Fuzzy Control of Intelligent Indoor Exercise

Environment in Air-Polluted Area


Shaodan Zhi, Yongbin Wei, Jun Wang, Wei Zhao
Technical Center, China State Construction Engineering Corporation Limited
No. 15 of Linhe Street, Shunyi District, Beijing 101300, People’s Republic of China
Email: zsdwow@hotmail.com, weiyongbin@cscec.com, wang.jun@cscec.com, 380950253@qq.com

Abstract— In the air-polluted area or period, the outdoor effectiveness of the municipal emergency measures, with
activities are unhealthy and even become the triggers for lowest value controlled within 10 micrograms per cubic
different kinds of diseases because of the inhalable particles. meter which represents a good air quality.
Most of the outdoor activities are transferred into indoor
lifestyle, such as entertainments, sports and working. And it In the air-polluted area or period, lots of school,
is highly unlikely to get fresh air by ventilating directly with factories and organizations are shut down. And most of the
outside air, while CO2 content will persistently increase in outdoor activities are transferred into indoor-mode, such as
the enclosed space so as to oppress people of oxygen-poor entertainments, sports and working.
feeling. On the other hand, the rapid technology
development and the urgent requirement growth of wireless
sensors simultaneously offer a possible solution for such
contradiction. For the sake of the health and comfort of the
indoor inhabitants, a fuzzy control method is proposed in
this paper for controlling the actuators of air cleaner and
ventilator. With a good coordination between the air-
cleaners and the ventilator, an intelligent environment which
meets the comfort level with good air quality can be
achieved. Exercise experiments which last for six days are
carried out with comparisons among three controlling
algorithms in the changing outdoor environments. Results
show a satisfaction from overlapping working mode based
on fuzzy control algorithm. Such algorithm has a broad
application prospect on the existing buildings for air-
polluted area.

Keywords—Fuzzy controller; Intelligent environment; Air


quality; Comfort level

I. INTRODUCTION (HEADING 1)
Fig. 1. Satellite haze image over Beijing[1]
Haze is traditionally an atmospheric phenomenon
where dust, smoke and other dry particles obscure the
clarity of the sky, being unlikely eradicated in a relative
short period of time. There are several hypotheses about
the main factors and how these inhalable particles formed.
Taking Beijing for example, it is embraced on three sides
and located where the North China Plain meets the
Taihang Mountains. Such special geographical situation
can easily gather particulates but hardly evanish. As we
can see in Fig.1, the satellite picture shows particulate haze
suspending over Beijing. Fig. 2. Air pollution PM2.5 (ȝg/m3) in 30 days of Beijing[2]
These inhalable particles (especially PM2.5, fine
particulate matter with diameter less than 2.5 micrometer) Though a massive scale pollution is uncontrollable for
do harm human body directly for outdoor-activity people. individual inhabitants, it is possible to reduce the pollution
Especially in the winter, the ongoing municipal heating impacts appropriately by preventive indoor actions [3].
brings in much more power consumption which results in However, the amount of indoor oxygen is limited in the
much more air pollution. enclosed space and will decrease as time goes on, as the
Within 30 days in winter (since mid-November to mid- people number increasing or the exercises intensity. The
December), the highest level of PM2.5 triggers red alert content CO2 will persistently increase to oppress people of
and even rises to 480 micrograms per cubic meter of air oxygen-poor feeling. But we could not open the door or
while the most dangerous line is 500. As shown in Fig.2, window directly for the “fresh air” oxygen from outside
the drastic fluctuation of PM2.5 value briefly explains the polluted air because of PM2.5. Therefore, an air cleaner is

978-1-5090-0626-7/16/$31.00 2016
c IEEE 678
necessary to cooperate with the ventilator to ensure the good coordination of working time and loads, an
comfort level and good air quality at the same time. There intelligent environment which meets the comfort level with
is an imminent need for a widely-accessible IAQ (Indoor good air quality can be achieved without manual operation.
Air Quality) monitoring system that can provide intuitive
sense of air quality conditions in indoor environments [4]. II. SMART GYM SYSTEM DESIGN
A good air quality, however, could not be achieved by The function structure of smart home contains several
just monitoring the air condition. A pivotal system which aspects, including smart home host, indoor monitor &
should be involved to solve the indoor-air pollution is inductor, security & intercom, and the executive module
Smart Control System, which is commonly used to for intelligent environment, as shown in Fig.3. All the
integrate various home automation devices and expanding devices in this function structure are the related products
rapidly as electronic technologies converge [5, 6]. With the from UIOT-company except the intercom terminal.
rapid technology development, it is possible to solve the
contradiction as mentioned above. The smart home host is the center for home network
and local control, which adopts ARM cortex-A8
Based on the application perspective of Internet of architecture and 45nm processor. By combining the
Things (IoT), the sensor technology and intelligence ZigBee smart-hardware devices, the smart home host can
embedded technology can be developed to deal with the receive monitoring and inducting data and then direct the
issues especially for the decision-making level based on executive module to work coordinately. These devices are
indoor environment and target state estimation [7, 8]. With is based on the wireless sensors which are distributed
forward application of wireless sensor network, the smart according to the information gathering requirements.
home system can be designed smarter and more efficient
[9, 10]. The smart lock and the intercom terminal can record
the access records for individual person and transmit data
Furthermore, the hardware system of smart home can to the smart home center. On the other hand, magnetic
be designed based on ZigBee technology through the window sensors of can detect whether the window is open
wireless networking of multiple monitoring and controlling or not. Intelligent environment box can assemble different
devices, which provides a feasible method for intelligent sensors for temperature, humidity, methanol, and so on.
home [11]. Wireless devices based on the ZigBee protocol Since we concern the concentrations of CO2 and PM2.5
are provided as individual nodes for the smart home here, corresponding sensors for these two matters are
network. As to focus on the balance controlling of air installed in the intelligent environment box to feed data
cleaner and ventilator, a suitable algorithm is critical that back to the host.
should be developed in advance.
The final decisions for the executive module are from
In addition to identifying and differentiating the the host which experts at decision-making based on the
characteristics of perspective users and their possible needs gleaned data abovementioned. If the outdoor air quality is
[12], there is a growing trend of automatically updating good and the magnetic sensor gets a judgment of open
model to reflect the pattern/schedule changes and adapting window, the window opener will be activated to close the
to the user’s explicit or implicit wishes [13, 14]. For the window. Otherwise, if the indoor air quality cannot reach
multifunctional controllable system, the minimum human the air health standard, the air cleaner will be open at the
intervention [15] can not only liberate the inhabitant’s corresponding power level to eliminate PM2.5. And if the
labor and attention, but also be convenient to adjust the indoor air contains too much CO2 which makes people
system toward the data-based intelligent environment with uncomfortable, the ventilator will be open for
cost-effective algorithm. Thus intelligent systemic corresponding work time.
solutions for smart home are advanced by observing,
learning and adapting the resident’s activities toward
intelligent home environments, including various
computational intelligence techniques [13].
Among these solutions, Fuzzy logic controller is the
most effective in the learning for the codependence of the
environment and emerging situations [16]. Fuzzy
algorithms involved contain several different aspects of
applications, including thermal-comfort and air-condition
controlling [17-19], human emotion analyzing [20], laser-
pointer detection for handicapped [21], characterizing
behavior of sensor nodes with soft boundaries [22], and
constructing ambient intelligent environments [20, 23, 24].
For the sake of the health and comfort of the indoor
inhabitants, a fuzzy control algorithm is proposed in this
paper in allusion to the actuators of air cleaner and
ventilator based on the data collected from monitoring
sensors to overcome the aforementioned challenge. These
function modulates are pivotal executive parts of receiving
commands from decision-making system, which calculates Fig. 3. Smart home structure based on products of UIOT
corresponding control decisions and then forward them to
the intelligent environment based on the sensors on-service As shown in Fig.4, there are three main parts in the
to collect information from ambient environment. With the intelligent gym which are suitable for urban communities.

2016 IEEE International Conference on Fuzzy Systems (FUZZ) 679


Because of the limited space, the content of CO2 will in the high intensity exercises. Thus most of the comfort
increase immediately once there are enough exercisers or discomfort feelings will perceived by the exercisers
doing sports at the same time. Since a good air condition from the indoor environment based on the subjective
should be guaranteed, the content of CO2 should be kept consciousnesses. Therefore, the fuzzy nature of the
within a certain range for these people in such enclosed comfort level has the stem from both of the subjective
space. exercise experience and the indoor environment. As
shown in Fig.5, there is a fuzzy mapping relationship
between the physical energy and the comfort feeling
through the CO2 perceived for indoor environment. The
more exercise volunteers are doing, the lower CO2
concentration they will need for the comfort zone. Since
the volunteers have their own evaluation system based on
their self-experience, it is necessary to build a universal
fuzzy expression for the comfort evaluation.

Fig. 4. Partition plan of intelligent pre-fabricated gym

III. FUZZY NATURE OF HEALTH AND COMFORT LEVEL Fig. 5. Fuzzy mapping between the exercise energy and comfort level
In the beginning of this paper, we are emphatically
focusing on the balance problem between the healthy level The content of CO2, p tCO , is monitored based on the
2

and the comfort level of indoor environment, involving combination of the expiration from volunteers and the
ventilation for Oxygen-rich air and filtration for high- ventilating efficiency. In the same content environment,
PM2.5 air. Such balance requires the solution for the the ith volunteer at his/her own exercise stage ei will
aforementioned contrast by utilizing a suitable control classify the air condition into the corresponding comfort
algorithm. Therefore, the primary basic information is to level ci, and ci ∈ [0,1] where value 1 means subjective
find the decision/strategy target for indoor-occupants’ comfort feeling while 0 means discomfort. The subjective
physical health and comfort. According to IAQ Standard in category of the exercise stage ei belongs to one of the
Chinese national standard (GB) and World Health fuzzy subset of Energy, i.e. energetic, sustained, endure or
Organization (WHO), the content limits of different exhausted. With the increasing of exercise time t (t ” 105
physical elements are listed as seen in Table I. min, within a time domain [0,105]), the energy level would
be classified correspondingly from energetic to exhausted,
named with E1, E2, E3 and E4, respectively. The
TABLE I. INDOOR AIR QUALITY STANDARD PARAMETER relationship between the exercise time and the energy
Data & Source
estimation state is shown in Fig.6.
Parameter
Unit Value Source
CO2 % 0.10 GB/T 18883
Membership Degree

PM2.5 ȝg/m3 25 (Criterion value) WHO Air-Guide

Although the above table shows the general standard


for health level, the indoor environment suitable for
exercises has the fuzzy and turbulent nature which is
varying according to the different individuals. Therefore,
thus national and world standard for indoor air quality has
to be fuzzified as the major condition factor for decision-
making of controlling. The standard as shown above
embodies the tolerated air condition which is harmless to
Fig. 6. Membership degree of energy state upon exercise time
the occupiers’ health. Despite the minimum standard for a
good indoor air, the requirements of proper environments Since the feeling of human body is inseparably
are different for different individuals and exercises. connected to the environment, the energy state estimation
Based on the above analyses, a group of young adults mentioned above should be bonded to the current indoor
are chosen as volunteers to avoid distinct individual CO2 content and the exercise time.
differences in the physical quality and subjective tolerance
680 2016 IEEE International Conference on Fuzzy Systems (FUZZ)
The energy estimation would be changed according to ­° pCO2 _ IN = pCO2 _ IN + rv tv pCO2 _OUT Vgym
the changed indoor CO2 content even the exercise time is ® (4)
not changed. Therefore, the energy estimation will be °̄hPM2.5_IN = hPM2.5_IN + hPM2.5_OUT rv tv Vgym
redistricted for exercisers themselves, with exhausted
feelings in high CO2 environment even if the exercise time The parameters of machines (the air-cleaner and
is not as long as usual. ventilator), the basic CO2 exhale rate of human body and
the basic outdoor atmosphere are shown in Table II.
(
En′ (t ) = En t ⋅ (p
CO2 )
(t ) − 0.1 0.1 ) (1)
TABLE II. PARAMETERS OF MACHINES, HUMAN AND
AUTOMSPHERE
In this way, the exhausted volunteers have the
minimum comfort feelings toward the final decision of Parameter Unit Value
controlling the ventilator and the air-cleaner, which means
their opinions have the maximum weighs on the decisions. CADR ra-c m3/h 200

wEn ( pCO2 ) = 1 − ( n − 1) 4, (n = 1,! , 4)


2
Usable area m 30
(2)
3
Ventilate rate rv m /h 300

IV. CONTROLLING STRATEGIES Exhale rate rex_rest mL/min 280

Works as shown above have the primary efforts to Outdoor CO2 content pCO2_OUT % 0.038
record the subjective feelings from the exercisers in the
same environment with different energy states. However,
the contents of PM2.5 cannot be directly felt by human The indoor air condition has been formed as a dynamic
body for the tiny size of the inhalable particulates. system with the changing feelings from volunteers based
on their exercise states. The overall estimate from all of the
In order to carry out this test, the ventilator used in this volunteers are counted through Eq.(8). The Comfort means
gym is same with the ones in the existing residential an average comfort level voted from all of the volunteers.
buildings, which means that such ventilator doesn’t have
N
the function of removing PM2.5. So the ventilator need to
cooperate with air cleaner. Comfort = ¦ wEn μ En ( pCO2 ) N (5)
1

Since the ventilator and air-cleaner are separated as On the other side, another controlling method is
independent systems, the smart gym system should resolve proposed based on real-time threshold judgment as to
the inconsistent between the “fresh air” and the “clean air” contrast with the fuzzy controlling method based on
especially in the hazy weather. human comfort level. Therefore, the ventilator switch
The ventilating rate of the ventilator can be expressed should be turned on if CO2 content is beyond the CO2
as rv. The intermittent working style of the ventilator will threshold. And the air-cleaner switch should be turned on
cooperate with the working of air-cleaner, which is aiming once PM2.5 content is higher than the PM2.5 threshold.
at reducing PM2.5 with Clean Air Delivery Rate (CADR) Both threshold values are determined based on the air
as ra-c. Assuming the air in the gym is the same with the quality standard as mentioned in Table I.
outdoor before the volunteers walking in. So the indoor
original value of PM2.5 hPM2.5_IN is same with the outdoor, V. EXERCISE EXPERIMENTS
hPM2.5_OUT.
Works as shown above have the primary efforts to
Then four air-cleaners will be kept working when the record the subjective feelings from the exercisers in the
ventilator is working and hPM2.5_IN is higher than the same environment with different energy states. However,
accepted health standard. The maximum capacity of the content of CO2 will directly influence human actions
volunteers N (N is based on the current number, in and out) while the tiny inhalable particulates usually cannot be
is 40 people at the same time. The exhalant CO2 will kept detected by human body. Therefore, it is necessary to keep
increase during the exercise time with CO2 exhale rate rex indoor PM2.5 and CO2 as lower as possible.
(with minimum value at rest rex_rest), which will be effected
Two kinds of working modes are proposed here to
by the exercise state En.
evaluate the working efficiencies of the ventilator and the
Then before the ventilator works, the monitored indoor air-cleaners, which are alternative working mode and
air quality (pCO2_IN & hPM2.5_IN) can be connected with the overlapping working mode. The ventilator and air-cleaners
working states of the air-cleaner and the motion states of are open alternately in the former mode based on the
the volunteers. evaluation of their efficiencies and the changes of air
compositions. While in the latter mode, the ventilator and
­ pCO2 _ IN = pCO2 _OUT + Nrex t Vgym air-cleaners can be open at the same moment as to the
°°
(
®rex = rex_rest ⋅ 1 + 1 (1 − wEn )) (3)
ultimate target for the better air quality.
°
°̄hPM2.5_IN = hPM2.5_OUT − 4ra-c ta − c Vgym A. Alternative Working Mode
Once the volunteers walk in the gym and begin doing
After a certain time, the indoor CO2 will be exercises, the indoor CO2 will increase continuously
accumulated to a level which need ventilator drawing less- especially when the exercise intensity increases. If there is
CO2 air from outside. none ventilator works, the CO2 content will increase to
0.699%, which is much higher than the standard value, as
shown in Fig.7.

2016 IEEE International Conference on Fuzzy Systems (FUZZ) 681


And it will cost four air-cleaners working 20.25 quality can be controlled dynamically through the mutual-
minutes to lower the indoor PM2.5 down the standard coupling among the ventilator and the air-cleaners.
value, and 27 minutes to eliminate all the indoor PM2.5 on
the condition of outdoor hPM2.5_OUT is 100ȝg/m3. And the Under the same initial conditions with the previous
time will be doubled once hPM2.5_OUT is 200ȝg/m3, as shown case, the overlapping working mode can be open directly
in Fig.7. based on the indoor air quality. Therefore, the air quality
can be influenced by all the devices during their
Since the accumulated CO2 will be much higher than overlapped working time. In this way, the air quality can
acceptable comfort level, it is necessary to open the be dynamically controlled through the mutual-coupling
ventilator at the correct time. working mode with the ventilator and the air-cleaners.

100 0.4

50 0.2

0 0
0 20 40 60 80 100 120
Exercise time t (min)

Fig. 9. Indoor air contents based on overlapping working mode


Fig. 7. Indoor air quality without ventilation
Since devices are allowed to be open frequently to
By recording the feelings of comfort level, the works
control the indoor air environment, lower average contents
of ventilator and the air-cleaner are coordinated with their
of CO2 and PM2.5 can be acquired by such overlapping
start-stop moments and their working duration, as shown
mode than the former one, which also are lower than the
in Fig.8.
standard values ruled in Table I.

C. Experiments within Changing Outdoor Air


The indoor air content analyses above based on two
kinds of working modes show an obviously decrease of
indoor PM2.5 and also keep the indoor CO2 within an
acceptable level. In order to consummate the dynamic
controlling process based on the hardware in the smart
gym as shown above, experiments are carried out at the
same time in the six days during March 19th through
March 24th.
According to the records once the exercise experiments
were carried out, the outdoor PM2.5 contents in these five
Fig. 8. Indoor air contents of PM2.5 and CO2 with ventlation days are 97, 87, 157, 154㸪35 and 29ȝg/m3, respectively.
Therefore, the working times of ventilator and the air-
When the outdoor PM2.5 is 100 ȝg/m3, the first start cleaners are changing based on their working abilities
time of ventilator will be the moment when the content of within different outdoor environment. By taking the
indoor PM2.5 firstly hit zero. It is critical to open the advantage of intelligent indoor environment box and the
ventilator earlier than necessary to avoid the too much executive module, the executive time and the indoor air
indoor PM2.5. The accumulated CO2 will be diluted but contents can be recorded.
keep elevated once the ventilator is closed. The
In order to obtain and verify the effects of the fuzzy
intermittent ventilation can lower the CO2 content about
controlling strategy, another strategy based on threshold
40% than the none-ventilation state to keep a relative
method is added here in the executive experiment, marked
comfort environment under the precondition of lower
as method C. And the threshold values of this controlling
indoor PM2.5. Though the air quality can be controlled in
method are determined according to the standard
a certain health and comfort level by this mode in which
parameters in Table I, which represent the average value
the ventilator and the air-cleaners are open alternatively, it
for indoor contents.
still has potential to be improved.
All these three controlling strategies are implemented
B. Overlapping Working Mode at different times in the same day. To avoid the deviations
As shown above, the working mode in which the from the fatigued exercisers, the sequences of different
ventilator and air-cleaners are open alternately brings a controlling methods are determined as in Table III. After
relative long time for accumulations of CO2 or PM2.5. all these six days exercise experiments, statistics results
Thus the mode should be transferred into the overlapping show the efficiencies of these three controlling methods
working mode, in which the working time of all these and also the comfortable satisfactions from exercisers.
devices can be overlapped or non-overlapped according to
the indoor air quality. And in this way, the indoor air TABLE III. SEQUENCE OF CONTROLLING METHODS

682 2016 IEEE International Conference on Fuzzy Systems (FUZZ)


[3] B. Fong and G. Y. Hong, "A Prognostics Framework for Health
Day Day1 Day2 Day3 Day4 Day5 Day6
Degradation and Air Pollution Concentrations," Journal of
No.1- Morning A B C A B C Advances in Information Technology, vol. 3, pp. 64-68, 2012.
[4] S. Abraham and X. Li, "A Cost-Effective Wireless Sensor Network
No.2- Noon B C A B C A System for Indoor Air Quality Monitoring Applications," in The
9th International Conference on Future Networks and
No.3- Evening C A B C A B Communications (FNC-2014), 2014, pp. 165-171.
[5] R. J. Robles and T. Kim, "Applications, systems and methods in
A B C smart home technology: a review," 2010.
30 [6] L. C. De Silva, C. Morikawa and I. M. Petra, "State of the art of
smart homes," Engineering Applications of Artificial Intelligence,
vol. 25, pp. 1313-1321, 2012-10-01 2012.
20
[7] B. Li and J. Yu, "Research and Application on the Smart Home
based on Component Technologies and Internet of Things,"
10 Advanced in Control Engineering and Information Science, pp.
[8] J. Gubbi, R. Buyya, S. Marusic, and M. Palaniswami, "Internet of
Things (IoT): A vision, architectural elements, and future
0 directions," Future Generation Computer Systems, vol. 29, pp.
1 2 3 4 5 6 1645-1660, 2013.
Exercise experiment day [9] M. Collotta and G. Pau, "Bluetooth for Internet of Things: A fuzzy
approach to improve power management in smart homes,"
Fig. 10. Statistics of indoor PM2.5 after exercise experiments Computers & Electrical Engineering, vol. 44, pp. 137-152, 2015-
05-01 2015.
[10] M. Collotta and G. Pau, "A Solution Based on Bluetooth Low
Energy for Smart Home Energy Management," Energies, pp.
11916-11938, 2015.
[11] Z. Liu, "Hardware Design of Smart Home System based on zigBee
Wireless Sensor Network," AASRI Procedia, vol. 8, pp. 75-81,
2014.
[12] C. Wilson, T. Hargreaves and R. Hauxwell-Baldwin, "Smart homes
and their users: a systematic analysis and key challenges,"
Personal and Ubiquitous Computing, vol. 19, pp. 463-476, 2015.
[13] P. Rashidi and D. J. Cook, "Keeping the resident in the loop:
Adapting the smart home to the user," Systems, Man and
Cybernetics, Part A: Systems and Humans, IEEE Transactions on,
vol. 39, pp. 949-959, 2009.
[14] B. Qela and H. T. Mouftah, "Observe, Learn, and Adapt (OLA)ü
Fig. 11. Statistics of indoor CO2 after exercise experiments An Algorithm for Energy Management in Smart Homes Using
Wireless Sensors and Artificial Intelligence," IEEE Transactions
It can be seen from Fig.10 and Fig.11 that the on Smart Grid, vol. 3, pp. 2262-2272, 2012.
overlapping working mode (method B) can realize a lower [15] N. U. Hassan, Y. I. Khalid, C. Yuen, S. Huang, M. A. Pasha, K. L.
PM2.5 and a relatively lower CO2 result, due to the Wood, and S. G. Kerk, "Framework for minimum user
participation rate determination to achieve specific demand
consideration of health over comfort. response management objectives in residential smart grids,"
International Journal of Electrical Power & Energy Systems, vol.
VI. CONCLUSION 74, pp. 91-103, 2016-01-01 2016.
[16] A. Paulauskaite-Tarasevicience, N. Morkevicius, V. Jukavicius, R.
It is important to keep the indoor environment health Jasinevicius, V. Petrauskas, and V. Kazanavicius, "Statistical
and comfort for occupants and especially the indoor Evaluation of Four Technologies used for Intelectualization of
exerciser in hazy days. The fuzzy control algorithm for air- Smart Home Environment," Information Technology and Control,
cleaner and ventilator in this paper has been carried out. pp. 334-344, 2015.
Within a health standard for PM2.5, ventilators are open [17] H. N., A. A. Dahalan, A. M. Nasib, and A. A. Aziz, "Performance
of a Variable Speed of the Split Unit Air Conditioning System
intermittently for less-CO2 air to increase the comfort using Fuzzy Logic Controller," in Proceedings of the International
feelings of exercisers. Exercise experiments which last for MultiConference of Engineers and Computer Scientists Hong Kong,
six days are carried out with comparisons among three 2015.
controlling methods in the changing outdoor environments. [18] B. K. Sahu, S. Pati, P. K. Mohanty, and S. Panda, "Teaching̢
Results show a satisfaction from overlapping working learning based optimization algorithm based fuzzy-PID controller
mode based on fuzzy control algorithm. Such algorithm for automatic generation control of multi-area power system,"
Applied Soft Computing, vol. 27, pp. 240-249, 2015.
has a broad application prospect on the existing buildings
[19] C. Li, G. Zhang, M. Wang, and J. Yi, "Data-driven modeling and
for air-polluted area. optimization of thermal comfort and energy consumption using
type-2 fuzzy method," Soft Computing, vol. 17, pp. 2075-2088,
ACKNOWLEDGMENT 2013.
[20] G. Acampora and A. Vitiello, "Interoperable neuro-fuzzy services
This research is supported by China State Construction for emotion-aware ambient intelligence," Neurocomputing, vol.
Engineering Corporation Limited through the project 122, pp. 3-12, 2013.
“Future Residential Housing Demonstration Research”. [21] F. Ch A Vez, F. Fern A Ndez, J. U. S. Alcal A Fdez, R. Alcal A, F.
Herrera, and G. Olague, "Genetic tuning of a laser pointer
environment control device system for handicapped people with
REFERENCES fuzzy systems,": IEEE, 2010, pp. 1-8.
[1] "http://earthobservatory.nasa.gov/NaturalHazards/view.php? ". [22] M. Usman, V. Muthukkumarasamy and X. Wu, "Mobile agent-
[2] "http://datacenter.mep.gov.cn/report/air_daily/airCityMain.jsp?city based cross-layer anomaly detection in smart home sensor
". networks using fuzzy logic," Consumer Electronics, IEEE
Transactions on, vol. 61, pp. 197-205, 2015.

2016 IEEE International Conference on Fuzzy Systems (FUZZ) 683


[23] M. I. A. Ros, M. Delgado, A. Vila, H. Hagras, and A. Bilgin, "A [24] S. Puteh, C. Langensiepen and A. Lotfi, "Fuzzy ambient
fuzzy logic approach for learning daily human activities in an intelligence for intelligent office environments,": IEEE, 2012, pp. 1-
ambient intelligent environment,": IEEE, 2012, pp. 1-8. 6

684 2016 IEEE International Conference on Fuzzy Systems (FUZZ)

You might also like