You are on page 1of 12

No.

Dated: 01/2018

Page: 1 / 11

Customer:
Contact:
Your reference:

Roof top
50EH 415V R410A MWC10
Roof mounted unit, reversible, ready to be installed, designed for air conditioning of large
volumes for industrial or commercial use.
Electric coil heating (resistances).
As per Brochure
MWC1 configuration: passive heat recovery circuit with rotary heat exchanger + Motorised fresh-air inlet
damper for Free Cooling + Return air plug fan on top box and motorised room exhaust damper
+ Supply air plug fan

Gross cooling capacity : 114.4 kW (99.7 + 14.7)


Eurovent classification :C
Mixing temperature (DB/RH) : 27.6 0C; 60.1 %(RH)
External temperature : 35.0 0C

Gross heating capacity : 100.8 kW (66.3 + 34.5)


Eurovent classification :A
DB Mixing temperature : 10.8 0C
Outdoor temperature : -10.5 0C

Heating capacity / Electrical heater 45.0 kW

Discharge air flow : 18,000 m3/h


Available static pressure : 46 mmWC
Impeller rotation speed : 1695 rpm
Refrigerant / GWP : R410A / 2088 kg /
tCO2Equ : 30 / 62.64

Standard electrical supply : 400 V / 3 ph / 50 Hz +E


PED 2014/68/UE : Category II
No.

Page: 2 / 12

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017

Description Quantity Price per unit


Without taxes
EUR (DDP Srbija)
50EH 415V R410A MWC10 1 38,860.00 EUR

COMMODITY SURCHARGE 1 INCLUDED

45 kW electrical heater, 2 stages.(Air flow monitoring included) 1 INCLUDED


Supply air plug fan with EC motor and constant air flow with air flow rate 1 INCLUDED
measurement sensor, standard available pressure
Return air plug fan with EC motor and constant air flow with air flow rate 1 INCLUDED
measurement sensor, high available pressure
Tandem compressors 1 INCLUDED
Crankcase heater for tandem compressor (T° < -8°C) (low temperature 1 INCLUDED
protection)
Heating element to protect the components inside the electrical box (T° < 1 INCLUDED
-8°C)
G4 filtration. 1 INCLUDED
Low pressure drop G4 filter on exhaust air, rotary heat exchanger 1 INCLUDED
(includes filter fouling sensor)
Low pressure drop G4 filter on fresh air, rotary heat exchanger (includes 1 INCLUDED
filter fouling sensor)
High grade switching devices 1 INCLUDED
Transformer (Power supply without neutral 3Ph + T) 1 INCLUDED
Electrical cabinet wire numbers and components identified by 1 INCLUDED
selfadhesives labels
Electronic regulation CARRIERrtc with PGD1 1 INCLUDED
Control with room temp. Sensor (wiring < 30 m), thermal free cooling 1 INCLUDED
(CARRIERrtc)
Quarter-turn locks for access panels 1 INCLUDED
Air direction 10 : lateral return / bottom discharge 1 INCLUDED
Heavy-duty pallet 1 INCLUDED
Rotary recuperator : material Aluminium, diameter 1.5 m, channel 17 1 INCLUDED
1/10 mm
Filters fouling detection 1 INCLUDED
PGD1 remote control kit + 2 TCONN bypass boards (for maximum 200 m 1 INCLUDED
wire length)

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 3 / 12

As per our general sales conditions in your possession. Validity of


prices: 1 month.
As part of our policy of continual improvement, we reserve the right to make any technical modifications we feel
necessary without prior notice.

Refrigerant information :
CE N°2037/2000 (JO CE 29/09/2000) European Norm does not allowed HCFC use anymore for all EEC
countries from : 01/01/2004

For regions with high humidity, stop drop on fresh air intake andthermo-enthalpic freecooling need to be
selected
The output of the heat pump depends on the weather conditions and drops as the temperature lowers.
The waste heat output at the lowest operating temperature must be checked.
Installing an auxiliary heating device (optional electric heater, gas burner or hot water coil) is recommended.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 4 / 12

COMPLETE PERFORMANCES ROOF TOP 50EH 415V R410A MWC10

Refrigerant / GWP : R410A / 2088


kg / tCO2Equ : 30 / 62.64
Number of refrigerant circuit(s) :2
Number of hermetic compressor(s) :4
Capacity control 4 stage(s) : 100-75-50-25-0 %

SUMMER OPERATION
Gross cooling capacity (frig + rec) : 114.4 kW (99.7 + 14.7)
Gross sensible cooling capacity (frig + rec) : 79.1 kW (64.4 + 14.7)
Total cooling capacity output : 108.9 kW
Sensible cooling capacity output : 73.5 kW
Compressor power input : 30.4 kW
Total input power : 47.1 kW
EER (EN 14511-2011) : 2.88
EER (EN 14511-2013) : 2.48
Outdoor Air : 35.0 0C / 54 %(RH) / 27.0 0C(WB) / 19.3 g/kg Dry air
Return air : 27.0 0C / 47 %(RH) / 19.0 0C(WB) / 10.5 g/kg Dry air
Mixed air : 27.6 0C / 60 %(RH) / 21.8 0C(WB) / 14.0 g/kg Dry air
Evaporator outlet air : 16.8 0C / 97 %(RH) / 16.4 0C(WB) / 11.5 g/kg Dry air
Supply air : 17.7 0C / 91 %(RH) / 16.7 0C(WB) / 11.5 g/kg Dry air
Efficiency for recovery wheel (Temp/Hum) : 79.90 % / 00.00 %

WINTER OPERATION
Gross sensible heating capacity : 121.6 kW (66.3 + 55.3)
Sensible heating capacity output : 127.1 kW
Compressor power input : 17.0 kW
Total maximum power input : 33.8 kW
COP (EN 14511-2011) : 3.85
COP (EN 14511-2013) : 3.43
Outdoor Air : -10.5 0C / 58 %(RH) / -11.7 0C(WB) / 0.9 g/kg Dry air
Return air : 18.0 0C / 49 %(RH) / 12.0 0C(WB) / 6.3 g/kg Dry air
Mixed air : 10.83 0C / 52 %(RH) / 6.42 0C(WB) / 4.2 g/kg Dry air
Condenser outlet air : 21.4 0C / 26 %(RH) / 11.3 0C(WB) / 4.2 g/kg Dry air
Supply air : 22.4 0C / 25 %(RH) / 11.7 0C(WB) / 4.2 g/kg Dry air
Efficiency for recovery wheel (Temp/Hum) : 71.65 % / 27.00 %

Electrical heater capacity : 45.0 kW


Number of stages :2
Supply air with auxiliary heating : 29.8 0C / 16 %(RH) / 14.7 0C(WB) / 4.2 g/kg Dry air

AIR HANDLING UNIT

Forced-draught outlet plug fan with EC motor


Maximum available pressure : 49 mmWC
Available static pressure for ducts : 46 mmWC
Discharge air flow : 18,000 m3/h
Fresh air flow : 7,200 m3/h
Fresh air percentage : 40 %
K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017
No.

Page: 5 / 12

Rated motor : 7.95 kW


Motor(s) absorbed power : 7.79 kW
Fan rotation speed : 1695 rpm
Transmission kit : 3 * R3G500RA2501
Filter thickness : 25 mm
Efficiency : G4

RETURN AIR FAN ON TOP BOX


Available static pressure : 26 mmWC
Return Air flow : 18,000 m3/h
Extracted air flow : 7,200 m3/h
Rated motor : 11.00 kW
Motor absorbed power : 4.95 kW
Rotation speed : 1689 rpm
Transmission kit : 2 * R3G500AQ3301

EXTERNAL SECTION

Number of fan(s) :2
Air flow : 30,000 m3/h
Total motor(s) power : 4.00 kW
Rotation speed : 895 rpm

Standard electrical supply : 400 V / 3 ph / 50 Hz +E


Current for power cable selection (excluding electric heater) : 109.5 A
Starting current : 308.9 A
Electric heater intensity : 65.0 A

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 6 / 12

SELECTED MOUNTING

Return - Discharge Mx wy denomination

I = Discharge MWC1 Rotary recovery (connected box) 3


R = Return dampers
E = Air extraction w : Return air direction (0 / 1 / 2) y :
N = Fresh air Discharge air direction (0 / 1 / 2)

DIMENSIONS AND WEIGHT


Length : 3,336 mm Width : 2,326 mm Height : 2,605 mm
Weight (empty) : 2,242.1 kg Weight (in operation): 2,243.1 kg
Rotary recuperator

Length : 1,981 mm Width : 1,214 mm Height : 2,605 mm


Weight (empty) : 715 kg Weight (in operation): 715 kg
Total weight : Weight (empty) : 2,957.1 kg Weight (in operation): 2,958.1 kg
Weight varies with the options chosen (given at +/- 10%).

RADIATED SOUND POWER LEVEL (Lw)


Break-out (Global Lw) : 92 dB(A)
Discharge (Global Lw) : 85 dB(A)
Intake (Global Lw) : 82 dB(A)
Sound power reference as per ISO 3744 : 10E-12 W, tolerance +/-3 dB.

RADIATED SOUND PRESSURE LEVEL (Lp)


Radiated (total Lp) : 64 dB(A)
Sound pressure level : reference 2 * 10E-5 Pa, tolerance +/-3 dB.
Calculated according to Lp = Lw - 10 x log S
(at 10 m, at 1,5 m from the ground, in free field directivity 2) Sound pressure levels depend on installation
conditions and are given for information only. We remind you that only sound power levels are certified and
reliable values.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 7 / 12

TECHNICAL DESCRIPTION ROOF TOP

Unit in accordance with the following European regulations and directives :


• Machines 2006/42/EC
• Electromagnetic Compatibility 2014/30/EC
• Low voltage 2014/35/UE
• PED 2014/68/UE : Category II
• Electromagnetic emission and immunity EN 61800-3 'C3'
• RoHS 2011/65/UE
• Machines EN 60-204-1
• Refrigerating systems and heat pumps EN 378-2

MAIN COMPONENTS
Unit with hermetic scroll compressor(s)
Option selected : Tandem compressors for high efficiency at partial load,
Internal protection of windings
Oil crankcase heater
Thermostatic expansion valve
Dryer
Cycle reverse valve (reversible range)
Pressure pick-ups for HP and LP manometers
Anticorrosion casing in galvanized sheet metal covered with polyester and varnish base lacquer
Removable electrical panel and filter access panels
Outdoor and indoor coil and with corrugated aluminium fins and copper tube,
Option selected: Plug fan supply air fan(s), EC motors with PID electronic control, for constant air
flow applications, with soft start. The operating point is adjusted by a rotary switch, and an air flow
rate sensor (analogue signal) adjusts the operating point to take account of filter fouling and
optimise filter service life.
Option selected: Plug fan return air fan(s), EC motors with PID electronic control, for constant air
flow applications, with soft start. The operating point is adjusted by a rotary switch, and an air flow
rate sensor (analogue signal) adjusts the operating point to take account of filter fouling and
optimise filter service life.
High performance Outdoor propeller Fans with 2 speeds managed by the control for a better seasonal
performance and with protection grilles
Automatic low speed/high speed changeover on outdoor fan depending on condensing or evaporation
pressure.
Filters G4 (standard) with metal frame, M1 fire classification
Main safety switch
Protections of fans and circuits by circuit breakers
Electrical panel with wiring under channel, conforms to NF C 15-100 and EN 60204
Acoustic cover(s) on compressor( s)
Phase control relay (standard) to control phase sequence and phase loose.

CARRIERrtc REGULATION
• LCD screen (PGD1) in the electrical cabinet,
• Heating, cooling, free cooling, extraction, air quality regulation,
• Compatible with all the sizes and optional mountings, • Anti-short cycle,
K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017
No.

Page: 8 / 12

• Defrosting (reversible range): DEGIPAC (indirect detection of frosting). Control of ambient


temperature and supply temperature, All seasons pressure control :
- Cooling mode : condensation pressure control in winter, -
Heating mode : evaporation pressure control in summer.
Compressor discharge temperature protection, Anti-
fire safety device.
• Air temperature sensor : outdoor, return, ambient (NTC by default, with communication RS485 as
an option for wire distances higher than 30m) and supply,
• Control with ambient temperature and anti-stratification function.

Control and display functions for maintenance of the standard terminal (PGD1)
• Access to parameter for commissioning,
• Different levels of parameter access (by password) : visualization and modification,
• Set point modification,
• Selection on/off, heating, cooling,
• Programming clock : it allows daily and weekly programming of the air conditioner operation.
• Display alarms with description,
• Control without PGD display : Several units may be interconnected (pLAN) with the CARRIERrtc
control. A single PGD display is sufficient in this case.
• This terminal is standard (removed by the option “Substitution TCO”), in the option “Kit remote
control PGD1” and in the option “Kit Service tool PGD1”.

CARRIERrtc OPTIONS AVAILABLE (see if options selected on page 2 or 3 of offer)


• Ambient temperature or enthalpy sensor with RS-485 communication,
• Control option with double ambient air sensor,
• Temperature comparison : free cooling operation by comparing temperature,
• Enthalpy comparison : Free cooling operation by enthalpy comparison,
• Ambient air quality sensor : Quantity of incoming fresh air modulated based on room CO2 level.
• TCO terminal instead of PGD1 in the electrical cabinet,
• Remote control kit (PGD1 + 2xTCONN) for remote maintenance or control. Does not eliminate the
console installed in the electrical cabinet,
• Kit Service tool PGD1 : PGD1 terminal + 1.5m telephone wire. It does not remove the terminal
installed in electric panel,
• Different bus communication options :Bacnet Ethernet, Bacnet MSTP RS485, Ethernet PcoWeb,
Konnex (KNX), LonWorks FTT and RS485 Modbus.

EQUIPMENT CHARACTERISTICS

ELECTRICAL HEATER
(factory mounted)
• Coils comprise shielded resistances in stainless steel pipe elements.
• Protection by manual safety thermostat

FILTERS FOULING DETECTION


• This item of equipment monitors filter clogging and sends a signal to the terminals. Volt-free SPDT
contact.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 9 / 12

PASSIVE RECOVERY OPTION


A real energy-efficient solution for fresh air needs.
The passive recovery option consists of :
• A rotating recuperator that delivers a high level of efficiency (>70%) between extracted air and
fresh air,
• Fresh air management.
• Droplet eliminators on fresh air intake : will prevent a water infiltration due to fog or rain.
Benefits of the passive recovery option :
• Reduce load of ventilation of the building,
• Increase energy efficiency : reduced energy consumption,
• Extend application range,
• Increase rate of incoming fresh air.

UNIT STRUCTURE
• Frame and casing made of panels coated with light grey (RAL 7035) polyurethane paint,
Designed for better visual integration.
• Hinges for access panels (except for models 90 to 180)

Unit tested and adjusted in the factory. Delivered in running order. Designed and
manufactured in an ISO 9001 certified factory.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


No.

Page: 10

Dimension drawings
No.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017


Page: 11

/ 11

1 : External air flow 12 : Condensates draining


2 : Standard internal air flow 13 : Optional auxiliary hot water coil
3 : Electrical panel 14 : Gas supply
4 : Power supply 15: Combustion air inlet
5 : Door switch 16 : Smoke exit
6 : Standard air discharge 17 : Minimum chimney height
7 : Optional air discharge 18 : Energy recovery circuit condesate drain outlet
8 : Standard air return 19 : Outdoor condensates drain pan pipe
9 : Optional air return
10 : Fresh air intake
11 : Air extraction
No.

K:\SHELL ADASEVAC RE.RTS - W - 365 PACKAGE V 03.00.59 A 09/2017

You might also like