You are on page 1of 8

engineers newsletter providing insights for today’s

hvac system designer

energy-conscious design ideas


Air-to-Air Energy Recovery
from the authors… exchangers (sensible-energy wheels).
Energy consumption costs money, Energy-Recovery All of these devices perform identically
uses natural resources, increases air Technologies on the psychrometric chart; only their
pollution, and contributes to global “Air-to-air energy recovery” refers to effectiveness differs.
warming. We all share responsibility for the transfer of sensible heat, or
prudent energy use. sensible and latent heat, between air Total-energy recovery systems not
streams. The 2000 ASHRAE only transfer sensible heat, but latent
The mechanical heating, ventilating, Handbook—Systems and Equipment heat as well—that is, energy stored in
and air-conditioning (HVAC) system compares the most common water vapor in the air stream. Such
accounts for a sizable portion of a technologies for air-to-air energy systems raise and lower both the dry
building’s energy costs. Heat gains and recovery. bulb and dew point of an air stream.
losses from various sources must be
offset to create a comfortable, healthy Sensible-energy recovery systems Common examples of total-energy
indoor environment. Discarded heat transfer only sensible heat. Adding recovery devices include total-energy
from one location may be useful sensible heat raises an air stream’s dry- rotary heat exchangers (also known as
elsewhere in the building, so it’s logical bulb temperature; removing sensible total-energy wheels) and fixed-
(and often cost-effective) to recover heat lowers the dry bulb. (Removing membrane heat exchangers.
energy that might otherwise be wasted sensible heat may cause condensation,
… particularly in a time of rising energy too, but it never prompts moisture
costs and deregulated utility rates. transfer to the colder air stream.)
Why Recover Energy?
Common examples of sensible-energy To help answer this question and to
recovery devices include coil loops, frame our discussion of air-to-air energy
fixed-plate heat exchangers, heat pipes, recovery, let’s categorize building
and sensible-energy rotary heat ventilation systems based on the
source of the air supplied to occupied
spaces.
Worth the Risk?
Questions about reliability have Dedicated outdoor-air systems
historically dogged rotary energy-recovery supply only first-pass outdoor air. For
devices. Consequently, many designers are
this discussion, a central air handler
reluctant to reduce heating-plant capacity,
even though the total-energy wheel makes (with a mechanical cooling coil) delivers
the extra heating capacity redundant. the ventilation air either:

A wheel differs little from a supply fan, ■ at low temperature, usually to local
however. If the wheel “breaks” due to a
mixed-air units; or
failed bearing, belt, or motor, the faulty
component must be fixed to assure ■ at space-neutral temperature,
continued operation of the system. As
usually to a mixing plenum or
wheels become more widely used and
accepted, reductions in heating-plant directly to each space.
capacity should become more common. ■

© 2000 American Standard Inc. All rights reserved Volume 29, No. 5 ■
Mixed-air systems supply a blend of Table 1. Applications for Air-to-Air Energy Recovery
outdoor air and recirculated return air to Ventilation System Energy-Recovery Technology
each space. The central air handler
Supply-Air Outdoor-Air
delivers the supply air either: Source Temperature Supply-Air Tempering Preconditioning
Dedicated Cold Not applicable ■ Sensible or total
■ at modulated temperature and outdoor air
Neutral ■ Sensible ■ Sensible or total
constant volume, usually to a single (parallel or series)
space; or Mixed air Modulated ■ Sensible ■ Sensible or total
(outdoor air plus (constant volume) (parallel or series)
■ at low temperature and varying recirculated return air)
Cold Not applicable ■ Sensible or total
volume, usually to multiple spaces. (variable volume)

Within the context of these ventilation


systems, recovered energy can be Tempering Supply Air. Dedicated the supply air. “Series” transfer of
used for two purposes: [1] to temper outdoor-air systems designed to deliver energy, also shown in Figure 1, reduces
(or reheat) supply air for independent cold, dry ventilation air to other (usually the need for tempering with new
control of space latent and sensible mixed-air) units do not require supply- energy. It also permits a reduction of
loads, or [2] to precondition outdoor air tempering, so energy recovery is not cooling-plant capacity when compared
air as it enters the building for suitable for that purpose. with other strategies for supply-air
ventilation. Only systems that control tempering.
supply-air dew point or space relative The opposite is true of dedicated
humidity are candidates for supply-air outdoor-air systems designed to deliver Warming the supply air to neutral
tempering. Any system may use neutral, dry ventilation air (usually temperature using series heat transfer
preconditioning to reduce the outdoor- directly to occupied spaces or to ceiling may require capacity control to avoid
air load. Some systems benefit from plenums). Sensible-energy recovery overheating the supply air when it is
both supply-air tempering and outdoor- may benefit such systems because it warm outside. Also, supplemental heat
air preconditioning. Table 1 summarizes offers a “reheat” alternative that may be warranted when the outdoor-air
these applications of air-to-air energy complies with energy codes and temperature is too cool to provide
recovery. standards. It may also decrease first sufficient tempering.
cost and operating cost when
Tempering supply air requires sensible- compared with approaches that use Mixed-air, constant-volume systems
energy recovery to raise the dry-bulb new energy for tempering. that deliver variable-temperature supply
temperature of the supply air without
changing its dew point. Total-energy As depicted in Figure 1, sensible heat
recovery would defeat the purpose of may be recovered from the exhaust air
Figure 1. Sensible-Energy Recovery
tempering during dehumidification. stream and transferred to the supply to Temper Dedicated Outdoor Air
Supply-air tempering is only needed air. Any sensible-energy recovery
during mechanical cooling operation. technology can be used. Coil-loop
systems are shown because they are
Outdoor-air preconditioning offers usually inexpensive and can be adapted
heat-recovery benefits during both to various system designs.
mechanical cooling and heating
operation. System economics “Parallel” recovery of energy saves the
determine whether preconditioning cost of tempering (reheating) the Parallel recovery (stream to stream)
should employ sensible- or total-energy supply air with new energy. It does not
recovery. Often, the savings in first cost reduce the first cost of the cooling
and operating cost make total-energy plant, however, when compared to
recovery the obvious best choice. supply-air tempering with new energy.

Alternatively, sensible heat may be


transferred from the outdoor air Series transfer (upstream to downstream)

upstream of the dehumidifying coil to

■ 2 Trane Engineers Newsletter — Vol. 29, No. 5


air also need supply-air tempering if temperature supply air to local VAV Any energy-recovery system used to
they directly control both temperature terminals, do not require supply-air precondition outdoor air is subject to
and relative humidity in the space. Such tempering at the central air handler. frost buildup during cold weather.
systems can usually benefit from Although some spaces may need local Sensible-energy recovery systems
sensible-energy recovery or transfer. supply-air tempering (reheat) at part must include controls to prevent frost
load, local air-to-air energy recovery is formation when the temperature
Figure 2 illustrates two arrangements. not economically feasible. outside drops below 28°F (estimated
“Parallel” recovery transfers sensible for return air at roughly 30 percent
energy from return air to supply air; it Preconditioning Outdoor Air. relative humidity). The frost-prevention
can eliminate the cost of tempering Buildings must be ventilated with threshold for total-energy recovery
with new energy, but will not reduce outdoor air to prevent the buildup of systems is much lower, about –5°F,
the first costs associated with heating- contaminants generated indoors. Any because they remove moisture from
and cooling-plant capacities. sensible- or total-energy recovery the exhaust air stream.
technology can precondition outdoor air
The “series” arrangement transfers brought into the building by any of the Frost can be avoided either by reducing
sensible energy from the mixed air four ventilation systems in Table 1. In energy-recovery capacity to raise the
entering the cooling coil to the supply summer, total-energy recovery can surface temperature of the heat
air leaving the cooling coil. It reduces or precool and pre-dry outdoor air by exchanger, or by preheating the outdoor
eliminates the need for tempering with rejecting both sensible and latent heat air before it enters the heat exchanger.
new energy; the mixed air is usually to the exhaust air. In winter, it can
warm enough to temper during most preheat and pre-humidify outdoor air by For total-energy systems, preheating
conditions that require removing both sensible and latent heat extends operating-cost savings by
dehumidification. from the exhaust air. permitting continued energy recovery

Unlike its application in dedicated


outdoor-air systems, series energy Determining Effectiveness and Energy Transfer
transfer in mixed-air systems does not ARI Standard 1060–2000, Rating For a given heat-exchanger geometry, ε
reduce cooling-plant capacity. That’s Air-to-Air Energy Recovery Ventilation can be determined at test conditions for
because no energy transfer occurs at Equipment, provides the following various flow rates. Generally, as the
the design cooling condition. equation to describe the effectiveness of an airflow rate decreases, ε increases but the
air-to-air heat exchanger used to recover overall energy transfer decreases.
energy:
Mixed-air, variable-air-volume (VAV) How much heat will a total-energy
ws ⋅ ( x1 – x2 ) we ⋅ ( x4 – x3 )
systems, which deliver constant- ε = ---------------------------------------- = ---------------------------------------- recovery device transfer? The answer lies
w mi n ⋅ ( x 1 – x 3 ) w min ⋅ ( x 1 – x 3 )
in this equation:

Figure 2. Sensible-Energy Recovery where: Q t = ε ⋅ 4.5 ⋅ V min ⋅ ( h 1 – h3 )


to Temper Mixed Air ε = sensible, latent, or total
effectiveness where:
x1 = dry bulb (°F), humidity ratio Qt = total heat flow, Btu/h
(gr/lb), or enthalpy (Btu/lb) of Vmin = the smaller airflow (supply or
entering supply air exhaust), cfm
x2 = dry bulb (°F), humidity ratio h1 = entering supply-air enthalpy,
(gr/lb), or enthalpy (Btu/lb) of Btu/lb
leaving supply air h3 = entering exhaust-air enthalpy,
x3 = dry bulb (°F), humidity ratio Btu/lb
(gr/lb), or enthalpy (Btu/lb) of
Parallel recovery (stream to stream)
entering exhaust air For sensible heat transfer,
x4 = dry bulb (°F), humidity ratio
(gr/lb), or enthalpy (Btu/lb) of Q s = ε ⋅ 1.085 ⋅ V m in ⋅ ( t 1 – t 3 )
leaving exhaust air
ws = mass flow rate of supply air where:
we = mass flow rate of exhaust air Qs = sensible heat flow, Btu/h
wmin = the smaller mass flow rate t1 = entering supply-air dry bulb,
(supply or exhaust air) °F
t3 = entering exhaust-air dry bulb,
°F ■
Series transfer (upstream to downstream)

“providing insights for today’s HVAC system designer” 3 ■


during very cold weather. On the other “Subsidizing” First Cost. To Figure 4. Design Parameters for
hand, reducing energy-recovery demonstrate, consider the HVAC Example School in Jacksonville, Florida
capacity at the heating-design condition system designed for a year-round
reduces first-cost savings in the heating school in Jacksonville, Florida. (Figure 4 HVAC system
plant and extends the payback period outlines the design conditions and ■ 2,600 operating hours annually
for the investment in energy-recovery airflows.) A total-energy wheel in the ■ central air handler with total-energy wheel,
equipment. school’s central air handler 82% effective
■ separate bathroom exhaust
preconditions 10,000 cfm of outdoor
Note: Although the schematics in this air. Local bathroom exhaust and Cooling design
newsletter don’t show the combined exfiltration limit central exhaust airflow ■ Outdoor air: 96°F DB, 76°F WB
use of energy recovery for supply-air to 7,000 cfm. 39.31 Btu/lb enthalpy
■ Return air: 78°F DB, 63.5°F WB
tempering and outdoor-air 28.81 Btu/lb enthalpy
preconditioning, coincident application The total-energy wheel, operating
Heating design
of both arrangements may be beneficial with unbalanced airflow and an
in certain cases and should be effectiveness of 82 percent, removes ■ 31°F DB outdoor air
■ 70°F DB return air
analyzed. Total-energy wheels are 270,000 Btu/h from the outdoor air at
depicted because they recover both the design cooling condition, which Design airflows
sensible and latent energy, which reduces the design capacity of the ■ 10,000 cfm outdoor air
usually makes them the most cost- cooling plant by 22.5 tons. At an ■ 7,000 cfm central exhaust air
effective choice for preconditioning. incremental cost of $500 per ton, the ■ 2,500 cfm local exhaust air (bathroom)

resulting cooling-plant savings of ■ 500 cfm exfiltration

Our investigations show that when $11,300 can be used to subsidize the
preconditioning outdoor air, a total- cost of the wheel.
energy wheel provides the greatest recovers 243,000 Btu/h from the
favorable impact on first cost— and Although the total-energy wheel exhaust air. Wheel operation can
usually the best payback potential. Let’s removes both sensible and latent reduce the design capacity of the
look more closely at the operation of energy from the exhaust air, only the heating plant as well as its first cost.
systems that use total-energy recovery sensible portion can be used to reduce Assuming an incremental cost of
to precondition outdoor air. heating-plant capacity during the $20 per 1,000 Btu/h, the resulting
heating season. Without the bathroom heating-plant savings approximate
exhaust, the total-energy wheel (still $4,900.
with an effectiveness of 82 percent)
Preconditioning for
Dedicated Outdoor Air
A system that includes a dedicated
Figure 3. Control Modes for Preconditioned Outdoor Air and Neutral Supply Air
outdoor-air unit (Figure 3) can benefit
from preconditioning with total-energy
recovery, if properly applied and example school in
controlled. This holds true whether the Jacksonville, Florida
dedicated air handler delivers the
preconditioned outdoor air to other
mixed-air units or directly to the
occupied spaces. full recovery,
RA partial cooling,
no recovery, h
partial tempering
total- (shown) partial cooling, RA
or sensible-energy partial tempering SA
SA DP
recovery
partial no recovery,
full recovery, recovery partial cooling
supplemental heating, only partial recovery,
supplemental preheat full recovery, partial cooling
supplemental heating
SAT

RAT

frost threshold critical temperature

■ 4 Trane Engineers Newsletter — Vol. 29, No. 5


Note: In very cold climates, the latent In either location, the savings in plant supplemental heat to maintain the
energy (moisture) recovered from the capacities can at least partially fund the supply-air dry bulb.
exhaust air can also be used to offset investment in the wheel and associated
the first cost and operating cost of the ductwork, as well as the incremental Region 2: Partial recovery, partial
humidification system. increase in fan horsepower. cooling. The outdoor conditions that
this region represents are found mostly
Despite reducing the effectiveness Proper Operation. A dedicated, in hot, dry climates. Using the exhaust-
of the wheel to 72 percent, ducting neutral ventilation system configured air bypass damper, modulate the
the bathroom exhaust to the central air for preconditioning outdoor air, as capacity of the total-energy wheel to
handler would improve airflow balance. shown in Figure 3, can be operated in recover as much energy as possible
It would also increase overall energy seven distinct, psychrometrically while maintaining the supply-air dew
recovery— cutting 26.9 tons ($13,500) defined modes (Table 2). Proper point at or below the target. Modulate
from the cooling plant and operation within each mode and proper the capacity of the cooling coil to
290,000 Btu/h ($5,800) from the transition between modes maximizes maintain the supply-air dry bulb.
heating plant. Plant savings grow from energy savings and minimizes the
$16,200 to $19,300. Clearly, adding the payback period. Note: Varying the wheel’s rotational
bathroom exhaust to the central air speed is often used to modulate the
stream makes better use of the Note: Other unit configurations and capacity of the wheel rather than
additional investment in energy control schemes may require the varying the position of the exhaust-air
recovery … and not just in Jacksonville. definition of additional and/or different bypass damper. We prefer the bypass
modes of operation. damper because it is less expensive to
The analysis for an identical school in install and operate, is easier to control,
Minneapolis indicates that the total- Region 1: Full recovery, partial and operates stably over a wider range
energy wheel provides additional plant cooling, partial tempering. All energy of conditions.
first-cost savings: $19,600 to $22,600 recovered at these outdoor conditions
($8,300 to $9,800 in the cooling plant, lessens the mechanical cooling load. To Region 3: No recovery, partial
$11,300 to $12,800 in the heating recover as much cooling energy as cooling. Operating the wheel at these
plant). possible, run the total-energy wheel psychrometric conditions would
and modulate the cooling coil and increase the cooling load rather than
decrease it. To avoid recovering
unwanted heat, turn off the total-energy
wheel. Open the bypass damper to
Table 2. Control Modes for Preconditioned Outdoor Air and Neutral Supply Air divert the exhaust air stream around
Annual Operation, hr (%) b the inactive wheel, thereby reducing
Control Mode
(see Figure 3) Psychrometric Conditions a Jacksonville, Fla. Minneapolis, Minn. fan horsepower. Modulate the cooling
1 Full recovery, partial cooling, OA enthalpy > RA enthalpy 1,584 hr (61%) 468 hr (18%)
coil to maintain the supply-air dry-bulb
partial tempering OA DP > SA DP target temperature.
2 Partial recovery, OA DB > RA DB 15 hr (<1%) 20 hr (<1%)
partial cooling OA DP < SA DP target Region 4: No recovery, partial
3 No recovery, SA DB < OA DB < RA DB 42 hr (<2%) 34 hr (<2%) cooling, partial tempering. As in
partial cooling OA DP < SA DP target Region 3, operating the wheel would
4 No recovery, partial cooling, OA enthalpy < RA enthalpy 414 hr (16%) 333 hr (13%) actually increase the mechanical
partial tempering OA DP > SA DP target
cooling load. To avoid unnecessarily
5 Partial recovery only OA DB < SA DB 76 hr (3%) 61 hr (2%)
adding heat and moisture, turn off the
OA DP < SA DP target [151 hr (6%)] [165 hr (6%)]
total-energy wheel, open the bypass
6 Full recovery, OA DB < critical temperature 469 hr (18%) 1,640 hr (63%)
supplemental heating [394 hr (15%)] [1,536 hr (59%)] damper, and modulate the cooling coil
7 Full recovery, OA DB ≤ frost threshold 0 hr (0%) 44 hr (<2%)
and supplemental heat to maintain the
supplemental heating, supply-air dry bulb.
supplemental preheat
a OA = outdoor air, RA = return air, SA = supply air, DB = dry bulb, DP = dew point
b Annual operation is based on 10,000 cfm of outdoor air and 7,000 cfm of exhaust air. Values enclosed in brackets []
represent annual operation based on 9,500 cfm of exhaust air (i.e., the addition of the bathroom exhaust).

“providing insights for today’s HVAC system designer” 5 ■


Region 5: Partial recovery only. Region 7: Full recovery, distribution, our discussion considers
Increased hours in this mode equate to supplemental heating, supplemental only VAV (variable-air-volume) systems.
fewer hours of heating-plant operation. preheat. To protect against frost
Modulate the heating capacity of the formation on the exhaust side of the “Subsidizing” First Cost. For the
total-energy wheel by controlling wheel, the wheel surface temperature same quantity of outdoor air, the total-
bypass airflow to maintain the supply- must be maintained above the exhaust- energy wheel provides the same
air temperature. (This strategy avoids air threshold temperature for frost. cooling- and heating-plant savings,
overheating the supply air.) Only fan Modulated, supply-side preheat regardless of how the supply air is
energy is required in this mode. The accomplishes this task while distributed.
total-energy wheel is not at full heating maximizing energy-recovery capacity.
capacity, so the recovered energy Remember the cost savings described
eliminates the heating-plant load. Note: All energy-recovery devices, for the school in Jacksonville? Adding a
both sensible and total, require frost total-energy wheel to the dedicated
A quick review of Table 2 reveals that protection. As noted earlier, avoid frost- outdoor-air handler permitted
centralizing the bathroom exhaust protection methods that reduce heat- downsizing of the cooling and heating
doubles the hours of Region 5 recovery capacity (for example, slowing plants … and yielded a first-cost
operation in both Jacksonville and the wheel speed). “subsidy” of $16,200 to $19,300. If the
Minneapolis. same school is instead served by a
constant- or variable-volume mixed-air
Note: Don’t make the mistake of system—and the minimum ventilation
continuously operating the wheel at full Preconditioning for requirement is unchanged (10,000 cfm
capacity. Recooling overheated outdoor Mixed Air of outdoor air) — the first-cost
air will increase energy consumption at In mixed-air systems (Figure 5), a “subsidy” of adding a total-energy
the cooling plant. central air handler delivers a blend of wheel remains $16,200 to $19,300.
outdoor air and recirculated return air to
Region 6: Full recovery, one or more occupied spaces. If Proper Operation. Figure 5 illustrates
supplemental heating. To recover properly applied and controlled, such six distinct operating modes for a
as much heat as possible from the systems can benefit from mixed-air system. These control modes
exhaust air when it’s cold outside, turn preconditioning with total-energy are summarized in Table 3; a brief
on the total-energy wheel (with bypass recovery. Although the benefit exists description of each mode follows.
damper closed), and modulate the for constant- and variable-volume air
heating coil to control the supply-air dry
bulb. Implement this mode when the
outdoor air is colder than the “critical
temperature.” Table 3. Control Modes for Preconditioned Mixed Air and Cold Supply Air (VAV)
Annual Operation, hr (%) b
Control Mode
Note: The “critical temperature” is a (see Figure 5) Psychrometric Conditions a Jacksonville, Fla. Minneapolis, Minn.
threshold defined by the supply-air dry 1 Full recovery, OA enthalpy > RA enthalpy 1,585 hr (61%) 468 hr (18%)
bulb, return-air dry bulb, and the partial cooling
effectiveness of the wheel at full 2 No recovery, economizer, OA DB > SA DB 672 hr (26%) 701 hr (27%)
capacity. It marks the condition at supplemental cooling OA enthalpy < RA enthalpy
which the wheel, operating at full 3 No recovery, OA DB < SA DB 281 hr (11%) 410 hr (16%)
heating capacity, can no longer economizer only OA airflow > minimum set point

maintain the target supply-air dry bulb. 4 Partial recovery only OA airflow = minimum set point 62 hr (2%) 496 hr (19%)
OA DB > critical temperature [62 hr (2%)] [853 hr (32%)]
5 Full recovery, OA DB < critical temperature 0 hr (0%) 481 hr (18%)
Decreased hours at Region 6
supplemental heating [124 hr (5%)]
conditions mean decreased hours of
6 Full recovery, OA DB ≤ frost threshold 0 hr (0%) 44 hr (<2%)
heating-plant operation. supplemental heating,
supplemental preheat
a OA = outdoor air, RA = return air, SA = supply air, DB = dry bulb, DP = dew point
b Annual operation is based on 10,000 cfm of outdoor air and 7,000 cfm of exhaust air. Values enclosed in brackets []
represent annual operation based on 9,500 cfm of exhaust air (i.e., the addition of the bathroom exhaust).

■ 6 Trane Engineers Newsletter — Vol. 29, No. 5


Region 1: Full recovery, partial Figure 5. Control Modes for Preconditioned Mixed Air and Cold Supply Air (VAV)
cooling. All energy recovered at these
total- (shown) or sensible-
conditions reduces the mechanical example school in
energy recovery
cooling load. To maximize the recovery Jacksonville, Florida

of cooling energy, run the total-energy


wheel and modulate the cooling coil to
maintain the supply-air dry bulb.

Implement this mode when outdoor-air RA


enthalpy exceeds return-air enthalpy.
Basing operation on temperature rather full recovery,

SAT
than enthalpy not only misses many full recovery, supplemental heating, partial cooling
supplemental preheat
hours of energy recovery, but also no recovery,
RA
yields many hours of wheel operation full recovery, partial no recovery, economizer plus h
that add to the cooling-plant load. supplemental heating recovery only economizer only partial cooling

Region 2: No recovery, economizer frost threshold critical temperature at


plus partial cooling. This is the minimum outdoor airflow
familiar “economizer-plus-mechanical
cooling” mode. No energy is available
for recovery, so wheel operation would Region 3: No recovery, economizer Jacksonville, Region 4 conditions would
increase the mechanical cooling load only. Again, no energy is available for increase from 540 hours (21percent) to
and operating cost. To avoid recovering recovery at Region 3 conditions. To 897 hours (34 percent) in Minneapolis.
unnecessary heat and moisture, turn avoid recovering unnecessary heat,
off the total-energy wheel, open both turn off the total-energy wheel, open Note: Don’t operate the total-energy
bypass dampers, and modulate the both bypass dampers, and modulate wheel continuously at full capacity
cooling coil to maintain the supply-air outdoor airflow to maintain the when outdoor conditions correspond to
dry bulb. Diverting airflow around the supply-air dry bulb. Region 2, Region 3, or Region 4.
wheel when it’s off saves fan energy. It Recooling overheated outdoor air
also allows the wheel to be sized for Note: “Free cooling” (Region 2 and increases energy consumption at the
ventilation airflow only, not economizer Region 3) with outdoor air accounts for cooling plant.
airflow. 37 percent of the school’s operating
hours in Jacksonville compared to Region 5: Full recovery,
43 percent in Minneapolis … not much supplemental heating. When it’s
difference despite the disparity of cold outside, turn on the total-energy
What about Operating Costs? climates. wheel (with bypass dampers closed) to
Typically, the “real” money in air-to-air recover as much heat as possible from
energy recovery accrues from the first-cost Region 4: Partial recovery only. the exhaust air. Modulate the heating
“subsidy” (plant-capacity savings applied Increased hours in this mode mean coil to control the supply-air dry bulb.
to the cost of the wheel) rather than lower fewer hours of heating-plant Decreased hours at Region 5
operating costs. Still, if first-cost savings
operation.To maintain the supply-air dry conditions mean that the heating plant
do not entirely offset the initial
investment in the wheel, operating-cost bulb without overheating, modulate the operates less.
savings may quickly make up the capacity of the total-energy wheel by
difference. controlling bypassed exhaust airflow Region 6: Full recovery,
with the supply-side bypass damper supplemental heating, supplemental
The interaction between wheel control
closed. Only fan energy is required in preheat. Modulated, supply-side
modes and economizer operation justifies
a detailed economic analysis using a tool this mode because the wheel is not at preheat protects against frost formation
such as TRACE™ or DOE-2. Such an full capacity. Recovered energy while maximizing energy-recovery
analysis can predict the length of the satisfies the entire heating-plant load. capacity. Implement this mode when
payback period based on building location, the exhaust-air temperature equals or is
building type, HVAC system type, HVAC
Although centralizing the bathroom less than the frost-threshold
system control, and local utility rates. ■
exhaust would not extend operation in temperature.

“providing insights for today’s HVAC system designer” 7 ■


Note: Many designers reduce heat- bathroom exhaust. In these
recovery capacity to keep the surface applications, bathroom-exhaust airflow
of the wheel warm, thereby avoiding must be sensed and maintained at
frost. This practice limits first-cost constant flow.
savings for the heating plant. Preheat
keeps wheel capacity high when you Consider these important control
costs of the heating and cooling
need it and can substantially reduce the alternatives the next time you design
plants.
first cost of the heating plant. an HVAC system that preconditions
outdoor air using total-energy recovery: ■ Implement a thoughtful control
strategy to lower operating costs and
■ Control wheel capacity using bypass shorten the payback period.
What about Controls? dampers to minimize fan energy and
Our necessarily high-level description increase control stability. Efficient HVAC systems demonstrate
of energy-recovery operation didn’t ■ Use preheat for freeze protection to good stewardship by the people who
provide control details. Suffice it to say minimize the first cost of the heating design and operate them. Don’t throw
that an air handler with total-energy- plant. away reusable energy unnecessarily. ■
wheel preconditioning poses a control
challenge in both dedicated-outdoor-air
By Dennis Stanke, staff applications
and mixed-air systems.
engineer; John Murphy, senior
Sage Advice applications engineer; and Brenda
Factory-installed controls with
Prudent energy use is important for any Bradley, information designer, The Trane
preprogrammed control sequences can
HVAC system, but it is particularly Company.
minimize controls engineering in the
relevant for applications such as
field and assure a system that delivers
schools, which require large amounts of You can find this and other issues
optimum performance.
outdoor air for proper ventilation. of the Engineers Newsletter in the
Through our discussion of energy- commercial section of www.trane.com.
When bypass dampers control wheel
recovery technologies for various To comment, send a note to The Trane
capacity, air pressure in the mixing box
ventilation systems, we identified ways Company, Engineers Newsletter Editor,
fluctuates; therefore, outdoor airflow
to increase the heating and cooling 3600 Pammel Creek Road, La Crosse,
must be measured and the intake
benefits derived from energy WI 54601, or e-mail us from the Trane
damper must be modulated to maintain
consumed by an HVAC system: Web site.
the minimum outdoor airflow. Building
pressure must be controlled as well.
■ For systems that use a cold coil to
control the latent load, apply energy
Note that the return-air pressure also
recovery to reduce the operating
changes with wheel capacity when the
cost of tempering.
central mixed-air unit includes
■ In any air distribution system, use
total-energy recovery for outdoor-air
preconditioning to reduce the first

The Trane Company


An American Standard Company
www.trane.com
Trane believes the facts and suggestions presented here to be accurate. However,
For more information, contact your
local district office or e-mail us at final design and application decisions are your responsibility. Trane disclaims
comfort@trane.com any responsibility for actions taken on the material presented.

■ 8 ENEWS-29/5

You might also like