Professional Documents
Culture Documents
Air-Conditioned Buildings
3. WATER EFFICIENCY
Singapore has limited water resources. It is important to encourage both domestic and non-domestic consumers to use
water efficiently.
Singapore’s domestic per capita water consumption has reduced from 165 litres /day in 1999 to 160 litres /day in 2005.
This is achieved partly through a series of community outreach programmes conducted by Public Utilities Board (PUB)
such as:
Points will be awarded for buildings applying for Green Mark Scheme based on water efficient labelled fittings with
ratings (see Table 6) as follows:
Dual flush low capacity flushing cisterns should be used. Each flushing should use 4.5 litres or less of water for a full flush
and less than 3 litres for a half flush.
Urinal flush valves that use not more than 0.5 litres of water per flush should be used. This is the recommended flush
volume for standard size urinal of 300mm width.
Dual Flush LCFCs Urinal Flush valve – 0.5 litres flush volume
PUB had conducted a pilot project and found that a flow rate of 2 litres/min at the wash basin taps in staff and public
toilets is sufficient for normal washing purpose. The lower flow rate will help to reduce water consumption and save on
the water bills.
Sensor taps with a flow rate of 2 litres/min can also be installed. These taps should also cut off water supply when the
hands are removed from under the tap, or when the preset timing of 30 or 60 seconds is reached, whichever is earlier.
Self-closing taps also help to prevent running tap after use. A combination of regulators and self-closing taps can achieve
significant savings.
Install self-closing delayed action taps (timing of between Install self-closing delayed action shower tap (timing not
2 and 3 secs) at all wash basins. The flow rate should be exceeding 15 secs) at all showers. The flow rate should
2 litres/min. not exceed 7 litres/min (except for hotels).
30 - 31
Green Building Design Guide
Air-Conditioned Buildings
3. WATER EFFICIENCY
Install constant flow regulators and adjust flow rate to Flow rate can be reduced by simple method such as
less than 6 litres/min for all bib taps and sink/ kitchen fixing thimbles or constant flow regulators
taps.
Where applicable, use drought resistant plants or plants that fit naturally into the existing climatic conditions including
rainfall and temperature pattern and require little irrigation.
The amount of turf area should be limited as most turf grasses need a lot of water and require continual upkeep.
Group plants by their water needs such as plants that need high, moderate or little to no irrigation rather than by appearance
or functions.
3.2.2. IRRIGATION
32 - 33
Green Building Design Guide
Air-Conditioned Buildings
3. WATER EFFICIENCY
Irrigation system should be zoned so that plants with different types of water needs are irrigated separately. For example,
turf grass should be watered separately from shrubs and flowers. Trees and shrubs that require little irrigation may only
require water during prolonged periods of dry season when they show signs of stress. For these plants, hand watering
may be all that is required.
Water efficient irrigation system such as drip irrigation system should be used. Drip irrigation applies water slowly and
directly to the roots of plants through small flexible pipes and flow control devices (called emitters). Since water is applied
directly to the root, evaporation and runoff is minimized. The irrigation system using potable water is only permitted for
system to be turned on manually and turned off automatically
Automatic controller should be used to turn the irrigation system off and to control the water flow through the various
zones according to a pre-set schedule. Rain sensors should be incorporated to automatically turn off irrigation system
during raining days.
POINT TO NOTE
• A flexible irrigation schedule can save water by adjusting to changing weather conditions. The schedule should
also be re-adjusted frequently during the growing season because as plants grow and become more mature,
they often need less water.
The main and sub-meters should be linked to a building management system (BMS). By linking the reading to BMS,
water usage trends can be recorded. An alarm could also be activated if there is a sudden increase in water consumption
or a new trend in water consumption as this will indicate the possibility of a water leakage.
Where applicable, NEWater should be used for cooling tower make-up water. The NEWater is cleaner than PUB water.
This would enable the tower to run at higher concentration cycles and hence increase water efficiency.
Condensate water from AHUs or FCUs could also be used for cooling tower make-up water. Using condensate water
from air side to top up cooling tower water not only lowers its water temperature to raise chiller efficiency, it also helps
to reduce the amount of make-up water needed.
Using NEWater for cooling tower Using Recycle A/C condensation for cooling tower
Cooling tower
water tank
NEWater
Collecting
condensate water
from AHU
34 - 35
Green Building Design Guide
Air-Conditioned Buildings
3. WATER EFFICIENCY
Cooling tower water treatment should be designed to achieve 6 or better cycles of concentration for water based cooling
system. With the quality of water supplied by PUB or NEWater, cycles of concentration of 6 or higher are achievable.
Higher concentration cycles reduce make-up and blow-down water requirements and hence reduce the cost of
operation.
The optimum concentration cycle should be decided in consultation with the water treatment service provider. The
potential for scale, corrosion, deposition and biological fouling problems should also be considered.
Efficient drift eliminator should be used. It should restrict the drift loss to less than 0.02% of cooling tower recirculating
water. The drift eliminators control unnecessary loss of water and help reduce the nuisance of water spraying near
the tower.
BMS monitors the pumping system NEWater is used for cooling tower
Innovation
• Effective and creative enhancement to hockey pitch watering system (see details in Section 6 on Innovation)
36 - 37