Voltage Variation
> 33 KV (-) 12.5% to (+) 10%
< 33 KV (-) 9% to (+) 6%
Low Voltage (-) 6% to (+) 6%
Insulation Class
Insulation Temperature
Class A 105°C
Class E 120°C
Class B 130°C
Class F 155°C
Class H 180°C
Class N 200°C
HT Connection Earthing
H.T Connection’s Earthing Strip 20mmX4mm Cu. Strip
CT & PT bodies 2Nos
PT Secondary 1Nos
CT Secondary 1Nos
I/C and O/G Cable+ Cubicle Body 2Nos
Standard Meter Room Size (As per GERC)
Upper level does not beyond 1.7 meter and Lower level
Meter Box Height
should not below 1.2 meter from ground.
Meter Box should be at front area of Building at Ground
Facing of Meter Box
Floor.
Meter Room / Closed Shade 4 meter square Size
For Domestic Load 500 watt per 100 Sq. foot of the constructed area.
For Commercial 1500 watt per 100 Sq. foot of the constructed area
For lift, water lifting pump, streetlight if any,
Other Common Load corridor/campus lighting and other common facilities,
actual load shall be calculated
Staircase Light 11KW/Flat Ex: 200Flat=200×11=2.2KW
Sanctioned Load for Building
Up to 50 kW The L.T. existing mains shall be strengthened.
11 kV existing feeders shall be extended if spare capacity
50 kW to 450 kW (500 kVA) is available otherwise, new 11 kV feeders shall be
constructed.
11 kV feeder shall be constructed from the nearest 33 kV
450 kW to 2550 kW (3000 kVA)
or 110 kV substation
2550 kW to 8500 kW (10,000 kVA) 33kV feeder from 33 kV or 110 kV sub station
8500 kW (10,000 kVA) 110 kV feeder from nearest 110 kV or 220 kV sub-station