www.tyco-fire.com
Contacts

Model LD — 11.2 K-factor


Large Drop Upright Sprinkler, Standard Response
Control Mode Specific Application
General Sprinkler
Description Identification
The TYCO Model LD, 11.2 K-factor
Large Drop Upright Sprinkler, Standard
Number
Response Control Mode Specific Appli- TY5153 – Upright, 11.2 K
cation is a glass bulb type automatic TY5153 is a redesignation of C5153
sprinkler. It is intended for use with
the National Fire Protection Associa-
tion “large drop sprinkler” installation Technical
criteria for the protection of high piled
storage. The LD Sprinkler can provide a Data
higher level of protection than standard
spray sprinklers and, in some cases,
Approvals Operation
UL and C-UL Listed
can provide an economic advantage by NYC Approved under MEA 289-04-E The glass bulb contains a fluid that
eliminating in-rack sprinklers. expands when exposed to heat. When
Maximum Working Pressure the rated temperature is reached, the
175 psi (12,1 bar) fluid expands sufficiently to shatter the
NOTICE
Pipe Thread Connection glass bulb, allowing the sprinkler to
The TYCO Model LD 11.2 K-factor, activate and flow water.
Large Drop Upright Sprinkler described 3/4 inch NPT or ISO 7-R3/4
herein must be installed and maintained
in compliance with this document, as
Discharge Coefficients
K = 11.2 GPM/psi1/2 Installation
well as with the applicable standards (161,3 LPM/bar1/2) The Model LD Sprinklers must be
of the National Fire Protection Asso- installed in accordance with this
ciation, in addition to the standards of Temperature Ratings
155°F (68°C) section.
any other authorities having jurisdiction. 200°F (93°C)
Failure to do so may impair the perfor- 286°F (141°C)
General Instructions
mance of these devices. Do not install any bulb type sprinkler
Finish if the bulb is cracked or there is a loss
The owner is responsible for main- Natural Brass of liquid from the bulb. With the sprin-
taining their fire protection system
Physical Characteristics kler held horizontal, a small air bubble
and devices in proper operating con-
Frame �������������������������������������������������������Bronze should be present. The diameter of the
dition. Contact the installing contrac-
Button �������������������������������������������������������Bronze air bubble is approximately 1/16 inch
tor or product manufacturer with any Sealing Assembly. . Beryllium Nickel w/TEFLON (1,6 mm) for the 155°F (68°C) rating
questions. Bulb. . . . . . . . . . . . . . . . . . . . . . Glass (5mm dia.) and 3/32 inch (2,4 mm) for the 286°F
Compression Screw �����������������������������������Brass (141°C) rating.
Deflector ���������������������������������������������������Bronze
A leak tight 3/4 inch NPT sprinkler joint
Design should be obtained by applying a min-
imum-to-maximum torque of 7 to 20
Criteria ft.-lbs. (13,4 to 26,8 Nm). Higher levels
of torque can distort the sprinkler inlet
The TYCO Model LD, 11.2 K-factor with consequent leakage or impairment
Large Drop Upright Sprinkler, Stan- of the sprinkler.
IMPORTANT dard Response Control Mode Specific Step 1. With pipe thread sealant
Always refer to Technical Data Application is only for use with National applied to the pipe threads, hand
Sheet TFP700 for the “INSTALLER Fire Protection Association “large drop tighten the Model LD Sprinkler into the
WARNING” that provides cautions sprinkler” installation criteria. sprinkler fitting.
with respect to handling and instal-
lation of sprinkler systems and com- Step 2. Using the W-Type 3 (End
ponents. Improper handling and B) Sprinkler Wrench (Ref. Figure 2)
installation can permanently damage applied to the sprinkler Wrench Flats
a sprinkler system or its compo- (Ref. Figure 1), tighten the Model LD
nents and cause the sprinkler to fail Sprinkler into the sprinkler fitting.
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 2 JUNE 2016 TFP335


TFP335
Page 2 of 2

1 - Frame 4 - Sealing * Temperature rating ** Pipe thread connections


2 - Bulb Assembly is indicated on per ISO 7-1 can be WRENCH
3 - Compression 5 - Button Deflector. provided on special RECESS
Screw 6 - Deflector * request. (END "B")

3 6*
APPLY
WRENCH AS
2-3/8" 2 5 SHOWN
WRENCH (60,3 mm)
FLAT
1 4 FIGURE 2
W-TYPE 3
3/4"
SPRINKLER WRENCH
NPT **

1/2" (12,7 mm)


NOMINAL MAKE-IN
CROSS
Limited
UPRIGHT SECTION
Warranty
FIGURE 1 For warranty terms and conditions, visit
MODEL LD LARGE DROP www.tyco-fire.com.
UPRIGHT SPRINKLER (TY5153)
Ordering
Care and Care must be exercised to avoid
damage to the sprinklers – before, Procedure
Maintenance during, and after installation. Sprin-
klers damaged by dropping, striking, Contact your local distributor for avail-
ability. When placing an order, indicate
The TYCO Model LD, 11.2 K-factor wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler the full product name and Part Number
Large Drop Upright Sprinkler, Stan- (P/N).
dard Response Control Mode Spe- that has a cracked bulb or that has lost
cific Application must be maintained liquid from its bulb. (Refer to Installa- Sprinkler Assemblies with NPT
and serviced in accordance with this tion Section.) Thread Connections
section. The owner is responsible for the inspec- Specify: Model LD (TY5153), K = 11.2,
tion, testing, and maintenance of their Upright Large Drop Sprinkler, (specify)
Before closing a fire protection system temperature rating, (specify) finish,
main control valve for maintenance fire protection system and devices in
compliance with this document, as P/N (specify):
work on the fire protection system that
it controls, permission to shut down the well as with the applicable standards 155°F (68°C) . . . . . . . . . . . . . . . . . 50-400-2-155
affected fire protection systems must of the National Fire Protection Asso- 200°F (93°C) . . . . . . . . . . . . . . . . . 50-400-2-200
be obtained from the proper authorities ciation (e.g., NFPA 25), in addition to 286°F (141°C) . . . . . . . . . . . . . . . . 50-400-2-286

and all personnel who may be affected the standards of any other authorities Sprinkler Wrench
by this action must be notified. having jurisdiction. Contact the install- Specify: W-Type 3 Sprinkler Wrench,
ing contractor or product manufacturer P/N 56-895-1-001
Sprinklers that are found to be leaking with any questions.
or exhibiting visible signs of corrosion
must be replaced. Automatic sprinkler systems are rec-
ommended to be inspected, tested,
Automatic sprinklers must never be and maintained by a qualified Inspec-
painted, plated, coated, or other- tion Service in accordance with local
wise altered after leaving the factory. requirements and/or national codes.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700