How to calculate HT XLPE CABLE for 11 kv / 433 v ,

1500 kva oil type trans


allinterview.com/showanswers/74610/calculate-ht-xlpe-cable-11-kv-433-v-1500-kva-oil-type-transformer-system-
provide.html

How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva


oil type transformer system?
plz provide step by step calculation

Answers were Sorted based on User's Feedback

Answer / divay chadha

3core-185 sq. mm

Calculation:-

Current at HT = (1500 x 1.4)/ (33*1.732)

Is This Answer Correct ? 223 Yes 127 No

Answer / s.srinivasan

Generally HT cable sizing is not done based on the full


load current of the equipment but based on the prospective
fault level. For a 11kV network, generally it shall not be
less than 150sqmm XLPE.

Fault level at 11kV(furnished by respective EB)=100 MVA(say)

Details on EB's fault level can be obtained from EB.

Therefore fault current= 100*1000/(SQRT(3)*11000)


= 5.25 kA

Short circuit current rating (for 3-sec duration)of HT 11kV


XLPE cables with Alu conductor is as below:
95 sqmm: 5.16 kA
120 sqmm: 6.51 kA
150 sqmm: 8.14 kA

Is This Answer Correct ? 121 Yes 25 No

Answer / j.kesavan

1/5
please slect your cable in 11kv py side how much current
check first after you slect your ht cable.

Is This Answer Correct ? 86 Yes 39 No

Answer / neeraj tyagi

simple for 11kv


Amp in HT= kva*1000/ 1.732*11000

= size for 78 amp HT XLPE 3 core 95 mm2 higher side.

Is This Answer Correct ? 87 Yes 47 No

Answer / gb

11kv----13 amps on primary side

1500 kva 1.4 = 2100 amps on secondary

Is This Answer Correct ? 41 Yes 27 No

Answer / madhu mohan

First calculate the current of primary side(HT) and derate the cable by atleast 0.7.
Eg:1500*1000/(1.732*11000)=78.73A
Current I after Derating =78.73/.7 =112A (0.7 if laid on the trays or value will vary if buried
in the ground).
Cable equivalent to rating has to be selected.
Now Short circuit withstand capacity (sq. of I X t in sec) has to be checked from the cable
catalogue.This value of cable should be higher then SC withstand capacity of the ground
usually it is 50KA.it less go for next size and finalise.

Is This Answer Correct ? 30 Yes 22 No

Answer / sairaj

90 Sq.mm Al Ar XLPE cable is sufficient. But as per statutory norms for 11kV, 185 Sq.mm
Cable is considered.

Is This Answer Correct ? 14 Yes 9 No

Answer / uday

1500kVA X 0.8 PF = 1200Kw = 1200000W


2/5
P=RT3 V I COS fi

SO, P
I = -----------
RT3 x V x COSfi

1200000
I = -----------------
1.732x1100x0.8

= 79 A

Now take cable table and select the suitable xlpe cable.

Uday

Is This Answer Correct ? 45 Yes 46 No

Answer / saad yar khan

Where can I get the chart for selecting HT cable based on 1500KVA i.e 78Amp

Is This Answer Correct ? 0 Yes 1 No

Answer / rasel-amie

HT Cable select, its depend of incoming capacity of feeder


line. say feeder capacity 100 MVA SO Calculate current I=
100*100/11*1.73=5.25kA. So we can select of HT Cable for
minimum short ckt current carrying capacity of minimum 5.2kA.

Is This Answer Correct ? 10 Yes 12 No

Post New Answer

More Electrical Engineering Interview Questions

Meaning of ingrace protection for motor.for ex IPXY

0 Answers BARC,

I have 10 amp MCB for my air conditioner of 1.5 ton capacity. When I connect the ac direct
it is started running but when connected through stabliser the Mcb Get trip and air
conditioner couldn't start.please confirm whether Mcb is required to be upgraded to 20 amp.
There is no fault in ac and the stabliser. Please advice the reason of tripping the mcb when
connected through the stabliser.

1 Answers

3/5
which calss ct's,pt', use protection,meatering and others

1 Answers

without any theoretical calculations, can u approximately tell the current rating of a
motor(above 30hp)working at 415VAC.

7 Answers

what is the minimum clearance between a 11KV 150KVAR capacitor cell and series
reactor.can a series reactor can be mounted in the same structure of the capacitor cells
structure

0 Answers APTransco,

I have 90KW Motor 60 Hz,380V Pf 0,88. after testing the Motor without Load is the no load
Current 36 A,but wenn i put load after 2 hours the current increase more than 156 A. Can
anybode tell me waht is the Problem?

3 Answers ABB,

why stator winding of synchronous machine are connected in star connection ?

1 Answers

Does induction motor start with dc power supply????

4 Answers Essar,

What happens if ac is applied to dc systems and vice versa?

5 Answers

what is mean by descripiency relay? & wht is its ansi code?

0 Answers

if the armature current in a dc generator is ac ( sinusoidal ) why doesnt the sjhape af


armature mmf a sinusoidal (ni) ? armature mmf in case of a dc machine is triangular.

0 Answers

what is dead tank CT AND what is live tank CT

2 Answers TATA,
4/5
Categories

5/5

You might also like