Particular Specification for

Fire Fighting & Fire Alarm Works


for Buildings - Education City

Doha Major Stations


M007-MML-FRS-SPE-00001 Rev 0.1
August 2014

Samsung - OHL - QBC JV


Particular Specification for Fire
Fighting & Fire Alarm Works for
Buildings - Education City
M007 MML-PUH SPE 00001 0.1
Document uncontrolled when printed
08 May 2014
Doha Major Stations
Particular Specification for Drainage Works for Buildings -
M007-MML-FRS-SPE-00001 Rev 0.1
Doha Major StationsM007-MML-PUH-SPE-00001 Rev 0.1
August 2014

Samsung - OHL - QBC JV

PO Box 22574
Doha
Qatar

Mott MacDonald, Doha Tower, Grand Hamad Street, PO Box 22574, Doha, Qatar
T +974 442 5145 F +974 442 5758 W www.mottmac.com
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Issue and revision record

Revision Date Originator Checker Approver Description Standard


0.1 04/08/2014 A Kumar F Donaghy S Evans Issued for Comments

1This document is issued for the party which commissioned it We accept no responsibility for the consequences of this
and for specific purposes connected with the above-captioned document being relied upon by any other party, or being used
project only. It should not be relied upon by any other party or for any other purpose, or containing any error or omission
used for any other purpose. which is due to an error or omission in data supplied to us by
other parties.

This document contains confidential information and proprietary


intellectual property. It should not be shown to other parties
without consent from us and from the party which
commissioned it..

M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Contents

Chapter Title Page

Introduction 1

1 Part 1 General 2
1.1 Introduction________________________________________________________________________ 2
1.1.2 General___________________________________________________________________________ 2
1.2 Regulations _______________________________________________________________________ 2
1.2.2 Civil Defence Department_____________________________________________________________ 2

2 Part 2 Fire Alarm and Detection System 3

3 Part 3 Analogue Addressable Fire Alarm System 4

4 Part 4 Fire Fighting System 5


4.1 General___________________________________________________________________________ 5
4.1.1 Scope ____________________________________________________________________________ 5
4.1.2 Codes and Standards ________________________________________________________________ 5
4.1.3 Protection of Piping Against Earthquake Damage __________________________________________ 6
4.1.4 Fire Fighting System Installer __________________________________________________________ 7
4.1.5 Regulatory Equipments ______________________________________________________________ 7
4.2 Sprinkler Systems___________________________________________________________________ 7
4.2.1. System Description__________________________________________________________________ 7
4.2.2. Sprinkler Heads ____________________________________________________________________ 9
4.2.3. Sprinkler System Alarm Devices ______________________________________________________ 10
4.2.4. Alarm Valve ______________________________________________________________________ 10
4.2.5. Basic Trim and Retarding Chamber ____________________________________________________ 10
4.2.6. Pressure Alarm Switches ____________________________________________________________ 10
4.2.7. Water Motor Alarms ________________________________________________________________ 10
4.2.8. Stop Valve _______________________________________________________________________ 10
4.2.11 Drain and Test Connection ___________________________________________________________ 10
4.2.12 Accessories ______________________________________________________________________ 10
4.2.13 Sprinkler Installation ________________________________________________________________ 10
4.3 Water Supply _____________________________________________________________________ 11
4.3.1 General__________________________________________________________________________ 11
Hoses ___________________________________________________________________________ 12
4.4 12
4.4.3 Hose Reels with Semi-Rigid Hose _____________________________________________________ 12
4.4.4 Hose Systems with Lay-flat Hose ______________________________________________________ 12
4.4.5 Fire Hose Cabinets _________________________________________________________________ 13
4.4.6 Accessories _____________________________________________________________________ 13
4.5 Fire Hydrants _____________________________________________________________________ 13
4.6 Pipes and Fittings __________________________________________________________________ 13
Pumps __________________________________________________________________________ 15
4.7 15

M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.7.1 General__________________________________________________________________________ 15
4.7.4 Fittings __________________________________________________________________________ 15
4.7.6 Controller and Transfer Switch ________________________________________________________ 16
4.7.8 Jockey Fire Pumps _________________________________________________________________ 17
4.7.10 Flow Measuring Systems ____________________________________________________________ 17
4.7.11 Gate Valve (Rising and Non-Rising) ____________________________________________________ 18
4.7.12 Butterfly Valve ____________________________________________________________________ 18
4.7.13 Check Valve (Non-Return) ___________________________________________________________ 18
4.7.14 Ball Valves _______________________________________________________________________ 18
4.8 Wet Riser (Combined Riser)__________________________________________________________ 18
4.9 Portable Fire Extinguishers __________________________________________________________ 20
4.10 Fire Blankets _____________________________________________________________________ 20
4.11 FM 200 System ___________________________________________________________________ 21

5 Part 5 Testing and Commissioning 24


5.1 General__________________________________________________________________________ 24
Testing, Start-up and Commissioning _____________________________________________________________ 24
5.2 24

M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Introduction

Fire Fighting and Fire Alarm Systems works shall be carried out in accordance with the QCS 2010 (Qatar
Construction Specifications 2010) Section 23 Parts 1 to 5, Volume 6 (Design Specifications) and Volume 7
(Materials and Workmanship Specifications) of the Employers Requirements (herein referred to as the
‘Base Specification’).

This document is the ‘Particular Specification’ for the Fire Fighting and Fire Alarm Systems works for the
Education City to be followed in addition to the standards and clauses of QCS 2010 Section 23, Volume 6
and 7 of the Employer’s Requirements. If there is a conflict between the ‘Base Specification’ and the
standards and / or clauses referenced in this ‘Particular Specification’, the latter shall take precedence.

Incase of contractor considering there is a need to deviate from any requirements of the ‘Base
Specification’ and this ‘Particular Specification’, he shall detail the matter and his reasoning, for the review
and consent of the Contractor’s Consultant.

In this ‘Particular Specification’, the actions in italics refer to the modifications in relation to the QCS.

1 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

1 Part 1 General

Add

1.1 Introduction

1.1.2 General

3. All fire fighting system and fire protection system equipment shall be designed, manufactured,
erected and tested to the requirement of relevant National Fire Protection Association (NFPA) codes
and standards, QCDD ( Qatar Civil Defence Department) requirements, and shall be UL listed/FM
approved.

Amend

1.2 Regulations

1.2.2 Civil Defence Department

2. The fire protection, fire alarm and fire fighting system contractor shall be registered with, and on the
approved list of the Civil Defence Department

End of Part 1

2 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

2 Part 2 Fire Alarm and Detection System

End of Part 2

3 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

3 Part 3 Analogue Addressable Fire Alarm


System

End of Part 3

4 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4 Part 4 Fire Fighting System

4.1 General

4.1.1 Scope

Add:
2. Related sections are as follows:
Section 13 Masonry
Section 19 Plumbing Works
Section 26 Painting and Decorating

4.1.2 Codes and Standards

1. Delete
ASTM A 47 Specification for Ferritic Malleable Iron Castings
ASTM A 106 Specification for Seamless Carbon Steel Pipe for High-Temperature
Service
ASTM A 135 Specification for Electric-Resistant-Welded Steel Pipe
ASTM A 395 Specification for Ferritic Ductile Iron Pressure Retaining Castings for Use
at Elevated Temperatures
ASTM A 197 Specification for Cupola Malleable Iron
ASTM A 234 Specification for Pipe Fittings of Wrought Carbon Steel and Alloy for
Moderate and Elevated temperatures
BS 750 Underground Fire Hydrants and Surface Box Frames and Covers
BS 1452 Specification for Grey Iron Castings
BS 2789 Iron castings with Spheroidal or Nodular Graphite
BS 5163 Double Flanged Cast Iron Wedge Gate Valves for Waterworks Purposes
BS 5423 Portable Fire Extinguishers
BS 6575 Fire Blankets
BS EN 671 Fixed Fire Fighting Systems – Hose systems

Add
ASTM A 53 Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-
Coated, Welded and Seamless
ASME B 16.10 Face to Face and End to End Dimensions of Valves
ASME B 16.42 Ductile Iron Pipe Flanges and Flanged Fittings
BS 336 Specification for Fire Hose Couplings and Ancillary Equipment.

5 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

NFPA 10 Standard for Portable Fire Extinguishers


NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 22 Standard for Water Tanks for Private Fire Protection
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm and Signalling Code
NFPA 101 Life Safety Code
NFPA 130 Standard for Fixed Guide way Transit and Passenger Rail System
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems
NFPA 5000 Building construction and Safety Code
NFPA 25 Standard for the Inspection, Testing and Maintenance of Water – Based
Fire Protection Systems.
NFPA 170 Standard for the Fire Safety and Emergency Symbols
NFPA 1961 Standard for Fire Hoses.
NFPA 1963 Standard for Fire Hose Connections
BS 5041-3 Specification for Inlet Breechings for Dry Riser Inlet
BS EN 1869 Fire Blankets

2. Amend
(a) Qatar Civil Defence Department
(b) National Fire Protection Association (NFPA)
Delete
(d) Loss prevention Council Board (LPCB)

Add

4.1.3 Protection of Piping Against Earthquake Damage

1. The system piping shall be protected against damage from earthquakes. Seismic protection shall
include flexible and rigid couplings, sway bracing, seismic separation assemblies where piping
crosses building seismic separation joints, and other features as required by NFPA 13 for
protection of piping against damage from earthquakes.
Add

6 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.1.4 Fire Fighting System Installer

1. Work specified in this section shall be performed by the Fire Fighting System Installer.

2. The Fire Fighting System Installer shall be regularly engaged in the installation of the type and
complexity of system specified in the Contract documents. Prior to commencing work, submit
data showing that the Fire Fighting System Installer has successfully installed fire fighting
systems of the same type and design as specified herein. Include the names and locations of at
least three installations where the Contractor or the subcontractor referred to above, has installed
such systems. Indicate the type and design of each system, and certify that the systems have
performed satisfactorily for a period of at least 24 months.

3. Qualifications of System Technician: Installation drawings, shop drawing and as-built drawings
shall be prepared, by or under the supervision of, an individual who is experienced with the types
of works specified herein, and is currently certified for this type of works. Contractor shall submit
data for approval showing the name and certification of all involved individuals with such
qualifications at or prior to submittal of drawings.

Add

4.1.5 Regulatory Equipments

1. Compliance with referenced NFPA standards is mandatory. This includes advisory provisions
listed in the appendices of such standards, as though the word "shall" had been substituted for
the word "should" wherever it appears.

2. In the event of a conflict between specific provisions of this specification and applicable NFPA
standards, this specification shall govern. Reference to "Authority Having Jurisdiction" shall be
interpreted to mean the local civil defence.

3. Materials and Equipment shall have been tested by Underwriters Laboratories, Inc. and listed in
UL Fire Prot Dir or approved by Factory Mutual and listed in FM P7825a and FM P7825b. Where
the terms "listed" or "approved" appear in this specification, such shall mean listed in UL Fire Prot
Dir or FM P7825a and FM P7825b.

4.2 Sprinkler Systems

4.2.1. System Description

Amend
1 Wet pipe sprinkler systems (combined with standpipe and hose system) shall employ automatic
sprinklers attached to a piping system containing water and connected to a water supply. Each
pipeline in the system shall be fully pressurised, so that water discharges immediately from
sprinklers opened by a fire.

7 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4. The fire fighting system shall be fed from a storage tank located at concourse level.
5. The (combined) sprinkler system shall be complete with an automatic packaged fire pumping
station and valves, water flow detectors, pressurised water main with distribution pipework, range
pipes, hangers and supports, sprinkler heads and a piped drain system.
6. All the isolation/control valves in sprinkler system shall be provided with supervisory switches and
interfaced with BMS (Building Management System) through fire alarm system. Flow switches
shall be interfaced with the BMS and FAS (Fire Alarm System). Such supervisions shall be
monitored at an approved, instantly attended location.
8. Drain/flushing of the wet/combined risers shall be through drain risers and shall be connected to
the nearest drain.

9. The distance between sprinklers shall not exceed 4.6 m. The maximum floor area to be covered
by a single sprinkler for different hazard class are as follows:
2
(a) Light hazard = 21 m
2
(b) Ordinary hazard = 12 m
2
(c) Extra high hazard = 9 m

12. The Contractor shall supply an adequate quantity of additional sprinkler heads of the correct
temperature rating. The number will depend on the size of the installation and number of
sprinkler heads likely to be opened. The following figures are the minimum number of additional
sprinkler heads that shall be kept as stock of spares:

(a) for systems not exceeding 300 sprinklers, 6 spare heads shall be maintained

(b) for systems exceeding 300 sprinklers but not exceeding 1000, 12 spare heads shall be
maintained

(c) for systems exceeding 1000 sprinklers, 24 spare heads shall be maintained

All the spare sprinkler heads shall be maintained on the premises so that any sprinklers that have
operated or been damaged in anyway can be promptly replaced.

Delete

7. The water motor alarm and gong shall consist of a simple water turbine having the shaft
connected to a rotary ball clapper mounted within a domed gong. The alarm system shall be self
winding, adjustable recycling non-thermal type and equipped with signal retarding device to
prevent false alarms due to surges in the water system. Auxiliary pressure sensing devices shall
be incorporated in the feed to the alarm gong to actuate the central fire alarm panel.

8 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.2.2. Sprinkler Heads

Amend
1. Sprinklers heads generally are of pendent, upright and sidewall type. Sprinklers for the concealed
ceiling and concealed floor spaces shall be provided in accordance with QCDD FSS -6.4.
Generally, parts of the voids in excess of 400mm in depth shall be provided with sprinkler
protection.
Add
6. Sprinklers with internal O-rings shall not be used. Sprinklers shall be used in accordance with
their listed coverage limitations. Sprinklers in high heat areas including attic spaces shall have
temperature classification in accordance with NFPA 13. Extended coverage sprinklers shall not
be used unless permitted by The Engineer.

7. Sprinkler Types and Categories: Nominal 12.7 mm orifice for "Ordinary" temperature
classification rating, unless otherwise indicated or required by application.

a. Open Sprinklers: UL 199, without heat-responsive element.

(i). Orifice: 12.7 mm, with discharge coefficient K between 5.3 and 5.8.
(ii). Orifice: 13.5 mm, with discharge coefficient K between 7.4 and 8.2.

8. Sprinkler Finishes: Chrome-plated for all areas. Sprinklers installed in stainless steel false ceiling
type shall have stainless steel finishes.

9. Special Coatings: Wax, lead, and corrosion-resistant paint.

10. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler mounting
applications. Escutcheons for concealed, flush, and recessed-type sprinklers are specified with
sprinklers. The escutcheon shall have a factory finish that matches the pendent sprinkler heads

(a) Ceiling Mounting: Chrome-plated steel or stainless steel as required, 1 piece, flat.

(b) Sidewall Mounting: Chrome-plated steel or stainless steel as required, 1 piece, flat.

(c) Pendent Mounting: Chrome-plated steel or stainless steel as required, 1 piece with a depth
of less than 20 mm and suitable for installation on pendent sprinklers.

11. Only UL listed and FM approved Sprinklers shall be approved.

12. Sprinklers shall be arranged such that there is no interference with the discharge pattern and
they shall be positioned between 75 and 150mm below ceilings.

13. Operating temperature of the sprinkler heads shall be based on the maximum room temperature
expected at the ceiling level at any time in accordance with clause 6.2.5 of NFPA 13.

14. Minimum design density and design area of application shall be in accordance with relevant
sections of NFPA 13 as applicable to the specific occupational hazard.

9 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

15. Minimum operating pressure of any sprinkler head shall be 0.5 bar. Where a higher minimum
operating pressure for the designed application is specified in the listing of the sprinklers, this
higher pressure rating shall be considered.

Delete

4.2.3. Sprinkler System Alarm Devices

4.2.4. Alarm Valve

4.2.5. Basic Trim and Retarding Chamber

4.2.6. Pressure Alarm Switches

4.2.7. Water Motor Alarms

4.2.8. Stop Valve

Amend

4.2.11 Drain and Test Connection


1. The system shall incorporate a 50 mm drain and a 25 mm test pipe connection for flow control
inspection testing and drainage of feed mains.

Add

4.2.12 Accessories
1. Sprinkler Cabinet: Spare sprinklers shall be provided in accordance with NFPA 13 and shall be
packed in stainless steel cabinet. Spare sprinklers shall be representative of, and in proportion to,
the number of each type and temperature rating of the sprinklers installed. At least one wrench of
each type required shall be provided.

2. Identification Sign: Valve identification sign shall be minimum 150 mm wide x 50 mm high with
enamel baked finish on minimum 0.6 mm aluminium with red letters on a white background or
white letters on red background. Wording of sign shall include, but not be limited to "main drain,"
"auxiliary drain," "inspector's test," "alarm test," "alarm line," and similar wording as required to
identify operational components.

4.2.13 Sprinkler Installation


1. Handle, transport and store sprinklers with care to prevent damage. Use only wrenches supplied
by manufacturer to tighten sprinklers in fittings.

10 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

2. Install sprinklers only in position for which they are designed. Deflectors are to be parallel to
ceiling and frames parallel to pipe and not across.

3. Locate sprinklers on ends of branch lines not more than half sprinkler spacing from walls or
partitions.

4. Do not alter or apply ornamentation, coatings or paint to sprinklers. Exercise care when painting
sprinkler piping to avoid touching sprinklers with paint.

5. Do not attach wiring, ropes or fixtures to sprinklers or to sprinkler piping.

6. Pendent Sprinklers: Drop nipples to pendent sprinklers shall consist of minimum 25 mm pipe with
a reducing coupling into which the sprinkler shall be threaded. Hangers shall be provided on arm-
overs to drop nipples supplying pendent sprinklers when the arm-over exceeds 300 mm. Where
sprinklers are installed below suspended or dropped ceilings, drop nipples shall be cut such that
sprinkler ceiling plates or escutcheons are of a uniform depth throughout the finished space. The
outlet of the reducing coupling shall not extend more than 25 mm below the underside of the
ceiling. On pendent sprinklers installed below suspended or dropped ceilings, the distance from
the sprinkler deflector to the underside of the ceiling shall not exceed 100 mm. Recessed
pendent sprinklers shall be installed such that the distance from the sprinkler deflector to the
underside of the ceiling shall not exceed the manufacturer's listed range and shall be of uniform
depth throughout the finished area.

7. Pendent Sprinkler in suspended ceilings shall be a minimum of 150 mm from ceiling grid.

8. Upright Sprinklers: Riser nipples or "sprigs" to upright sprinklers shall contain no fittings between
the branch line tee and the reducing coupling at the sprinkler. Riser nipples exceeding 750 mm in
length shall be individually supported.

4.3 Water Supply

4.3.1 General

Amend

1. Unless otherwise stated elsewhere in the Project Documentation, the water supply shall consist
of:

(a) Two electric motor driven fire pump connected in parallel (one working and one standby)

Delete

(b) Diesel motor driven fire pump with back-up

11 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Amend

2. The capacity of the reservoirs/storage tanks from which fire fighting systems draw water shall be
as stated in the project drawings.

Amend

4.4 Hoses

4.4.1 General

Amend

1. Hoses shall be installed in locations as indicated in the project drawings unless otherwise
directed by the Civil Defence Department.

3. The supplier shall make available an installation and maintenance manual for the hose system.

Delete

2. Fire hose reel assemblies shall be provided with full operational instructions for display on or
adjacent to the hose reel.

5. Hose reels shall be marked with following information.


(a) suppliers name or trademark, or both
(b) year of manufacture
(c) maximum working pressure
(d) length and bore of hose
(e) nozzle diameter (marked on the nozzle)

Delete

4.4.3 Hose Reels with Semi-Rigid Hose

Delete

4.4.4 Hose Systems with Lay-flat Hose

Add

12 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.4.5 Fire Hose Cabinets

1. Description: Stainless Steel 316 cabinet with 5 mm thick tempered glass door, and complete with
the following features:

(a) Valves: UL 668, 2070 kPa (300-psig) minimum pressure rating, 90 degree angle pattern hose
valve with female NPS inlet and outlet, unless otherwise indicated.
(b) Valve Operation: Pressure-regulating type.
(c) Threads and Gaskets: NFPA 1963 and matching local fire department threads.
(d) Fire Hose: NFPA 1961 and UL 219, lined fire hose with couplings, gaskets, and nozzle.
Include the following fire hose materials:

(i) Jacket: Synthetic thread.


(ii) Lining: Rubber compound.

(e) Nozzles: UL 401.


(f) Drain Valves: UL 1726.
(g) 1 No of fire extinguisher [10lbs, Dry Powder (ABC type)]
(h) Mounting: surface mounted/wall mounted type.

4.4.6 Accessories

1. Valve Temper Switch: Provide valve tamper switch(es) to monitor the open position of valve(s)
controlling water supply to the standpipe system. Switch contacts shall transfer from the normal
(valve open) position to the off-normal (valve closed) position during the first two revolutions of
the hand wheel or when the stem of the valve has moved not more than one-fifth of the distance
from its normal position. Switch shall be tamper resistant. Removal of the cover shall cause
switch to operate into the off-normal position.

Delete

4.5 Fire Hydrants

4.6 Pipes and Fittings

4.6.1 General

Amend

1. Pipes shall be UL listed and FM approved. Pipes shall be exterior galvanized steel to ASTM A 53
Grade B seamless sch 40 with a working pressure of 17 bar. Couplings to be of roll grooved type,

13 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

for pipe sizes 65 mm and above. Couplings to be of cut grooved type, for pipe sizes 50 mm and
below.

2. Fittings shall be UL listed and FM approved. Mechanical grooved pipe couplings and fittings as
manufactured by specialised manufacturers shall be used for all fire fighting systems application.

(a) Standard flexible couplings shall be cast ductile iron to ASTM A 536 Grade 65-45-12 with
chlorinated butyl gaskets and heat treated carbon steel bolts and nuts to ASTM A 183,
zinc plated to ASTM B 633
(b) Grooved end fittings shall be cast ductile iron to ASTM A 536 Grade 65-45-12.
(c) Flange adapters shall be cast ductile iron to ASTM A 536 Grade 65-45-12 with a hinged,
two-piece design, suitable for opening and engaging the grooves, and shall be secured in
position with a tight-fitting lock bolt. Flange Adapter allows a direct transition from flanged
components into a grooved piping system. Flange bolt patterns conform to ANSI class 125
and 150 standards.
(f) All the valves except butterfly valves shall be flanged end design with encapsulated body
and disc for sized 65 mm and above, and shall be threaded/screwed end design for sizes
50 mm and below. All the butterfly valves shall be grooved end design and shall be with
gear actuator.

Add

(g) Matching steel flanges applicable for valves with flanged end design shall comply with
ANSI B 16.5 class 300.

Add

4.6.3 Pipe Sleeves

1. Where a pipe enters a building/crosses through wall, it shall be accommodated in a sleeve that
has previously been solidly built-in and the space between the pipe and the sleeve shall be filled
with non-hardening, non-cracking, water-resistant material for a minimum length of 150 mm at
both ends to prevent the passage of water, gas or insects.

2. Sleeves:

(a) Galvanized-Steel Wall Pipes: ASTM A 53, Schedule 20, with plain ends and welded steel
collar, zinc coated.

3. Sleeve – Seal Systems:

Description: Modular sealing-element unit, designed for field assembly, for filling annular space
between piping and sleeve.

14 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

(a) Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include
type and number required for pipe material and size of pipe.
(b) Pressure Plates: Carbon steel.
(c) Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating of length
required to secure pressure plates to sealing elements.

4.7 Pumps

4.7.1 General

Amend

1. Furnish and install where shown on the drawings two number of UL listed and FM approved
single stage or multistage centrifugal fire pump complete with motor, controller, necessary fittings
and speciality accessories necessary to complete the installation in every respect. The complete
installation shall be in accordance with the requirements of, and meet with the approval of, the
Civil Defence Department and any other Authorities Having Jurisdiction. Centrifugal fire pumps
shall have a horizontal shaft with electric motor drive. Jockey fire pumps shall have electric
motor drives.

2. Pumps serving water supply to fire fighting systems are normally driven electrically and shall
always be arranged to start automatically in the event of system operation. In addition,
arrangement for starting manually shall also be installed. It is important that the electricity supply
shall always be maintained to the pumping set. It is therefore essential that the electrical
connections be such that a power supply is always available for the motors when the switches for
the distribution of electrical power throughout the building are cut. Any switches on the power
feed to the motor shall be clearly labelled, “FIRE PUMP MOTOR SUPPLY -NOT TO BE
SWITCHED OFF IN THE EVENT OF FIRE”. Such switches shall be of the locking type and shall
be kept locked on. An indicator lamp shall be provided to show continuously that full power
supply is available for the motor. Any fuses in the electricity sub-circuit shall be of the high
rupturing capacity (HRC) type.

4.7.4 Fittings

Amend

1. The contractor shall provide the following accessory fittings:


(b) concentric tapered discharge increaser

15 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Delete

(h) mains relief valve

(i) strainer (waste cone)

4.7.6 Controller and Transfer Switch

Amend

1. The controller and transfer switch shall be UL listed and FM approved and shall be the combined
manual and automatic, across the line type. Control equipment shall be furnished in a steel
mounted, drip proof enclosure with front operated circuit breaker and disconnect switch.

Add
5. Description: UL 218 and NFPA 20; listed for electric-drive, fire-pump service and service
entrance.

a. Type Starting: Autotransformer, closed transition.

6. Rate controllers for scheduled horsepower. Include short-circuit withstand rating at least equal to
short-circuit current available at controller location. Take into account cable size and distance
from substation or supply transformers.

7. Automatic Transfer Switches: UL 218 and UL 1008 and requirements for and attached to fire-
pump controllers. Include enclosure complying with UL 50, Type 2, with automatic transfer switch
with rating at least equal to fire-pump driver-motor horsepower. Include ampere rating not less
than 115 percent of motor full-load current and suitable for switching motor-locked rotor current.

8. Controllers: As follows:

(a) Isolating means and circuit breaker.

(b) "Power on" pilot lamp.

(c) Fire alarm system connections for indicating motor running condition, loss-of-line power,
and line-power phase reversal.

(d) Automatic and manual operation, and minimum run-time relay to prevent short cycling.

(e) Water-pressure-actuated switch with independent high and low calibrated adjustments
responsive to water pressure in fire-suppression system.

(f) Automatic and manual shutdown.

(g) System pressure recorder, electric ac driven with spring backup.

16 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

(h) Mounting: Wall type for field electrical connections.

(i) Enclosure Finish: Manufacturer's standard red paint applied to factory assembled and -
tested unit before shipping.

4.7.8 Jockey Fire Pumps

Amend
3 The motor controller shall be QCD approved for fire pump service. Control shall include a
combination type starter with fused disconnect switch, thermal over-current protection and a
hand-off automatic selector switch in the enclosure. Control shall also include an adjustable
pressure switch with gauge cock.

7. The installation shall come complete with a 65 mm diameter bronze check valve with clapper /
disc.

8. The jockey pumps and pump drives shall be installed on suitable RCC foundation in accordance
with the manufacturer’s recommendations.

Delete
5. The installation shall come complete with a 20 mm relief valve on the discharge line of the jockey
pump to relieve excess pressure to floor drains

Add

4.7.10 Flow Measuring Systems

1. Description: FM-approved, fire-pump, flow-measuring systems that indicate flow to not less than
175 percent of fire-pump rated capacity. Include sensor of size to match pipe, tubing, flow meter,
and fittings.

(a) Pressure Rating: to match pump head and system requirements.

(b) Sensor: Venturi type unless otherwise indicated.

(c) Flow Meter: Compatible with flow sensor with dial not less than 4-1/2 inches (115 mm) in
diameter or manufacturer's equivalent size.

(d) Permanently Mounted: Flow meter suitable for wall mounting with copper tubing to connect
to flow sensor.

(e) Portable: Flow meter, with two 12-foot (4-m) hoses, in carrying case with handle.

(f) Include complete operating instructions

17 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.7.11 Gate Valve (Rising and Non-Rising)

Gate valve shall be UL listed and FM approved. It is specifically designed for fire line
applications, where a positive indication of the open or closed position necessary. The valve shall
have flanged ends with cast iron body and a working pressure of 12 bar.

4.7.12 Butterfly Valve

Butterfly valve shall be UL listed and FM approved. They shall be gear operated butterfly valves
with internal or external monitor switch. They shall have a wafer style body with grooved ends.
They shall be rated for a 12 bar operating pressure and have a cast iron body and an EPDM seat
with bronze disc.

4.7.13 Check Valve (Non-Return)

Check valve shall be UL listed and FM approved. It shall be a swing check type with flanged end
connection. They shall be rated for a 12 bar operating pressure and have a cast iron body.

4.7.14 Ball Valves

Ball valves shall be UL listed and FM approved. It shall be with bronze body and threaded ends.

Amend

4.8 Wet Riser (Combined Riser)

4.8.1 General

Amend

1. The wet riser (combined with sprinkler system) installation shall incorporate an inlet box which
shall be constructed from 1.5 mm thick galvanized sheet steel and shall be suitable for recessed
mounting, with 3 mm thick x 40 mm wide architrave. The box shall be provided with a hinged,
lockable door with a central panel glazed with wired glass and having the words “BREECHING
INLET” in 50mm high red letters on the inside face. The box shall be finished in baked enamel
inside with prime coat outside to the required colour, and shall be supplied by an approved
manufacture of fire equipment.

3. The wet riser (combined with sprinkler system) installation shall incorporate landing valves which
shall be a spindle valve controlled breaching with a 65 mm diameter inlet and 65 mm diameter
instantaneous female outlet with blank cap. The chain valves shall be straight or oblique pattern

18 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

as required, and shall be fixed in the closed position. Each landing valve shall be provided with a
30 m long by 65 mm diameter fire hose lined with coated woven synthetic fire hose as well as a
diffuser branch pipe nozzle. The valve, hose and nozzle shall be accommodated in a wall
mounted box supported on purpose made hangers and ready for immediate use. The box shall
be generally constructed as for the inlet breaching, but with the words “WET RISER OUTLET” in
50 mm high red letters on the inside face of the glazing.

4. The top of each wet riser shall be fitted with a 25 mm automatic air release valve (brass
construction, with internal solid rubber ball) and a pressure gauge with isolation cock.

Add

4.8.2 Fire-Department Connection

1. Type: Flush, for wall mounting.

2. Minimum Pressure Rating: 1200 kPa (175 psig)

3. Body Material: Cast Iron / Ductile Iron.

4. Inlets: Brass with instantaneous coupling to BS 336: 1989 and matching local fire department
sizes.

5. Caps: Brass, lugged type, with gasket and chain.

6. Escutcheon Plate: Rectangular, brass, wall type.

7. Outlet: Flanged end

8. Body Style: Horizontal

9. Number of Inlets: Four

10. Escutcheon Plate Marking: Similar to "AUTO SPKR and STANDPIPE".

11. Finish: Polished chrome plated

12. Outlet Size: DN 150 (NPS 6).

13. Check Valve: Wafer type

19 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

4.9 Portable Fire Extinguishers

4.9.1 General

Amend

1. Fire extinguishers shall be UL listed.

2. Fire extinguishers shall be colour coded according to their type. The colour shall be as follows:

(a) black - carbon dioxide

(b) blue - dry powder(ABC)

3. The types of extinguishers that can be used on a fire is dependent upon the class of the fire.
Final selection of extinguisher type shall be in accordance with and to the approval of the Civil
Defence Department.

4. The capacity of fire extinguishers shall be as indicated in the drawings.

Add

5. Multipurpose Dry-Chemical Type FE-1: UL-rated 4-A:60-B:C, 4.5-kg (10-lb) nominal capacity, in
enameled-steel container.

6. Carbon-Dioxide Type FE-2: UL-rated 10-B:C, 4.5-kg (10-lb) nominal capacity, in manufacturer's
standard enameled-metal container.

Delete
Table 4.2

4.10 Fire Blankets

4.10.1 General

Amend

1 Fire blankets shall be manufactured from fire resistant glass fiber fabric, coated on both sides
with white silicon rubber, fully tested in accordance with BS EN 1869.

2. The blankets shall be supplied in container suitable for wall mounting. Fire blankets shall be
provided in the following standard sizes:

20 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

(a) 1100 mm x 1100 mm

(b) 1200 mm x 1200 mm

(c) 1800 mm x 1200 mm

Add

3. The total mass of any fire blanket shall not exceed 4.5 kg.

4.11 FM 200 System

4.11.1 System Description

Amend

1. The FM 200 system shall be sized to provide the required 6.25 – 7.0 % design concentration of
agent in the space protected. A piping arrangement and nozzle shall convey the agent from the
cylinders to the hazard and discharge the agent completely within 10 seconds. The discharge
time is defined to achieve 95 % of the minimum design concentration for flame extinguishment,
based on 20 % safety factor or otherwise required by the Authority Having Jurisdiction. The
piping and nozzles shall be engineered for the specific flow rates required and calculations shall
be furnished with the system layout drawings for review and approval by the Engineer.

4.11.3 Basic Pipes and Pipe Fittings

Amend

2. Pipes shall be UL listed and FM approved. Pipes shall be exterior galvanized steel to ASTM A 53
Grade B seamless sch 40. Couplings to be of roll grooved type, for pipe sizes 65 mm and above.
Couplings to be of cut grooved type, for pipe sizes 50 mm and below.

3. Fittings shall be UL listed and FM approved. Mechanical grooved pipe couplings and fittings as
manufactured by specialised manufacturers shall be used for all fire fighting systems application.

(a) Standard flexible couplings shall be cast ductile iron to ASTM A 536 Grade 65-45-12 with
chlorinated butyl gaskets and heat treated carbon steel bolts and nuts to ASTM A 183,
zinc plated to ASTM B 633
(b) Grooved end fittings shall be cast ductile iron to ASTM A 536 Grade 65-45-12.

21 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

(c) Flange adapters shall be cast ductile iron to ASTM A 536 Grade 65-45-12 with a hinged,
two-piece design, suitable for opening and engaging the grooves, and shall be secured in
position with a tight-fitting lock bolt. Flange Adapter allows a direct transition from flanged
components into a grooved piping system. Flange bolt patterns conform to ANSI class
125 and 150 standards.
(d) Matching steel flanges shall comply with ANSI B 16.5 class 300.

4.11.4 Control Panel

2. The unit shall include the following functions and logic sequence:

(a) Operation of all smoke detection circuits

(b) Operation of all agent discharge circuit

(c) Operation of all audible (and visual) pre-alarm and alarm signals

(d) Provide primary power (and control backup power) for entire system.

(e) Provide interconnection to main fire alarm control panel and BMS.

Delete

4. A set of contacts for connection to pre–action valve shall be provided.

Delete

4.11.15 Automatic Fire Dampers


4.11.16 Basic Identification of Installation

Delete

2. Underground Piping Identification: Provide continuous underground type plastic marker,


located directly over buried line at 150 to 200 mm below finished grade.

Amend

4. Mechanical Equipment Identification: Provide engraved plastic laminate sign or plastic


equipment marker on or near each major item of mechanical equipment and each operational
device, including main control and operating valves.

22 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Add

4.11.21 Enclosure Integrity Test

1. Enclosure integrity test shall be performed as per clause 7.7.2.3 of NFPA 2001 (2012 edition).

End of Part 4

23 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1
Part 5
5 Part 5 Testing and Commissioning

5.1 General

5.1.2 References

Add

2. The following standards are referred (for fire protection systems) to in this Part:

NFPA 13 Standard for the Installation of Sprinkler Systems


NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire
Protection Systems
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems

5.2 Testing, Start-up and Commissioning

5.2.1 General

Add

2. (h) Sprinkler heads


(i) All valves
(j) Gas discharge nozzles
(k) Fire extinguishers
(l) Fire pump units
(m) FM 200 system package

Amend
3. The fire controller and associated devices and modules shall be tested in accordance with the
guidelines set out in relevant NFPA and the testing instructions provided by the manufacturer.

Add

10. Leak Test: After installation, charge systems and test for leaks. Repair leaks and retest until no

24 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

leaks exist.

11. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and
equipment.

12. Flush, test, and inspect sprinkler and hose systems according to NFPA, "Systems Acceptance"
Chapter.

13. Energize circuits to electrical equipment and devices.

14. Coordinate with fire alarm tests. Operate as required.

15. Coordinate with fire-pump tests. Operate as required.

16. Verify that equipment hose threads are same as local fire-department equipment.

17. Fire system will be considered defective if it does not pass tests and inspections.

18. Prepare test and inspection reports.

19. Enclosure integrity test for FM 200 protected rooms.

Amend

5.3 Maintenance

5.3.2 System Spare Parts

1. The Contractor shall provide a detailed list of the system spare parts as per the relevant
standards that shall be kept on-site for maintenance of the system. The system spare parts which
shall be considered for inclusion in the list include the following:

(a) Heat detectors


(b) Smoke detectors
(c) Flame detectors
(d) Call points
(e) Alarms
(f) Beacons
(g) Door retention units
(h) Fuses
(i) Circuit breakers.
(j) Sprinkler Heads
(k) Hoses
(l) Gas discharge nozzles
(m) Fire extinguishers
(n) Fire pump spares

25 M007-MML-FRS-SPE-00001 Rev 0.1 04 August 2014


Document uncontrolled when printed
Particular Specification for Fire Fighting and Fire Alarm Works for Buildings – Education City
Doha Major Stations M007-MML-FRS-SPE-00001 Rev 0.1

Amend

5.4 Training

5.4.1 General

1. The contractor shall provide details of the training required by personnel to operate and maintain
the fire protection, fire detection and alarm system.

End of Part 5