You are on page 1of 4

ModBus Memory Map Table

Company : AUTONICS
Device Name : TK4
Date : 25/11/2013

No ModBus Address R/W Size Parameter


1 40001 0000 R/W 1 Set Value

2 40002 0001 R/W 1 Heating MV

3 40003 0002 R/W 1 Cooling MV

4 40004 0003 R/W 1 Auto/Manual Control

5 40051 0032 R/W 1 RUN_STOP

6 40052 0033 R/W 1 Multi SV No

7 40053 0034 R 1 Heater Current Monitoring

8 40054 0035 R/W 1 Alarm1_Low

9 40055 0036 R/W 1 Alarm1_High

10 40056 0037 R/W 1 Alarm2_Low

11 40057 0038 R/W 1 Alarm2_High

12 40058 0039 R/W 1 SV-0 Setting Value

13 40059 003A R/W 1 SV-1 Setting Value

14 40060 003B R/W 1 SV-2 Setting Value

15 40061 003C R/W 1 SV-3 Setting Value

16 40101 0064 R/W 1 Auto-Tuning Execute

17 40102 0065 R/W 1 Heating_ Proportional Band

18 40103 0066 R/W 1 Cooling_ Proportional Band

19 40104 0067 R/W 1 Heating_Integral Time

20 40105 0068 R/W 1 Cooling_Integral Time

21 40106 0069 R/W 1 Heating_Derivation Time

22 40107 006A R/W 1 Cooling_Derivation Time

23 40108 006B R/W 1 Dead_Overlap band

24 40109 006C R/W 1 Manual Reset

25 40110 006D R/W 1 Heating_ON Hysteresis

26 40111 006E R/W 1 Heating_OFF Offset

27 40112 006F R/W 1 Cooling_ON Hysteresis

28 40113 0070 R/W 1 Cooling_OFF Offset

29 40114 0071 R/W 1 MV Low Limit

30 40115 0072 R/W 1 MV High Limit

31 40116 0073 R/W 1 Ramp_Up Rate

32 40117 0074 R/W 1 Ramp_Down Rate

ModBus Memory Map Table AUTONICS / TK4 1


33 40118 0075 R/W 1 Ramp Time Unit

34 40151 0096 R/W 1 Input Type

35 40152 0097 R/W 1 Unit

36 40153 0098 R/W 1 Low Input Range

37 40154 0099 R/W 1 High Input Range

38 40155 009A R/W 1 Scaling Decimal Point

39 40156 009B R/W 1 Low Scaling

40 40157 009C R/W 1 High Scaling

41 40158 009D R/W 1 Display Unit Lamp

42 40159 009E R/W 1 Input Bias

43 40160 009F R/W 1 Input Digital Filter

44 40161 00A0 R/W 1 SV Low Limit

45 40162 00A1 R/W 1 SV High Limit

46 40163 00A2 R/W 1 Operating Type

47 40164 00A3 R/W 1 Control Method

48 40165 00A4 R/W 1 Auto-Tuning Type

49 40166 00A5 R/W 1 Output1(SSR_Curr) Type

50 40167 00A6 R/W 1 OUT1 SSR Function

51 40168 00A7 R/W 1 OUT1 Current Range

52 40169 00A8 R/W 1 Output2(SSR_Curr) Type

53 40170 00A9 R/W 1 OUT2 Current Range

54 40171 00AA R/W 1 Heating_Control Time

55 40172 00AB R/W 1 Cooling_Control Time

56 40201 00C8 R/W 1 Alarm1 Mode

57 40202 00C9 R/W 1 Alarm1 Type

58 40203 00CA R/W 1 Alarm1 Hysteresis

59 40204 00CB R/W 1 Alarm1 NO/NC

60 40205 00CC R/W 1 Alarm1 ON Delay Time

61 40206 00CD R/W 1 Alarm1 OFF Delay Time

62 40207 00CE R/W 1 Alarm2 Mode

63 40208 00CF R/W 1 Alarm2 Type

64 40209 00D0 R/W 1 Alarm2 Hysteresis

65 40210 00D1 R/W 1 Alarm2 NO/NC

66 40211 00D2 R/W 1 Alarm2 ON Delay Time

67 40212 00D3 R/W 1 Alarm2 OFF Delay Time

68 40213 00D4 R/W 1 LBA Time

69 40214 00D5 R/W 1 LBA Level

ModBus Memory Map Table AUTONICS / TK4 2


70 40215 00D6 R/W 1 LBA Band

71 40216 00D7 R/W 1 Analog Output Mode

72 40217 00D8 R/W 1 Low Out Scale

73 40218 00D9 R/W 1 High Out Scale

74 40219 00DA R/W 1 Unit Address

75 40220 00DB R/W 1 Bit Per Second

76 40221 00DC R/W 1 Parity Bit

77 40222 00DD R/W 1 Stop Bit

78 40223 00DE R/W 1 Response Waiting Time

79 40224 00DF R/W 1 Communication Write

80 30105 0068 R 10 Model Name

81 40251 00FA R/W 1 Multi SV

82 40252 00FB R/W 1 Digital Input Key Function

83 40253 00FC R/W 1 Digital Input 1 Func

84 40254 00FD R/W 1 Digital Input 2 Func

85 40255 00FE R/W 1 Initial Manual MV

86 40256 00FF R/W 1 Preset Manual MV

87 40257 0100 R/W 1 Error MV

88 40258 0101 R/W 1 Stop MV

89 40259 0102 R/W 1 Stop AlarmOut

90 40260 0103 R/W 1 User Level

91 40261 0104 R/W 1 Parameter Initialize

92 40262 0105 R/W 1 Lock SV

93 40263 0106 R/W 1 Lock Parameter 1

94 40264 0107 R/W 1 Lock Parameter 2

95 40265 0108 R/W 1 Lock Parameter 3

96 40266 0109 R/W 1 Lock Parameter 4

97 40267 010A R/W 1 Lock Parameter 5

98 40268 010B R/W 1 Password Setting

99 31001 03E8 R 3 Present Value

100 31002 03E9 R 1 Decimal Point

101 31003 03EA R 1 Unit

102 31004 03EB R 3 Set Value

103 31005 03EC R 1 Heating MV

104 31006 03ED R 1 Cooling MV

105 31008 03EF R 1 Heater Current Monitoring

106 31007 03EE R(bit 0) 1 ºC Lamp

ModBus Memory Map Table AUTONICS / TK4 3


107 31007 03EE R(bit 1) 1 ºF Lamp

108 31007 03EE R(bit 2) 1 % Lamp

109 31007 03EE R(bit 3) 1 OUT1 Lamp

110 31007 03EE R(bit 4) 1 OUT2 Lamp

111 31007 03EE R(bit 5) 1 AT Lamp

112 31007 03EE R(bit 6) 1 SV1 Lamp

113 31007 03EE R(bit 7) 1 SV2 Lamp

114 31007 03EE R(bit 8) 1 SV3 Lamp

115 31007 03EE R(bit 9) 1 AL1 Lamp

116 31007 03EE R(bit 10) 1 AL2 Lamp

117 31007 03EE R(bit 11) 1 MAN Lamp

118 31007 03EE R(bit 12) 1 DI-1 IN

119 31007 03EE R(bit 13) 1 DI-2 IN

Total Num : 119

ModBus Memory Map Table AUTONICS / TK4 4

You might also like