Chilled Water
Precision Air Conditioners
Air Technology Systems, Inc.
STULZ-ATS is dedicated to providing innovative solutions Compact CW vertical, floor mounted air condi-
for critical temperature and humidity control needs. tioning units provide precision temperature and hu-
STULZ-ATS designs and manufactures specialized envi- midity control for computer rooms and other critical
ronmental control equipment for commercial, industrial areas where continuous 24 hourrs/day, 365 days/year
and custom military applications. SATS serves a diverse operation is required. Designed for front only ac-
marketplace - including telecommunications, information cess.
technology, medical, financial, educational, industrial
process and government contracts - utilizing world-class
Compact CW systems require minimal floor
SECTION - 1 SECTION - 4
Non-Proprietary Parts
- NYC MEA Approved (MEA-433-00-E)
Compact CW systems incorporate non-proprietary
- CSA Compliance
components where possible. Most major HVAC, refrigera-
tion and electrical distributors stock an exact model cross
reference or an alternate to most factory provided compo-
nents.
Warranty
- 2 Year Parts Standard
CCD-( )-CW
(Down-flow Air Pattern)
Down-Flow Air Pattern
1 2
Down-Flow Systems:
Top “Free” or “Ducted” Return with:
Bottom Discharge
Into Raised Floor
CC D-90 0-CW E
*
Up-Flow Down-Flow
Air Patterns Air Patterns
Standard Features
Model 300 600 900
SELECTED STANDARD FEATURES:
TEMPERATURE CONTROL
2-Way Modulating Chilled Water Control Valve Standard Standard Standard
3-Way Modulating Chilled Water Control Valve Optional Optional Optional
2-Stage Electric Reheating/Heating Standard Standard Standard
3-Stage Electric Reheating/Heating N/A N/A N/A
Hot Water Reheat Optional Optional Optional
Cooling &/or Heating Only (No Humidity Control) Optional Optional Optional
High Efficiency, Aluminum Fin/Copper Tube Coils Standard Standard Standard
HUMIDITY CONTROL
Electrode Canister Steam Humidifier Standard Standard Standard
Dehumidification Mode- Electric Reheat Standard Standard Standard
CABINET
Access panels shall be fabricated wires shall be color coded and shall
provide precision temperature and/or from heavy gauge steel and shall be be individually numbered at each
humidity control for computer rooms securely attached to the base and end for ease of service tracing. All
Guide Specifications
System Components ate in the Class 1 operating range. The high water alarm with built-in time
blower(s) shall be corrosion protected. delay shall provide an indication to
Chilled Water Cooling Coil:
The blower(s) shall be belt driven with change canister. The humidification
The coil shall be constructed of dual belts sized for 200% of the fan system shall require no cleaning main-
seamless drawn copper tubes, motor horsepower. The blower shall tenance during the cylinder life.
mechanically bonded to tempered have an adjustable base for belt ten-
aluminum fins with a fin design sioning and a locking system to prevent The humidifier shall discharge steam
for maximum heat transfer, and the motors from moving. The motor’s at 212°F, atmospheric pressure. It shall
mounted in a condensate drain drive sheaves shall have an adjustable be capable of operating with water
pan. The coil shall be designed for pitch to change the speed of the blow- in the range of 200 to 1500 microm-
under 500 ft/min face velocity. The ers. The motor shall be 1725 rpm and hos. The steam shall be introduced
water circuit shall be designed to shall have overload protection and a into the air stream after the chilled
distribute water into the entire coil minimum NEMA service factor of 1.15. water coil by a calibrated discharge
face area tube, designed to equally distribute
CW Control Valve:
the steam to the air stream without
HUMIDITY CONTROL: condensation. The humidifier shall be
provided with a manual adjustable
capacity control.
- Standard Equipment
Reheat / Heat
UP-FLOW:
(CCU-( )-( ))
The air conditioner shall be config-
ured for an up-flow air pattern with
free return air through front filtered
grille and conditioned supply air
through the top of the unit.
DOWN-FLOW:
(CCD-( )-( ))
The air conditioner shall be config-
ured for a down-flow air pattern
with free return air from the top
and conditioned supply air discharge
through bottom of the A/C into the
raised floor.
Notes
Air Technology Systems, In
OPTION ...........................................................page
Compact CW
Model CCD-900-CW
Guide Specifications
High Efficiency EC Fan shall automatically meter the flow
SELECTED OPTIONS of chilled water to the cooling coil
as needed for cooling load control,
Compact CW systems include the
C6000 Microprocessor Controller, the remaining flow shall bypass the
Electrode Canister Steam Humidi- cooling coil. A proportional signal
fier and Dehumidification Mode (0-10 VDC) is provided to the valve
with Electric Reheat/Heat for total Stulz-ATS Compact-Line Models ranging by the microprocessor controller. The
temperature and humidity control, rom 10-100 tons are available with the pressure rating of the valve is 600 psi.
as a standard. energy efficient EC Fans in our unique, Manual override capabilities shall be
However, these standard features energy-saving cabinet design. Refer to standard on the actuator drive.
can be deleted and/or substituted the SATS Compact CWE™ engineer-
with alternate features to allow ing manual for complete specifica-
you the flexibility to select the tions on Compact Chilled Water A/C Manual Control Override Switch
configuration best suited for your systems utilizing EC Fans.
application. A front panel mounted keyed switch
Filtration shall allow full fan operation and
ACCESSORIES 100% chilled water valve flow once
Compact CW A/C’s are available with engaged in the unlikely event of a
the following optional, high efficiency controller failure.
Adjustable Floor Stand
Filters ratings are based on dust spot Two individual main power input dis-
efficiency ratings based on ASHRAE Test connect switches shall be provided,
Standard 52-76. one for each incoming power source.
In the event the primary power fails
or a phase loss/imbalance occurs, the
Top Discharge Plenum Box
automatic transfer switch immedi-
(Upflow Units Only)
An adjustable floor stand shall ately transfers power to the second-
be provided to allow for ease of
ary power source. Once the primary
A 2- or 3-way plenum discharge box power has been restored, the transfer
installation of the A/C onto a raised shall be provided.The plenum box shall switch automatically shifts the power
floor. Floor stand height shall be include double-deflecting, adjustable load back to the primary power. The
adjustable. The Floor stand shall grilles. transfer time from one source to the
ship separately for field installation. other is user adjustable to allow stag-
3-Way Chilled Water ing or sequence restart of load.
Additional Floor Stand Control Valve
Options: In addition to the automatic transfer
Seismic Zone-4 Rated: switch function, the local controller
The adjustable floor stand shall be display shall indicate which power
certified rated for seismic zone-4 source has failed. This indication is
installation. a visual depiction that allows the
user to determine the status of the
Turning Vane: input source. This status can also be
A 3-way fully modulating valve shall conveyed thru the BMS serial com-
Turning vanes shall be factory in-
be factory piped and wired. The 3- munication link.
stalled to each unit’s floor stand.
way chilled water modulating valve
Firestat
light is available for a fast local notifi-
cation of available power sources. The
indication is on if power is available.
Smoke Detection
Notes
Air Technology Systems, In
“Index”
Category ...................................................page
Specifications:
Electrical:
Compact CW
Model CCD-900-CW
Performance Specifications
“CW” Model CCU/D-300 CCU/D-600 CCU/D-900
Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions
2-way (standard) - Modulating
Size / (Cv) 1”/(14 Cv) 1 1/4”/(20 Cv) 1 1/2”/(28 Cv)
Valve Pressure Rating - psi 600 600 600
Close-off Pressure Rating - psi 200 200 200
3-way (optional) - Modulating
Size / (Cv) 1”/(14 Cv) 1 1/4”/(20 Cv) 1 1/2”/(28 Cv)
Valve Pressure Rating 600 psig 600 psig 600 psig
Chilled Water Coil - Aluminum Fin, Copper Tube
Rows/Face Area (ft2) 6 / 15.2 4 / 27.6 6 / 27.6
Face Velocity, fpm 408 380 416
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower 5 Hp 5.0 Hp 7.5 Hp
CFM @ ext. st. press. 6,200 @ 0.3” 10,500 @ 0.3” 11,500 @ 0.3”
Drive Method Belt Belt Belt
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor Heat
ELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)
Heater Kw Rating (No. of Stages) 12 Kw (2-stg) 24 Kw (2-stg) 24 Kw (2-stg)
Total BTU/H w/ Evap Mtr Ht: 53,670 94,625 100,980
HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, 60°F WB (Optional)
BTU/H 115,809 110,995 117,290
Performance/Capacity Data
Model: 300-CW 600-CW 900-CW
NET COOLING CAPACITY - BTU/H @ 50°F EWT, 0% Glycol Solution (Includes motor heat @ std CFM & e.s.p. ratings)
80°FDB/67°FWB, 50% RH
High Flow Total 144,442 268,350 348,803
(10°F ∆Tw) Sensible 119,891 233,549 270,830
GPM / (pd. Ft.) 31.6 / 21.7 56.2 / 46.9 73.7 / 44.3
Med. Flow Total 119,756 255,766 334,492
(12°F ∆Tw) Sensible 108,911 224,906 263,705
GPM / (pd. Ft.) 22.2 / 12.6 44.7 / 31.6 59 / 30.2
Low Flow Total 88,565 236,187 317,517
(14°F ∆Tw) Sensible 88,565 211,689 254,925
GPM / (pd. Ft.) 14.6 / 7.7 35.6 / 21.9 48.2 / 21.8
75°FDB/62.5°FWB, 50% RH
High Flow Total 82,188 179,881 216,065
(10°F ∆Tw) Sensible 82,188 179,881 216,065
GPM / (pd. Ft.) 19.1 / 10.4 28.6 / 24.9 47.2 / 21.7
Med. Flow Total 69,750 159,297 193,312
(12°F ∆Tw) Sensible 69,750 159,297 193,312
GPM / (pd. Ft.) 13.9 / 7.4 28.7 / 15.9 35.7 / 14
Low Flow Total 62,744 134,513 165,332
(14°F ∆Tw) Sensible 62,744 134,513 165,332
GPM / (pd. Ft.) 10.9 / 6.1 21.1 / 10.6 26.5 / 9.5
72°FDB/60°FWB, 50% RH
High Flow Total 61,137 143,529 173,569
(10°F ∆Tw) Sensible 61,137 143,529 173,569
GPM / (pd. Ft.) 14.9 / 7.9 31.3 / 18 38.7 / 15.7
Cooling w/ Humidification
208/3/60 28.9 36.1 50 28.9 36.1 50 37.1 46.4 70
460/3/60 13.5 16.9 25 13.5 16.9 25 17.4 21.8 35
575/3/60 11.0 13.8 20 11.0 13.8 20 13.8 17.2 25
Dimensional Data
Index
(Drwg. #) MODEL TYPE .................................................... page
- Index
(CW-04) “Down-Flow” Air Pattern Configuration......... 5-5
(CW-01) CCU-300-CW
“Up-Flow” Vertical A/C
(as “Ducted” or with Opt. “2 or 3-way Plenum Box”)
- 10 Tons (“Up-Flow” Air Pattern Systems)
4” - 10” 6 5 7
4” - 10” 8 7 9
4” - 10” 10 9 11
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
12 - 24”
Dimensional Data
(CW-02) CCD-300-CW
“Down-Flow” Vertical A/C
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
(CW-03) CCU-600/900-CW
“Up-Flow” Vertical A/C
(as “Ducted” or with Opt. “2 or 3-way Plenum Box”)
- 20 to 40 Tons (“Up-Flow” Air Pattern Systems)
4” - 10” 6 5 7
4” - 10” 8 7 9
4” - 10” 10 9 11
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
12 - 24”
Dimensional Data
(CW-04) CCD-600/900-CW
“Down-Flow” Vertical A/C
(“Free Return” or with Opt. “Ducted Return”)
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26