You are on page 1of 9

AREA TECHADA

N° DE AREAS LARGO ANCHO AREA


A1 3.40 2.30 7.82
A2 7.30 6.00 43.80
A3 3.70 1.27 4.70
A4 1.94 1.00 1.94
A5 1.25 2.30 2.88
A6 2.08 1.00 2.08
A7 3.40 2.15 7.31
A8 6.00 1.75 10.50
A9 5.20 1.35 7.02
A10 4.10 6.00 24.60
A11 1.96 3.60 7.06
A12 2.02 1.00 2.02
A13 1.50 2.15 3.23
A14 2.08 1.00 2.08
A15 3.40 2.15 7.31
A16 6.00 1.70 10.20
A17 5.20 1.65 8.58
A18 2.65 2.35 6.23
A19 2.30 2.28 5.24
AREA TOTAL TECHADO 164.59

AREA NO TECHADO
N° DE AREAS LARGO ANCHO AREA
A1 2.45 2.00 4.90
A2 5.70 3.05 17.39
A3 1.55 1.00 1.55
A4 0.46 1.00 0.46
A5 1.35 0.65 0.88
A6 1.35 0.80 1.08
AREA TOTAL NO TECHADA 26.25

1. CALCULO DE LA CARGA INSTALADA (C.I.)

C.I.1 ATT(m2) CARGA UNITARIA (W/m2)


C.I.1 164.59 25
C.I.1 4114.66 w

C.I.2 ATNT(m2) CARGA UNITARIA (W/m2)


C.I.2 26.25 5
C.I.2 131.26 w

CARGAS PEQUEÑAS
C.I.3 1500 w

CARGA ESPECIAL (COCINA ELÉCTRICA ) (C.I.4


C.I.4 3500 w

CARGA ESPECIAL (THERMA) (C.I.5)


C.I.5 1200 w

CARGA ESPECIAL (ELECTROBOMBA) (C.I.6)


C.I.6 242.45 w

CARGA ESPECIAL (SISTEMA AISLADO) (C.I.7)


C.I.7 2700 w

CARGA ESPECIAL (ASCENSOR) (C.I.8)


C.I.8 0w

2. CALCULO DE LA CARGA INSTALADA TOTAL (C.I.t)

C.I.t 13388.38 W

3. CALCULO DE LA MAXIMA DEMANDAL (M.D)

C.I. F. de D. TOTAL
M.D.1 1.00 2740.13 2740.13
M.D.2 131.26 1.0 131.26
M.D.3 1500 1.0 1500.00
M.D.4 3500 0.8 2800.00
M.D.5 1200 1.0 1200.00
M.D.6 242.45 1.0 242.45
M.D.7 2700 1.0 2700.00
M.D.8 0 0.00

4. CALCULO DE LA MAXIMA DEMANDA TOTAL (M.D.t)

M.D.t 11313.84 W

5. CALCULO DE SECCION DEL CONDUCTOR ALIMENTADOR

5.1 INTENSIDAD DE CORRIENTE

M.D.t 11313.84 Wat CALCULAMOS LA CORRIENTE DE DISEÑO


K 1.00
Un 220.00 Voltios Id In 25% a mas
Cosᶲ 0.90 Id 57.14 1.25
In 57.14 Amperios Id 71.43

5.2 CAIDA DE TENSION

K 2.0000
Id 71.4258
δ 0.0175
L 15.1100
Cosᶲ 0.9000
Sc 16.0000
∆U 2.1248 ∆U% 0.96580023

5.3 ELECCION DE ELECTRODUCTO

PVC - P - 25 mm φ (1"φ)

5.4 ELECCION DEL INTERRUPTOR GENERAL TD - 01

itm Id BUS CAT FA RESUMEN


itm 71.43 0.8 THW - PVC - P -25 mm φ ; itm = 2 x 63 A
itm 89.28

6. CALCULO DE LOS CIRCUITOS DERIVADOS.

TABLERO DE DISTRIBUCION TD - 01

5.1 CIRCUITO DE ALUMBRADO C - 1

SECCION MINIMA DEL CONDUCTOR THW - 2.5 mm2


MAXIMO DE SALIDAS POR CIRCUITO 12 Und
CONCIDERANDO POR CENTRO DE LUZ 100 Wat
Pn 1200 Wat
Un 220 V
In 5.45 Amp
Id 6.82 Amp
Ic 8.52 Amp
Itm 16 Amp THW - 2.5 mm2 ; PVC - L -20 mm
DIAMETRO 20 mm
PVC - L - 20 mm

5.2 CIRCUITO DE TOMACORRIENTE C - 2


SECCION MINIMA DEL CONDUCTOR THW - 4 mm2
MAXIMO DE SALIDAS POR CIRCUITO 18 Und
CONCIDERANDO POR CENTRO DE LUZ 150 Wat
Pn 2700 Wat
Un 220 V
In 12.27 Amp
Id 15.34 Amp
Ic 19.18 Amp
Itm 25 Amp
DIAMETRO 20 mm THW - 4 mm2 ; PVC - L -20 mm Φ
PVC - L - 20 mm

5.3 CIRCUITO DE COCINA ELECTRICA

SISTEMA MONOFASICO
Pnt 3500 Wat
K 1
Un 220 V
Cosᶲ 1
In 15.9090909 Amp
Id 19.8863636 Amp
Itm 32 Amp THW - 2.5 mm2 ; PVC - P -25 mm
THW - 2.5 mm2
CAIDA DE TENSION
K 1.0000
Id 19.8864
L 5.2700
Cosᶲ 1.0000
I 60.0000
Sc 2.5000
∆U 2515.2273

5.4 CIRCUITO DE THERMA ELECTRICA C- 4

UBICACIÓN S.S.H.H.
SISTEMA MONOFASICO
Pnt 1200 Wat
K 1
Un 220 V
Cosᶲ 1
In 5.45454545 Amp
Id 6.81818182 Amp
Itm 25 Amp THW - 2.5 mm2 ; PVC - L -20 mm
THW - 2.5 mm2
5.5 CIRCUITO DE ELECTROBOMBA C - 5

UBICACIÓN PRIMER PISO, JARDIN, ENSIMA DE LA CISTERNA


SISTEMA MONOFASICO
Pnt 242.45 Wat
K 1
Un 220 V
Cosᶲ 1
In 1.10204545 Amp
Id 1.37755682 Amp
Itm 20 Amp THW - 2.5 mm2 ; PVC - L -20 mm
THW - 2.5 mm2

5.6 CIRCUITO DE SISTEMA AISLADO C - 6

SECCION MINIMA DEL CONDUCTOR THW - 4 mm2


MAXIMO DE SALIDAS POR CIRCUITO 18 Und
CONCIDERANDO POR CENTRO DE LUZ 150 Wat
Pn 2700 Wat
Un 220 V
In 12.27 Amp
Id 15.34 Amp
Ic 19.18 Amp
Itm 25 Amp
DIAMETRO 20 mm THW - 4 mm2 ; PVC - L -20 mm Φ
PVC - L - 20 mm
TE DE DISEÑO
HALLANDO LA SECCION DEL CONDUCTOR

Sc 16 mm

-25 mm φ ; itm = 2 x 63 A

HW - 2.5 mm2 ; PVC - L -20 mm Φ ; Itm = 2 x 16 A


HW - 4 mm2 ; PVC - L -20 mm Φ ; Itm = 2 x 25 A

HW - 2.5 mm2 ; PVC - P -25 mm Φ ; Itm = 2 x 32 A

HW - 2.5 mm2 ; PVC - L -20 mm Φ ; Itm = 2 x 25 A


HW - 2.5 mm2 ; PVC - L -20 mm Φ ; Itm = 2 x 20 A

HW - 4 mm2 ; PVC - L -20 mm Φ ; Itm = 2 x 25 A

You might also like