0.85% Moisture
The Dielectric Frequency Response test is used to assess 3.71 pS/m Oil Conductivity
10-8
the integrity of a transformer’s insulation system. The
Capacitance & Loss
a1 Phase
b1 Phase
c1 Phase
Mag 0.1
d1 Baseline
60m
50 500k
Frequency
Our client provided ABB with a list of seven Xfrmr# Temp Type Construction Oil Cond Moisture by Oil Moisture by DR
(°C) (pS/m) Sat (%wt) (%wt)
transformers. In each case, moisture in oil test
1 23 GSU Core 0.381 2.5 0.9
results indicated the need for oil processing and
2 28 GSU Core 0.492 1.8 0.9
drying. Working with the client, ABB performed 3 23 GSU Core 0.412 1.4 0.9
DFR testing and determined that only two units 4 23 GSU Core 1.34 2.8 0.7
actually required drying instead of seven. ABB’s 5 13 3-wdg Shell 1.5 * 1.2