PV Array 1:

Modules : SPR-327NE-WHT-D
Type: Monocrystalline
Configuration: 6 Strings
Temp. Coeffiecent of Pmax = -0.38% / oC
Temp. Coeffiecent of Voc = -176.6mV / oC
Temp. Coeffiecent of Isc= 3.5mA / oC

Port A:
Effiency Test 1st Run 2nd Run
Nominal Power 18312.00 18312.00
Solar Irradiance (W/m2) 894.00 887.00
Peak Sun Factor 0.89 0.89
Module Temperature (oC) 60 60
Temperature Factor 0.8670 0.8670
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array string 13483.91 13378.34


Measured Power from PV Array string 11760.00 11620.00

Factor (Measured/Estimated) 87.22% 86.86%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) Pass(>100MΩ)
Grounding Test Pass(<100Ω)
Remarks (if any)

Port B:
Effiency Test 1st Run 2nd Run
Nominal Power
Solar Irradiance (W/m2) 731.00 744.00
Peak Sun Factor 0.73 0.74
Module Temperature (oC) 46 46.4
Temperature Factor 0.9202 0.9187
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 0.00 0.00


Measured Power from PV Array string 3030.00 3050.00

Factor (Measured/Estimated) #DIV/0! #DIV/0!


Sysem Acceptance Test Passed 90% 90%
Insulation and Grounding Measurement Remarks
Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)
Voc/Isc No. of panels
-0.38
-0.32 38 6
0.053 8.95 1

60
3rd Run
18312.00
18312
0.00
14
1.0950
0.95

0.00
3100.00

#DIV/0!
90%

46
3rd Run

737.00
0.74
46.4
0.9187
0.95

0.00
3090.00

#DIV/0!
90%
PV Array 2:
Modules : SPR-327NE-WHT-D
Type: Monocrystalline
Configuration: 6 Strings
Temp. Coeffiecent of Pmax = -0.38% / oC
Temp. Coeffiecent of Voc = -176.6mV / oC
Temp. Coeffiecent of Isc= 3.5mA / oC

String 2A:
Effiency Test 1st Run 2nd Run
Nominal Power 4905.00 4905.00
Solar Irradiance (W/m2) 788.00 791.00
Peak Sun Factor 0.79 0.79
Module Temperature (oC) 48.4 47.9
Temperature Factor 0.9111 0.9130
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array string 3345.38 3365.12


Measured Power from PV Array string 3210.00 3240.00

Factor (Measured/Estimated) 95.95% 96.28%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)

String 2B:
Effiency Test 1st Run 2nd Run
Nominal Power 4905.00 4905.00
Solar Irradiance (W/m2) 810.00 797.00
Peak Sun Factor 0.81 0.80
Module Temperature (oC) 48.3 48.3
Temperature Factor 0.9115 0.9115
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 3440.21 3385.00


Measured Power from PV Array string 3390.00 3230.00

Factor (Measured/Estimated) 98.54% 95.42%


Sysem Acceptance Test Passed 90% 90%
Insulation and Grounding Measurement Remarks
Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)

String 3C:
Effiency Test 1st Run 2nd Run
Nominal Power 4905.00 4905.00
Solar Irradiance (W/m2) 808.00 815.00
Peak Sun Factor 0.81 0.82
Module Temperature (oC) 48.5 48.8
Temperature Factor 0.9107 0.9096
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 3428.86 3454.23


Measured Power from PV Array string 3310.00 3300.00

Factor (Measured/Estimated) 96.53% 95.53%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)

String 2D:
Effiency Test 1st Run 2nd Run
Nominal Power 4905.00 4905.00
Solar Irradiance (W/m2) 820.00 845.00
Peak Sun Factor 0.82 0.85
Module Temperature (oC) 48.9 49.4
Temperature Factor 0.9092 0.9073
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 3473.97 3572.40


Measured Power from PV Array string 3370.00 3410.00

Factor (Measured/Estimated) 97.01% 95.45%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)

String 2E:
Effiency Test 1st Run 2nd Run
Nominal Power 4905.00 4905.00
Solar Irradiance (W/m2) 844.00 856.00
Peak Sun Factor 0.84 0.86
Module Temperature (oC) 49.2 49
Temperature Factor 0.9080 0.9088
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 3571.17 3624.97


Measured Power from PV Array string 3410.00 3550.00

Factor (Measured/Estimated) 95.49% 97.93%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)

String 1F:
Effiency Test 1st Run 2nd Run
Nominal Power 3270.00 3270.00
Solar Irradiance (W/m2) 858.00 851.00
Peak Sun Factor 0.86 0.85
Module Temperature (oC) 49.3 49.5
Temperature Factor 0.9077 0.9069
System Losses (Cable, Inverter, Etc.) 0.95 0.95

Estimated Power from PV Array 2419.26 2397.51


Measured Power from PV Array string 2310.00 2340.00

Factor (Measured/Estimated) 95.48% 97.60%


Sysem Acceptance Test Passed 90% 90%

Insulation and Grounding Measurement Remarks


Insulation Test (DC) 2.2GΩ Pass(>100MΩ)
Grounding Test 0.0Ω Pass(<100Ω)
Remarks (if any)
Voc/Isc No. of panels
-0.38
-0.32 38 6
0.053 8.95 1

48.4
3rd Run
4905.00
800.00
0.80
48.1
0.9122
0.95

3400.57
3300.00

97.04%
90%

48.3
3rd Run
4905.00
785.00
0.79
47.7
0.9137
0.95

3342.37
3240.00

96.94%
90%
48.5
3rd Run
4905.00
831.00
0.83
48
0.9126
0.95

3533.82
3430.00

97.06%
90%

48.9
3rd Run
4905.00
837.00
0.84
49.1
0.9084
0.95

3543.03
3390.00

95.68%
90%
49.2
3rd Run
4905.00
850.00
0.85
49.2
0.9080
0.95

3596.55
3480.00

96.76%
90%

49.3
3rd Run
3270.00
862.00
0.86
49.6
0.9065
0.95

2427.48
2350.00

96.81%
90%
Other Info
Measurement
Tilt Angle 27.5o
Azimuth of 5o E of S

Note:
Peak Sun Factor = Measured Irradiance / 1000W/m2
Temperature Factor =
1+ [((Module Temperature Coefficient for Power)/100) x (Module Temperature in oC - 25)]