Consultant: ( 2 )- 1/4/2003 HEAT LOAD Condition Data Design Data Outdoor Indoor Difference The Input Data And Calculation Month 8 dB F 115.00 75.00 40.00 Space Data Yearly Range 50.00 0 WB F 84.00 63.00 21.00 Machine No Height (ft) 18.00 Daily Range 25.00 % RH 30% 50% Space No Area ( ft2) 1080.00 Time 16.00 GR./LB 135.00 66.00 69.00 Floor No. GROUND FLOOR Volume ( ft3) 19440.00 Latitude 25 N Dew point 54 53 1 Units Type DUCTED Altitude 26.00 Haze Factor (0 to .15) 0.15 Solar &Trans Gain Glass External Load SOLAR GAIN TRANS GAIN GLASS H W Glass Area Ft2 U SC COLOR Frame Factors BTU/HR BTU/HR N 0.00 0.58 0.40 D 0.00 0.00 0.00 NE 0.00 0.58 0.40 D 0.00 0.00 0.00 E 0.00 0.58 0.40 D 0.00 0.00 0.00 SE 0.00 0.58 0.40 D 0.00 0.00 0.00 S 0.00 0.58 0.40 D 0.00 0.00 0.00 SW 0.00 0.58 0.40 D 0.00 0.00 0.00 W 0.00 0.58 0.40 D 0.00 0.00 0.00 NW 0.00 0.58 0.40 D 0.00 0.00 0.00 HORIZONTAL 0.00 0.58 0.40 D 0.00 0.00 0.00 Total Solar &Trans Gain Glass 0.00 0.00 Trans Gain -Except Glass External Load WALL H W Total Wall Area Ft2 Net Wall Area Ft2 U Mass Ib/Ft2 Color TRANS GAIN N 0.00 0.00 0.09 47.98 D 0.00 NE 0.00 0.00 0.09 47.98 D 0.00 E 0.00 0.00 0.09 47.98 D 0.00 SE 0.00 0.00 0.09 47.98 D 0.00 S 0.00 0.00 0.09 47.98 D 0.00 SW 0.00 0.00 0.00 0.00 0.09 47.98 D 0.00 W 0.00 0.00 0.00 0.00 0.09 47.98 D 0.00 NW 0.00 0.00 0.09 47.98 D 0.00 External Load Trans Gain -Wall 0.00 H W Area Ft2 EX OR NO U Mass Ib/Ft2 Color heat to space% Exposure TRANS GAIN ROOF 0.00 1.00 0.08 113.72 D 100% E 0.00 FLOOR 58.00 18.00 1044.00 1.00 0.28 86.97 D 50% 5846.40 PARTITION 0.00 0.00 0.00 1.00 0.27 54.60 D 50% 0.00 CEILING 0.00 1.00 0.28 86.97 D 50% 0.00 Trans Gain- Roof & Others 5846.40 Internal Load SENSIBLE LATENT MOTORS HP 0.00 REHEAT WATT 0.00 ELEMENTS APPLIANCES WATT 4500.00 15300.00 MISC. WATT 0.00 0.00 STEAM LB/H 0.00 W/FT2 Watt Light Factor Total Watt Operat % Heat to space% SENSIBLE LIGHTS 3.50 3780.00 1.25 4725.00 100% 100% 16065.00 FT2/ Person Persons Activity Level Attendance % SENSIBLE LATENT PEOPLE 70.00 15.43 1 100% 3780.00 3162.86 40991.40 3162.86 CFM/Person CFM 0.00 VENTILATION Air Change /Hr No 0.00 Out Door Air V 0.00 0.00 Infiltration % 0.00 INF. 0.00 0.00 Sub-Total BTU/HR 40991.40 3162.86 SH % 10.00% Safety Factor 4099.14 SAFETY FACTOR s LH % 5.00% 158.14 Others% 5.00% Duct Losses+ Fan HP 1352.72 UNITS DATA Operat. Time No Of Units T adb by-pass F(BF) Trm - Tsa Off Coil Air ToF PI Losses SENSIBLE LATENT 24.00 2.00 53.00 0.15 16.00 55.00 2.00 Effective Room Heat 46443.26 3321.00 TOTAL LOAD BTU/HR CFM THERMAL INSULATION Effective Room Total Heat 49764.26 Total Grand Load 49804.26 Supply Air 2299.63 Out Door Air Heat 0.00 0.00 Total Sensible Heat 46483.26 Return Air 2299.63 Total Latent Heat 3321.00 Out Door Air 0.00 Roof Load To Plenum 10 TONS BTU/HR.FT2 CFM/FT2 SHF Lights Load To Plenum 30 4.15 46.12 2.13 0.93 A PERFECT SOLUTION FOR A PERFECT LIFE Sensible Heat (Plenum) 40