Professional Documents
Culture Documents
ABSTRACT: In-situ testing of a lively floor is necessary for the design of an effective remedy. The ideal evaluation is to use
full experimental modal analysis, which requires substantial equipment including at least one floor shaker, to fully define the
natural modes of the floor system; however, it may not be possible, at least for an initial evaluation, because of cost. An
alternate testing procedure is to use a handheld spectrum analyzer with heel-drop and timed walking excitations. This paper
describes the procedure and compares results with experimental modal analysis techniques. The method is further evaluated
with results from a laboratory floor and an occupied building. The method is shown to be economical, convenient and effective.
possible walking paths near the area of concern, but is usually of a single degree of freedom system subjected to a harmonic
confined to one bay. forcing function with some modifications for occupant/walker
locations and effective mass. (It is noted that Reference [2]
4
Peak Accel. = 3.95%g
uses very a similar criterion, but rms rather than peak
Meas. Acceleration (%g)
X: 10.7 The laboratory floor shown in Figure 3 was used to verify the
0.04 Y: 0.0382
testing procedure. The floor was a single 9.14 m by 9.14 m
X: 14.25
Y: 0.03271
(30 ft by 30 ft) bay constructed and tested at the Virginia Tech
0.03 Thomas M. Murray Structural Engineering Laboratory in
2006. The 222 mm (8-3/4 in.) composite slab consisted of a
0.02 117 mm (4-5/8 in.) steel deck covered with 105 mm (4-1/8
in.) of 24 MPa (nominal 3.5 ksi) normal weight concrete. The
0.01 floor was supported only at the perimeter with W530x66
(W21x44) girders and W360x32.9 (W14x22) beams which
framed into W310x60 (W12x40) steel stub columns.
0
8 10 12 14 16 18 Temporary shoring was provided at the third points of the slab
Frequency (Hz) to limit the dead load deflections during the concrete
placement. The slab supported no nonstructural elements such
(b) Spectrum. as cladding or partitions.
Figure 1. Example heeldrop test result.
0.04 Deck Span
FRF Magnitude (%g/lbf)
X: 14.3
Y: 0.03092
X: 10.8
0.03 Y: 0.02815
W14
W21
0.02
0
8 10 12 14 16 18
Frequency (Hz)
Figure 2. Example FRF magnitude.
The acceptance criterion commonly used in North America (b) Section
is in the American Institute of Steel Construction/Canadian
Institute of Steel Construction Design Guide 11 Floor Figure 3. Laboratory floor.
Vibrations due to Human Activity, Chapter 4 [1]. The Prior to walking tests, the first natural frequency of the floor
criterion states that the peak acceleration due to walking was found to be 4.98 Hz. Walking tests were then performed
should not exceed 0.5% of gravity (5 milli-g’s) for offices and by measuring the acceleration at the center of the specimen
residences. The Guide provides a method to predict normal due to a single individual walking across the slab as shown in
walking acceleration, which is based on the resonant response Figure 4. Using a metronome, the intended walking speed
Proceedings of the 8th International Conference on Structural Dynamics, EURODYN 2011 1011
was 1.66 Hz or 100 bpm (4.98Hz/3 x 60 bpm) which was the differences are not as large because the input energy is spread
third subharmonic. The acceleration record with the over narrow bands instead of being a sinusoid at one spectral
maximum recorded ESPA is shown in Figure 5. The 2 sec. line. However, the differences in acceleration due to small
RMS acceleration is the dashed line and the maximum value step frequency variations are still often sizeable. (Occupied
is 0.753 %g. The ESPA is 1.06 %g, which is reasonable since building floors usually have much higher damping resulting in
EMA determined damping was only 0.5%. a much wider and shorter peak, creating much smaller
acceleration differences due to small step frequency errors.)
0.5
0.3
X: 5.025
0.2 Y: 0.1743
0.1
0
4 4.5 5 5.5 6
Figure 4. Walking tests. Frequency (Hz)
Figure 6. Laboratory floor FRF magnitude.
Measured Acceleration (%g)
walking across the 9.14 m (30 ft) laboratory floor. Note that 0.015
usually the test walking speed attempts to cause resonance by
matching the third or fourth harmonic to the dominant X: 1.688
bpm (0.05 Hz) and 4 bpm (0.067 Hz) error at the third and
fourth harmonics, respectively. Further, because a very
0.005
lightly damped system such as the laboratory floor or an
unoccupied building has a very narrow and tall FRF peak,
walking speed error can result in less than the theoretical peak 0
acceleration. For example, using a shaker and force plate, 1 2 3 4
measured accelerance (ratio of acceleration output to force Frequency (Hz)
input, both at mid-bay) FRF is shown in Figure 6. From this Figure 7. Step frequency identification.
plot, it is obvious that very small differences in sinusoidal
force input frequency result in very large differences in Figures 8 and 9 show the ESPA for all parallel and
acceleration response. For example, at 4.975 Hz and 5.025 perpendicular to the deck span walking tests, respectively.
Hz (a mere 3 bpm frequency difference), the accelerance The maximum acceleration occurred at 1.69 Hz, with the third
values are 0.364 %g/lbf and 0.174 %g/lbf, respectively. harmonic nearly matching the measured natural frequency of
Walking acceleration differences due to small step frequency 4.98 Hz. The absolute maximum accelerations were 1.06 %g
Proceedings of the 8th International Conference on Structural Dynamics, EURODYN 2011 1012
and 0.836 %g for walking parallel and perpendicular to the Figure 11 shows the heeldrop test waveform and spectrum
slab span, respectively. which indicates that the dominant natural frequency is 5.85
The maximum ESPA, 1.06 %g, exceeds 0.5 %g which is Hz and another natural frequency exists at 7.95 Hz, both of
the recommended peak acceleration limit for residence and which can be excited by one of the first four harmonics of the
office occupancies in Reference [1]. If the slab was used in an walking force.
actual structure, the damping would likely be 2.5% to 5% of
critical damping as compared to 0.5% which was determined
during EMA tests. Therefore, this slab would surely be 6.5m 6.5m 6.5m
adequate in an occupied building.
W610x174 W610x174 W610x174
0.8
0.6
0.4
0 W610x92
1.5 1.6 1.7 1.8 1.9 2 W610x82 W610x92
Step Frequency (Hz)
Figure 8. Laboratory floor ESPA vs. step frequency (all tests,
walking parallel)
Figure 10. UK Pharmacy partial framing plan
1.2 1
Peak Acceleration (%g)
1
0.5
0.8
0.6 0
0.4
0.2 -0.5
4 CASE STUDY
A large bay in the Second Floor of the University of Kentucky 0.03
College of Pharmacy building was also tested and those
results are used to further illustrate the testing and evaluation X: 5.85
Y: 0.01912
procedures. 0.02
The tested bay supports tables, very light book shelves,
computer desks, a small medication storage area, and no
partitions. The floor was constructed using a conventional 0.01 X: 7.95
Y: 0.007192
0.2
-0.2
X: 5.8
Y: 0.03065
0.03
0.02 X: 7.725
Y: 0.0161
0.01
X: 1.95
Y: 0.002823
0
2 4 6 8 10
Frequency (Hz)
(b) Spectrum
Figure 12. Walking test results for UK Pharmacy
5 CONCLUSION
It is shown that a simplified experimental program using only
a handheld spectrum analyzer and human induced floor
excitations can be used to evaluate floors for possible
annoying vibrations. The proposed procedure is economical,
fast, and causes only minor interruptions in an occupied
building.