SCHEDULE OF QUANTITIES FOR FIRE FIGHTING SYSTEM

PROJECT : PROPOSED MAPSKO CASABELLA AT GURGAON. (Tower - A : For Ground and 24 upper floors)

RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
1 Supply & erection of ISI marked portable fire
extinguishers, wall mounted type, wall brackets
complete in all respect as per standard item with all
accessories, delivery hose & nozzle whereever
required, including fixing on walls as per the directions
of Engineer-in-charge.

(MAKE : Minimax / Cease Fire / Safex / Padmini /


Newage)

Water CO2 gas cartridge type. 9 Lt.capacity (IS:940) 26 NOS 1700.00

CO2 gas type. 4.5 kg. Capacity (IS:2878) 26 NOS 5700.00


2 Supply, erection and testing of ISI marked ERW M.S.
pipes (Class C - heavy duty) and specials etc. (as
per IS:1239 for upto 150 mm dia and IS:3589 for 200
mm and above) for above ground laying for hydrants
and sprinkler system including transportation of
materials upto the worksite, cutting the pipes to
required length, edge preperation, welding, fixing /
erection of pipes including specials i.e. bends, tees,
reducers, flanges, expansion joints and bellows
wherever required, washers, nuts, bolts etc. in proper
position including all supports. jointing by welding,
aligning the pipe line, painting with two primer coat by
zinc chromate primer and two coats of synthetic
enamel fire red colour, providing tapping for pressure
gauges and for other instruments etc. Hydrostatic
testing of system as specified, flushing & cleaning by
water etc. complete as per drawings & direction of the
Engineer-in-charge.

The pipes and accessories will be provided with all


type of supports (Maximum Support spacing = up to
25 mm dia @ 2 m, 32 mm to 100 mm dia @ 2.5 m,
150 mm & above dia @ 3 m) by minimum 3 mm thick
G.I. clevis / sprinkler hangers / clamps / Tie rod
supports with G.I. nuts, bolts, anchor / dash fastner
and washer for hydrant / sprinkler piping, for 100 &
150 mm dia pipe the support will be through 50x50x6
mm painted / pre galvanized MS angle iron along with
G.I. U clamp, nuts, washers, anchor fasteners etc as
the case may be.

The quoted rates shall also include for making holes in


masonry / RCC slab, wall, chases in wall, providing
sleeves in RCC wall & slabs whereever required &
making good the same by sealing the opening to
original conditions. The cost of sleeve will be as per
seperate item.

Fire Protection Page 1


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
upto 40mm dia. pipe threaded fittings and threaded
joints shall be provided and for 50mm dia & above
pipes welded joints shall be used. The forged fittings,
G.I. / M.S. (IS:1239-2) or Malleable Iron (IS : 1879) or
Ductile iron fittings shalll be heavy duty suitable to
withstand at least a pressure of 150% of maximum
working pressure with minimum of 15kg/cm2..

(Pipe make : Jindal (Hissar) / Bharat / Prakash Surya)

(Fitting make : Zoloto / UNIK / VS / BM / jainsons)

25 NB (IS: 1239, 4.0 mm thick) 1800 M 280.00

32 NB (IS: 1239, 4.0 mm thick) 350 M 350.00

40 NB (IS: 1239, 4.0 mm thick) 425 M 400.00

50 NB (IS: 1239, 4.5 mm thick) 425 M 465.00

65 NB (IS: 1239, 4.5 mm thick) 550 M 605.00

80 NB (IS: 1239, 4.8 mm thick) 225 M 750.00

100 NB (IS: 1239, 5.4 mm thick) 75 M 1070.00


150 NB (IS: 1239, 5.4 mm thick) 175 M 1525.00
3 Same as in item above but of G. I. Class B - medium
duty for drainage pipe.

50 NB (IS: 1239, 3.6 mm thick) 30 M 470.00

80 NB (IS: 1239, 4.0 mm thick) 75 M 720.00


4 Supply & installation of ISI marked single headed 63
mm dia. Stainless steel Hydrant Valve, 80 mm dia
flanged inlet with 63 mm female instantaneous outlet
confirming to IS : 5290 on the fire wet riser/down
comer, including making 80 NB pipe connection with
riser, fixing the landing valves in proper positions,
including supply of nuts, bolts, gaskets, caps, chains
etc. testing the hydrant and completing the work in all
respect as per directions of the Engineer-in-charge.
(MAKE : Newage / Safeguard / Padmini )

26 NOS 7800.00
5 Supply & fixing in position ISI marked cast iron double
flanged butterfly valves (PN 1.6 MPa) as per
IS:13095, with SS disc, shaft, seating rings, nitrile
rubber lining, internal fastening, nuts, bolts including
transporting to worksite, 3 mm thick rubber gaskets
etc. including testing, Complete as per drawings &
directions of the Engineer-in-charge.

(MAKE : Kirlosker / IVC / Zoloto / Venus / Audco /


Advance / AIP)

50 MM NB 25 NOS 2955.00

100 MM NB 25 NOS 5090.00

150 MM NB 1 NOS 8875.00

Fire Protection Page 2


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
6 Supply & fixing in position cast iron body double flange
dual plate wafer type check valve (NRV) (PN 16)
with SS 304 plates, hinges, pins, springs, nitrile
rubber lining, including transportation to worksite,
supply & fixing SS nuts, SS bolts, 3 mm thick rubber
gaskets, complete with testing as per direction of the
Engineer - in - charge.

(MAKE : Kirlosker / IVC / Zoloto / Venus / Audco /


Advance / AIP)

150 NB 1 NOS 9355.00


7 Supply, fixing, testing & commissioning of 20 mm bore
and 30 meter long hose (high pressure rubber braided
hose pipe as per IS:444) and hose reel suitable for
10 kg/sqcm operating pressure for first aid fire fighting
conforming to IS : 884, with 180o full swing drum, fixing
brackets, 5 mm dia shut off Stainless steel nozzle,
connecting directly from the riser through 40 mm dia.
MS (Class C) pipe with sockets, elbows, nipples,
40x20 mm reducer, 20 dia pipe, 20 mm dia. hand lever
operated isolating ball valve, etc. including providing
operating instructions on a metal plate and fixing it
near hose reel. The system shall be complete in all
respects as per drawings and directions of Engineer-
in-charge. (MAKE : Newage / Safeguard / Padmini)

26 NOS 8290.00
8 Providing Stainless steel ISI marked 63 mm. dia.
male Instantaneous pattern short branch pipes with
20 mm dia. Nozzle as per IS : 903, suitable for 10
kg/sqcm operating pressure and suitable for
interconnections to hose pipe coupling as required.
(MAKE : Newage / Safeguard / Padmini)
26 NOS 2000.00
9 Providing ISI marked RRL (IS : 636, type-A) fire hose
pipe 15 meter long and 63 mm dia with ISI marked (IS
: 903) Stainless steel male and female coupling
bound and rivetted to hose pipes with copper rivets
and copper wire complete as required.
(MAKE:Jayshree / Newage / Padmini)
52 NOS 4350.00
10 Providing & fixing standard carbon steel fireman axe
with rubber insulated handle tested to 20000 Volts.
26 NOS 650.00
11 Providing and fixing stainless steel orifice plates at
appropriate places to restrict the pressure up to 3.5
Kg/ Cm2 at different floors on the hydrant / sprinkler
system and yard hydrant. It shall be inserted between
the flange and hydrant valve. The size of plate being
150 mm, 100 mm or 80 mm dia (as the case may be),
the orifice diameter to be not less than 50% of the
internal dia of pipe into which it is fitted and the plate
thickness shall not be less than 6 mm.

20 NOS 2520.00

Fire Protection Page 3


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
12 Providing & fixing 25 mm dia air release valve with
forged brass body full way ball valve type isolating
valve, flanges / union, suitable for sprinkler / wet riser /
down comer system with all necessary connections
complete in all respects. (Make : Newage / CIM /
Leader / Sant)

25 mm dia air release valve 2 NOS 2550.00

13 Supply, fixing, testing & commissioning of 25 mm dia


inspecting and testing assembly with gun metal
valve, sight glass, by pass valve and connection to the
drain line as required to complete the system.
25 Set 6000.00
14 Providing & fixing electrically operated water flow
switches (Vane type) for sprinkler system suitable to
operate with the flow of even one sprinkler including
accessories, junction box, IP 55 protection complete
as required, with potential free contact with 2 NO / 2
NC suitable for fixing on fire pipe including connection
for wiring. (Make : System sensor)

for 100 mm diameter pipe 25 Set 5400.00


15 Providing, fixing, testing and commissioning of
microprocessor type / solid state type Annunciation
panel for monitoring of required number of flow
switches, fabricated out of 16 SWG CRCA sheet ,
powder coated in approved shade after 7 tank
treatment process, with locking arrangement, audio /
visual indication of fault and actuation of automatic
sprinkler system. The panel shall have fault indication
with audible alarm for each zone, indication of fire
zone, fire / fault hooter, 2 nos 12 volts 24 AH
emergency SMF battery with battery charger trickle
cum boost to take complete load of panel and mains
supply, indication of low battery voltage, monitoring
open circuit, short circuit, earth fault in control cable
between panel and flow switches etc. The panel
should be suitable for interface for connection to
building automation system including all accessories,
control wiring complete in all respects as required.
(Safeway / Agni / Agni Suraksha / Daksh / Morley)

30-Zone annunciator panel 1 SET 38000.00

Fire Protection Page 4


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
16 Supply and laying of ISI marked Copper conductor
PVC insulated control cable as per IS 1554 PVC
sheathed 1100 volts grade. On surface the cable run
shall be fixed by GI clamps complete in all respect
.The armouring of the cable shall be properly
connected with the earth conductor including fixing of
palm or pin type copper tin plated cable socket (lug) to
the cable leads, insulating with tape and making
connections complete in all respect including supply of
clamps, lugs, tape etc complete upto the satisfaction
of Engineer-in-charge. (Make : Gloster / Nicco / RPG /
Finolex / Polycab / Rallison)

2 x 1.5 sq mm armoured 1,100 M 81.00


17 Supply, fixing, testing & commisioning of C.P. bronze /
gun metal Sprinklers as per IS : 9972, comprises of
15mm dia, 68oC, glass bulb type, 25 kg/sq cm test
pressure, UL / FM listed / approved. The installation
shall be complete as per the drawings with positioning
of sprinklers as per final coordinated plan and
requirement of IS : 15105, local fire service &
Engineer-in-charge.
(MAKE : HD / Tyco / Globe / Newage)

Horizontal side wall mounted sprinkler


1152 Nos 300.00
18 Providing and fixing standard fire hose cabinet door
frame (900 mm x 1650 mm ) suitable to fit in the duct
made of not less than 16 SWG MS sheet having full
fronted glass hinged door (5 mm thick glass) including
necessary locking arrangement with handle as
required as per drawings, including brackets for
mounting accessories, painting (one coat primer and
two coats of fire red colour). The door shall be fixed in
the masonry wall or as required. The words "FIRE
HOSE" to be painted on the box.

25 NOS 3850.00
19 Providing and fixing standard fire hose cabinet (900
mm x 1650 mm x 450 mm) indoor type suitable for
accomodating internal hydrant, hose reel made of not
less than 16 SWG MS sheet having full fronted glass
hinged door (5 mm thick glass) including necessary
locking arrangement with handle for housing two nos.
15 meter long fire hose pipes, 30 meter long hose
reel, branch pipe and hydrant valve as required as per
drawings, including brackets for mounting
accessories, painting (one coat primer and two coat of
fire red colour). The cabinet shall be mounted on
suitable raised platform. The words "FIRE HOSE" to
be painted on the box.

1 NOS 9000.00

Fire Protection Page 5


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
20 Providing and fixing in position PVC sleeves (6
kg/cm2) (IS:4985) of upto 300 mm long in RCC
beams, slabs, walls and other structural members
before pouring of concrete. (for the crossing of
sprinkler pipes)

75 MM dia. 1000 Nos. 80.00

110 MM dia. 175 Nos. 110.00

160 MM dia. 75 Nos. 185.00

TOTAL COST

Fire Protection Page 6


round and 24 upper floors)

AMOUNT (Rs.)

44,200.00

148,200.00

Fire Protection Page 7


AMOUNT (Rs.)

504,000.00

122,500.00

170,000.00

197,625.00

332,750.00

168,750.00

80,250.00
266,875.00

14,100.00

54,000.00

202,800.00

73,875.00

127,250.00

8,875.00

Fire Protection Page 8


AMOUNT (Rs.)

9,355.00

215,540.00

52,000.00

226,200.00

16,900.00

50,400.00

Fire Protection Page 9


AMOUNT (Rs.)

5,100.00

150,000.00

135,000.00

38,000.00

Fire Protection Page 10


AMOUNT (Rs.)

89,100.00

345,600.00

96,250.00

9,000.00

Fire Protection Page 11


AMOUNT (Rs.)

80,000.00

19,250.00

13,875.00

4,067,620

Fire Protection Page 12


SCHEDULE OF QUANTITIES FOR FIRE ALARM SYSTEM

PROJECT : PROPOSED MAPSKO CASABELLA AT GURGAON. (Tower - A : For Ground and 24 upper floors)

RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
1 Providing, fixing, testing and commissioning of UL /
FM / EN / VDS listed / approved conventional
automatic fire Alarm detectors -
(MAKE : System Sensor / Apollo /
Edward / Bosch)

(a) Optical/Photoelectric type smoke detectors


(digitally addressed type) of photo-optic sensing
chamber, 12 / 24 volt D.C., visual alarm indicator
(LED's) "Blink - green" in stand by and "Steady - red"
in alarm complete in all respects with base as
required.
775 NOS 1300.00
(b) Fixed cum rate of rise temprature type heat
detectors (digitally addressed type), 12 / 24 volt D.C.,
visual alarm indicators (LED's) "Blink - green" in stand
by and "Steady - red" in alarm complete in all respects
with base as required.
201 NOS 1200.00
2 Providing, fixing, testing and commissioning of
resettable type manual call points break glass type
housed in sheet steel / Polymer housing in
surface/recess including making connections with
wires complete in all respects and as per
specifications. The manual call point should have an
indicator, which should "blink" in stand by condition.
(Make : Agni Suraksha (ASES), Safeway, Honeywell)

26 NOS 400.00
3 Providing, fixing, testing and commissioning of
electronic hooters with LMT (hooters shall also be
able to work as public address system sounders)
housed in sheet steel / Polymer housing suitable for
wall / ceiling and surface / recess mounting including
making connections with wires complete in all
respects and as per specifications. (Make : Agni
Suraksha (ASES), Safeway, Honeywell)
26 NOS 460.00
4 Providing,fixing,testing and commissioning of
response indicators with dual LED suitable for
operation on 12/24 volts D.C., sheet steel / Polymer
housing suitable for surface/recess mounting including
making connections with wires complete in all
respects. (Make : Agni Suraksha (ASES), Safeway,
Honeywell)
26 NOS 165.00

Fire Protection Page 13


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
5 Providing, fixing, testing and commissioning of
digitally addressed having addressable features
(Capable of giving individual address of each detector)
16 Zone fire alarm control and indicating panel,
microprocessor based with RS 485
communication, LCD display, pulser, timer for dual
stage alarm facility complete with indicators, floor
selector switches, stand by SMF lead acid battery
(suitable for 48 hours normal operation & after that
min. 30 minutes for full load operation), battery
charger unit with boost & trickle charger, battery box,
connections to building automation system / Fire
fighting pump panel etc. as required, complete in all
respect as per specifications and requirements. The
panel shall have facility of automatic dialling to 5
telephone numbers in case of alarm. The main control
panel should give a distinct visual signal of the
isolation of zone from the local indication panel. If all
the zones at the local panel are isolated or if the fuse
of the LCP gets blown, it should result in an open
circuit fault indication at the Main Panel. Each zone
should have provision of activation of hooter. (Make :
Agni Suraksha (ASES), Safeway, Honeywell)

4 Set 45000.00
6 Providing, installing, testing and commissioning of
totally enclosed PA system operator console with
Two way communication (Talk back system) with
microphone, all call facility, with suitable mixer
complete with controller having inbuilt amplifer of 160
watt, for 28 zones with facility for recorded message
& connectivity to third party DVD Music Player,
microphone with selector switches, housed in free
standing / wall mounted Rack with Front & back
openable, front with Glass, rack should be from
reputed company. PA system shall be coupled to the
fire alarm system. (Makes : BOSCH / PHILIPS / Agni
Suraksha / Matrix / Ahuja)

1 Set 100000.00
7 Providing, fixing, testing and commissioning of Talk
back hand set reciever with hands free
communication with speaker phone,microphone ,
push button digits and mounted on wall with 16 gauge
stove enamelled guard. (Makes : Agni Suraksha /
Matrix / Beetel)
26 Each 1500.00
8 Supply of Remote programming test unit for
programming of detectors. (Make : System Sensor /
Agni Suraksha (ASES), Safeway, Honeywell)
1 Each 10000.00

Fire Protection Page 14


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
9 Supply and fixing of ISI marked (IS:3419 & 2509) 2
mm thick PVC conduit in concealed / exposed system
in wall, ceiling or on floor including cutting of brick
work, laying of conduit and fixing it with M.S. hooks
and then plastering with cement, sand motar finished
to the level, on floor the conduit shall be covered in
PCC 1:2:4 for protection, including cost of threading
of conduit and providing necessary sockets, bends,
tees etc as directed at site by the engineer-in-charge
with supply of all material labour and T & P required
for proper completion of work. conduit being laid either
in concealed system in ceiling slab or wall or on
surface or under the frame of false ceiling including
flexible conduits or through wooden partition including
clamping arrangements as required (Make : B.E.C. /
AKG / Cap / Sieko / polypack)

25 mm dia. conduit 4000 M 62.00


10 Supplying, receiving, storing, handling, fixing, wiring
for fire alarm system wiring using ISI marked (IS 694)
1100 Volts grade, PVC insulated, flexible, flame
retardant low smoke (FRLS) copper conductor wire,
drawn in existing solid / flexible conduits / casing
caping including connections to the detectors, manual
call points, hooters, response indicators, accessories,
fire alarm control panel etc. including termination with
bottle type copper lugs, connectors etc as required to
complete the system. (Make : FINOLEX / RR / RPG /
Polycab / Rallison / Bonton)

2 x 1.5 sq mm 7,000 M 39.00

11 Supply and laying of ISI marked Copper conductor


PVC insulated cable as per IS 1554 PVC sheathed
1100 volts grade. On surface the cable run shall be
fixed by GI clamps etc. of suitable size or on existing
cable tray complete in all respect .The armouring of
the cable shall be properly connected with the earth
conductor including fixing of palm or pin type copper
tin plated cable socket (lug) to the cable leads,
connectors, terminal blocks, connectors, insulating
with tape and making connections complete in all
respect including supply of clamps, lugs, tape etc
complete upto the satisfaction of Engineer-in-charge.

(Make : Fort Gloster / National / RPG / Finolex /


Polycab / Rallison)

8 x 1.5 sq mm armoured 1,300 M 175.00

Fire Protection Page 15


RATE
S.No DESCRIPTION QTY UNIT
(Rs.)
12 Providing, drawing, connecting and testing of 4 pair
Cat 6 LAN (local area network) cable, UL listed, in
existing conduit including connections etc as required
complete in all respects. (Make : AMP / Systemax /
Legrand / Finolex)
50 M 38.00
13 Supply and erection of Perforated type cable trays
made out of prefabricated Galvanized sheet steel
including tees, bends, crossings, reducers, couplings
to be laid in cable trenches, over head on wall or
hanged from ceiling including all neccessary
supports, brackets, grouting, levelling, suspention and
fixing arrangements, dash fastners, G.I. nuts & bolts
complete in all respects.

Make : Indiana / Skaber / Bharti / Slotco / Steelways

300 mm (W) X 35 mm (H) X 1.5 mm (T) 80 M 750.00

150 mm (W) X 35 mm (H) X 1.5 mm (T) 5 M 550.00


14 Providing and fixing of self illuminated / auto glow
"EXIT" signs printed on photoluminescent sheet
containing self illuminated base chemical, of
appropriate size not less than 400 x 150 mm,
suspended from ceiling or fixed to the walls with
accessories as required and as directed at site. (Make
: Glow light / Legrand / Autoglow / Pierlite / Agni
Suraksha)
26 NOS 1200.00

TOTAL COST

Fire Protection Page 16


round and 24 upper floors)

AMOUNT (Rs.)

1,007,500.00

241,200.00

10,400.00

11,960.00

4,290.00

Fire Protection Page 17


AMOUNT (Rs.)

180,000.00

100,000.00

39,000.00

10,000.00

Fire Protection Page 18


AMOUNT (Rs.)

248,000.00

273,000.00

227,500.00

Fire Protection Page 19


AMOUNT (Rs.)

1,900.00

60,000.00

2,750.00

31,200.00

2,448,700

Fire Protection Page 20

You might also like