements, similar side economizer is the best solution, one
shutoff temperature setpoint is deter- to the differential dry-bulb temperature must consider several conditions, begin-
mined during system design, and the control. In this control method, the AHU ning with the building usage and occu-
system operates based on that setpoint. control system assesses the economizer pancy type. If the usage for the building
If the outdoor-air temperature is below mode based on the OA enthalpy and dry- requires tight humidity control, such as
that setpoint, the air-side economizer is bulb temperature against the RA enthal- in museums, hospitals, or laboratories,
enabled, thus the RA damper and OA py and dry-bulb temperature. If either of the AHUs may not have the capability of
damper modulate together to meet load. the respective OA air properties is above providing adequate control of the space
If the OA temperature is lower than the either of the RA air properties, econo- during the use of an air-side economizer.
RA temperature, the air-side economizer mizer mode remains disabled. Furthermore, if the building is to have a
is enabled, the RA damper is opened, When the 2013 edition of ASHRAE central cooling plant, the OA-condition
and the OA damper is reduced to the Standard 90.1: Energy Standard for restrictions of the local climate may be
minimum position. If the AHU system Buildings Except Low-Rise Residential so restrictive that the run time for the
is capable, the OA damper position can Buildings was released, the standard no water-side economizer would exceed that
vary in this mode based on system car- longer permitted economizer control of the air-side economizer. This would
bon dioxide (CO 2) levels and building evaluating dewpoint and fixed dry-bulb make a water-side economizer a more

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 39


Modernizing a chilled-water system

Figure 2: The plate and frame heat exchangers in the Wrigley Field campus chilled-water plant allow for the chilled-water system
to operate in water-side economizer.

enticing option as it would be used more viding up to 100% of the expected system 90.1. To have an integrated control of a
frequently. cooling load at OA temperature of 50°F water-side economizer per Standard 90.1,
There are arguments that could be dry-bulb/45°F wet-bulb and below.” This the system is responsible for not only
made against water-side economizers typically requires the engineer to calcu- providing free cooling when the outdoor
due to their high use of make-up water. late the economizer capacity using the wet-bulb temperature is 45°F and below,
However, due to the low cost of water in load calculation with loads on the build- but also for prolonging the free cooling
Chicago as compared with the national ing broken down by OA temperature. period by precooling the condenser-
average, a water-side economizer for this One exception for this section involves water temperate and warming the return
application had a clear advantage. computer rooms; there is a table to evalu- chilled-water temperature.
A potential justification for designing ate the requirements based on the climate
a water-side economizer is if the OA and zone. The other exception for this sec- Cooling towers
exhaust louver locations established by tion includes dehumidification require- In some cases, the air-side economizer
the project are restrictive. Often for air- ments that cannot be met at a 50°F dry- option has been integrated into the sys-
side economizer projects, the AHU needs bulb/45°F wet-bulb outdoor condition tem design. Unlike data centers for an
to be near the exterior façade to enable and where the expected system cooling office building, hotel, or mixed-used
a short connection to the outdoors. This load at 45°F dry-bulb and 40°F wet-bulb complex commercial building (such as
often forfeits the sought-out perimeter is met by the water-cooled fluid econo- a high-rise), the variation between the
offices for executives. A water-side econo- mizers. Standard 90.1 also requires the summer load versus winter load can be
mizer minimizes this because, instead of fluid economizer to have integrated large—from 4:1 to as high as 10:1.
large ductwork resulting in lower ceilings economizer control. For most cooling tower manufactur-
or perimeter offices becoming mechani- When designing the water-side econo- ers, cooling towers or cooling tower cells
cal rooms with a view, the ductwork is mizer with plate and frame heat exchang- can be winterized by using weir dams or
sized for minimum OA and the econo- ers, there are two piping arrangements for maintaining 50% or more of peak summer
mizer requirement is met by the heat which the heat exchangers can be con- condenser flow at the nozzles to prevent
exchanger at the central cooling plant. figured in relation to the chillers: par- scaling during winter operation. Depend-
Per ASHRAE Standard 90.1-2016 Sec- allel (Figure 3) and series (Figure 4). If ing on specific cooling tower selections,
tion 6.5.1.2, Fluid Economizers, if the the building system only has the option some manufacturers can reduce winter
project team elects to design a water-side of a water-side economizer, then series condenser flow even more than 50%.
economizer, the cooling towers/fluid arrangement with integrated control is Therefore, when choosing cooling tow-
economizer needs to “be capable of pro- the only option when following Standard ers and chillers for the project, the main

40 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


selection criteria included the winter
load, summer load, winter condenser
flow, summer peak condenser flow, chill-
er capacity, and each cooling tower or cell
capacity. The integrated/series application
can start to perform free cooling at 47° to
Figure 3: A water-side
50°F wet-bulb with better approach tem-
economizer configura-
peratures. The cooling tower approach
tion is shown with a
temperature ideally should be limited to
heat exchanger in a
5°F and operation for said cooling tower
parallel piping con-
can be optimized if variable-speed drives
figuration.
(VSDs) are included on the cooling tower
fans and condenser-water pumps.
If cooling tower size is based on the
gallons-per-minute performance require-
ment for both summer and winter loads
with an implemented air-side economiz-
er in system design, along with weather
data and winter cooling capacity, it is a
comprehensive effort to validate the heat
exchanger and winter cooling tower cell
capacity.
It also is critical that the appropriate
heat-exchanger configuration is reviewed
and vetted. Cross-flow cooling towers
start to have inner-cell ice forming with Figure 4: This water-
ambient temperature ranges from 40° side economizer con-
to 45°F dry-bulb. It is recommended figuration has the heat
to slightly increase the temperature of exchanger in series
chilled water and warm side of the heat piping configuration.
exchanger during winter operation. This
increases the condenser-water flow across
the cooling tower fill, which helps prevent operation are the key ways to truly save as the office location of the Chicago Cubs
tower icing. energy, especially when the application Baseball Organization. This proved to
An additional criterion that must be applies to hospitality/residential/hospi- be challenging because all four sides of
met if a water-side economizer is used tal buildings. This temperature should the office tower were planned for retail
involves preheating the domestic hot- be used as a starting point at the begin- storefront, which left minimal facade for
water system. Per ASHRAE Standard 90.1 ning of the condenser-water evaluation intake and exhaust louvers. At this point,
Section 6.5.6.2, facilities that operate 24 and should be adjusted depending on the the design team decided to integrate a
hours a day where the total installed heat- age and type of chillers. Over the past 30 water-side economizer into the central
rejection capacity of the water-cooled years, chiller performance has improved by cooling plant to serve chilled water to the
system exceeds 6 million Btu/hour of effectively operating at lower conditions. Wrigley Field Campus.
heat reject and the design service water- Existing chillers may only perform effec- The Wrigley Field Plaza Building is a
heating load exceeds 1 million Btu/hour, tively down to 60°F, whereas newer chiller 220,000-sq-ft building with retail ten-
the domestic hot-water system must technology has allowed some chillers to ants on the ground floor and parts of the
be preheated. The heat exchangers will perform effectively down to as low as 45°F. 2nd floor, a conference center on the 2nd
seasonally switch over from water-side floor (Level 2), tenant offices on Level 3,
economizer to preheating of domestic hot Designing a mixed-use building the Chicago Cubs Baseball Organization
water, which needs to be reviewed as an During the planning and design of on levels 4 through 6, and a mechanical
integrated building energy savings. the Wrigley Field Plaza Building located penthouse on Level 7. Below the 7-story
Standard 90.1 compliance as well as adjacent to Wrigley Field, the design team mixed-use building are two subgrade
maintaining a desirable condenser tem- was tasked to provide an architecturally basement levels of equal gross area. These
perature at 55°F and above for chiller appealing office building that would serve two subgrade levels comprise the central

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 41


Modernizing a chilled-water system
chilled-water plant, Wrigley Field conces- denser-water supply, return, and equal- the campus was straightforward; dur-
sion storage, a central kitchen commis- izer piping. Due to the limiting heights ing July, when a building in Chicago
sary responsible for all food preparation of the screened wall, coordination of the typically peaks, building usage is at its
of Wrigley Field, staff dining and locker cooling tower piping connections and peak. A baseball game with a fully occu-
rooms, and the clubhouse, player locker elevations of the piping to the support pied office building, retail restaurants,
rooms, laundry, strength and condition- structure was critical. The chilled-water and kitchen commissary at full usage is
ing, and hydrotherapy suite. system is piped in a constant primary not uncommon for a typical July day at
With the large number of locker rooms, variable secondary system with two Wrigley Field.
laundry, and kitchen areas in the sub- separate secondary systems. When calculating the low load, howev-
grade levels demanding large exhaust One secondary loop serves the Plaza er, the opposite was the case—the calcu-
airflows (thus, OA for make-up), intake Building and is routed in the core of the lated load occurs during the winter when
and exhaust were challenging. These con- building up to the AHUs in the penthouse, occupancy loads are less clear. Important
ditions made designing the central cool- serving levels 2 through 6. The other sec- criteria the design team assessed when
ing plant with a water-side economizer ondary loop serves Wrigley Field and is determining the minimum cooling
the optimal solution to provide the owner routed underground to the ballpark; it load included whether the team would
with desired spaces and ceiling heights. runs overhead on the concourse level. be using the facilities for training dur-
The central cooling plant at the Wrig- Currently, the piping serves the conces- ing the offseason, the loading of the
ley Field campus is made up of three sion stands, but there are plans in future intermediate-distribution frame closets
585-ton centrifugal chillers in Level B2 phases to serve additional loads depending throughout the campus (which would be
with equally sized cooling towers on on future programming still in design. substantially lower as the office tower
the roof. One cooling tower is winter- During the design, one of the critical and ballpark operations would be mini-
ized to allow for water-side economizer performance metrics was the minimum mal), and whether the kitchen commis-
operation with heat tracing on outdoor design load of the chilled-water system. sary refrigerators and freezers would be
piping and isolation valves on the con- Determining the peak cooling load for emptied at the end of the season.

Open Unitary Controller


•Open protocol – BACnet/IP
®

and MS/TP
•Open drag and drop component
based programming language –
Sedona Framework™
•Unrestricted programming
tool – our free Sedona
Application Editor
input #21 at www.csemag.com/information

BAScontrol
Learn more at www.ccontrols.com/controllers
Additionally, the maximum load on
the water-side heat exchanger and cool-
ing tower cells also was assessed to
determine the heat-exchanger capac-
ity. Important criteria the design team
assessed when determining the maxi-
mum water-side cooling load, besides
the Standard 90.1 requirement, included
whether there would be a winter event at
the ballpark (i.e., outdoor hockey game),
occupancy loads and uses, refrigeration Figure 5: This view shows the secondary chilled-water pumps at the Wrigley Field
equipment usage, and computer room campus chilled-water plant.
cooling loads.
Among other cold-climate chilled- cooling tower basin, and variable-speed chillers of 400 to 600 tons required 0.560
water systems, careful consideration is condenser-water pumps. kW/ton at full load (FL) and 0.500 kW/ton
required to prevent continuous operation (integrated part-load value; IPLV) for Path
through the winter months to prevent Modified chiller efficiencies A. Additionally, Path B required 0.585 kW/
freezing. During the design of the Wrigley ASHRAE Standard 90.1-2013 Table ton (FL) and 0.380 kW/ton (IPLV) for the
Field Plaza Building, there were a number 6.8.1-3 dictates minimum efficiency same chiller type and load range.
of precautions taken. These included heat requirements for water-chilling pack- Both requirement paths are based on
tracing outdoor piping used in water-side ages that all projects are required to meet. AHRI Standard 550/590 testing crite-
economizer operation, isolation of valves Effective Jan. 1, 2015, the requirements ria. The difference is Path A is intended
not winterized for system drain-down, were further restricted where water- for applications where most of the load
condenser-water bypass through the cooled, electrically operated centrifugal is full load while Path B is intended for

©2016 The Metraflex Company

input #22 at www.csemag.com/information


Modernizing a chilled-water system
applications where most of the load made based on a formula from Standard 0.470 kW/ton. Based on these results, the
includes partial loads. Commonly, Path 90.1 that calculates alternative compli- chillers were selected and far exceeded the
B includes chillers with VSDs whereas ance efficiencies based on the design Standard 90.1 requirements. The installed
Path A includes chillers without VSDs; parameters. For the Wrigley Field campus chillers have a full-load efficiency of 0.648
however, this is not a requirement. Dur- chilled-water system, this was the case. kW/ton and an NPLV of 0.379 kW/ton,
ing the design of the chillers at the Wrig- Design conditions for the chillers which exceed the FL requirement of 0.706
ley Field Plaza Building, the load profile supplying the Wrigley Field campus kW/ton by 8.2% and the NPLV require-
was concluded to be dynamic, thus VSDs were established to have an LWT and ment of 0.470 kW/ton by 19.4%.
were to be used for the chiller operation EWT of 42° and 56°F, respectively, on
and compliance Path B was taken. the evaporator. Design conditions for Suzan Sun-Yuan is a vice president at
Fur t hermore, compliance with the chiller condensers were established Environmental Systems Design Inc. She
ASHRAE Standard 90.1-2013 Table 6.8.1- to have an LWT and EWT of 100° and has extensive experience in the design of
3 can be met if the chiller is designed 85°F, respectively. Due to these varia- commercial, institutional, and educational
toward AHRI 550/590 testing criteria. tions from AHRI 550/590, the chillers facilities. She serves as the point of contact
This requires that the chiller be designed were designed around the calculated for clients, consultants, and contractors,
by the manufacturer for an evaporator- full load and IPLV from the formula in with responsibility for design quality assur-
leaving water temperature (LWT) of 44°F ASHRAE Standard 90.1-2010 Section ance, coordination of the project team, and
and flow rate of 2.4 gpm/ton. Addition- 6.4.1.2.1. ASHRAE Standard 90.1-2010 scheduling of phases.
ally, the chiller is required to be designed was used while the project was being
for a condenser-entering water tempera- designed and permitted because it was Cory J. Abramowicz is a senior associate
ture (EWT) of 85°F and flow rate of 3 the adopted code for Illinois. at Environmental Systems Design Inc. He
gpm/ton. If the desired chiller criteria Full-load efficiency was calculated to is a member of the Consulting-Specifying
are to vary from the prescribed compli- be 0.706 kW/ton and nonstandard part- Engineer editorial advisory board and a
ance requirements, a calculation can be load value (NPLV) was calculated to be 2017 40 Under 40 award winner.

2017Lighting & Lighting Controls


Improve your Lighting & Lighting Controls business with CSE Research
Turning research into insights to make better business decisions

The 2017 Lighting & Lighting Controls study was completed by Consulting-Specifying
Engineer to evaluate customer awareness, usage of, and preference for suppliers
of various types of lighting and lighting controls products and systems. Respondents
to the Consulting-Specifying Engineer 2017 Lighting and Lighting Controls
study identified six high-level findings.

According to the data in the Lighting & Lighting Controls report, when asked
to identify important features considered when selecting one lighting product
over another, 73% of respondents said the overall quality of the product is
highly important, and 61% said the same of the product’s energy efficiency
capabilities. Other valuable factors include the manufacturer’s reputation and
the initial product cost.

Download the new Consulting-Specifying Engineer Lighting & Lighting


Controls Research today! www.csemag.com/2017LightingStudy
Designing buildings
for the Internet of Things
The networking of things within a building must be anticipated
by building engineers.
BY TIM KUHLMAN, PE, RCDD; TEECOM, Portland, Ore.

I
n the past few years, the term “Inter- ’90s, cell phones only handled telephone
Learning net of Things” (IoT) has become the calls. During this time, cell phones had
objectives favored buzzword to describe the next access to the telephone network but not
 Understand the basics of stage of evolution of the information the internet.
Internet of Things (IoT) and age. This is an abstract term, which In the early ’90s, we saw the birth of
how its evolution will impact makes the concept more difficult to the web and smartphones. When phones
building systems. understand. How does this abstract term could be used to access data from external
 Anticipate IoT’s influence affect building design? It would make data sources, they became an IoT device.
on building systems, infra-
more sense to use the term as a verb, such As an infant IoT device, cell phones could
structure, and the evolution
of design. as “the internetting of things,” or simpler be used for email and text messages. They
yet, “the networking of things.” eventually grew into web browsers. Cur-
What we are really talking about with rently, smartphones are only limited by
IoT is taking items or devices (things) and the applications loaded on them. Com-
connecting them to a network where the munications and access to data were key
items have access to information. The to cell phones becoming smartphones.
devices will use the information in dif- Today, cell phones have multiple wire-
ferenent ways. The simple devices will less modes (cellular, Wi-Fi, Bluetooth,
interpret and display information. More and others) that allow them to exchange
sophisticated devices will receive infor- data from the “cloud” and control other
mation from their environment and com- devices near and far.
municate it back through the network. The cell phone is just one example.
The most sophisiticated devices have Consider the following: We have cars
integrated logic or intelligence to per- that can communicate to a dealership
form control functions and to interact when they need service or if they are in
with other devices. How can we anticipate an accident, vending machines that tell
the impact and trends of IoT so we can the distributor when they are running
extrapolate its impact on infrastructure? low on product and allow payment via
Let’s start with an analysis of probably the credit card or mobile phone wallet, and
first IoT device, the cellular phone, to see televisions and DVRs that automatical-
how it evolved. ly check for software updates from the
The cell phone didn’t start as an IoT manufacturer.
device, but because of its access to the As architects and engineers, we need
cell phone wireless network, it was in to anticipate IoT trends as we design
the unique position to become an IoT facilities. IoT devices will continue to
device. From the early 1980s to the early become more popular for personal use,

46 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


business applications, and facility opera-
tions. There is an expectation that the
facilities we design today will be able to
support IoT devices without needing to
be redesigned.

Disparate lifespans
In considering a facility design that sup-
ports IoT, the challenge for the designer
is anticipating the technology trends for
key building components with different
lifespans. Cell phones as IoT devices do
not actually wear out in 18 months, but
they are driven to obsolescence by the
introduction of new technology and com-
petitive market forces. A cell phone battery
has an estimated life span of 2 years, but
when faced with the choice of replacing
the battery for 10% of the cost of a new
phone, often the choice is to replace the
phone to take advantage of the technol-
ogy improvements. Of all IoT devices, cell
phones probably have the shortest lifespan.
They also represent a new category of
devices in the workplace, often referred to
as “bring your own device” or BYOD. This
could apply to personal laptops, tablets, or
other electronic devices that are owned by
a person but used in a facility to conduct
business. Whereas a company may have
a corporate policy to replace an employee Figure 1: There are many different types of IoT devices depending on their function
laptop computer every 4 years, a person and how they interact with their environment. Some are designed to interact with
who brings their own laptop may decide people; many are designed to communicate with other devices or systems to auto-
to replace their laptop every 2 years. This mate our surroundins. All graphics courtesy: TEECOM
implies two things: The IT network must
be adaptable to newer technologies, and the device is used. The trend is for an source in the network room. Current
the IT department may not be in control increase in devices to be wireless. Wire- technology allows for a device with a
of their technology rollout. less allows for more flexibility for mobile single cable to communicate with video,
devices; for stationary devices, it elimi- data, control signal, and power just shy
Internet vs. intranet, nates the cabling. The biggest drawback of 100 W.
wired vs. wireless of wireless devices is the source of power. Related to IoT, another big user of
As the term implies, IoT devices are IoT devices are not inherently passive. wired devices is the wireless infrastruc-
connected to the internet. This is not They require power from a battery or an ture. To make wireless devices work, they
always true. This is another reason why external source. There are new devices, need to communicate with a cellular sys-
IoT devices should be considered the however, that have integrated photovol- tem or a Wi-Fi network. Within a facil-
“networking of things.” Besides access- taic cells to allow for recharging from ity, this will likely be through the building
ing data from across the internet, an IoT ambient light sources. Wi-Fi network. Each wireless access point
device may access data from a local net- Wired IoT devices in need of a power (essentially a radio) requires power and
work (intranet) or exchange data locally source can use the same data cable that data. The more devices communicating in
with a peer device. It depends on where is used to transmit and receive data. No one area, the greater the number of wire-
the device is and where the data is located. external power supply is necessary. This less access points needed to maintain a
IoT devices can be wired or wireless. uses a Power over Ethernet protocol or quality of service. The trend in wireless
This all depends on the device and how some other Class 2 or Class 3 power is for a higher density of wireless access

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 47


Designing buildings for IoT
points with a higher bandwidth (more the building. The network communi-
radio channels) and needing more power. cation rooms should house all network
equipment, whether it is for private use
How buildings need to adapt to or public-access networks.
support IoT devices For example, a company may decide
One way to consider the impacts of not to allow public IoT devices to access
IoT devices to the facility design is to their private network or even their guest
work backward from the IoT devices. wireless private network. Mobile IoT
IoT devices in a facility will be wired devices can communicate with multiple
or wireless, and there are still a lot of types of wireless protocol. They may be
wires needed for wireless infrastructure. able to communicate over a cellular net-
All these wires go back to the network work if a public-access Wi-Fi network is
not available. Extending
From an architectural view- the public cellular net-
works into a building
point, assume the network through a distributed
antenna system is com-
communication rooms will mon. This equipment
continue to increase in size. takes space, requires
power, and should be
communication room. The cabling takes integrated into the network communica-
space in the network communication tion rooms.
rooms and in the pathways getting back The electrical loads for the network
to the rooms. Both the pathways and the equipment will continue to increase.
rooms need to be designed with growth The power system should be designed
in mind. A good rule is to allow for 100% to allow for scaling up and the addition
growth for the horizontal cabling spaces of power circuits. The mechanical or
(cables going from a device back to the HVAC system for the network commu-
network communication room) and 50% nication room also should be scalable.
Connectrac ® wireways growth for the backbone cabling spaces This does not mean the HVAC system
that interconnect the network commu- should be completely built today for the
provide a proven power and nication rooms. This allows room for future load. However, depending on the
IT alternative to expensive growth in both the network communi- system, some techniques can be built now
cation rooms and cable trays. to lessen the impact of scaling up in the
and disruptive core drilling, Both the IoT devices that are wired and future, such as oversizing a chilled water
trenching and unsightly power the wireless access points need power. line in anticipation of additional taps or
This power also will come from the local installing additional refrigerant lines in
poles. Our ultra-low profile network communication rooms serving anticipation of a future direct-expansion
wireway is so discreet it’s a building zone. If more power is being unit to be installed.
transferred through the network commu- Scalability can be applied to the archi-
barely noticeable as
nications rooms, some of that power will tectural design of the network commu-
it elegantly blends in to any turn into heat in the rooms, which implies nication rooms. When working with the
more heat rejection is required. technology engineer to locate the network
environment while
From an architectural viewpoint, communication rooms, avoid locations
accommodating power assume the network communication where the rooms cannot be expanded,
rooms will continue to increase in such as next to exterior walls, vertical
and data.
size. The technology engineer should shafts, and stairwells. Strategically locat-
design a room for the equipment being ing a small conference room next to a
® installed on day 1 as well as for equip- network communication room would
ment to be added over the lifespan of allow for the network technology room
Connect without core drilling the building. Based on product lifecy- to grow into the conference space in the
cles, it may be necessary to refresh the future while minimizing impact to the
connectrac.com/NeverCoreDrillAgain network several times over the life of floor space.
1.877.480.5637
input #23 at www.csemag.com/information 48 Consulting-Specifying Engineer • JUNE 2017
NEW

Connectrac 2.7 Under-Carpet Wireway

It’s so good at
cable management
you’ll expand technology.
Introducing Our New Under-Carpet Wireway
Available Now for Pre-Order
Connectrac ® wireways provide a proven power and IT alternative
to expensive and disruptive core drilling, trenching and unsightly
power poles. Our ultra-low profile wireway is so discreet it’s
barely noticeable as it elegantly blends in to any environment
while accommodating power and data.
Delivers Power + Data
®

Connect without core drilling


1.877.480.5637 input #24 at www.csemag.com/information connectrac.com
Patent Pending
Designing buildings for IoT
Technology can’t wait for tenant The next step is the evolution of the search routines and use of language. With
improvement technology systems into the architectur- Siri, you can ask a question and the pro-
The traditional building design al building interiors. Imagine a building gram can serve up data compiled from the
mentality of considering the building area where the ceiling, raised access floor, internet. Now imagine going to a concert
technology to be part of the tenant- or wall systems are integrated with the and trying to find your seat. By logging
improvement phase of the project will technology. Interior finishes can incorpo- into the venue’s guest wireless network
not prepare facilities for future technol- rate wireless access points, LED lighting, and accessing the venue map, Siri can
ogies. Architects and engineers should building automation sensors, and secu- direct you. Or, imagine visiting a client’s
be engaging their technology partners rity devices in a modular system. Instead office complex and having Siri direct you
at the beginning of the project. The of an architect having their vision for an to the correct conference room.
technology disciplines (telecom, secu- interior space be pockmarked with wire- There are other artificial intelligence
rity, building automation, and lighting) less access points and other technology systems, like Alexa, which interacts with
have been going through a convergence devices, they can choose a design where Amazon’s Echo. Devices such as these
over the past several years, with telecom these components are integrated. currently work independently; the next
wired and wireless networks becoming step is for them to be interconnected and
the common utility for all the technology Anticipating the next step more thoroughly integrated into our sur-
disciplines. of IoT evolution roundings or building systems. In addi-
Where these systems were once con- Predicting the future is difficult, but tion to Alexa learning my voice and my
sidered separate and required their own there are a couple of emerging technolo- desired light level for a room, a network
space for equipment and pathways, gies that show promise for IoT. The first of Alexas would be able to respond wher-
they are starting to share more of these is in the realm of artificial intelligence ever it recognizes my presence.
spaces. This has an impact on the archi- and automated response. Siri is Apple’s Another promising step for IoT is
tectural layout of the building and the intelligent assistant, which was released the use of mesh networks to intercon-
concentration of loads on the electrical in 2011 for several Apple platforms. It is nect IoT devices. In a mesh network,
and mechanical systems. a program that can adapt to a person’s every node interconnects with a nearby
node to pass data. Mesh networks can
be set up to be self-recognizing and self-
healing. This allows new devices to be
introduced as they encounter the rest
of the network, or for the network to
transfer data along an alternative path if
a node is removed from the mesh. This
technology has been around for a while
for wired networks.
The next step is to see wireless devices
create mesh networks with other wireless
IoT devices in the vicinity. It may not be
possible for the network Wi-Fi to reach
every place in a building, but through
the wireless interconnection of nearby
nodes, IoT devices can act as digital
repeaters.

Tim Kuhlman is an associate principal


at TEECOM, where his focus is designing
telecommunication systems for commercial
and industrial facilities. He combines his
6 years of construction experience with 23
years of engineering to expertly solve com-
Figure 2: Wireless devices are an oxymoron in that to make wireless devices work, it plex problems for his clients. He is a mem-
takes a lot of wiring infrastructure. As wired and wireless IoT devices become more ber emeritus of the Consulting-Specifying
pervasive, the cabling infrastructure to support them will increase. Engineer editorial advisory board.

50 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Integrating BAS, controls
for smart buildings
Technology integration between all engineering disciplines will create
a smart building that can enhance building operations.

BY BRANDON McCARRON, Envise, Garden Grove, Calif.

S
mart buildings are made up of experts from the architecture, engineering,
complex systems containing and construction tiers focused on reducing Learning
equipment, control devices, and construction and lifecycle costs through a objectives
sensors managed with network- technology-focused approach.  Learn how networking
ing infrastructure, processors, building infrastructure and
computers, and servers. The traditional Maximizing the sum of all parts systems can lead to a smart
construction approach to smart building A successfully integrated system will building.
infrastructure pushes down most imple- add greater value to the overall project as  Plan for integrated building
mentation details and technology choices opposed to each individual design disci- technology with CSI Master-
Format Division 25.
to multiple levels of contractors. In turn, pline that uses embedded technologies to
these professionals design, procure, and monitor and control its respective systems.
implement infrastructure systems with- For example, lighting and HVAC have
out any collaboration of effort or choices many overlapping features, such as zone
across disciplines. occupancy sensors and schedules, front-
The resulting absence of a standardized end visualization software, tools for
network architecture, security scheme, and setup and configuration, Ethernet and
user interface for the entire facility creates fiber-optic cabling, and communication
a fragmented network of systems that protocols. These similarities present an
proves more difficult to operate, maintain, opportunity to remove duplications and
and expand over the building lifecycle. minimize the number of devices required
Although it is possible to manipulate to accomplish the same goal; automation
a smart building after construction is tasks also can be streamlined once the
complete, it comes at a cost. The tradi- systems are live. All of this adds up to
tional construction approach must rap- eliminated waste.
idly evolve, much like today’s operational In addition to lighting and HVAC,
technologies, to change the way that smart several other systems are responsible for
building technology is incorporated into maintaining any complex project includ-
new construction. Embracing this trans- ing access control, closed-circuit TV, life
formation will help building owners and safety, metering for utilities, and solar
operators avoid the sunk costs of meeting and energy storage. The importance of
specifications at minimum, as well as the eliminating inefficiencies and minimiz-
costs of integrating smart systems after the ing waste in any building is no longer a
building is occupied. Translating the idea value add. Today, it is a necessity for the
of integration to actuality requires upfront long-term lifecycle management of any
coordination and a collaborative team of smart building.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 51


Integrating
BAS, controls

Figure 1: The West 2nd District project team that includes Envise is employing breakthrough strategies in design, engineering,
construction, and environmental systems to create a game-changing new cultural place. Courtesy: West 2nd District

Applying the CSI MasterFormat consequently, continuity did not exist in As emerging technology becomes
specification operational technology implementations viable, Division 25 serves as both a blue-
When planning for integrated tech- from one building to the next. print for upgrading existing technologies
nology upfront, consider using the Con- As rapid adoption of direct digital con- as they reach their end of life and as a
struction Specifications Institute (CSI) trol and networkable technology acceler- technology version-control system for
MasterFormat Division 25: Integrated ated, so did the need for data assimilation continuously improving and solving old
Automation specification as the coordi- in what used to be traditionally segmented problems with new, viable technology.
nation point between design, construc- systems within a building environment. As While the inclusion of Division 25 adds
tion, and service teams. This will enable a result, the MasterFormat was revised to sweat equity and coordination to the early
the project team to address technology address the growing need for governance development process, it is an essential
framework for addressing the long-term
sustainability of these facilities.
Implementing Division 25 as a coordination hub for Cost and quality remain at the top of
our industry’s priority list, and that will
design, construction, and service teams is critical. not change. However, our approach to
incorporating smart building technology
integration first and define goals and of all disciplines to converge the enormous into new construction must revolution-
requirements prior to construction. amount of technology being implemented. ize to more fully integrate project teams,
Introduced in 1963, the CSI Master- That revision is now known as Division which in turn, minimizes and even elimi-
Format specification for design coordina- 25: Integrated Automation. nates unnecessary and costly gaps. A true
tion and contract documentation for con- Implementing Division 25 as a coordi- champion of operational technology inte-
struction projects in the U.S. did not have nation hub for design, construction, and gration allows the appropriate accountabil-
a place, or need, for integrated technology. service teams is critical for addressing ity and responsibility of normalizing net-
Each division of the MasterFormat was commonalities between all the similar work architectures while creating criteria
covered under different disciplines, verti- technologies being applied to the same for standardizing operational technology
cals, and tiers within the new construction portfolios and new-construction oppor- software, hardware, and communications.
industry, with designers as experts in their tunities. Large campuses, hospital facili- The result is more efficiency, less waste,
respective field responsible for each piece ties, government agencies, data centers, and overall greater cost savings.
of the overall system. and other high-performing or complex
In essence, an architect responsible environments that have large operational Brandon McCarron is technology integra-
for converging systems was not part of requirements are especially prone to inef- tion engineer at Envise, a national build-
the design or construction process, and ficiencies without standardization. ing systems integrator.

52 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


We proudly salute manufacturing innovation
and invite you to explore and celebrate
the success stories of these participating
manufacturing innovators:

Aerco Int’l. Inc. National Lightning


Protection Corporation
Armacell LLC
Baldor Onicon Incorporated

Belimo Air Controls PVI Inc.


Bradley Corp Red-White Valve Corp.
Carlo Gavazzi SEMCO LLC
Carnes Company SimplexGrinnell
Carrier Stored Energy Systems
Cleaver-Brooks STuLz
Connectrac Thomson Power Systems
Contemporary Controls Titus
Delta Cooling Towers unison Comfort Technologies
Firetrace Industrial uV Resources
Greenheck Fan Corporation Varco Pruden Buildings
Linx Industries

Look for the special Innovations videos at:


www.csemag.com/innovations
A DV E R T I S E M E N T

Benchmark® Platinum’s Innovative Technologies


Optimize Performance and Efficiency
The Benchmark Platinum is for applications that feature combination systems
AERCO’s most advanced boiler including multi-zone space heating, space heating
yet featuring a powerful bundle with domestic hot water, radiant floor heating, snow
of innovative technologies includ- melt, and pool heating, or as the system’s by-pass to
ing AERtrim (patented O2 Trim the high temperature connection.
technology), Dual Returns (enables
design flexibility and maximum onAER Remote Monitoring
efficiency), and onAER Remote onAER Remote Monitoring continuously monitors
Monitoring (unique pro-active the overall health of the system helping customers
health of system monitoring). properly maintain and protect their investment.
onAER provides a convenient site that offers an
AERtrim instant, intuitive overview of the system including unit
AERtrim, AERCO’s advanced, performance, plant efficiency, upcoming maintenance
patented O2 Trim technology, required, detailed technical data and more. onAER
monitors actual site conditions and allows for quick resolution and prevents more serious
self-adjusts its combustion process to ensure problems from developing that can result in inefficient
the boiler is operating at optimal O2 levels despite operation and increased expenses.
environmental variations such as humidity, atmospheric
pressure, filter dust loading and delivered gas energy
content. Proper O2 levels provide greater uptime
reliability, increased energy savings, lower emissions,
and an additional 1%-2 % seasonal efficiency gain.

Dual Returns Monthly reports and instant email alerts notify


Benchmark Platinum’s Dual Returns allow engineers customers and facility managers of any faults or
to take full advantage of diverse load demands specific decline in equipment to prevent unnecessary wear-
to a site in order to design the most efficient system and-tear as well as premature failure.
possible. Most traditional boilers offer a single
return that forces the blending of hot and cold water In addition to these features, AERCO offers an industry-
temperatures. However, Benchmark Platinum’s Dual best warranty for the Benchmark Platinum. Benchmark
Returns keep cold water separate, creating a larger Platinum is an innovative, state-of-the-art system that
condensing zone in the heat exchanger that improves provides maximum efficiency for bigger savings and
boiler efficiency up to 7%. Dual Returns are ideal greater Return on Investment.

sales@aerco.com | 845-580-8000 | www.aerco.com

input #25 at www.csemag.com/information


A DV E R T I S E M E N T

Designed for Food Safety: Dodge Mechanical Products


and Baldor-Reliance Motors
Food and Beverage processing equipment should be designed, used, and maintained with
food safety principals as a priority. Failure to adhere to these practices can cost companies
thousands, if not millions, to resolve. It is critical that food and beverage companies not only
consider the initial purchase price, but also the Total Cost of Ownership (TCO) that includes
the cleanability, maintenance, and reliability of the equipment provided by suppliers who
understand the principles of sanitary design.

Industry leading Dodge® mechanical and Baldor-Reliance® electrical products


help ensure the highest level of food safety, reliability, and
performance in the food industry.

Long before we invested in the people, equipment and


material required to produce Dodge washdown reducers and
Baldor • Reliance Washdown Duty motors, we invested our time
and attention in listening to equipment designers, operators and
plant maintenance engineers. We learned about their toughest
processing applications in the food and beverage industry. We took
notes when they shared their wish lists of product capabilities and characteristics.

That was over 30 years ago, and we’re still listening to customer input.
That is why Baldor-Reliance Stainless Steel motors and Dodge Ultra Kleen gear reducers are
engineered to meet the toughest demands of food production and processing. These products
have been designed, tested and certified to meet IP69K requirements for water protection, and
provide the necessary protection from severe washdown conditions without allowing caustic
chemicals or water to enter the product.

Baldor-mediarelations@abb.com | 479-646-4711 | www.baldor.com


input #26 at www.csemag.com/information
A DV E R T I S E M E N T

Carnes High Temperature Smoke Exhaust Fans


In the United States, a fire occurs in a structure once sheaves and custom designed motors capable of
every minute. During a fire the amount of oxygen in running at higher temperatures for longer. The
the air decreases as it is used up as fuel and the innovative one-piece outer housing incorporates the
presence of particulates and fumes increases. To fan inlet and is fully welded to the curb cap for
make matters worse, as the oxygen is depleted there structural strength and durability.
exists a situation known as “incomplete combustion,”
which results in an increase in the amount of toxic The VQ series has been thoroughly tested by UL,
gasses that can quickly incapacitate occupants the foremost authority in safety testing, to vigorous
making escape drastically more difficult. The primary standards to ensure proper operation when it matters
cause of death related to fires is not burns, but most. The entire series of fans are rated to operate at
asphyxiation related to inhalation of the toxic fumes 500 degrees Fahrenheit for over 4 hours and at 1000
and particulates in smoke. The importance of degrees for a minimum of 25 minutes. This means
escaping early is paramount and necessitates the use more time for occupants to get to safety.
of systems to extend the period of time when
conditions are safe enough for occupants to flee. [1] Visit www.carnes.com for other safety products
from Carnes as well as a large variety of quality air
ventilation, distribution, and conditioning equipment.

Introducing the Carnes VQ Series Fan


The Carnes VQ series centrifugal high temperature Carnes Company is headquartered in Verona, WI
exhaust fan was created for just this purpose.
It was designed to handle the exhaust of extremely
hot, smoke laden air during building fire situations.
The fan discharges unbreathable air to provide vital
Nick Howe
minutes needed during emergency evacuations.
Product Engineering Manager
Carnes Company
The VQ series is manufactured in the US using
heavy duty construction to withstand the extreme
conditions of a building fire. The robust design
incorporates dual high temperature-rated belts and

National Fire
[1]

Protection Association
(NFPA)

Contact carnes@carnes.com | 608-845-6411 | www.carnes.com


input #27 at www.csemag.com/information
A DV E R T I S E M E N T

Carrier® AquaForce® 30XV Air-Cooled Screw Chiller:


Designed for tomorrow. Fit for today.
and narrow sizes as well as shorter airway lengths to
fit tight mechanical spaces. Additionally, the reinvented
39M is streamlined, easy to install and offers many
more options including greater motor speed control
selections, direct-drive plenum fans and LED marine
lights. Moreover, new filter kits in many different types
and efficiencies will satisfy an even greater breadth
The AquaForce® 30XV air-cooled of applications.
screw chiller with Greenspeed® intelligence yields an
industry-leading IPLV and has the smallest footprint in its class.
Carrier® Dual-Stage
Relief Economizer
The AquaForce® 30XV air-cooled variable-speed (DSRE) rooftop unit
screw chiller was developed to ensure the best perfor- upgrade feature
mance and efficiency in a solution that’s easy to install,
Carrier’s DSRE is similar
easy to service, highly reliable and quiet. The 30XV
to a typical economizer
delivers with industry leading efficiency (IPLV Ratings
with barometric relief The award-winning Carrier Dual-Stage Relief
greater than 21.0 available in certain models) and Economizer (DSRE) rooftop upgrade feature
but also integrates an
sound. Its smaller footprint can replace just about all provides additional building pressure relief without
additional relief plenum
older equipment going back two generations. electricity. The DSRE is available on Carrier48/50 TC,
from the building space HC, KC and LC models of packaged rooftop units.
that bypasses the
The 30XV can be customized to fit most building
traditional barometric relief dampers. The DSRE
needs, anywhere. With value-added features such as
uses no motors, fans or electricity to relieve building
fully air-cooled variable frequency drives for next
pressure and can help eliminate the need for
generation sub-systems including rotary screw
electricity-consuming power exhaust fans. Carrier’s
compressors and quiet AeroAcoustic® fan system,
Dual-Stage Relief Economizer (DSRE) rooftop
integrated with microchannel condenser coils, it’s
upgrade feature captured the 2017 AHR Expo®
made for versatility, robustness and efficiency. Its
Innovation award in the Green Building category
user-friendly control with color touchscreen display is
and Consulting-Specifying Engineer® magazine’s
self-optimizing, enabling the 30XV to run at optimum
Silver Award for “Product of the Year” in 2016.
performance at any given set of conditions.

Carrier® Aero® 39M Commercial Air Handler


The reinvented Carrier® Aero® 39M
The reinvented Carrier ® Aero® 39M AHU delivers air handler provides even more
greater flexibility and versatility through an expanded advanced technology and custom
number of available sizes, configurations and features in a streamlined, easy-to-
additional features. Featuring the Aero’s proven install package. Indoor and outdoor
units are available to handle a wide
foam-filled, double-wall construction and Agion® variety of applications.
anti-microbial technology to protect the unit over its
lifespan, the latest version of the 39M is available in tall

1-800-Carrier | CarrierCommercialSystems@carrier.utc.com | Carrier.com/commercial


input #28 at www.csemag.com/information
A DV E R T I S E M E N T

Dedicated R&D Center at Cleaver-Brooks


Advances Boiler Technology
constraints, allowing for
system engineering
flexibility and maximum
boiler efficiency.

Another design advantage


of the CFC-E is its large-
water-volume pressure
vessel with low pressure
drop, making it ideal for
primary-variable-flow
pumping systems. In its
small footprint, the CFC-E
CBEX Elite boilers at Stanford University features patented AluFer® tube and burner technology
along with intelligent controls to optimize system
Cleaver-Brooks is the leading global engineer and performance and minimize costs.
manufacturer of fully integrated boiler room systems.
The company designs and manufactures hot water Firetube Boiler Technology Reimagined
and steam-generation products aimed at integrating The CBEX Elite boiler features proprietary EX
and optimizing the boiler, burner, controls and technology, the first dramatic evolution in firetube
exhaust system to maximize energy efficiency while boiler design to occur in decades. CFD modeling
minimizing emissions. enabled engineers to increase heat transfer in the
tubes by 85% and optimize the furnace geometry for
Cleaver-Brooks is one of only a few boiler
near-perfect combustion.
manufacturers to operate a dedicated R&D center.
In addition to developing energy-efficient, low- The CBEX Elite achieves 10:1 turndown while main-
emissions products, the company engineers state- taining 3% 02 across the full operating range. It also
of-the-art retrofit solutions for commercial, reduces emissions to never-before-achieved <5 ppm
institutional and industrial markets. NOx levels without selective
catalytic reduction. The
Cleaver-Brooks is the pioneer of firetube and watertube
CBEX Elite is 15% smaller and
boilers, and its products are known for their reliability
heats up 20% quicker than
and longevity. Many of its boilers installed 40 years ago
traditional firetubes.
still operate today.

Exceptional Performance with System


Engineering Flexibility
The ClearFire®-CE (CFC-E) condensing boiler is a
compact, high-mass firetube design that achieves up
to 99% efficiency. It features dual temperature returns,
enabling maximum operating efficiencies in a variety
of system applications. There are no flow limitations to
consider and no need to satisfy multiple-boiler design

To find a Cleaver-Brooks representative near you, visit cleaverbrooks.com/reps.

800.250.8552
info@cleaverbrooks.com
cleaverbrooks.com
input #29 at www.csemag.com/information
A DV E R T I S E M E N T

Connectrac Brings New Cable Management Solution


with the Under-Carpet Wireway

Connectrac’s latest cable installation process come with ramps and an array of
management solution – the core drilling, Connectrac is accessories and options.
Connectrac Under-Carpet efficient with the users’ time
Wireway— is now available and can be reconfigured as The Connectrac On-Floor
for purchase and shipping. This workspaces evolve. Wireway is Connectrac’s most
new wireway is the sleekest and flexible wireway, able to be
most low-profile design ever The Connectrac Under-Carpet installed on top of any flooring.
from Connectrac and looks to be Wireway elegantly accom- They lead the industry in both
an industry game-changer. modates power, data, and AV ease of installation and capacity
cabling and performs ideally for for telecom and A/V cables. The
Connectrac reduced the profile classroom lecterns, executive Connectrac On-Floor Wireway
of the wireway further to the offices, reception desks, and is the best wireway solution
point where any carpet can be much more! The low-profile when the speed of installation,
laid over the system, making it wireway used for the Under- flexibility, and value are critical.
virtually invisible. This factor Carpet system is also available
will take cable management in the Connectrac In-Carpet and With the Connectrac
out of sight and out of mind, On-Floor Wireway options. Under-Carpet, In-Carpet, and
blending in seamlessly with On-Floor Wireways, users can
any application design. The Connectrac In-Carpet deliver power, data, and A/V
Wireway offers discreet and connectivity to anywhere in
Now that carpeting completely elegant power and technology their interior application. The
covers the wireway, users can cable management, integrated three wireway options from
provide wireless aesthetics to into the carpeting with a Connectrac ensure it the most
their workspaces without the removable top cap for easy elegant and cost-efficient cable
hassles associated with cable and wiring access. It management solution over
alternatives like core drilling combines an extruded aluminum other alternatives such as
or trenching. While time central wireway flanked by core drilling, trenching, and
consuming and an arduous ultra-low sloping floor transition power poles.

Connectrac.com
info@connectrac.com | 1.877.480.5637

input #30 at www.csemag.com/information


A DV E R T I S E M E N T

Powerful, Flexible Fire Protection Solutions

Firetrace International is the global leader in special hazard fire protection. The first to adapt to
new technologies, Firetrace supplies powerful, flexible fire management solutions worldwide.
Headquartered in Scottsdale, Arizona since its inception in 2000, Firetrace has expanded from
its initial 2,000sq ft (185sq m) facility to over 80,000sq ft (7,500sq m). Its European operations are
based just outside Gatwick Airport near London and, to ensure timely, effective support around the
world, it also maintains sales offices in Sydney, Singapore, New Delhi, Dubai and Johannesburg.
As one of the largest global installers of fire suppression systems, Firetrace has an established
product division. Skilled engineers in electrical, electronic and mechanical engineering are
dedicated to the ongoing research and development of all kinds of fire suppression systems.
Firetrace also sits on a range of different fire suppression committees that seek to determine and
promote best practice. This enables the business to not only remain compliant today, but also to
make accommodations for the future and ensure it continues at the forefront of any new learnings
or technologies.
It is this focus on innovation, flexibility and adaptability that sets Firetrace apart from its
competitors. If a customer comes to Firetrace with fire suppression needs that aren’t fulfilled – or
aren’t optimally fulfilled – by the company’s current range, the team works with them to make the
necessary changes.
A perfect example of Firetrace’s innovation is its E4 engineered clean agent
systems; the newest evolution in total flooding fire suppression. Firetrace E4
systems are shattering traditional design limitations using 500psi/35 bar
pressure in lower-cost, low pressure equipment, while achieving the
performance of more expensive high pressure or ‘nitrogen driver’ systems.
A further demonstration of Firetrace’s unique adaptability is its complete family
of UNECE (United Nations Economic Commission for Europe) R107 approved fire
suppression systems for buses. Firetrace is the only manufacturer to offer the
mass transit industry a wide choice of approved systems specifically designed
for their sector.

Mark Osborne
President, Firetrace International

www.firetrace.com | info@firetrace.com
+1 888 607 1218 (USA & Canada) +1 480 607 1218 (international enquiries)
input #31 at www.csemag.com/information
A DV E R T I S E M E N T

Greenheck Lowers Sound and Simplifies Start-up


in Packaged Rooftop Outdoor Air Units
Greenheck’s highly configurable packaged rooftop Low Sound Condensing Fans
units are specifically designed for DOAS or high In addition to achieving outstanding energy efficiency,
percentage outdoor air applications. Models RV and Greenheck’s packaged rooftop units include low
RVE (with energy recovery) are ideal for schools, sound condenser fans that reduce unit sound levels
hospitals, hotels and other commercial buildings. up to 8 dB.

The quiet operation allows for installation closer to


the spaces they are serving and shorter duct work
runs while ensuring compliance with local sound
codes. The radiated sound levels of the RV and RVE
models are tested in a state-of-the-art sound lab and
published in the unit submittal.

Intuitive Start-Up
Greenheck’s preconfigured and intuitive controls
Model RVE simplify start-up and reduce installation time. Control
sequences are optimized for Dedicated Outdoor Air
Systems and Variable Air Volume applications.
Model RV and Model RVE
• Up to 13,500 cfm
Greenheck Controller
• 2” Double Wall R13 Foam
• Cooling Options:
— Packaged DX
— Split DX
— Chilled Water
• Heating Options:
— Indirect Gas Furnace
— Electric Heater
— Hot Water
• Available with Modulating Hot Gas Reheat with
precise humidity control The controller is preprogrammed for the specific
job but parameters are easily adjustable in the
High Turndown Furnace field without additional programming devices or
An optional high turndown furnace can be specified factory technicians.
to provide up to 16:1 seamless turndown for more
precise temperature control and less furnace cycling. The microprocessor controller is capable of
This option is especially beneficial in variable air operating stand-alone or it can be integrated into
volume applications when decreased airflow causes a Building Management System (BMS) at any time
excessive cycling with lower turndown furnaces. through a protocol card using BACnet ® MS/TP or IP,
Higher turndown also improves occupant comfort on LonWorks ® or Modbus ® RTU protocols. Each unit is
part-load days or when the furnace is sized for a large factory-tested to ensure optimum performance
temperature rise. and quality.

715-359-6171 | greenheck.com

input #32 at www.csemag.com/information


A DV E R T I S E M E N T

ProCoat Duct Systems: Specify Performance


and Appearance In One

Linx Industries, formally known as Lindab USA, is a ProCoat has an average


division of DMI Companies and has announced the thickness of 4 mils and
release of a new coated ductwork line. ProCoat™ and will meet or exceed 3,000
ProCoat Plus™ HVAC duct systems were first intro- hour salt spray test per
duced at AHR Expo 2017 in Las Vegas. Visitors were ASTM B117-97.
able to examine ProCoat’s smooth exterior and test its
durability firsthand. ProCoat products are immediately Desired colors are
available to North American’s construction industry. matched using the RAL
color system. Standard
ProCoat products are an alternative to PVC, PDS, ProCoat products are
PCD, and other precoated steel products. The coating coated on the outside
exhibits superior chemical resistance characteristics surface. ProCoat Plus
over precoated sheet metal alternatives. In addition, products are coated both inside and outside of the
ProCoat ductwork can be fabricated using industry ductwork and are recommended for laboratories,
standard welding methods, adding quality while main- pools, and similar corrosive environments.
taining aesthetic appearance and corrosion resistance.
Products are available in diameters up to 60-inch.
“As a manufacturer, our goal is to systematically ProCoat products are not limited to spiral round duct
reduce energy waste and increase performance systems. They can be fabricated in flat oval systems
while providing the finest quality of ductwork. With as well. Related accessories such as sheet metal
ProCoat, engineers will find the screws and band hangers can also be
product dynamic and consistent… coated to match.
perhaps something that is missing
when ductwork is painted at the With round and oval ductwork becoming
jobsite or fabricated from precoated more mainstream in exposed applications,
sheet metal,” said Dave Shaeffer, the Linx ProCoat and Safe self-sealing
Linx Industries’ president. systems offers specifying engineers the
solution for applications that demand both
ProCoat duct systems are delivered appearance and performance. To learn
custom coated and factory-direct. more, email engineering@li-hvac.com.

Linx Industries, Inc. | Tel: (800) 797-7476


www.li-hvac.com

input #33 at www.csemag.com/information


A DV E R T I S E M E N T

The Most Advanced


Lightning Protection System in the World
The Prevectron 3 ® is the most advanced lightning protection
system in the world today. The Prevectron® has a lengthy history
which boasts thousands of successful installations on high profile
structures all over the world. The Prevectron® has been tested
under real lightning conditions on five different continents as well
as numerous high voltage laboratories. The Prevectron 3 ® is the
world’s first UL Certified ESE lightning conductor (UL File E478687)
and conforms to multiple international standards.

The Lightning Innovation and Research Institute (LiRi) is an


integrated department of INDELEC (Inventor of the Prevectron® ).
This forward-thinking research team of highly skilled engineers
provides INDELEC with unparalleled R&D abilities. LiRi operates a
1.6 million volt High Voltage Laboratory capable of generating
electrical arcs several meters long in a highly controlled
environment. LiRi is among the largest lightning research centers
with regularly published articles, videos, and links to support
international research and global knowledge on lightning. LiRi is
dedicated to improving knowledge of lightning phenomenon,
physics, and lightning protection practices as well as the research
and development of new technologies like the OptiMax ® system in
the Prevetron 3 ®.

A lightning strike is the attachment between electrical energy in


the sky (a downward leader) and energy from the ground (upward
leader). One of the Prevectron’s unique features is its ability to
read the rate of change in the surrounding natural electric field.
During storm conditions this field increases rapidly as the energy
from the downward leader gets close to the ground.

The Prevectron is able to react to this rapid increase in the natural


electric field and produce a stronger upward leader synchronized
with the downward leader. Within the naturally occurring process
of a lightning strike a charge can form around the tip of lightning
rods which makes them less effective. The OptiMax ® system in
the Prevetron 3 ® neutralizes this charge so that the upward leader
is not only produced at a precisely synchronized time it is also
produced in optimum conditions.

Many attempts have been made to imitate the Prevectron® but it


has never been equaled.

800-628-2816 | sales@nlpcorp.com | www.NationalLightning.com


input #34 at www.csemag.com/information
A DV E R T I S E M E N T

Red-White Valve Corp. presents its new range of


Pressure Independent Control Valves (PICV)
9700 Series valves implement high-quality
technical features with a compact design.

• Simplified presetting without need for


complicated diagrams
• Rotating analog dial to allow easy setting
of desired flow regardless of changes of
pressure in the line
• Actuator capable of full stroke modulation
independent from preset

• Available in multiple connections (MNPT, FNPT


and Solder)
• Test points to allow measurement of differential
pressure across the valve
• Works with On-Off and Modulating (0-10V)
electrical Actuator
• Integrated Isolation Valve optional
• Operating ∆P range up to 58 psi
• 300WOG

Working conditions: Water 15°F - 260°F


below 32°F only for water with added antifreeze fluids
over 212°F only for water with added anti-boiling fluids
(Ethylene-glycolic and propylene-glycolic mixtures up
to 50% may be used)

9700 Series valves comply with the


Buy American Act and are constructed of
the following materials:
• Corrosion Resistant DZR Brass Body
• Springs and piston in Stainless Steel
• NSF approved EPDM Perox

Tel: 800-222-RWVC (7982) | Fax: 949-859-7200 | info@rwvcusa.com | redwhitevalvecorp.com


input #35 at www.csemag.com/information
A DV E R T I S E M E N T

Addressable Notification Provides


Safer, Smarter Protection
Addressable notification is innovative, game-changing technology
that’s helping SimplexGrinnell, now part of Johnson Controls, to
deliver safer, smarter protection. While addressable technology has
been used for many years for fire detection, we’re now leveraging
addressable notification to provide valuable benefits at every stage
in the life cycle of a fire alarm system, from design and installation to
operation and ongoing service.

• Flexible wiring architecture: The wiring architecture of our


SIMPLEX TrueAlert ES notification systems is very flexible, so more
appliances can be connected per circuit. This allows for more
efficient wire runs and makes it easier to correct wiring mistakes.
Wiring distances can be increased significantly, with
circuits supporting a larger number of appliances. The
flexibility of the wiring also means that fewer power
supplies, batteries and dedicated AC lines are required.

• Targeted emergency messaging: One of our latest


innovations is the introduction of addressable TrueAlert
ES fire alarm speakers with individual device control.
This technology provides the capability to deliver audio
messages to specifically targeted areas within a build-
ing. Each audio unit has its own address on the fire alarm
system and is supervised by the fire alarm panel.

This means the fire alarm panel can be programmed


to select which speakers are to be used and what
message will be played on them during emergencies.
This targeted audio paging capability enables the delivery
of critical,event-specific information exactly where it’s needed.

• Notification appliance self-testing: The revolutionary self-


testing capability of TrueAlert ES appliances enables testing to
be done through a SIMPLEX ES fire alarm panel, greatly reducing
interruptions to building occupants and business operations. Work
that used to take hours or even days can now be done quickly and
efficiently – and with virtually no disruption to building operations.

The self-test process takes just seconds to complete. It can be


initiated manually or programmed via the fire alarm control panel
to run automatically at a convenient time, eliminating the burden of
after-hours testing. Self-testing can reduce business disruption and
provide significant time and cost savings for your clients.

For more information, visit www.tycosimplexgrinnell.com


input #36 at www.csemag.com/information
A DV E R T I S E M E N T

User Driven, Purpose Built Designs:


Precision Cooling & Ultrasonic Humidification
The Data Center Experts
From Edge to Enterprise, from
wholesale to retail, from the smallest
IT closet to the largest hyperscale data
center, STULZ has a user driven,
purpose built solution ideally suited for
your needs.

The STULZ product range includes


traditional room cooling, high density
cooling, micro data centers, retrofit
solutions, modular containers, air
handling units with adiabatic cooling,
retrofit solutions, and ultrasonic
humidification. STULZ offers the
broadest range of chilled water and
direct expansion systems with Direct
and Indirect Free Cooling solutions. Micro Data Centers with optional
Liquid Cooling Solutions
The Everything Experts
STULZ CyberMDC is a complete IT infrastructure system,
STULZ provides solutions for many incorporating all the key components necessary for an efficient,
industries beyond data centers, reliable, and secure data-center-in-a-box. With the added benefit
including medical/hospital, agricultural of STULZ’ Chip-to-Atmosphere liquid cooling, STULZ is able to
(medical cannabis, humidor, etc.), provide cooling options ranging from small IT workloads to high
archival and clean room, laboratory density Edge data centers.
and research, commercial construction,
and industrial applications. Custom Indoor Air Handling Units
Small Space Systems STULZ Custom AHU’s are engineered to order solutions that are
STULZ offers multiple systems geared currently deployed in many of the largest data centers around the
toward small spaces, or in modular data world. Custom AHU’s are a prime example of how STULZ listens
centers with the potential for growth. to customers and delivers tailor-made solutions.
STULZ CeilAiR includes an expansive
Innovation through
range of ceiling mounted systems that
free up valuable floor space for rack Collaboration
systems. STULZ Mini-Space is a small Whether your need is solved with
floor mounted unit serving low density a standard pre-engineered product
applications, such as server closets. or you require a customized
solution, our engineers and product
specialists will work with you to
choose the right solution.

info@stulz-ats.com Joerg Desler


(301) 620-2033 President
www.stulz-usa.com Stulz Air Technology Systems, Inc.
input #37 at www.csemag.com/information
A DV E R T I S E M E N T

Thomson Power Systems introduces Mission Critical


Narrow Frame Medium Voltage Switchgear
Thomson Power Systems has launched their
new GCS2400 MV-ND, 5 and 15 KV Metal Clad
Switchgear system. This unique design features
significantly narrower widths with a flexible
modular concept and front cable termination
access, allowing customers to maximize floor
space. The GCS2400 MV-ND is certified to IEEE
C37.20.2. The compact construction of each
section measures 26” Wide, 97” High and
59”Deep, which is significantly smaller than
traditional MV Switchgear.

Electrical rooms in general are under constant


pressure to be reduced in size. Mission Critical
Applications such as Data Centers and Hospitals
place an even greater premium on floor space.

Where installation space for electrical distribution


systems is constrained the GCS2400 MV-ND is an
ideal choice. The unique front cable termination
access reduces the Switchgear installation foot
print providing engineers the freedom to locate
their switchgear anywhere in the electrical room
and get full utilization of available space.

Existing installations are also able to take


advantage of our new compact design.
Switchgear retrofits and upgrades present a
unique challenge to engineers. Limited space and
access can force less than ideal design decisions.

The compact design and front cable termination


access of GCS2400 MV-ND gives the owners of
existing installations, such as legacy data centers,
health care facilities, and water treatment and
pumping facilities the ability to access and utilize
the existing space more efficiently.

info@thomsonps.com | Tel: 604-888-0110 | www.thomsonps.com


input #38 at www.csemag.com/information
A DV E R T I S E M E N T

Important Breakthrough in VAV Diffuser Technology


Helios can be installed so that climate zones in separate
offices can be controlled individually. This means an
end to — forgive the pun — heated discussions about
thermostat settings. Ladies, put away those jackets and
scarves; gentlemen, you can let your sleeves down.

Tradition of Technical Innovation


Titus has, once again, engineered a game-changing
component in air distribution technology. Helios is unlike
any other diffuser in the market today. And because of
its clear economic and functional advantages, it’s likely
to quickly become an industry standard.

There’s never been anything quite like the new


Helios VAV Diffuser before. Powered by ambient The introduction of Helios means big savings
light, it solves a host of challenges for building for building owners and contractors, and
owners, architects, contractors and occupants.
also signals the end of the Thermostat Wars.
It saves money and increases the comfort of
building occupants. Let’s take a closer look.
Increased user comfort, digital accuracy, ease of
Each unit operates independent of any building installation and improved cost-efficiency make Helios
power source, so there’s no need for additional an important breakthrough
wiring. This alone can mean significant savings, in VAV technology. It’s
both during installation and subsequent opera- exactly what you’d expect
tion. Helios stores power derived from ambient from Titus, the leader in
light, and has the capacity to continue working innovative air distribution
even after several days in complete darkness. technology.
Additionally, the Helios VAV requires no additional
duct work — a huge benefit for any architect or
The Helios VAV diffuser is an AHR Expo
contractor engaged in a retrofit. Because there’s 2017 Innovations Award winner.
less installation construction required, the
innovative Helios is quicker and easier to install,
saving both time and resources.

The Thermostat Wars Are Over


With traditional office VAV systems, large
climate zones are often established, and this Digital accuracy and
means that groups of occupants have to make independent power
do with a single thermostat setting. Tradition- source make Helios
ally, men prefer a lower indoor temperature than a big cost-saver.
women, and that’s why we sometimes see men
in short-sleeved shirts working side-by-side
with female colleagues in jackets.

communications@titus-hvac.com | 972-212-4800 | www.titus-hvac.com/helios


input #39 at www.csemag.com/information
A DV E R T I S E M E N T

Cx-Series Custom Hydronic Air Handler


Fills a Gap with New Technology

Incorporating advanced green motor and


acoustics technology, the Cx-Series offers direct-
drive fans with brushless EC motors to reduce
energy consumption. Backward-inclined fan
blades reduce sound for quiet operation. Hot
water and chilled water coil customization let
designers match the exact needs of each project.

Using an online form, representatives can


quickly select a wide range of options in a robust casing.

We know that a one-size-fits-most solution doesn’t


meet the needs of everyone. At the same time,
one-off products can be expensive and often have
extended design and production lead-times. That’s
why Innovent® offers the Cx-Series, a custom
hydronic air handling solution with quick and
accurate selections in the design process and
reliable manufacturing lead-times.

The Innovent Cx-Series provides streamlined Taking advantage of modern technologies creates a superior alternative
design and construction for today’s fast-paced to a welded floor.
environment. Applications include chilled and hot
water air handling needs in healthcare, hospitality, An innovative breakthrough in construction offers
education, commercial, industrial and laboratories. distinct advantages over a conventional welded
floor. A durable protective coating over a sheet
The Cx-Series offers metal floor creates a waterproof, non-slip surface
a wide range of throughout the unit. This 2” basin offers true wash
energy-efficiency down construction. Removable panels provide
options in a robust, easy upgrade of components enabling 30+ years of
foam-injected, service life.
variable-aspect ratio
casing. An online From configurable to custom, Unison® Air Handling
selection webpage has the right solution for your next project. Unison
enables Unison reps has earned a reputation for expertise in energy
to submit a unit recovery and refrigeration. With Valent configu-
selection and receive rable packaged rooftops and Innovent custom air
design documents in handling equipment, Unison has the products that
a matter of minutes. today’s energy-efficient buildings require.
“The Innovent Cx series bridges the gap between
custom units and configured products for fast-
track, cost-sensitive projects,” says Jennifer Schroer,
Vice President of Unison Air Handling.

www.innoventair.com | sales@unisoncomfort.com | (612) 877-4800


input #40 at www.csemag.com/information
A DV E R T I S E M E N T

UV Resources Helps Boost HVAC Performance by 10-30%


Ultraviolet Germicidal Irradiation, or UV-C, is an incredibly effective and
affordable technology for keeping critical components of commercial
HVAC systems clean and operating to “as-built” specifications.

UV Resources has been a key driver in advancing this technology and


establishing modern sizing and efficacy software for its use.

Save 10-30%
HVAC system performance can begin to degrade within one year of
start-up. According to the 2015 ASHRAE Handbook—HVAC
Applications, UV-C reduces mold, biofilm and coil pressure drop, as
well as coil-cleaning. It further states that UV-C can increase airflow
and heat-transfer coefficients and reduce both fan- and refrigeration-
system energy use. Savings of 10-30% have been reported once
capacity is restored. And, UV-C equipment costs an average of less
than $0.15 per cfm.

“UV-C eliminates accumulated organic materials on HVAC/R


equipment to significantly improve airflow and heat-exchange
efficiency while providing cleaner, healthier, odor-free air.”

Large air handler solutions


The RLM Xtreme™ fixtureless UV-C lamp system delivers
high-output ultraviolet energy to irradiate coils and destroy
mold, bacteria and viruses in demanding and high-volume
HVAC environments.

Packaged rooftop units


The X-Plus™ NEMA 4X design is ideal for hard-to-access
outdoor and indoor HVAC equipment up to 30 tons, including
rooftop package units, through-the-wall or fan coil units.
The flexible system helps improve heat transfer, reduce
energy use, lower odor and maintenance, and “sustain”
AHU capacity while improving IAQ.

Rapid Roi
For one commercial building owner, an independent audit
documented a 47% increase in airflow following the
installation of UV-C. The ultraviolet energy lowered energy
consumption enough for the project to pay for itself in just
three-months—an impressive 90-day ROI.

Although UV-C is a relatively simple technology, many engineers and building owners are amazed that
something so simple can yield such significant savings. Learn more today!
Call UV Resources at 877-884-4822 or visit www.uvresources.com

877-884-4822 | info@uvresources.com
www.UVResources.com
input #41 at www.csemag.com/information
A DV E R T I S E M E N T

Innovative New Product Helps Insulate


Steel Frame Buildings
Varco Pruden’s new ThermaLift™ Insulation System combined with VP’s SSR clip offerings, lifts roof
allows steel framed building owners to achieve R-34, panels up to 7” above the secondary structural –
the highest R-value in the industry, using regular roll creating enough space for two layers of
roofing by “Literally raising the roof cavity so that blanket insulation.
you can double the amount of insulation capacity.”
according to John Brewer, Product Manager for VP offers four sizes of clips for varying insulation
Varco Pruden. thickness: 3½”, 4”, 4½” and 5” tall.

Varco Pruden, in conjunction with parent


company BlueScope Buildings North America,
owns its own Hot Box testing facility to confirm
the thermal achievement. VP’s SSR Roof meets
IBC-2015 and ICC-ES2527, as well as Factory Mutual
and UL-90 requirements.

Engineered to be installed above the building


structure, ThermaLift eliminates the need for
banding, and reduces installation time and costs
when compared to other alternatives. Additionally,
once the roof is installed, structural members are
accessible to other trades for attaching items such
as duct work and sprinkler systems.

Brewer explains that “With older roof systems, using


rolled insulation is impossible to meet the R-values of
future building codes. The ThermaLift™ System offers
an innovative approach for getting more insulation
under the roof.”

Thermal performance testing in accordance with


ASTM-C1363 has resulted in U-factors as low as
0.029. The result is a cost-effective roof system that
meets today’s and tomorrow’s more stringent
energy codes, including IECC 2015 and Canada’s Brewer pointed out that each ThermaLift package
NECB 2011 code. is custom engineered and made to order for that
specific building so that installation is swift,
Developed to work with Varco Pruden’s SSR and easy. ThermaLift is compatible with VP’s
(Standing Seam Roof) system, ThermaLift includes a PrisMAX ™ SL daylighting product, DuraCurb™ and
patented proprietary 5” x 48” insulation bridge to roof accessory items.
provide additional space for insulation between the
roof panels and the building structure. Made from For more information, visit www.vp.com and click
sturdy 22-gauge galvanized steel, the bridge, when on products.

901-748-8000
vpsales@vp.com
www.vp.com
input #42 at www.csemag.com/information
ADVERTISEMENT

Armacell: Innovations in Energy Efficiency


Armacell is a global innovator in foam technologies and the world leader
in the market for elastomeric mechanical insulation for chilled water
systems. As the inventors of Armaflex®, the most trusted brand in flex-
ible, fiber-free mechanical insulation, we have over 60 years of proven
expertise in expanded foam technology. Today Armacell is a leading
producer of closed-cell insulation for condensation control, reducing
energy waste and absorbing noise.

Armaflex for Chilled Water Systems - AP Armaflex tubes, sheets and rolls are ideal for controlling conden-
sation and ensuring long lasting thermal efficiency for chilled water systems. The closed-cell nature of the
material provides a built-in water vapor barrier, so it won’t wick moisture, doesn’t require jacketing indoors
and surface punctures won’t affect its performance over time. AP Armaflex products are GREENGUARD Gold
certified and made with Microban® antimicrobial technology to resist the growth of mold in the insulation.

Support You Can Trust - Our Technical Managers can answer questions about products or performance. We
have a team of Specification Managers to help write specs as well as conduct educational Lunch & Learns
for continuing education credits.
About Armacell - Armacell operates six manufacturing facilities
in the US and one in Canada.
info.us@armacell.com | 800-866-5638 | www.armacell.us
input #43 at www.csemag.com/information

cse201706_innovHlf_armacell.indd 1 5/17/2017 12:01:39 PM

ADVERTISEMENT

Solving Low Delta T Leveraging IoT


The Belimo Energy Valve is now an IoT device utilizing advanced cloud-based
technology to leverage captured system data providing energy savings and
the most efficient operation. The Energy Valve is a pressure independent valve,
which measures and manages coil energy by using an embedded electronic
flow meter, along with supply and return water temperature sensors. It is ideal
for water-side control of heating and cooling coils with programmable
maximum flow settings from 1.65 - 713 GPM in valve body size ½” to 6”.

• Delta T Optimization and Flow Setpoints provide recommendation which One Optimized Complete Solution –
can be updated remotely or automatically. Now Cloud Based.
• Performance Reporting graphically showing current and historical data of Discover all the advantages at
flow rates, energy usage, and Delta T. www.belimo.us or contact your
• Lifetime Data Access for future optimization. local Belimo Sales Engineer at
• Online Tech Support to assist you remotely. 800-543-9038.
• Software Updates provided for maximum productivity and reliability.
• Extended Warranty increased to 7-year with Belimo cloud connection.

In addition, the Energy Valve offers glycol monitoring assuring concentrations


meet design needs providing optimum efficiency and safe operation and
reduces operating cost. www.belimo.us
800-543-9038

input #44 at www.csemag.com/information


ADVERTISEMENT

Design On Demand™ Program Provides Customized Solutions


Bradley Corp.’s exclusive Design On Demand™ program offers
customized services and product solutions that are ideal for large or
small industrial applications in the most demanding environments.
With in-house engineering experience, system design consultation and
individualized services, Bradley’s qualified experts help design plumbing
systems according to each customer’s needs and project goals.
Bradley offers a complete range of efficient and reliable plumbing
products for tempering water and liquid processing. In effect, this
program is designed to provide customers with the most innovative and
dependable products for each application.

Design On Demand industrial plumbing products can be bundled or


pre-assembled to meet specific application requirements. Products
feature Bradley’s expansive line of Emergency Safety Fixtures featuring Halo™
technology, Enclosed Safety Showers, Keltech® Electric Water Tankless Heaters
and Navigator ® Thermostatic Mixing Valves – all of which are built for the
most challenging industrial situations.

For more information, visit www.bradleycorp.com/design-on-demand


or contact: designondemand@bradleycorp.com

input #45 at www.csemag.com/information

cse201706_innovHlf_bradley.indd 1 5/11/2017 10:07:03 AM

ADVERTISEMENT

A Global Force With Electronic Automation Components


Founded in 1931, CARLO GAVAZZI is a multinational electronics group
active in the design, manufacture and marketing of electronic and electrical
components for industrial automation and building automation.

With several ISO9001 and ISO14001 certified manufacturing and R&D


facilities throughout Europe and Asia, and dozens of sales offices spanning
the globe, you are assured that product support, service, and inventory are
only a phone call, email or mouse click away. CARLO GAVAZZI products
are developed and manufactured in full compliance with the most important
standard regulations, such as UL and CSA.

Typical customers are original equipment manufacturers (OEMs) of


packaging machines, injection molding (plastics) machines, agriculture machines, food and
beverage production, conveying and materials handling equipment, door and entrance
control systems, parking guidance systems, elevators and escalators as well as
heating, ventilation and air conditioning devices. System
integrators and distributors are typically the channels
we utilize to reach the market.
sales@CarloGavazzi.com | 847.465.6100
www.GavazziOnline.com

input #46 at www.csemag.com/information


ADVERTISEMENT

Unitary Controller Sequence of Operation Emulation on a PC


Contemporary Controls has just released its BASemulator which
replicates on a PC the operation of the company’s BAScontrol series of
open unitary controllers, thereby allowing sequence of operation (SOO)
verification without having the actual controller. Using a PC, specifying
engineers can now view the same program that will be used on the job to
verify that it meets the engineer’s intended sequence of operation. For a
contractor, programs can be developed, configured and then saved on
a PC for eventual downloading to the intended controller at the job site.

The BAScontrol series of BACnet/IP unitary controllers are built on


the Sedona Framework™. Sedona is an open-source technology that
facilitates component-oriented programming where components are
assembled onto a wire sheet, configured and interconnected, to create
applications. The BASemulator is free and joins the other free Sedona
tools such as the Sedona Application Editor (SAE) which allows for Contemporary Controls believes that
Sedona programming, and BASbackup which will save and restore all an open controller requires tools
BAScontrol configuration and programming files as a project. available to all without restriction.

Learn more at
www.ccontrols.com/controllers
input #47 at www.csemag.com/information

cse201706_innovHlf_contempCtrl.indd 1 5/11/2017 8:32:02 AM

ADVERTISEMENT

Delta Unveils World’s First Anti-Microbial Cooling Tower


Legionella, the bacteria that causes potentially fatal Legionnaire’s Disease,
and other strains of deadly pathogens that are hosted by some cooling towers,
have been substantially reduced by the development of a unique anti-microbial
HDPE material introduced by Delta Cooling Towers. According to the CDC, in
many of these cases Legionella is incubated and spread through water systems,
including the cooling towers that are essential items in commercial building
HVAC systems and industrial process cooling.

Delta has just launched a line of towers constructed of anti-microbial resin,


which is fully compounded into the base cooling tower material. The anti-
microbial resin and cooling tower fill contain additives that operate on a cellular level to continuously disrupt and
prevent uncontrolled growth of microorganisms and biofilm. Efficacy tests were performed by Special Pathogens
Laboratory, The Legionella Experts®.

The design of many cooling towers creates pockets where water may stagnate, another condition
that can lead to microorganism development. The stagnant water areas are prime breeding
grounds for Legionella. To avoid such problems, Delta’s cooling tower designs feature
a sloped basin and/or basin sweeper system. A 20-year
factory warranty provides evidence of the durability of sales@deltacooling.com
these HDPE cooling towers. 973-586-2201
http://deltacooling.com

input #48 at www.csemag.com/information


ADVERTISEMENT

NEW from ONICON - Configurable Energy Meter with Native BACnet®


The System-20 BTU Meter provides highly accurate thermal energy measurement
in water and water/glycol cooling, heating and condenser water systems. Energy
measurements are based on signal inputs from a pair of temperature sensors and
any of ONICON’s flow meters that are ordered separately.
The flexible design provides energy, flow and temperature data on the local display
via analog and pulse outputs, and over a BACnet MS/TP or MODBUS RTU network.
Three auxiliary inputs are also provided to totalize pulses from other devices and
communicate those totals directly to the network. Each System-20 is subjected to a
series of conformance tests using highly automated, computer controlled, advanced test equipment.
This comprehensive testing ensures that each meter is fully functional and meets published performance
and accuracy specifications. The absolute accuracy of conformance test equipment is directly traceable to N.I.S.T.

Features Include: Chilled, Hot, and Condenser Water System Applications for:
• Multiple Outputs, Flow Meter and • Central plant monitoring, campus energy monitoring and cost allocation
Temperature Sensor Options • Performance/efficiency evaluations
• Auxiliary Pulse Inputs • AHU and CRAC units for commercial office tenant billing
• Built-in Interval Data Logger • Solar, geothermal and ground-source
• Suitable for Water and Water/Glycol Solutions energy monitoring
• User-Friendly Interface Display
FLOW AND ENERGY MEASUREMENT
www.onicon.com | sales@onicon.com | 727-447-6140
input #49 at www.csemag.com/information

cse201706_innovHlf_onicon.indd 1 5/15/2017 9:07:12 AM

ADVERTISEMENT

Larger Condensing Storage Water Heaters


The TURBOPOWER® 96 gas-fired, fire-tube, storage water
heater features 96% thermal efficiency and a tank and removable
heat exchanger fabricated from pickle-passivated duplex
stainless steel. Product line offers a heat input range from 500 to
1600 MBtu and storage capacities from 250 to 1500 gallons.
A full 15 year warranty is provided with the tank.

Additional features include a touch screen operating control,


low NOx combustion, and PVC or polypropylene venting. The
efficiency gain is accomplished by adding a stainless steel
economizer to the time-tested, 2-pass, TURBOPOWER heat
exchanger (more than 30,000 installations since 1983).
Water heaters are ASME stamped for 150 psi and ETL listed to
ANSI Z21.10.3/CSA 4.3. From PVI Industries, LLC a WATTS brand.

800-784-8326 | www.PVI.com

input #50 at www.csemag.com/information


ADVERTISEMENT

FR-PANL Solutions Offer Protection and Low Installation Cost


The SEMCO FR-PANL™ is a National Fire Protection Association (NFPA)-
certified acoustical/thermal panel for HVAC system and power generating
enclosure, plenum, ductwork and structural wall barrier applications.

The FR-PANL™ has no screws through the panel joints, eliminating the
possibility of air and noise leaks while also reducing installation costs.
Available in a 4-inch thickness, these panels protect equipment inside
the enclosure from surrounding fires and also prevent fire spread to
surrounding environments when originating inside the enclosure.

The SEMCO FR-PANL™ is the Industry’s only certified fire protection


SEMCO’s FR-PANL
panel that’s also building code-compliant for use in structural, acoustical
and thermal applications. It has been preliminarily and successfully tested
under UL-263 “Standard for Fire Tests of Building Construction and Materials” using ASTM-E119 test criteria.
Its significantly low thermal transfer rate exceeds one hour of protection during fire events.

SEMCO panels are easy to install because of their quick-installing tongue-


and-groove design versus competing panel brands requiring excessive
field-applied fasteners.
www.semcohvac.com
sales.semco@flaktgroup.com | 573-443-1481

input #51 at www.csemag.com/information

cse201706_innovHlf_semco.indd 1 5/1/2017 12:04:18 PM

ADVERTISEMENT

Innovations in Industrial DC Power Systems


Driving availability up, cost down
SENS (Stored Energy Systems) has recently introduced three technologies that drive up
the availability of critical DC-powered industrial applications and drive cost down.
Ruggedized, modular rectifiers - The telecommunications industry has for years used
modular switch-mode rectifiers designed to operate in clean, indoor environments. Now,
with the advent of MicroGenius 2 rectifiers/battery chargers, SENS is delivering modular,
convection- cooled DC rectifiers for harsh industrial applications. These rectifiers operate
in parallel to scale power and provide N+1 redundancy. With N+1 redundancy, systems
such as the outdoor MicroCab 1500 can deliver extremely high availability at lower cost.
Modular rectifiers in MicroCab 1500
Battery life extending charging - Also in MicroGenius 2 is new charging technology that
up to doubles the life of flooded SLI batteries used for emergency generator starting, helps prevent sudden
battery failure, and ensures that batteries are fully charged in compliance with NFPA-110.
Low crank voltage alarm - The best predictor of a bad generator starting battery is low engine cranking voltage.
SENS has included another innovation - a low crank voltage alarm and crank history monitoring - in the MicroGenius 2,
giving users advance warning of an impending generator start failure.

SENS utilizes advanced signal processing technology to deliver these


innovations at essential no additional cost to the customer.
Call 1-866-736-7872 or visit www.sens-usa.com to learn more.
input #52 at www.csemag.com/information
Digital Edition
Exclusive Content
Visit www.csemag.com/digitaledition for exclusive content and for
more technical feature articles. The digital edition includes tablet-friendly
viewing (HTML5), headlines linking to longer versions, and an emailed link
as soon as it’s ready.

DE-1 The basics of daylighting


A design strategy needs to be considered in order
to provide optimal daylighting in a space.
BY ALEXANDER SASSOON, EIT, LEED AP BD+C, WELL AP

Visit www.csemag.com/research for a


variety of research studies, including: research

 Electrical and power systems


 Fire and life safety
 HVAC, BAS
 Lighting and lighting controls
 2016 MEP Giants
 Salary survey.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 77


The basics of
daylighting
A design strategy needs to be considered in order to provide
optimal daylighting in a space.

BY ALEXANDER SASSOON, EIT, LEED AP BD+C, WELL AP, P2S, Long Beach, Calif.

E
ffective daylight design in tasks and limit glare. Luminance is the
Learning buildings creates a comfort- measurement of task lighting, and Illu-
objectives able and productive environ- minance is a measurement of direct
 How to identify successful ment for occupants. Effec- glare. The unit of measurement for
daylighting design. tive daylighting can reduce luminance is a footcandle (fc), or lux,
 Explore the elements of energy use, but also must limit HVAC and the unit for illuminance is candelas
daylighting. loads. The U.S Green Building Council’s per square meter (cd/m2). Uniformity
 Learn how to integrate day- LEED rating system and the Interna- glare is also important, which is the ratio
lighting and lighting control tional WELL Building Institute’s WELL of luminances in adjacent spaces.
systems. Building Standard are two well-known People need between 5 and 10 fc for
rating systems that reward outstanding circulation and orientation in a space,
daylighting design. between 30 and 50 fc to perform most
visual tasks, and between 50 and 100
Daylighting design fc to perform difficult tasks involving
It’s important to first identify the ele- low contrast or high accuracy. People
ments of successful daylighting design. also need uniform light. The differ-
Buildings that are daylit provide ade- ence between lighting in task areas and
quate lighting to perform most visual adjacent areas (uniformity glare ratio)
should be close to 3:1, and the unifor-
mity glare ratio between task areas and
remote areas should be close to 5:1. At
no point should the brightest spot be
more than 10 times brighter than the
darkest spot, or it will become a source
of indirect glare.
There are two ways to bring daylight
into a building: from the walls or from
the ceiling. Once daylight is brought
into a building, it’s important to make
sure that glare wasn’t introduced.
Sidelighting refers to daylighting
from windows. Windows can bring
twice as much daylight into a space.
Figure 1: A closed-loop photosensor measures both natural and artificial light in the For example, if the top of the window
space. All graphics courtesy: P2S Engineering Inc. is 10 ft above the floor, daylight will

DE1 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


Figure 2: With multiple sources of day-
light and user needs, zoning lighting
controls is challenging.

penetrate up to 20 ft into the room. Window


daylighting has several advantages and
disadvantages. Windows allow occu-
pants to look out into the world, con- Figure 3: An open-loop photosensor measures only natural light in the space.
tributing to visual comfort. The LEED
V4 Indoor Environmental Quality credit and low-incident sunlight (such as at (IESNA) and others recommend auto-
calls for view glazing for 75% of the reg- sunrise and sunset) cause direct glare. matic shading, since occupants often
ularly occupied floor area. But, windows Reflections off of interior surfaces leave shades closed.
reduce insulation efficiency and allow cause indirect glare. Uniformity glare Reducing indirect glare hinges on
solar heat gain, resulting in increased occurs when illuminance varies greatly reducing the reflectivity of interior sur-
HVAC energy. Windows on all but the between adjacent areas of a room. faces. Selecting satin instead of glossy
north side of a building present glare The only way to limit direct glare is finishes, for instance, goes a long way
conditions unless controlled. to reduce incident light coming through toward reducing glare. Materials with
Toplighting is the application of day-
lighting from the ceiling. This includes
skylights, solar collectors, clerestories, People need between 5 and 10 fc for circulation and
or sawtooth structures. Toplighting can
typically supply light to an area equal orientation in a space, between 30 and 50 fc to perform
to the mounting height. A skylight
aperture mounted 20 ft above the floor most visual tasks, and between 50 and 100 fc to perform
can provide daylight to a 20x20-ft area
below the skylight. Skylights get more
difficult tasks involving low contrast or high accuracy.
sun exposure than windows, leading to
increased heat gain, but solar tubes can windows. Static exterior shading low light-reflectance values (LRV)
reduce this. Toplighting can penetrate reduces heat load and glare throughout reduce glare but also reduce daylight
deep into buildings, but it favors only the year, but it is not adjustable. Inte- penetration. Rotating highly reflective
1- or 2-story buildings and does not pro- rior shading, such as adjustable blinds surfaces is also important to reduce
vide views to the outdoors. or shades, also reduce direct glare and undesirable indirect glare. The WELL
After bringing daylight into the space, heat gain. Electrochromic glass also is Building Standard recommends orient-
reducing glare is just as important. a popular and affordable option that ing computer screens so they are per-
There are three types of glare: direct alters the visible transmittance of glar- pendicular to windows that are within
glare, indirect glare, and uniformity- ing by up to 90%. The Illuminating 15 ft of them and allowing a minimum
related glare. Unshielded light fixtures Engineering Society of North America LRV of 50% for furniture.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 DE2


The basics of daylighting
Daylighting design strategies occupied spaces be within 25 ft of view glazing with the right balance between
There are several design factors that windows. Balancing surface reflectance visual transmittance and solar heat-gain
can reduce uniformity-related glare. and minimizing opaque interior parti- coefficient is difficult and often requires
Providing multiple daylight sources can tions can also improve light uniformity. coordination between daylight and
balance daylight penetration and uni- There are other tradeoffs to bal- energy models.
formity. Examples of this are installing ance besides glare. Along with visible The location and orientation of glaz-
windows on different walls or installing light, infrared light also enters build- ing and the facade design can also
a window and a skylight. Reducing the ings, contributing to solar heat gain. significantly impact heat gain. North-
“lease depth”—the distance from the This can be an advantage in hot cli- facing glazing experiences lower heat
window to the nearest interior parti- mates, where it contributes to passive gain than south-, east-, or west-facing
tion—allows light to enter the space. design strategies. But the improper glazing. Since sidelighting penetrates
Feature 61 in the WELL Building Stan- application of daylighting in cooler the space based on the top-of-sill height,
dard requires that 75% of regularly climates can waste energy. Selecting the bottom-of-sill height can be raised
to reduce solar heat gain. Floor-to-ceil-
ing windows significantly contribute
to heat gain while providing limited
daylighting. Clerestories and skylights
bring daylight deep into spaces, but do
not offer outside views. Another way
to reduce solar heat gain is to provide
an exterior shade or awning above the
glazing.
To analyze daylighting beyond rules
of thumb, specialized software is neces-
sary. LEED and WELL Building Stan-
dard guidelines both prescribe software
modeling to receive credits for a day-
lighting strategy. There are two types
of analysis: discrete and continuous.
Discrete analysis simulates lighting at a
particular hour of the year. Continuous
analysis simulates lighting throughout
Figure 4: Light penetrates the space twice as deep as the window top-of-sill height. the year using 10 hours of each day.
The analysis then generates statistics on
annual performance based on defined
criteria.
Discrete analysis provides direct
luminance and illuminance values on
a surface. These values help to analyze
glare and daylighting potential. The
summer and winter solstices (June 21
and Dec. 21) and spring and fall equi-
noxes (March 21 and Sept. 21) are
common dates to use. These are days
where the sun is highest, lowest, and at
the midpoint in the sky, making them
ideal analysis days. Typical times are
8 a.m., noon, and 4 p.m., representing
both east, south, and west exposures.
These simulations give the designer
information about extremes, but pro-
Figure 5: Skylights should be spaced equal to the mounting height of the aperture in vide little about annual performance.
the space. Their upside is they can be performed

DE3 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


much faster than continuous-analysis difficult to interpret and have limited can maintain programmatic features
simulations. direct value to daylighting design. and allow fine-grain control of daylit
Continuous analysis provides sta- spaces. Individual fixture controls use
tistics to determine if there is glare or Integrating lighting control systems software to create digital zones. These
adequate daylight. To do this, continu- After developing a successful day- zones can then overlap with each other
ous analysis performs many discrete lighting plan for the project, integrat- and respond to sensor and user inter-
analyses. Simulations analyze condi- ing the lighting control system is the actions. Individual fixture controls also
tions during every hour between 8 a.m.
and 5 p.m. on a daily basis. In this case,
the continuous analysis is performing Successful daylighting also complements the
3,650 discrete analyses, which takes
some time.
There are three common types of lighting design and improves occupant comfort.
continuous analysis, with each serving
a different purpose: Reducing lighting power and heat gain with daylighting
n Daylight factor (DF) is the ratio also reduces energy use in the building.
of indoor to outdoor illuminance.
Because it measures relative
brightness, it is useful for analyz- next step. Without this, there will be often include their own daylight and
ing light uniformity. It is also easy very little energy savings and general occupancy sensors. This allows them to
to use DF to estimate illuminance occupant confusion. The two primary be independent but still controllable as
levels and validate using physical lighting control components for day- a group, giving users the best of each
models or existing buildings. lighting coordination are photosensors method.
and zoning. Successful daylighting requires close
n Spatial daylight autonomy (sDA) Photosensors measure light and con- coordination between architecture,
is the percentage of a space that trol light fixtures in response to avail- structural, mechanical, and lighting
can be daylit most of the time. For able daylight. There are two types of design. Without coordination, daylight-
instance, a value of sDA300/50 photosensors—closed-loop and open- ing is likely to upset both occupants and
at 55% means that at least 55% of loop. This refers to the type of feedback owners as well as waste energy. Success-
the area is lit to 300 Lux (28 fc) at control and impacts the installation ful daylighting also complements the
least 50% of the time. and zoning capabilities of the system. lighting design and improves occupant
Closed-loop photosensors measure the comfort. Reducing lighting power and
n Annual sunlight exposure (ASE) amount of light in a space, from both heat gain with daylighting also reduces
is the percentage of a space that artificial and natural lighting. This energy use in the building.
experiences too much light, makes it easy to set a specific minimum Artificial lighting uses around 25%
resulting in glare conditions. A light level, but the photosensor only of the building’s energy, and daylight-
value of ASE1000/250 at 10% controls one zone of lighting. Open- ing can reduce that use by up to 80%.
means that no more than 10% of loop photosensors only measure day- This limits solar gains and lowers
the space experiences more than light and can control multiple zones. HVAC loads that offset the internal
1000 Lux (93 fc) for more than This limits their ability to set a specific lighting load. Apart from energy sav-
250 hours/year. light level and relies on the space not ings, daylighting contributes to the
changing after commissioning. health and well-being of occupants. It
Other methods include useful day- Advanced lighting controls are nec- helps increase productivity and reduce
light illuminance (UDI) and averages essary to set up control zones that can absenteeism while providing high-
of discrete time analyses. UDI is the respond to both daylight and occupant quality light for task and ambient uses.
percentage of time when useful daylight needs. For instance, take a room that is Daylighting is valuable and necessary
is available. Averages of discrete time daylit from two directions and requires a for efficient building design.
analyses include annual footcandle lev- “projector screen” zone. A typical room
els or luminance levels. Both give more controller or panel-based lighting con- Alexander Sassoon, LEED AP BD+C,
granular information than the sDA and trol system requires at least three zones WELL AP is an electrical design engineer
ASE values, making them useful for for that room, and they may overlap. and project manager at P2S Engineering
accent daylighting. But they are more But if each fixture is its own zone, they Inc.

www.csemag.com Consulting-Specifying Engineer • JUNE 2017 DE4


MEDIA SHOWCASE FOR ENGINEERS

MOTOR
WattNode® Meter
Module for HVAC

PLUGS
Load Measurement

NEW
QUICKLY CONNECT
& DISCONNECT POWER

OFF
Button
Multi-measurement energy
metering on a single board
RS485 communications
Externally (instrument) powered Safety Shutter
For all (120-600 Vac) Services (on receptacle)
Single or three-phase
Designed for -30C to +80C Rated up to 200A, 75hp
Options for interface and
mounting, including DIN
4 Connector + Switch in 1 device
4 Maximizes Arc Flash Protection
1-888-928-8663 4 Minimizes PPE Requirements
sales@ctlsys.com meltric.com
www.ctlsys.com
800.433.7642 A company of MARECHAL ELECTRIC GROUP

Input #100 at www.csemag.com/information Input #101 at www.csemag.com/information Input #102 at www.csemag.com/information

Product & Literature Digest


Check out Consulting-Specifying Engineer’s

New E-Newsletters!
Providing helpful and specific information that’s
Why Should You directly applicable to your career

Filter Your Water?

NewsWatch: Data Centers


Access articles, news, videos, Webcasts, and other items focusing
on data centers and mission critical facilities, including electrical/
Scale formation reduces the heat transfer rate and power, HVAC, fire suppression, and other engineering topics.

increases the water pressure drop through the heat NewsWatch: Hospitals
This newsletter focuses on hospitals and health care facilities,
exchanger and pipes. In fact, one study has shown including codes and standards, electrical/power, HVAC, fire and
that .002" fouling will increase pumping needs by 20%. life safety, and other engineering topics.

The Best Engineered Water Filtering


Solution Always Costs Less
2 67 2 S . L a C i e n e g a B l v d . L o s A n g e l e s , C A 9 0 0 3 4 U S A
Sign up today!
( 8 0 0 ) 3 3 6 - 194 2 ( 310 ) 8 3 9 - 2 8 2 8 F a x : ( 310 ) 8 3 9 - 6 87 8
w w w. t e k l e e n . c o m info@tekleen.com www.csemag.com/newsletters
Input #103 at www.csemag.com/information Input #104 at www.csemag.com/information

cse201301_eNewslt_QTR.indd 1 1/14/2013 11:27:35 PM


78 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com
3.5" wide x 4.5" high
Future of Engineering
NEIL CHURMAN, Houston; and
ANDY JOHNSTON, Charlotte, N.C.,
7 Mile Advisors

How engineering firms can enhance value


with software and intellectual property
Enhanced technology will provide the tools to create more
value for engineering firms.

T
he exponential growth of com- Technology is already employed Assuming the former can be over-
puting power, increasingly in less complex service businesses come, engineering firms should
innovative software applica- to reduce manually intensive tasks, understand that a different set of com-
tions, and a relentless pursuit of automate easily defined transactions, petencies is needed to make the latter
streamlined project delivery has led and facilitate reuse of similar historic successful.
many engineering firms from the solutions. At the farthest end of the These firms need a dedicated staff
world of T squares and slide rules to technology spectrum, artificial intel- whose only job is to build, maintain,
suddenly resembling Silicon Valley ligence is seeking to replace human and sell the software. They also need
startups. Customers are constantly recollection, judgment, and estimation to have an appetite for a different
demanding better, faster, and cheaper in a scalable manner that delivers either business model that involves building
projects. As a result, engineering firms comparable or better results derived prototypes, piloting, gaining traction
have looked to software and intellectu- from highly trained people. The pri- through marketing, and then waiting
al property (IP) to gain a leg up. These mary advantage technology-based solu- for revenue to come in. There is little to
innovations, if properly harnessed, tions have over human capital is scale. no immediate value creation in a soft-
should lead to an increase in value if Delivery methods like virtual design ware-as-a-service business model, but
one of the below paths are followed. and construction will soon become the it is incredibly scalable and can add a
new norm for projects of all sizes, so high-margin, recurring revenue stream
Third-party applications or IP firms will need to adapt their methods to the typical project-based business
The first, and more traditional, route and become fluent in the processes and model of an engineering firm.
is leveraging a third-party application or tools necessary to compete. Tools like The takeaway is that firms that believe
internally developed IP to improve effi- Revit, coupled with contract structures IP has value beyond internal use will
ciency. If a firm can employ technology that enable and incentivize efficiency, need to think differently about their
to do their work better-faster-cheaper, can be tremendous value-creation approach. Software and IP should be
profit margins should improve. In the methods for firms in the industry. more than just a way to get projects out
If an engineer can produce two sets of the door.
plans in the same amount of time it used Monetizing proprietary software
to take to produce one, the firm’s profit The second, and less traveled, route Neil Churman is a director at 7 Mile
and loss statement should benefit. This, is to monetize a proprietary software or Advisors, where he advises architecture,
of course, is under the assumption that application externally by marketing it engineering, and construction industry
the revenue generated by each project to other industry partners. Many firms firms.
is constant, regardless of the amount of that have developed IP have struggled
time or cost to produce them. to find ways to monetize it, either Andy Johnston is a founding partner
Firms that work on a lump-sum or because they feared they’d lose the of 7 Mile Advisors. The investment
fixed-fee basis stand to gain the most advantage it afforded them to compete banking firm focuses on working with
from the improved efficiencies technol- for projects or because they lacked the providers of consulting and professional
ogy and IP can provide. ability to effectively market it. services.

80 Consulting-Specifying Engineer • JUNE 2017 www.csemag.com


PUSH YOUR
EXPECTATIONS

Low Harmonics
IEEE519-1992 Compliant

Power Factor
0.98 or higher

You can get more out of your


current system performance by
Greater Efficiency
integrating the new Z1000U 19% less system losses
Matrix Drive from Yaskawa.
Our new offering gives you
everything you need to maximize
operations and reduce costs. Power Regeneration
Reduced Energy Demand
Push your expectations.
Learn more at Yaskawa.com/
z1000umatrix.
Compact Size
65% Reduction
Z1000U Matrix Drive

Expanded Motor Control


IM/PM Motor Control

For more info:


http://budurl.me/YAI1038 input #53 at www.csemag.com/information

YASKAWA AMERICA DRIVES & MOTION DIVISION YASKAWA.COM 1-800-YASKAWA


The most versatile chiller. Anywhere.

OR HERE OR HERE

OR HERE EVEN HERE


WOULD BE
PERFECT HERE

REDUCED

HIGHEST
FOOTPRINT
TIERED
AVAILABLE PERFORMANCE
EFFICIENCY

Introducing the all-new AquaForce® 30XV from Carrier – the air-cooled screw chiller
that’s designed for tomorrow and fit for today.
Today’s cooling systems face a multitude of demands and limited spaces – and the same old
solutions just can’t cut it. That’s why Carrier developed the new 30XV with a range of available
benefits, tiered performance, innovative features and more. Plus, with industry-leading efficiency,
quieter operation, a wide operating range and quick restart capability it all adds up to the
versatility you need to meet almost any cooling demand, in any type of building, anywhere.

For more information, visit carrier.com/30XV


©Carrier Corporation 2017. A unit of United Technologies Corporation. Stock symbol UTX.

input #54 at www.csemag.com/information

You might also like