Professional Documents
Culture Documents
Notes: d is effective depth = 261 mm (10.3 in.); a is shear span; As is area of tension reinforcement; φ is diameter of reinforcement bar (mm); Lf and Df are length and diameter of
steel fiber, respectively; b is width of specimen = 150 mm (6 in.); 1 in. = 25.4 mm.
Fig. 2—Test setup and instrumentations used for: (a) flexure; and (b) shear sets of specimens.
mixture. The values of the water-cement ratio (w/c) used in of 0.8 was used with the values of fck to compute the corre-
the concrete were 0.55 and 0.50 for the flexure and the shear sponding values of fc′. As expected, no significant difference
sets of specimens, respectively. Two different values of w/c was noted in the concrete compressive strength by adding
were used to get a variation in the fck values for the same the steel fibers into the concrete mixture. In some cases, the
grade of concrete. Thermo-mechanically treated (TMT) steel compressive strength of SFRC was slightly smaller than that
bars with a specified yield strength of 415 MPa (60.2 ksi) of the plain concrete.
were used as both longitudinal reinforcement and trans-
verse stirrups in the specimens (Table 1). Two numbers of Test setup and instrumentation
8 mm (0.31 in.) diameter bars were used at the compression Two different test setups were used for the testing of the
sides of all specimens to hold the shear stirrups at the proper flexure and the shear sets of specimens (Fig. 2). A four-point
locations. The reinforcement detailing in the specimens bending test setup was used for the flexure sets of specimens
was carried out as per Indian Standard IS:456-200030 code in which the equal magnitude loads were applied at two
provisions. End-hooked steel fibers 60 mm (2.4 in.) long and points located at a distance of one-third of the span length
0.75 mm (0.03 in.) in diameter (that is, fiber aspect ratio = from either support. In the shear set of specimens, a three-
80) were used in the SFRC specimens. The specified tensile point bending test setup was used in which a point load was
yield strength of steel fibers was 1100 MPa (159.4 ksi). applied at the midspan. This was carried out to simulate a
Standard cubes of size 150 x 150 x 150 mm (6 x 6 x 6 pure flexure action for the flexural sets of specimens and to
in.) and cylinders of size 100 x 200 mm (4 x 8 in.) were vary the value of a/d in the geometrically similar specimens.
prepared to measure the concrete compressive strengths as A recent study8 concluded that there would be no signifi-
per Indian Standard IS:516-195931 code provisions. At least cant difference in the behavior of SFRC specimens tested
four cubes and cylinders representing all batches of concrete using three-point and four-point bending tests. A mono-
mixtures used in a specimen were tested at 28 days of stan- tonic-increased load was applied to the specimens at an
dard curing. Table 1 shows the average values of concrete increment of approximately 10 kN until the ultimate resis-
cube compressive strengths fck and the values of cylinder tance of specimens was noticed, beyond which the crack
compressive strength fc′. Wherever the cylinder compres- propagation was considered as the control parameter. A load
sive strength data was not available, a multiplication factor cell of 2000 kN (440 kip) capacity was used to monitor the
TEST RESULTS
The main parameters investigated in this study are: 1) load
versus midspan displacement response; 2) ultimate resis-
tance; 3) ductility response; 4) crack propagation/failure
mechanism; and 5) state of strain in tension reinforcement
bars of the specimens. A detailed discussion on the observed
behavior of the flexure and shear sets of specimens is
provided in the following sections.
Load-displacement response
For the flexural set of specimens, the observed values
of flexural resistance Mu are normalized with respect to a
factor fckbd.2 As shown in Fig. 3(a), the normalized flex-
ural strengths (Mu/fckbd2) of the SFRC specimens with M20
grade concrete were higher than that of the corresponding
RC specimen. For the SFRC specimen (M20-F-0.50) with
a fiber content of 0.5%, the maximum value of Mu/fckbd2
was noted as 0.23. All the SFRC specimens with M20
grade concrete exhibited a more extended post-peak soft-
ening branch as compared with the RC specimen. Similar
load-displacement behavior was also noted for the flexural
set of specimens with M25 grade of concrete, as shown in
Fig. 3(b). The maximum value of Mu/fckbd2 was approxi-
mately 0.25 for the SFRC specimen (M25-F-1.00) with a
fiber content of 1.0%. Although a higher percentage of
longitudinal reinforcement was used in the flexural set of
specimens with M25 grade concrete, no significant increase
in the normalized flexural strength was noticed in the SFRC
specimens with the increased fiber contents. A more stable
post-peak behavior with the higher residual flexural strength,
however, was observed in both cases with the increase in the
fiber content due to the better fiber-bridging action.
For the shear set of specimens, the shear resistance Vu
values at different midspan displacements are normalized
with respect to a factor fck bd . As shown in Fig. 3(c), the
ultimate shear strength of SFRC specimens was increased Fig. 3—Normalized load-versus-midspan displacement
with the increase in the fiber content. The maximum value response of: (a) flexure set (M20); (b) flexure set (M25); and
of normalized shear strength (Vu / fck bd ) was noted as 1.00 (c) shear set of specimens. (Note: 1 in. = 25.4 mm.)
for the SFRC specimen (M20-S-1.25) with 1.25% fiber imen. This observation also justified the recommendations
content. The SFRC specimen (M20-S-0.75) with 0.75% of ACI 318-0811 which states that a minimum amount of
fiber content exhibited a very negligible post-peak response, 0.75% of end-hooked steel fibers should be used to replace
indicating its brittle behavior. With the increase in the fiber the shear stirrups to achieve the same shear strength as the
content, a better post-peak residual strength response was conventional RC flexural members. This study, however,
noted in the SFRC specimens. The RC specimen (M20-S- shows that a minimum of 1.0% fiber content should be used
0.0) showed a large post-yield ductile behavior due to the to achieve a ductile behavior before the shear failure of
presence of adequate shear stirrups at a spacing of 120 mm SFRC members without shear stirrups.
(4.7 in.) on centers throughout its length. Although the shear
stirrups were completely eliminated in the SFRC speci- Ultimate load-carrying capacity
mens, the normalized shear strength values were nearly Table 2 summarizes the observed values of peak load
equal to or higher than that of the corresponding RC spec- carried by the test specimens. In all cases, the addition of
Note: vu = Vu/bd.
steel fibers increased the ultimate resistance of the specimens. Table 3—Displacement ductility response of test
The maximum value of the ultimate flexural load carried by specimens
the SFRC specimen with 1.0% fiber content and M20 grade
Specimen type Name of specimen Ductility
concrete was 192.0 kN (42.3 kip), which increased to a value
of 294.5 kN (64.9 kip) for the corresponding specimen with Flexure M20-F-0.00 3.4
M25 grade of concrete. In the shear sets of specimens, the Flexure M20-F-0.50 5.8
maximum value of ultimate resistance was noted as 218.0 kN Flexure M20-F-1.00 5.6
(48.1 kip) for the SFRC specimen (M20-S-0.75) with 0.75%
fiber content. For a constant value of the shear span-depth Flexure M20-F-1.50 4.6
ratio and fiber content, the normalized ultimate shear stress Flexure M25-F-0.00 4.3
(Vu / fc′bd ) was found to be higher for the specimens with Flexure M25-F-0.50 9.3
the high grade of concrete. An increase in the percentage
Flexure M25-F-1.00 9.1
of longitudinal reinforcement by 32% in the flexure sets of
specimens increased the normalized shear stress values by Flexure M25-F-1.50 7.8
approximately 35%, even if a larger spacing of shear stirrups Shear M20-S-0.00 5.1
was used. Table 2 also shows the failure modes of all test
Shear M20-S-0.75 1.0
specimens. Although the RC specimen (M25-F-0.00) with
M25 grade of concrete failed in shear indicating the inade- Shear M20-S-1.00 3.7
quacy of shear stirrups, the addition of a minimum of 0.5% Shear M20-S-1.25 1.9
fiber content changed the failure mode from (brittle) shear to
(ductile) flexure. All SFRC specimens without shear stirrups approximately 120% compared with the RC specimen. The
failed in shear, as expected. SFRC specimens with 1.5% fiber content showed a slightly
smaller value of ductility compared with the specimens with
Displacement ductility response the fiber content of 0.5 or 1.0%. This can be attributed to the
Displacement ductility is computed as the ratio of the uneven distribution of fibers in the concrete matrix because
displacement at which the load-displacement response devi- of the reduced workability in case of the higher dose of
ates from the approximately linear response to the displace- steel fibers. Thus, a fiber content of 0.5% might be suffi-
ment corresponding to the sudden loss of the load-carrying cient to enhance the displacement ductility of SFRC spec-
capacities of the test specimens. Table 3 summarizes the imens having the shear stirrups throughout their lengths.
computed values of displacement ductility of the speci- In the SFRC members without shear stirrups, however, a
mens. The ductility values were significantly increased for minimum fiber content of 1.0% is required to achieve the
the flexure set of specimens due to addition of steel fibers ductile behavior (Table 3).
in the presence of shear stirrups. For the specimens with
M20 grade of concrete, the ductility value was increased by Crack propagation and failure mechanism
70% for the SFRC specimens as compared with the corre- The first vertical (flexural) crack in the RC specimen
sponding RC specimen. For the specimens with the higher (M20-F-0.00) was noticed at the midspan at a load level
concrete compressive strength and the higher (approxi- of 40 kN (8.8 kip). As the load magnitude was increased,
mately 30%) longitudinal reinforcement ratio, the maximum several flexural and shear cracks were noted in the spec-
increase in the ductility values for the SFRC specimens was
ANALYTICAL PREDICTIONS
As discussed previously, several models and design
Fig. 7—Crack propagation and failure mechanisms in shear
guidelines are available in the literature to estimate the shear
sets of specimens.
capacity of SFRC beams. Some models (Type 1) consider the
contribution of fiber resistance and the concrete contribution strengths of the shear sets of SFRC specimens. Table 4
independently, in a way similar to the stirrups improving the summarizes various models and the related expressions used
shear capacity of conventional RC members, to predict the to predict the shear strength. Most of these selected models
shear strength of SFRC members. Other models (Type 2) fall under the Type 1 category. Table 5 shows the ratio of the
assume that the addition of steel fibers directly modifies shear strengths predicted using these models to the observed
the concrete strength in flexure, shear, and tension. Both values for the shear sets of specimens. The predicted values
these models include several parameters, such as concrete of shear strength of the SFRC specimens were in the range
compressive strength, shear span-depth ratio, percentage of of 65 to 110% of the observed values. The model proposed
longitudinal reinforcement, type of fiber, amount of fiber by Khuntia et al.18 provided a more conservative result,
content, and fiber matrix bond strength. A model developed whereas the shear strengths values predicted using the model
by Dinh et al.25 considers the value of flexural strength of proposed by Kwak et al.3 were much closer to the experi-
standard ASTM beams at a target crack width to estimate mental values found in this study. A maximum difference
the shear strength of SFRC members. Both types of models of 15% was noted between the predicted and the observed
are used in this study to predict the shear strength of SFRC values of shear strength for the SFRC specimen with 0.75%
specimens without stirrups. fiber content. For the SFRC specimens with higher fiber
content, however, this difference was less than 5%. It should
Comparison of observed values with be noted that the model proposed by Kwak et al.3 takes
predicted values several parameters into account, such as fiber-matrix bond
Seven different models proposed by various stress, fiber fraction, shear span-depth ratio, and percentage
researchers2,3,13,14,18,23,25 were used to predict the shear of longitudinal reinforcement.
Mansur et al.13 Vu = 0.16 fc′ + 17.2ρ(Vd /M ) + σ tu bd; M/V = a-d for a/d > 2.0; df = 1 for end-hooked fibers; σtu is FRC
2
(Type 1) post-cracking tensile strength; τ is fiber-matrix bond stress
σtu = 0.41τF; F = dfVfLf/Df; τ = 0.68√fc′ MPa
3
Narayan and
Darwish2
{ }
′ + 80ρ(d /a ) + vb bd ;
Vu = e 0.24 fspfc
fcuf = fiber-reinforced concrete cube strength; e = 1 for a/d > 2.8
(Type 1) ′ = 0.7 + F + fcuf / (20 − F ) ; vb = 0.41τF; τ = 4.15 MPa
fspfc
1/ 3
Ashour et al.14 d
Vu = 2.11( fc′) + 7F ρ
1/ 3
4 a
bd —
(Type 1)
Khuntia et al.18
5 Vu = ( 0.167e + 0.25F ) fc′bd e = 1 for a/d > 2.5
(Type 1)
d
1/ 3
Kwak et al.3 ′ 2 / 3 ρ + 0.8vb bd ; vb = 0.41τF; τ = 4.15 MPa;
Vu = 3.7efspfc
6 a e = 1 for a/d > 3.4
(Type 1)
′ = 0.7 + F + fcuf / (20 − F )
fspfc
Dinh et al.25 Vu = 0.13Asfy + b(d – c)σt ; c = 2M/(0.85bh√fc′); As is area of tension reinforcement; fy is yield strength of rein-
7
(Type 1) σt = 2M/0.9bh2 forcement; M is maximum moment in ASTM beam testing
Fig. 8—State of strain in tension reinforcement bars at midspan of: (a) flexure; and (b) shear sets of specimens. (Note: 1 kN =
0.220 kip.)
Relationship between fiber content and shear [12 in.]) to eliminate the size effects, if at all exists. The
strengths of SFRC specimen measured shear strengths Vu of test beams were normalized
Considering the large variation in equations proposed with respect to their corresponding √f¯c′bd values. Figure 9
by several researchers, an effort was made in this study to shows the relation between normalized shear stress (vu/√fc′)
establish a correlation between the fiber content and the and the fiber content for both the medium-scale and large-
shear strengths of the SFRC specimens using the test results scale beams. The increase in fiber content in the beams
as reported in the literature.2,3,13,20,25,32-37 A total of 84 RC leads to the increase in the normalized shear stress. For the
and SFRC beams (including these research findings) without fiber content higher than 1.0%, however, the percentage of
shear stirrups were used in this evaluation. Various proper- increase in the normalized shear stress was little higher for
ties of these beams considered are as follows: 1) shear span- the medium-scale beams as compared with that for the large-
depth ratio (a/d) ≥ 2.5; 2) longitudinal tension reinforcement scale beams. Figure 9 also shows the mean μ and mean μ +
ratio ρ ranging between 1.2 and 4.5%; 3) concrete cylinder standard deviation σ values of the corresponding data set.
strength fc′ varied from 20.0 to 60.0 MPa (2.9 to 8.7 ksi); 4) Using a curve-fitting procedure, a best-fit line was drawn
hooked steel fibers in volume fractions Vf varied from 0 to joining the mean values of each data set for fiber content.
1.5%; 5) fiber tensile strength fu ≥ 1030 MPa (150 ksi); and The correlation factor R2 values were greater than 95% in
6) fiber length-diameter ratio (Lf/Df) varied from 55 to 100. both cases. Thus, the relationship between the average
All these data points were divided into two categories of test shear strength and the fiber content of SFRC beams can be
specimens based on their effective depth d, namely, medium expressed as follows (in SI units)
scale (d < 300 mm [12 in.]) and large scale (d ≥ 300 mm
(
Vu = 0.251 + 0.173V f + 0.069V f 2 ) fc′bd
(1)
is necessary;
3. Most of the existing models available in the literature
(for d < 300 mm [12 in.]) to predict the shear strengths of SFRC members without
shear stirrups give a conservative or reasonable estimate of
the shear strengths. For the SFRC beams considered in this
(
Vu = 0.202 + 0.377V f − 0.113V f 2 ) fc′bd
(2)
study, the predicted values of shear strength are in the range
of 65 to 110% of the observed values; and
(for d ≥ 300 mm [12 in.]) 4. Two simple expressions relating the fiber content to the
shear strengths of SFRC members are derived using a large
The aforementioned equations use only a single vari- set of test results for both medium-scale and large-scale
able, that is, fiber volume fraction Vf to compute the shear beams. A good correlation (R2 > 95%) exists between the
strengths of SFRC beams. Due to the limited test data avail- shear strength and fiber content for members with normal-
able for the SFRC beams with 2% fiber content, the correla- strength concrete (that is, fc′ < 60 MPa [8.7 ksi]).
tions are established only up to a fiber content of 1.5%,
a value regarded as the upper limit in the practice. These AUTHOR BIOS
equations are valid for the beams with the normal-strength ACI member Dipti Ranjan Sahoo is an Assistant Professor in Depart-
concrete (that is, fc′ < 60 MPa [8.7 ksi]). It should be noted ment of Civil Engineering, Indian Institute of Technology (IIT), Delhi,
India, and was formerly a postdoctoral Fellow in the Department of Civil
that although the fiber geometry may control the overall Engineering at the University of Texas at Arlington, Arlington, TX. He
behavior of the SFRC beams due to the different fiber- received his PhD in civil engineering from IIT Kanpur, India. His research
matrix bond characteristics, these equations provide an interests include fiber-reinforced concrete, seismic behavior of structural
members, and seismic strengthening of structures using passive energy
approximate estimate of the average value of shear strength dissipation devices.
to be used in the design process.
Abhimanyu Sharma is a Researcher in the Department of Civil Engi-
SUMMARY AND CONCLUSIONS neering, Indian Institute of Technology (IIT), Delhi, India, where he
received his BTech in civil engineering. His research interests include
A series of 12 RC and SFRC beam specimens were tested behavior of fiber-reinforced concrete structures.
under monotonically increased loading. The effect of several
parameters, such as fiber content, percentage of longitudinal ACKNOWLEDGMENTS
reinforcement, amount of transverse stirrups, shear span- The authors wish to express their gratitude to Bekaert Steel Wire Co.
for the donation of the steel fibers for this research. The help and support
depth ratio, and compressive strength of concrete on the received from the UG students (Abhishek, Pawan, and Sidhant) and the labo-
overall behavior of beams was studied. Based on this study, ratory staff of Structural Engineering Section, Civil Engineering Depart-
the following conclusions can be drawn: ment, IIT Delhi is greatly appreciated. The funding received from Ministry
of Human Resources Department (MHRD), India, is highly acknowledged.
1. The addition of steel fibers enhances the flexural strength
and the ductility of the SFRC members with sufficient shear