You are on page 1of 59

Contract No.

52054
Office 3, St. Paul’s Place, Sheffield

SPRINKLER INSTALLATION
OPERATION & MAINTENANCE MANUAL

for

OFFICE 3
St. PAUL’S PLACE
SHEFFIELD
S1 2JF

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

CONTENTS

1. Description of Works & General Operational Information

2. As Fitted Sprinkler Protection Drawings

3. Completion & Pressure Test Certificates

4. Technical Data Sheets

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

1.

Description of Works &


General Operational Information

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Brief Description of Works

Works carried out to new multi-story office building.

New installation (No. 1 Wet) comprising the following:

• 2no. Water storage tanks located on roof with a combined effective


capacity of 64,740 litres fed from infill pipework with a minimum flow rate
of 500L/min.
• 80mm Viking Installation Control Valve and associated rising pipe work to
levels Ground through Nine (See Section 4 for Manufacturers Data
Sheet).
• Distribution mains, supported from existing roof structure and feeding
range pipework array (as shown on our drawings: See Section 2).
• Flexible 2nd fix feeds to ceiling sprinklers, supported from support bars
fixed to the ceiling grid.
• Ground floor has the addition of sprinkler protection above the ceiling fed
directly from the range pipework.
• Ground floor void sprinklers are Viking VK345 – K80 – Standard
Response (See Section 4 for Manufacturers Data Sheet).
• Ceiling sprinklers throughout are Viking VK302 – K80 – Quick Response
(See Section 4 for Manufacturers Data Sheet).

New installation (No. 2 Dry) comprising the following:

• 100mm Viking Installation Control Valve and associated pipe work to Basement
Level. (See Section 4 for Manufacturers Data Sheet).
• Distribution mains, supported from existing roof structure and feeding
range pipework array (as shown on our drawings: See Section 2).
• Basement soffit sprinklers are Viking VK345 – K80 – Standard Response
(See Section 4 for Manufacturers Data Sheet).

New Dry Riser comprising the following:

• Twin Breeching Inlet cabinet located at ground floor level adjacent fire
brigade entrance on external wall.
• Landing valve outlet at each level in building core area.

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Operable & Maintainable Equipment

1 no. Electric booster pump set located in sprinkler pump room at basement level.

2no. Electric fire pumps located in sprinkler pump room at basement level.

1no. 80mm Wet installation control valve set, located in sprinkler pump room at basement
level.

2no. 100mm Dry installation control valve sets located in sprinkler pump room at basement
level.

The new installation valves are fitted with by-pass arrangements for use during routine valve
maintenance.

The pressure switches provided on the installation control valve sets (wired by others)
should be linked to the main building fire alarm system; indicating activation.

In the event of a fire the sprinkler system is fully automatic and does not require any
assistance.

In order to comply with BSEN 12845: The new installation valve sets should be serviced
every six months by a competent company, fully conversant with the requirements of LPC
Rules for Automatic Sprinkler Installations: incorporating BSEN 12845.

Should you wish us to provide a quotation for the service and maintenance, please contact
our Service Department on 0161 336 0001 or alternatively you can send an email to
Terri.Ball@adpsrinklers.co.uk.

STORAGE ARRANGEMENTS AND LIMITATIONS

Although the sprinkler system is designed to fight the fire it relies on the early response to
prevent the fire spread. The faster the sprinklers operate the more efficient they will be at
controlling and/or suppressing the fire.

Storage arrangements and methods play a vital role in keeping the sprinkler system fully
efficient.

Offices and all other rooms should always be kept tidy and a clearance of at least 500mm
should be maintained between the top of any goods and the sprinkler heads at the ceiling
level.

If in doubt seek advice from us or your insurance company.

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

2.

As Fitted Sprinkler Protection Drawings

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Drawing Drawing Title Date Rev


Number

Basement Level
52054-B00 28.01.2016 As Fitted
Sprinkler Layout

Ground Floor 28.01.2016


52054-000 Sprinkler Layout As Fitted

First Floor
52054-001 28.01.2016 As Fitted
Sprinkler Layout

Second Floor
52054-002 Sprinkler Layout 28.01.2016 As Fitted

Third Floor
52054-003 28.01.2016 As Fitted
Sprinkler Layout

Fourth Floor
52054-004 28.01.2016 As Fitted
Sprinkler Layout

Fifth Floor
52054-005 28.01.2016 As Fitted
Sprinkler Layout

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Drawing Drawing Title Date Rev


Number

Sixth Floor
52054-006 28.01.2016 As Fitted
Sprinkler Layout

Seventh Floor
52054-007 28.01.2016 As Fitted
Sprinkler Layout

Eighth Floor
52054-008 28.01.2016 As Fitted
Sprinkler Layout

Ninth Floor
52054-009 28.01.2016 As Fitted
Sprinkler Layout

Roof Level
52054-010 28.01.2016 As Fitted
Sprinkler Layout

Elevations &
52054-011 28.01.2016 As Fitted
Sections Layout

Sprinkler System
52054-012 Electrical 28.01.2016 As Fitted
Schematic

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Drawing Drawing Title Date Rev


Number

Sprinkler Pump
52054-013 28.01.2016 As Fitted
Room Layout

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

3.

Completion & Pressure Test Certificates

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
COMPLETION CERTIFICATE – SPRINKLER SYSTEM

AD Sprinkler Protection Ltd hereby certify that we have completed on the 2nd March 2016 an
automatic sprinkler installation designed and erected in accordance with all the appropriate
requirements and, except as detailed here, recommendations of LPC Rules for Automatic Sprinkler
Installations incorporating BS EN 12845 and associated Technical Bulletins.

Contract: Office 3, St. Paul’s Place Contract No: 52054

Client: Imtech Engineering Services

Address: Office 3, St. Paul’s Place, Sheffield, S1 2JF

PROTECTED AREA HAZARD INSTALLATION No OF TYPE & MAKE of


CLASS NUMBER SPRINKLERS SPRINKLERS
Levels 0 through 9 Ceilings OH1 1 925 Viking Model VK302
Levels 0 through 9
OH1 1 9 Viking Model VK345
Cleaners Cupboard Soffit
Level 0 Plenum Void OH1 1 81 Viking Model VK345
Basement Car Park OH2 2 85 Viking Model VK345
Basement Core Area OH2 2 12 Viking Model VK302
Basement Pump Room OH2 2 6 Viking Model VK345
List of Deviations from above Standard:

Omit sprinkler protection below open tread stairs at level 8- Deviation from clause 12.4.10.

DATE: 04/03/2016

NAME: Steve Lacey

SIGNATURE:

FormA8
Date: 17/12/2014
COMPLETION CERTIFICATE – WATER SUPPLIES

AD Sprinkler Protection Ltd hereby certify that we have completed and commissioned on the 2nd
March 2016 an automatic sprinkler water supplies installation designed and erected in accordance
with all the appropriate requirements and, except as detailed here, recommendations of LPC Rules
for Automatic Sprinkler Installations incorporating BS EN 12845 and associated Technical Bulletins
for the minimum requirements for the respective hazard classifications.

Contract: Office 3, St. Paul’s Place Contract No: 52054

Client: Imtech Engineering Services

Address: Office 3, St. Paul’s Place, Sheffield, S1 2JF

Commissioning Date: 02/03/2016

Commissioning Engineers: Steve Lacey of AD Sprinkler Protection Limited


Peter Easton of SPP Pumps Limited

List of Deviations from above Standard:

N/A

DATE: 04/03/2016

NAME: Steve Lacey

SIGNATURE:

Form A8-2
Date: 17/12/2014
Water Storage Tank(s)

Manufacturer 1 2
Type: Superior Supply Tank Superior Supply Tank
LPCB listing: LPS1276 LPS1276
Capacity (Net) m3: 65 25
Reduced capacity / Full capacity: Half Capacity Reduced Capacity
Contents gauge reading 100% 100%
Infill / inflow pipe lagged / Trace heated No No
Inflow proving device / meter fitted Yes Yes
Installed date 07/12/2015 19/11/2015
Sprinkler Pumps

Jockey Pump
Pump Manufacturer and type Lowara 1SV15T – Vertical Multistage
Pump cut in pressure 8.5bar
Pump cut out pressure 9.0bar
Electric Pump
Pump No 1
Motor rating (kw) 45
Qmax 1131.1 l/min @ 6.31 bar
Electric Pump
Pump No 2
Motor rating (kw) 45
Qmax 1131.1 l/min @ 6.31 bar

Form A8-2
Date: 17/12/2014
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

4.

Technical Data Sheets

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Contract No. 52054
Office 3, St. Paul’s Place, Sheffield

Please find below a list of items installed as part of this contract and accompanying
manufacturer’s data sheets on the following pages.

a) Wet Installation Control Valve Set – Viking Model J-1


b) Dry Installation Control Valve Set – Viking Model F-1
c) Water Motor Alarm – Viking Model F-2
d) Alarm Pressure Switch – Viking Model 1381
e) System Pressure Gauge – Viking Model GAU
f) Isolation Butterfly Valves – Viking Model GD20 Grooved
g) Ceiling Sprinkler Head – Viking Model VK302
h) Soffit / Void Sprinkler Head – Viking Model VK345
i) Dry Riser Twin Breeching Inlet Valve
j) Dry Riser Landing Valve

AD SPRINKLER PROTECTION LTD


UNIT 2/8, HEATON MILL, DENTON, MANCHESTER, M34 3RG
TEL: 0161 336 0001 FAX: 0161 336 6608
Form No. F_031914 Rev 14.1 Page 1 of 2

J-1 WET ALARM VALVE


TECHNICAL DATA WITH EUROTRIM FOR
LPCB MARKET

Viking SupplyNet Ltd, Unit 2 Byram House, Newborn Court, Chapel Street, Epworth, DN9 1HQ, United Kingdom
Telephone: +44-1427-871-000 Fax: +44-1427-873-917 Email: vikinguk@vikingcorp.com
1. DESCRIPTION
The Viking Model J-1 Alarm Check Valve serves as a check valve by
trapping pressurized water above the clapper and preventing reverse
flow from sprinkler piping. The valve is designed to initiate an alarm
during a sustained flow of water (such as the flow required by an
open sprinkler) by operating an optional water motor alarm and/or
alarm pressure switch. The valve is made suitable for use on variable
pressure water supplies by adding the optional retard chamber to the
standard trim.

2. LISTINGS AND APPROVALS


cULus Listed

FM Approved

LPCB - 096b/01

CE Certified

3. ORDERING INFORMATION
To order a Viking Eurotrim follow our three step selection process:

TABLE 1: VALVE SIZES AND END CONNECTIONS

End 3” 4” 6” 8”
End DN150
Connection DN80 DN100 DN200
Base Valve & Trim

Connections
Types 89 mm 114 mm 165 mm 168 mm 219 mm
ANSI ET08235 ET08238 ET08244
Step 1:

Flange-Flange PN10 ET08241 ET09111


ET09108 ET09109
PN16 ET12388
ANSI ET08236 ET08239 -- ET08245
Flange-Groove PN10 ET08242 ET09877
ET09535 ET09536 --
PN16 ET12389
Groove-Groove -- ET08237 ET08240 ET09405 ET08243 ET08246

TABLE 2: ALARM TRIM


Step 2:
Alarm
Trim

Part Number Approval Type


19416 LPCB Market

TABLE 3: OPTIONAL COMPONENTS


Components
Optional

Part Number Component


Step 3:

05904B Retard Chamber


880214 Monitoring Switch for Alarm Line Ball Valve
8121960050 Bracket for Monitoring Switch
Form No. F_031914 Rev 14.1 Page 2 of 2

J-1 WET ALARM VALVE


TECHNICAL DATA WITH EUROTRIM FOR
LPCB MARKET
Viking SupplyNet Ltd, Unit 2 Byram House, Newborn Court, Chapel Street, Epworth, DN9 1HQ, United Kingdom
Telephone: +44-1427-871-000 Fax: +44-1427-873-917 Email: vikinguk@vikingcorp.com

4. DIMENSIONS

Size A B C D E F G H I
3” DN80 258.8 184.2 220.0 209.5 395.5 167.1 190.9 158.5 130.2
4” DN100 269.9 187.3 241.0 221.6 416.6 157.2 192.4 161.1 180.2
6” DN150 339.7 257.2 243.2 244.4 418.7 103.6 246.1 185.9 180.2
8” DN200 431.8 211.1 285.7 269.8 461.2 41.7 169.9 211.3 180.2
All dimensions are approximations.

5. MOUNTING INSTRUCTIONS
1. Attach the gauges and their spigots to the
valve (1) 4
2. Attach the base trim to the valve by tightening the
three unions (2)
3. Attach the alarm trim to the base trim by
tightening the union (3)
4. If a retard chamber is required the remove the
½” x ¾” reducer from the alarm line (4) and 1
insert the retard chamber. The reducer has 2
been installed with PTFE tape to allow for easy
removal.
3
February 21, 2013 Dry 121a

TECHNICAL DATA Model F Dry valve trim

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Model F Dry Valve Trim


Valve Size Trim Part Number
3” 10158
4” 08395
6” 09456
Standard Trim Sets include galvanized
nipples and fittings.

4” Dry Valve Shown


Notes: For use with Trim Chart on Page 121b
General Notes:

• Valve must be trimmed as shown. Any deviation from trim size or arrangement may affect the proper operation of the valve.
• All pipe, 3/4” (20 mm) and smaller, shall be galvanized steel except when other materials are specified in the Technical Data for the
system used.
• Dimensions in parentheses are millimeter and may be approximations.
• Viking uses ASME fitting designations. Tees shall be called out in the following order: 1 - Largest outlet on run; 2 - Smaller outlet on run;
3 - Branch size.

Note 1: Connection for electric Alarm Pressure Switch to activate electric alarm panels. NOTE: After the Dry Valve trips, supply to this
location cannot be shut off until the water supply to the Dry Valve is shut off.
Note 2: Water flow alarm connections: 3/4” (20 mm) NPT for Water Motor Alarm (strainer required) and 1/2” (15 mm) NPT for electric
Alarm Pressure Switch to activate electric alarm bells.
Note 3: Recommended location for Air Supervisory Switch.
Note 4: 1” (25 mm) NPT connection for sprinkler.
Note 5: Locate listed Air Maintenance Device (order separately) as close to this connection as possible. Refer to installation standards.
Recommended location for connection of optional Air Maintenance Compressor.
Note 6: Tube must discharge TO OPEN DRAIN. DO NOT crimp or plug tube. Secure tube to 1/2” x 9” nipple below priming water level
test valve with cable tie included in trim kit.

Form No. F_030693 Replaces page 121a-d, dated January 27, 2012.
(Updated figures to show D-3 Drip Check Valve)
Dry ����
121b February 21, 2013

TECHNICAL DATA Model F Dry valve trim

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
February 21, 2013 Dry 121c

TECHNICAL DATA Model F Dry valve trim

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
B C

D
A (VALVE TAKE OUT)

F (4" & 6" VALVES)


F (3" VALVE)

Valve Size A B C D E F
3” 18-1/4” (464) 12-3/16” (310) 10-9/16” (268) 19-13/16” (503) 8-1/16” (205) 16-3/4” (425)
4” 18-1/4” (464) 13-5/16” (338) 10-1/2” (267) 20-3/4” (527) 8-1/16” (205) 13-5/16” (338)
6” 20-1/16” (510) 13-13/16” (351) 10-15/16” (278) 21-7/16” (545) 8-1/16” (205) 13-5/8” (346)
Figure 3 - Dry Valve with Conventional Trim with No Accelerator
B C

F (4" & 6" VALVES)


F (3" VALVE)

A (VALVE TAKE OUT)

Valve Size A B C D E F
3” 18-1/4” (464) 12-3/16” (310) 10-9/16” (268) 34-3/16 (875) 8-1/16” (205) 16-3/4” (425)
4” 18-1/4” (464) 13-5/16” (338) 10-15/16” (278) 34-1/4” (870) 8-1/16” (205) 13-5/16” (338)
6” 20-1/16” (510) 13-13/16” (351) 10-15/16” (278) 35-1/8” (892) 8-1/16” (205) 13-5/8” (346)

Figure 4 - Dry Valve with Conventional Trim with Model D-2 Accelerator
Dry ����
121d February 21, 2013

TECHNICAL DATA Model F Dry valve trim

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

B C

F (4" & 6" VALVES)


F (3" VALVE)
A (VALVE TAKE OUT)

Valve Size A B C D E F
3” 18-1/4” (464) 12-3/16” (310) 10-9/16” (268) 33-1/4” (845) 8-1/16” (205) 16-3/4” (425)
4” 18-1/4” (464) 13-5/16” (338) 10-9/16” (268) 33-3/16” (843) 8-1/16” (205) 13-5/16” (338)
6” 20-1/16” (510) 13-13/16” (351) 10-15/16” (278) 34-3/16 (875) 8-1/16” (205) 13-5/8” (346)

Figure 5 - Dry Valve with Conventional Trim with Model E-1 Accelerator

Form No. F_030693 Replaces page 121a-d, dated January 27, 2012.
(Updated figures to show D-3 Drip Check Valve)
Page 1 of 4

TECHNICAL DATA WATER MOTOR ALARMS

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
The Viking water motor alarms are mechanical devices actuated by a flow
of water. They are designed to sound a continuous alarm while a sprinkler
system operates. An alarm is a required component of every sprinkler
system having more than 20 sprinklers.
A. Features
1. The water motor alarms are tapped 3/4” NPT on the inlet and 1”
NPT on the drain outlet.
2. The water motor alarm package includes a drive shaft 16-3/4”
(425 mm) long for walls 14” (356 mm) thick or less. A special ex-
tension shaft is available for walls up to 30-1/4” (768 mm) thick.
3. The package also includes the required 3/4” (20 mm) NPT strain-
er for installation on the alarm line.
4. Rated water working pressure of Model F-2 is 250 PSI (17.2 bar).
B. Accessories: (order separately)
1. Extension Mounting Cup: Viking Part Number 05957B, Material: 14-Gauge Cold Rolled Steel, UNS-G10080, coated with black
E-coat. The extension mounting cup is required when the wall thickness is less than 3” (76.2 mm). Refer to “INSTALLATION”
instructions. See Figure 2.
2. Closure Plate: For use with Model F-2 only, Viking Part Number 05820B, Material: 16-Gauge Galvanized Steel, UNS-G10080.
The closure plate is required when the Model F-2 Water Motor Alarm gong is mounted on an irregularly surfaced wall. It serves
to prevent birds from entering the inside of the gong. The closure plate also serves as a mounting plate for sheet metal walls.
Refer to “INSTALLATION” instructions. See Figure 2.
3. Special Extension Shaft: Viking Part Number 03312B, Material: Stainless Steel, UNS-S30400. The extension shaft is required
when the F-2 or G-2 Water Motor Alarm is installed on walls from 14” (356 mm) to 30-1/4” (768 mm) thick.

2. LISTINGS AND APPROVALS


Model F-2: Viking Technical Data may be found on
cULus Listed - VPLX The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
FM Approved - Water Motor Gongs The Web site may include a more recent
LPCB Approved edition of this Technical Data Page.
CE - Standard EN 12259-4, EC-certificate of conformity 1725-CPD-H0001
New York City Board of Standards and Appeals - Calendar No. 219-76-SA
Model G-2:
VdS
CE - Standard EN 12259-4, EC-certificate of conformity 1725-CPD-H0001
The 07862 and 07868 Water Motor Alarms Model F-2 and Model G-2 conform to the provision of EN12259-4 standard.
EN12259-4 approvals are provided by:FM Approvals Ltd. 1 Windsor Dials Windsor, Berkshire, UK. SL4 1 RS
Approval Certificate No. issued February 15, 2010.

3. TECHNICAL DATA
Specifications
Available since 1991
Shipping Weight: Model F-2: 11 lbs. (5.0 kg); Model G-2: 13 lbs. (5.9 kg)
Model F-2 Water working pressure: Rated to 300 psi (21 bar); Model G-2 Water working pressure: 175 psi (12 bar)
Material Standards (See Figure 3)
Viking E-coat Spec: SPF02 W01
Ordering Information
Model F-2, Viking Part No. 07862
Model G-2, Viking Part No. 07868

4. INSTALLATION
Locate the water motor on an exterior wall as close as practical to the valve being monitored for water flow. A 3/4” (20 mm) strainer
(included) is required on the alarm line as close as possible to the alarm outlet of the valve being monitored for water flow (or outlet of
the retard chamber, if used). The location must be easily accessible for cleaning.

Form No. F_082789 Rev 15.1


Page 2 of 4

TECHNICAL DATA WATER MOTOR ALARMS

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Figure 1: Accessories
A. Cut a 1-7/16” (36.5 mm) minimum to 1-5/8” (41.3 mm) maximum diameter hole in the building wall to accommodate the 3/4” (20
mm) galvanized spacer pipe. (Note: Spacer pipe is NOT included in Water Motor Alarm Package). The hole through the wall must
be level or pitched slightly downward toward the water motor.
B. Measure the wall thickness.
C. Cut and thread the spacer pipe to a length equal to: The wall thickness minus 1” (25.4 mm). If the extension mounting cup is
used, add an additional 3” (76 mm) to the spacer pipe.
D. Cut the drive shaft (10) to a length equal to: The total wall thickness plus 2-3/4” (70 mm). If extension mounting cup is used, add
an additional 3” (76 mm).
E. File the drive shaft to provide a 3/32” (2.4 mm) x 450 chamfer on both corners of both ends. File off all burrs and insert the drive
shaft into the hole of the striker arm shaft.
F. Slide the spacer pipe over the shaft and thread the end of the spacer pipe into the gong support assembly coupling (12).
G. Slide the closure plate (if used) over the free end of the spacer pipe, up to the back of the gong. If desired, the closure plate may
be fastened to the gong support by using the 9/32” (7.14 mm) diameter hole in the gong support. Use only a flat or round headed
fastener that will not interfere with striker arm movement.
H. Position the support assembly on the exterior wall surface by sliding the free threaded end of the spacer pipe into the hole from
outside the building.
I. On the inside surface of the wall: Slide the wall plate provided (9), over the free threaded end of the spacer pipe. (If an extension
mounting cup is used, place it over the end of the spacer pipe with the flared end toward the wall before sliding the wall plate
into position).

Figure 2
Form No. F_082789 Rev 15.1
Page 3 of 4

TECHNICAL DATA WATER MOTOR ALARMS

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
J. Remove the plastic thread protectors from the threaded openings in the body of the water motor.
K. Attach the water motor assembly by threading the body (3) onto the free threaded end of the spacer pipe. The chamfered ends
of the drive shaft allow it to slide into position as the water motor body is threaded onto the spacer pipe. When the assembly
is properly tightened, the water motor should be positioned with the 1” (25 mm) NPT drain outlet facing downward and the
3/4” (20 mm) NPT alarm line inlet horizontal. See Figures 1 and 3.
L. Attach the gong, the flat washer, and the gong label (16, 17, and 18) to the gong support installed on the exterior surface of the wall,
with the 5/16-18 x 12” (13 mm) screw (19). Note: The flat washer must be installed between the gong and the gong support (17).
M. With galvanized, brass, or other approved corrosion-resistant piping, not less than 3/4” (20 mm) diameter, connect the water
motor inlet to the alarm outlet of the waterflow detecting device. A 3/4” (20 mm) strainer (included) is required on the alarm line
as close as possible to the alarm outlet of the waterflow detecting device (or outlet of the retard chamber if used). The location
must be easily accessible for cleaning.
N. The drain outlet of the impeller housing must discharge to an open drain. Care shall be taken to keep the drain line clean at all times.
O. Note: A water motor drain line that:
1. Has too many fittings, and/or
2. Has a very short length of pipe between the 1” (25 mm) outlet and the first elbow in the water motor drain pipe, and/or
3. Is very long may result in slow drainage and reduced water motor speed. This condition can be remedied by increasing the
drain pipe diameter, increasing the length of pipe to the first elbow, and/or pitching the pipe toward the discharge location.

5. OPERATION (See Figure 3)


When a sprinkler system is activated, water flows from the alarm outlet of the valve, through the 3/4” (20 mm) strainer and alarm line
piping, into the inlet of the water motor. From the 1/8” inlet orifice, the water flows through a nozzle (4), which restricts the flow into
a pressurized stream directed onto the impeller (7). Force from the water stream turns the impeller and drive shaft (10), causing the
striker arm (20) to rotate. The striker (25) impacts against the gong (16), producing a continuous alarm. A minimum of 5 PSI (.34 bar) is
required at the nozzle to cause a continuous alarm. When properly installed, the Model F-2 Water Motor Alarm produces the required
90 decibel output and the Model G-2 produces 100 decibels. After passing through the water motor, the water is discharged through
a 1” (25 mm) drain outlet in the bottom of the impeller housing. The discharged water must be piped through the wall to atmosphere
or to a suitable open drain.

6. INSPECTIONS, TESTS AND MAINTENANCE


Weather-resistant materials are used in the construction of the water motor alarm. At regular intervals, examine and test the water
motor to ensure that the nozzle and drain line are clean and free of obstruction, and that the alarm functions properly. Also, at regular
intervals and before disassembly of the water motor, clean and inspect the alarm line strainer located at the alarm outlet of the water-
flow detecting device, or the outlet of the retard chamber, if used. (Note: Some retard chambers may be equipped with a strainer built
in). For minimum maintenance and inspection requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have
additional maintenance, testing, and inspection requirements that must be followed. Before proceeding with disassembly of the water
motor alarm, notify the Authority Having Jurisdiction and occupants of the area covered by the system affected. Take all appropriate
precautions. The water motor alarm will be disabled during disassembly.
A. Water Motor Disassembly (See Figure 3)
1. Isolate the water motor alarm by closing the alarm line valve in the trim of the waterflow detecting device. (Refer to appropri-
ate technical data for the system used.)
2. Remove pipe plug (5).
3. Remove all round head machine screws (1) from the water motor cover.
4. Separate the cover (2) and the gasket (6) from the housing (3).
5. Remove the impeller (7).
6. Inspect and, if necessary, carefully clean the nozzle (4) with a wire or pipe cleaner brush.
7. Flush the nozzle way and drain line with water or compressed air.
B. Water Motor Re-Assembly
1. Re-install the pipe plug (5).
2. Re-install the impeller (7).
3. Replace cover gasket (6) and attach cover (2) by using round head machine screws (1).
4. Open the alarm line valve.
5. Test the water motor alarm.
6. When test is complete and water motor alarm operation is satisfactory, place the alarm line valve in the proper “alarm” posi-
tion. Reset and return the affected systems to service.

7. AVAILABILITY
Viking Water Motor Alarms are available through a network of domestic and international distributors. See the Viking Corp. Web site
for closest distributor or contact The Viking Corporation.

8. GUARANTEES
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Form No. F_082789 Rev 15.1


Page 4 of 4

TECHNICAL DATA WATER MOTOR ALARMS

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Figure 3: Replacement Parts

PART NUMBER NO.


ITEM NO. DESCRIPTION MATERIAL
F-2 G-2 REQ’D
1 * * Screw, R. H. Self-tap #10-24 x 3/8” lg. Zinc Plated Steel 6
2 07867 07870 Cover Steel 1
3 * * Housing Cast Iron 1
4 * * Nozzle Brass 1
5 01925S 01925S 1/2” Pipe Plug Cast Iron 1
6 02550B 02550B Cover Gasket Cellulose/Nitrile/Glass Blend 1
7 02547C 02547C Impeller Delrin 1
8 * * Bearing Brass: Sintered Bronze 1
9 05603A 05603A Wall Plate Galvanized Steel 1
10 05604B 05604B Drive Shaft Stainless Steel 1
11 -- -- 3/4” Pipe (C.O.J.) not furnished Galvanized Steel 1
12 * * Coupling Brass 1
13 02556B 02556B Striker Arm Shaft Celcon Glass Filled 1
14 * * Bearing Brass 1
15 * * Gong Support Stainless Steel 1
16 05821C 06508C Gong Aluminum 1
17 02766A 02766A Flat Washer, 11/32” ID x 11/16” ID x 1/16” Stainless Steel 1
18 05768A 06505C Gong Label Aluminum (F-2), Vinyl (G-2) 1
19 -- -- Screw, B.H. Slotted, 5/16-18 x 1/2” lg. Stainless Steel 1
20 * * Striker Arm Stainless Steel 1
21 -- -- Flat Washer, 11/32” ID x 11/16” OD x 1/16” Stainless Steel 1
22 -- -- Screw, H.H. Self-tap 5/16-18 x 1/2” lg. Zinc Plated Steel 1
23 * * Striker Pin Stainless Steel 1
24 * * Striker Arm Washer Stainless Steel 1
25 * * Striker Canvas Phenolic 1
--Indicates replacement part not available
*Indicates replacement part only available in a Sub-Assembly listed below
SUB-ASSEMBLIES
1-8 07863 07869 Motor Assembly
20, 23-25 02558B 02558B Striker Arm Assembly
12-15, 20-25 05606C 06506C Support Assembly

Form No. F_082789 Rev 15.1


Alarm Pressure Switch
1381

Alarm Devices
Technical Features
• Weight : 0.9kg (2.0lbs) 22
44
58
106

• Enclosure : Zinc Diecast


• Pressure Connection : 1/2” BSP male brass fitting .5

19.5
M 2 0 x1

• Switch Contacts : One set of Single Pole Double Throw (SPDT)


switch contacts. 5.0 A @ 250 VAC.
• Environmental Specifications:

105
- Temperature Effects: The ambient temperature range of the 24 A/F

switches is -10°C to +85°C. The temperature coefficient is

23
approximately 0.03% of the range per °C from 20°C.
- Temperature Range: -10°C (14°F) to 80°C (185°F). Ø78 ½” BSPP

IP65 Rated Enclosure

Alarm Pressure Switch - 1381 Physical Data


Max. SPDT Differential
Thread Weight
Reference Pressure Contact Pressure Range Pressure / Hysteresis Pressure Setting
Size (kg/lbs)
(bar/psi) Set(s) (bar/psi)
PSW036138114 0.30 / 4.4 Adjustable to any point 1
0.5 - 14 bar /2” BSP
13.75 / 199 1 Adjustable from 5% to within Pressure Range. 0.9 / 2.0
PSW0361381V14 (7.3 to 203 psi) male
95% of range Accurate to 0.22 bar (3.2 psi)

Alarm Pressure Switch - 1381 Material List


5
Item Description Material
1 Diaphragm* Beryllium Copper
2 Seal* Glass Filled PTFE
4
3 Connection Brass, 1/2” BSP male
4 Housing Zinc Diecast
5 Cover Glass Filled Nylon with Nitrile Seal

Updates version of 2004-11-22 (Pressure range modified)


* Not shown 3

Alarm Pressure Switch - 1381 Wiring Instructions & Pressure Setting


PSW036138114 Pressure Setting PSW0361381VA
P1 = 1 & 4 P-
P0 = 1 & 2
P+
1
1 1
_
4 4
P1
2 + 2
P0

P
09-04-2014

Differential Pressure /
Hysterisis
(PSW9361381VA only)
< / = 0.75 MAX.
< / = 0.75 MAX. < / = 0.75 MAX.

Worldwide Fire Protection www.viking-emea.com

Manufactured for Viking by Bailey & Mackey Ltd.. Refer to Manufacturer’s datasheet. Specifications subject to change without notice.
Pressure Gauge
GAU

Gauges
Technical Features
• Connections : 3/8” BSP male threaded.
• Specifications : complies to BS1780 and IP65.

Note : Can be supplied with company name on gauge face,


subject to minimum order.

A
Pressure Gauge - GAU Physical Data
Pressure Range (bar)
Internal Dimension A (mm/inch) Reference
min max
0.0 16.0 Dry 102 / 4.0 GAU022DRY0-16
0.0 16.0 Glycerine 102 / 4.0 GAU022GLY0-16
0.0 10.0 Dry 102 / 4.0 GAU022DRY0-10
0.0 10.0 Glycerine 102 / 4.0 GAU022GLY0-10
-1.0 1.0 Glycerine 102 / 4.0 GAU022GLY-1+1
No Loss Connector : Order separately - Reference: GAU022NLC

This datasheet updates the version of 2004-07-20 - Part Numbers corrected


Pressure Gauge - GAU Materials List 7
Item Part Material
1 Pointer Black Enamelled Aluminium 5
2 Window Polycarbonate
3* Bourdon Tube Copper Alloy
4* Movement Brass
5 Dial Black Lettering on White Background 1
6 Connection Brass
7 Casing Stainless Steel
* Not visible 2

6
2006-08-18

Worldwide Fire Protection www.vikingcorp.com

Manufactured for Viking SupplyNet by Universal. Refer to Manufacturer’s datasheet. Specifications subject to change without notice.
Butterfly Valve (Grooved)
GD20

Control Valves
Technical Features
• Sizes available (Nominal) : DN50/2”, DN65/21/2”,
DN80/3”, DN100/4”, DN125/5”, DN150/6”, DN200/8”, CE Compliant
DN250/10” and DN300/12”
• Pressure data :
Working pressure: 20 bar (300 psi).
Test pressure: Leak 23 bar (333 psi), Shell 31bar (450 psi).
• Service Temperature : -15°C ~ +120°C
• Finish : Nylon Coated Ductile Iron.
• Connections : Grooved joint dimensions are made in
accordance with ANSI/AWWA C606 (Ductile iron pipe
and steel pipe) and metric pipe specifications.
• Supervisory Switches :
The gearbox is fitted with one internal supervisory position
switch and one internal auxiliary switch.
Also available without supervisory switch.
• Note : The valves are suitable for use outdoors. Some degradation of
the painted/coated surfaces may occur (including rusting) which will
not affect the performance of the valve. The switch operation is not
affected by outdoor conditions providing the proper installation
instructions are followed.

Butterfly Valve (Grooved) - GD20 Physical Data


Nominal
Dimensions (mm) Weight
Pipe Size Reference
(kg)
mm inch OD a b Øe Ød ØC ØG ØH ØN Ø1 A B D L1 Ø M
50 2 60.3 16 7.93 57.15 50.8 67 65 50 7 12.6 100 70 82.4 32 30 8.86 GD20020 6.95
56 2½ 73.0 16 7.93 69.09 63.5 80 65 50 7 12.6 106 75 96.8 32 32 8.86 GD20025-073 7.40
76.1 76.1 16 7.93 72.3 63.5 80 65 50 7 12.6 106 75 96.8 32 32 8.86 GD20025-076 7.40
80 3 88.9 16 7.93 84.9 76.2 97 65 50 7 12.6 112.5 82 96.8 32 32 8.86 GD20030 7.90
100 4 114.3 16 9.53 110.08 99.5 123 90 70 10 15.77 135 100 115.85 32 38 11.1 GD20040 9.70
125 5 141.3 16 9.53 137.0 128.0 151 90 70 10 18.92 148.7 119 147.6 32 44 12.7 GD20050 12.80
150 6 168.3 16 9.53 163.96 149.0 180 90 70 10 18.92 176 130 147.6 32 47 12.7 GD20060-168 14.80
165.1 165.0 16 9.53 161.0 149.0 180 90 70 10 18.92 176 130 147.6 32 47 12.7 GD20060-165 14.80
200 8 219.1 19 11.1 214.4 203.2 231 125 102 12 22.1 204 162 133.4 45 53 15.9 GD20080 27.00
250 10 273.05 19 12.7 268.27 253.0 284 125 102 12 28.45 228.09 200.31 158.75 45 60 20.6 GD20100 37.00
300 12 323.85 19 12.7 318.3 303.0 335 140 102 12 31.6 228.19 223.88 163.58 45 64 22.1 GD20120 48.90

Butterfly Valve (Grooved) - GD20 Materials GD20 - Gear Operator Physical Data

Datasheet updates the version of 24-07-2014 (Modified weights)


Item Description Material Specification Valve Size
Ratio P F K I J Q
1 Upper Stem Stainless Steel ASTM A583 Grade 416 mm inch
2 Stop Cover Steel 50-150 2-6 24:1 150 54 151 74 89 113
3 Bolts Steel 200-250 8 & 10 30:1 300 77 238 87 90 123
4 Bushing PTFE 300 12 50:1 300 83 227 82 116 124
5 “O” Ring Buna-N
6 Body Ductile Iron ASTM A395 65-45-12
7 Disc Ductile Iron ASTM A395 65-45-12
(EPDM Coated)
8 Lower Stem Stainless Steel ASTM A583 Grade 416
9 Screw End Carbon Steel
10 “O” Ring Buna-N ASTM D2000
11 Name Plate Aluminium
12 Rivet Aluminium
13 Name Plate Aluminium
14 Rivet Aluminium
15 Bolts Steel
16 Spring Spacer Carbon Steel AISI 1566
17 Indicator Flag Cast Iron ASTM A126-B
23-10-2014

18 Gear Operator Cast Iron Housing & Ductile Iron Gear


19 Wire & Switches

Worldwide Fire Protection www.vikinggroupinc.com

Manufactured for Viking SupplyNet by Nibco Inc. Refer to Manufacturer’s datasheet. Pressure ratings require the use of couplings with equivalent pressure ratings. Rigid couplings are recommended for all valve end connections
Specifications subject to change without notice.
Butterfly Valve (Grooved)
GD20

Control Valves
Design requirements The valve should never be forced to seat by
applying excessive torque to the gearbox or through the
The butterfly valve should be connected to the piping use of a wrench. This may distort the valve components
system with approved couplings available from Viking or score the sealing surface.
SupplyNet. Flow may be from either direction through The use of excessive force to open or close the valve
the valve, and the valve may be positioned in any violates all warranties whether express or implied.
direction. The gearbox has been designed with a slow
Conduit and electrical connections to the
close handwheel operator that effectively minimizes
supervisory/auxiliary switches must be in
water hammer during the opening or closing of valve
accordance with the requirements of the
during flow conditions. These valves feature minimum
Authority Having Jurisdiction.
flow restriction and pressure loss when in the fully open
position. Care and Maintenance
Installation Inspect and verify proper operation on an annual basis
When the valves are received from Viking or according to the requirements of the Authority Hav-
SupplyNet they should be handled carefully to ing Jurisdiction. Check for
avoid breakage and damage to the seating area. leakage at the valve pipe connection and body-
Before installation of the valve, clean the piping, and to-operator connection. Installation, inspection
connecting coupling. Lubricate the coupling gasket and maintenance should be performed by a
with approved lubricant, and place over the adjoining qualified person(s) certified by the Authority
pipe or fitting. Position the valve against the mating Having Jurisdiction.
pipe or fitting and slide the gasket into position on the
valve such that the gasket seal seats properly on the If the valve closes hard, check to make sure that there
valve and pipe/fitting according to the manufacturer’s is no debris lodged in the waterway around the seating
recommendations. Assemble the couplings according area. Backing off the handwheel and closing the valve
the manufacturer’s recommendations. again can often correct this condition.
To prevent distortion, properly support the piping
adjacent to the inlet and outlet of the valve. Avoid
damage and do not use the valve to force the pi­ping
into position.

Butterfly Valve (Grooved) - GD20 Wiring Instructions


The GD20 butterfly valve comes complete with one internal Switch number Wire Wire color Mode/Description
supervisory position switch and one internal auxiliary switch. Supervisory switch #1 A Yellow Normally closed
The supervisory/auxiliary switches operate by a cam connect- Supervisory switch #1 B Orange Common
ed to the valve stem and are designed to notify in the case of Auxiliary switch #2 C Blue Normally open
valve closure. Please refer to the relevant installation standard

Datasheet updates the version of 24-07-2014 (Modified weights)


Auxiliary switch #2 D Violet Normally closed
and Authority Having Jurisdiction. Auxiliary switch #2 E Red Common
The switches will change position and close within two (2) full F Green Ground lead
turns of the hand wheel from the fully open position. Notes : Connection to power limited circuitry is required. Switch rating is limited to 11amps @ 125
VAC 60Hz or 1 amp @ 28 VDC

SUPERVISORY SWITCH
23-10-2014

Worldwide Fire Protection www.vikinggroupinc.com

Manufactured for Viking SupplyNet by Nibco Inc. Refer to Manufacturer’s datasheet. Pressure ratings require the use of couplings with equivalent pressure ratings. Rigid couplings are recommended for all valve end connections
Specifications subject to change without notice.
Page 1 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small
thermosensitive glass bulb spray sprinkler available with various finishes
and temperature ratings to meet design requirements. The special Polyester,
Polytetrafluoroethelyne (PTFE), and Electroless Nickel PTFE (ENT) coatings
can be used in decorative applications where colors are desired. In addition,
these coatings have been investigated for installation in corrosive atmospheres
and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global approves ENT finish as corrosion resistant. FM
Global has no approval classification for PTFE and Polyester coatings as corro-
sion resistant.)

2. LISTINGS AND APPROVALS


cULus Listed: Category VNIV
FM Approved: Class Series 2000
VdS Approved: Certificates G414009 and G414010
LPCB Approved
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001

CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria
for FM Approval requirements that must be followed.
Viking Technical Data may be found on
3. TECHNICAL DATA
The Viking Corporation’s Web site at
Specifications:
http://www.vikinggroupinc.com.
Minimum Operating Pressure: 7 psi (0.5 bar)
The Web site may include a more recent
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar) edition of this Technical Data Page.
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4” (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Black PTFE = N, and ENT = JN
Temperature Suffix: 135 °F (68 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB

Form No. F_033314 Rev 15.1 (Added CCCF Approval)


Page 2 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Available Finishes And Temperature Ratings: Refer to Table 1.


Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/B (available since 2000).
B. Wrench for Recessed Pendent Sprinklers: Part No. 16036W/B** (available since 2011)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)
**A ½” ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Protective Sprinkler Wrench Flat


Clip

Protective Sprinkler
Cap

Figure 1: Standard Sprinkler Wrench 10896W/B

Form No. F_033314 Rev 15.1


Page 3 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature Sprinkler Nominal Maximum Ambient


Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT
Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F
(57 °C)
Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. For ENT coated automatic sprinklers, the waterway is
coated

Sprinkler wrench 16036W/B**


for recessed pendent
sprinklers

** A 1/2” ratchet is required


(not available from Viking)

Carefully slide the wrench sideways around


the protective cap, ensuring engagement with
the sprinkler wrench flats
Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers

Form No. F_033314 Rev 15.1


Page 4 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Approval Chart 1 (UL)


The Viking Microfast® Quick Response
Pendent Sprinkler VK302
Maximum 175 PSI (12 Bar) WWP

Base Nominal Overall Listings and Approvals3


Sprinkler Thread Size
Part SIN K-Factor Length (Refer also to Design Criteria.)
Style
Number1 NPT BSP U.S. metric2 Inches mm cULus4 VdS LPCB 7

12979 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X A1 A1Z, B1Y D1Z, C1Y -- D3Z
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06662B VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X -- -- -- -- --
18021 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1X, B1Y A1 A1X, B1Y D1X, C1Y8 D1X, C1Y9 --
Approved Temperature Ratings Approved Finishes Approved Escutcheons
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F 1 - Brass, Chrome, White X - Standard surface-mounted escutcheon or the
(79 °C), 200 °F (93 °C), 286 °F (141 °C) Polyester5,6, Black Polyes- Viking Micromatic® Model E-1 Recessed Escutcheon
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F ter5,6 Y - Standard surface-mounted escutcheon or the
(79 °C), and 200 °F (93 °C) 2 - ENT5 Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micro-
C - 155 °F (68 °C), 175 °F (79 °C), and 3 - Chrome matic® Model E-1, E-2, or E-3 Recessed Escutcheon
200 °F (93 °C) Z - Standard surface-mounted escutcheon or the
D - 155 °F (68 °C), 175 °F (79 °C), 200 °F Viking Microfast® Model F-1 Adjustable Escutcheon
(93 °C), 286 °F (141 °C)
Footnotes
1
Base part number shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
4
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5
cULus Listed as corrosion-resistant.
6
Other colors are available on request with the same Listings and Approvals as the standard colors.
7
CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001.
8
CE Certified, Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003.
9
MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008.

DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)

cULus Listing Requirements:


The Viking Microfast® Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.

Form No. F_033314 Rev 15.1


Page 5 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Approval Chart 2 (FM)


The Viking Microfast® Quick Response
Pendent Sprinkler VK302
Maximum 175 PSI (12 Bar) WWP

Base Part Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals3
SIN
Number1 Style NPT BSP U.S. metric 2
Inches mm (Refer also to Design Criteria.)
12979 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
06662B VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2
18021 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y
Approved Escutcheons
Approved Temperature Ratings X - Standard surface-mounted escutcheon or the
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F Viking Micromatic® Model E-1 Recessed
(93 °C), 286 °F (141 °C) Approved Finishes Escutcheon
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 1 - Brass, Chrome, White Polyester4, Y - Standard surface-mounted escutcheon or the
200 °F (93 °C) and Black Polyester4 Viking Microfast® Model F-1 Adjustable Escutcheon,
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 2 - ENT5 or recessed with the Viking Micromatic® Model E-1
°F (141 °C) or E-2 Recessed Escutcheon
D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) Z - Standard surface-mounted escutcheon or the
Viking Microfast® Model F-1 Adjustable Escutcheon
Footnotes
1
Base part number shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
3
This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
4
Other colors are available on request with the same Approvals as the standard colors.
5
FM approved as corrosion resistant.

DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage upright and pendent
sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable
FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but
not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.

Form No. F_033314 Rev 15.1


Page 6 of 6

MICROFAST® QUICK
TECHNICAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Ceiling Opening Size:


2-5/16” (58.7 mm) minimum
1/2”
2-1/2” (63.5 mm) maximum
(15 mm)
NPT 2-1/8”
(54 mm)

1-1/2”
2-1/4” 2” (38 mm)
1-3/4”
(57 mm) (51 mm) Min.
(44.5 mm) Max.

Installed with a standard Installed with a Microfast Note: At maximum, adapter is


1/8” surface-mounted Model F-1 Adjustable exposed 1/2” (12.7 mm) from
escutcheon Escutcheon face of ceiling

Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon

Ceiling Opening Size:


2-5-16” (58.7 mm) minimum
2-1/2” (63.5 mm) maximum

2-1/8” 2-1/8”
(54 mm) (54 mm)

1-1/8” 1-1/8”
1-3/4” (28.6 mm) 2”” (28.6 mm)
(44.5 mm) Min. (51 mm) Min.
Max. Max.

Installed with a Installed with a Model


Model E-1 Recessed E-2 Thread-on Recessed
Escutcheon Escutcheon
Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons

Form No. F_033314 Rev 15.1 (Added CCCF Approval)


Page 1 of 4

MICROFAST® QUICK
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK345 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
The Viking Microfast® Quick Response Upright Sprinkler VK345 is a small, thermo-
sensitive, glass-bulb spray sprinkler available in several different finishes, tempera-
ture ratings, and K-Factors to meet design requirements. The special Polyester
coatings can be used in decorative applications where colors are desired. In
addition, these coatings have been investigated for installation in corrosive atmos-
pheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global has no approval classification for Polyester coatings as
corrosion resistant.)

2. LISTINGS AND APPROVALS


FM Approved: Class Series 2000
VdS Approved: Certificates G414011
LPCB Approved
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
NOTE: Other International approval certificates are available upon request.
Refer to Approval Chart 2 and Design Criteria FM Approval requirements that must be followed.

3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/16” (56 mm)
Viking Technical Data may be found on
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar).
The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). The Viking Corporation’s Web site at
Material Standards: http://www.vikinggroupinc.com.
Frame Casting: Brass UNS-C84400 The Web site may include a more recent
Deflector: Copper UNS-C19500 edition of this Technical Data Page.
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with
PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for
the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, and Black Polyester = M-/B
Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G
For example, sprinkler VK345 with a 15 mm thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12984AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)
Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)

Form No. F_033114 Rev 15.1 (Added CCCF Approval)


Page 2 of 4

MICROFAST® QUICK
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK345 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

4. INSTALLATION
Refer to appropriate NFPA Installation Standards.

5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.

6. INSPECTIONS, TESTS AND MAINTENANCE


Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7. AVAILABILITY
The Viking Microfast® Quick Response Upright Sprinkler VK345 is available through a network of domestic and international distributors.
See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES


Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue

Sprinkler Finishes: Brass, Chrome, White Polyester, and Black Polyester

Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.

Protective Sprinkler Cap

Wrench Flat

Figure 1:
Standard Sprinkler Wrench 10896W/B

Form No. F_033114 Rev 15.1


Page 3 of 4

MICROFAST® QUICK
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK345 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 1 (UL)
Microfast® Quick Response
Upright Sprinkler VK345
Maximum 175 PSI (12 bar) WWP

Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals3
SIN
Number1
NPT BSP U.S. metric2 Inches mm cULus VdS LPCB 5 6

12984 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- A1 A1 B1 -- B2


NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- A1 A1 B1 B1 --

Approved Temperature Ratings


Approved Finishes
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and
1 - Brass, Chrome, White Polyester4, and Black Polyester4
286 °F (141°C)
2 - Chrome
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Other colors are available on request with the same Listings and Approvals as the standard colors.
5
CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001.
6
MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.

Form No. F_033114 Rev 15.1


Page 4 of 4

MICROFAST® QUICK
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK345 (K5.6)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Approval Chart 2 (FM)


Microfast® Quick Response
Upright Sprinkler VK345
Maximum 175 PSI (12 bar) WWP
Base Part Thread Size Nominal K-Factor Overall Length FM Approvals3
SIN
Number1 NPT BSP U.S. metric2 Inches mm (Refer also to Design Criteria below.)
12984 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A1
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A1

Approved Finishes
Approved Temperature Ratings
1 - Brass, Chrome, White Polyester4, and Black
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
Polyester4

Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Other colors are available on request with the same Approvals as the standard colors.

DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)

FM Approval Requirements:
The Microfast® Quick Response Upright Sprinkler VK345 is FM Approved as a quick response Non-Storage upright sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.

Form No. F_033114 Rev 15.1 (Added CCCF Approval)