Alamo, Tennessee
CERTIFIED TEST REPORT
Status: Passed

5/27/2013 11:25:31
Test Date:
PM
Condenser 2226148
Apparatus: ABB Job Number:
Bushing 1
ABB Order
Bushing Type: O Plus C
Number:
Style: 046W2000UD Version: 5
Rating: 46 kV
BIL: 250 kV
Max L-G Voltage: 29 kV
2000 Amps (Bottom
Serial Number:
Connected)
Ambient
24 oC Humidity: 51%
Temperature:
1. Power Factor and Capacitance
The power factor/capacitance test is conducted per IEEE Std.
C57.19.00-2004 & Std. C57.19.01-2000. Test equipment includes a
dielectric test set for measurements above 10kV and a
dissipation factor/capacitance bridge #018
Before 60 Hz Withstand
Applied Power Factor Capacitance
Measurement
kV (%) (Pfd)
(C1) Stud to
10 .26 424
Tap
(C2) Tap to
1 NA NA
Flange
Stud to Flange 10 NA NA
2. Tap Test: 2 kV 60 Hz one minute applied test, tap to flange:
Passed

3. Dry 60 Hz Withstand and Partial Discharge:


The tests were conducted per IEEE Std. C57.19.00-2004, IEEE
Std. C57.19.01-2000 specifications. The dielectric and partial
discharge detection equipment is designed to meet or exceed
IEEE 454-1973, C57.113-1991, and C63.2-1996 requirements which
includes dividers, detectors, power sources to 1MV, and partial
discharge detectors. For units requiring partial discharge in
microvolts, tests are conducted per NEMA 107-1987.

Start Finish
Test Voltage (kV) Test Duration (Min) PC PC
44 NA 1 NA
125 1 2 1
44 NA 1 NA
NA NA NA NA
NA NA NA NA
4. After 60 Hz Withstand (Nameplate information):

Applied Power Factor Capacitance


Measurement
kV (%) (Pfd)
(C1) Stud to
10 .26 424
Tap
(C2) Tap to
1 .24 424
Flange
Stud to Flange 10 NA NA
5. The pressure and vacuum sealing of this bushing has been verified by testing in accordance with IEEE
C57.19.00 - 2004 section 7.4.5. This unit was filled at the factory with PCB-free (non-detectable) dielectric
fluid in accordance with U.S. Federal polychlorinate biphenyl (PCB) regulation 40 CFR 61, dated May 31,
1979. The analysis is verified per ASTM-D4059 with a detection level of less than 1 ppm. Bushings are
filled with mineral oil that is certified passivator free and certified tested corrosive sulfer free. All tests
were conducted on bushings that meet or exceed IEEE C57.19.00-2004.
All dielectric withstand levels for power frequency meet or exceed the routine test levels required by the
applicable IEC standards.

Test Specialist: Ej Jelks Date: 5/27/2013 11:25:31 PM

Remarks:

*.26* *424* *.24* *424*

Form: CTR-Condenser Bushings/IEEE v1.0 Form Date: 1/1/2000