RTU560

Data Sheet Rack 560SFR02

Rack 560SFR02 Allocation of the slots:


Two slots for:
1 or 2 power supply units (each 2 slots
wide)
17 slots for:
Up to 8 communication units
Up to 17 I/O boards (with redundant
power supply)
Up to 18 I/O boards (if only one PSU is
Application used)
The 560SFR02 rack is designed to be used with For the physical interfacing of boards edge con-
or without redundant power supply. Therefore, it nectors of type F (DIN 41612) are used. Rows 2
has 2 slots for redundant power supply units to 20 of the edge connectors connect the RTU560
(PSU) and 17 slots that can be used for I/O system bus and are soldered directly to the
boards, communication units (CMU) or a mixture printed circuit board. The connection of the proc-
of both. It is interfaced to other racks via the ess signals is done via the rows 22 to 32 by
RTU560s serial peripheral bus. Up to 7 means of sub-connectors. The sub-connector is
560SFR02 racks can be connected to a system. clipped into a cut-out in the edge connector (see
By using the bus connection unit 560BCU05, the Fig. 1). The connection of the signal wires is made
560SFR02 becomes a rack with up to eight com- by means of crimp clips using snap-in fixing. In
munication units (560CMU05/560CMU02R2). addition to the use of prefabricated cables it is
Also for applications with only one communication also possible to attach individual wires during
unit the usage of BCU05 is required. commissioning
It is installed in a swing frame cabinet or in a
frame.
DIN-F connector with
Only in slot 19 the second PSU can be inserted cut-out for row 22-32
and will be operated. It is not allowed to put in
other modules. Slot 18 is available, when the op-
tion of the second PSU is not used.

Characteristics
The 19“ rack has a height of 3 HE for single Euro-
card format boards (DIN 41494). There are 20
slots available for the installation of boards.
Sub connector
Each power supply unit has a predefined slot allo-
cated to it (slot 21 and slot 19). These slots can Figure 1: Sub-connector design
be used only with PSU modules.
Slot 1 to 17 can be used for I/O boards and/or
CMU modules. If no redundant power supply is
used, slot 18 can be used for an additional I/O
board.

Doc-No.: 1KGT 150 731 V001 1


RTU560
Data Sheet Rack 560SFR02

This interface technology minimizes the number of Besides to the process signal connections, the fol-
cable connectors as well as the space required in lowing interface possibilities are located on the
the rack 560SFR02. rear side of the printed circuit board:
A monitoring circuit on the rack 560SFR02 checks Interface to the serial peripheral bus
the supply voltages of the board (24 V DC, 5 V
DC). Supply voltage failure is indicated by a status Status relay contact for monitoring the in-
relay contact. ternal voltages (24 V DC and 5 V DC) and
status of PSU´s.
An additional circuit shows the status of the power
supplies. Power supply failure is also indicated by Interface and supply power for the
a status relay contact. 560BCU05

560PSU02

Figure 2: Front View (only one 560PSU02 shown)

560PSU02 560PSU02 560CMU05 560CMU05 560CMU05 560CMU05


23AE23 23BA20 23BE23

24V 24V
ERR ERR ERR ERR
5V 5V
ON ON ST ST ST
PST
OFF OFF
1 9
+ + 2 10
- - 3 11
PE PE 4 12
5 13
6 14
7 15
8 16

CO

ABB ABB ABB ABB ABB ABB ABB ABB ABB

2 Doc.-No.:1KGT 150 731 V001


RTU560
Data Sheet Rack 560SFR02
Figure 3: Configuration example (Redundant power supply, four 560CMU05, three I/Os)

X2 X1 Rack No X15 X14 X13 X12 X11 24V, 5V, 0V


24 V 0V X16
V
1

Cut-out for process connections

PE PE

Figure 4: Rear View (Backplane)

RJ45

Bus printed circuit

Process
Connector

Figure 5: Side View

Doc.-No. 1KGT 150 731 V001 3


RTU560
Data Sheet Rack 560SFR02

Technical Data
In addition to the general technical data of the Monitoring Connections
RTU560, the following applies:
PowerSupply WARNING

X13, X14, X15 Plug-in terminal strip,


Rack 2-pole each
19“, 3 HE, 20 slots
Relay contact Normal closed contact
according DIN 41494
1 A / 60 V DC / 30 W
1 slot = 20.32 mm

Dimensions 132,8 x 482,6 x 210 mm


(H x W x D) Monitoring Connections ALARM
With boards 232 mm (D) X11, X12 Plug-in terminal strip,
2-pole each
With boards and 280 mm (D)
connector
Relay contact Normal closed contact
1 A / 60 V DC / 30 W
Weight 2.6 kg

Printed Circuit Board


Protection Earth
Dimensions 433,7 x 132,8 mm
PE 2 * Fasten 6,3 mm
(W x H)

Operating Information
Type of Connection
Temperature -40 °C … +85 C
Peripheral boards Indirect, 48 pole, Type F
DIN 41612 with cut-out
Relative humidity 5 … 95 %
for sub-connector
non condensing
Process signal 18 pole sub-connector
connection with crimp clips
Ordering Information
23XS40R1001
23XS40R2001 560SFR02 R0001 1KGT 022200 R0001

Accessories Ordering information


Serial Interfaces
Bus Connection Unit
SPB (X1, X2) 2 *. RJ45-jack
560BCU05R0001 1KGT 022400 R0001
560BCU05R0002 1KGT 022400 R0002
Compliances

EMC EN550011, EN61000


Environmental EN60255, IEC60870
Safety EN60950

4 Doc.-No.:1KGT 150 731 V001


RTU560
Data Sheet Rack 560SFR02

Doc.-No. 1KGT 150 731 V001 5


RTU560
Data Sheet Rack 560SFR02

Note:
We reserve the right to make technical changes or modify
the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars
shall prevail. ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of information
in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents - in whole or in parts –
is forbidden without prior written consent of ABB AG.

Copyright© 2011 ABB


All rights reserved

6 Doc.-No.:1KGT 150 731 V001