Professional Documents
Culture Documents
Data acquisition begins at the Programming Logic Controller, PLC level and includes
meter readings and equipment statuses that are communicated to the SCADA as
required. Data is then compiled and formatted in such a way that a control room
operator using the HMI can make appropriate supervisory decisions that may be
required to over-ride normal PLC controls. (A SCADA system includes all the
pieces, HMI, controllers, I/O devices, networks, software, etc.).
In short, interfacing on of SCADA with PLC offers efficient monitoring and control
of process in a large installation site and with large number of distributed equipment
at a site. SCADA provide alarm notification, historical and on-line trending plots of
control parameters for effective process monitoring and control. SCADA system can
also be implemented with PPM schedule maintenance notification and reminder.
The SCADA that are installed at the remote sites can be linked to a Master Station
via communication system (Radio frequency or WIFI or other on-line communication
channels). The data from an equipment is collected via on-line data acquisition or,
unless otherwise allowed, on batch mode via data logging devices.
The SCADA software can also activate alarm messaging to inform the operator
station for exceptional event (critical alarm) reporting. Remote Access Server (RAS)
features can provide for either via Internet or other dial-up method (fixed line and/
or wireless modem).
All the proposed SCADA software shall be scalable and flexible enough to allow the
integration of any additional SCADA controller in future expansion. It shall provide
with many industrial standard protocols to allow the user to integrate easily.
C-2 Purpose
This document will provide basic technical requirement for implementation of
integrated SCADA/HMI in sewerage system.
The SCADA system shall be Window based client/server system and make use of
the following technologies: -
C-4 Architecture
The SCADA architecture shall be flexible and scalable to allow expansion requirements.
The basic architecture shall incorporate all but not limited to the followings:
Software system displays shall include but not limited to the followings: -
• Menu/navigation displays
• Alarm summary
• Event summary
• Trends
• Operating groups
• System status displays
• Configuration displays
• Loop Tuning displays
• Diagnostic and maintenance displays
• Summary displays
Optional Live Video integration shall provide remote viewing and viewing control
features.
Security software feature shall provide restricted access, no access and full access
(plant management).
C-7 Database
The SCADA software shall but not limited to the following real-time database:
• Analog configuration parameters
• Digital configuration parameters
• Accumulator configuration parameters
• User defined configuration parameters
Each point in the database has a number of associated configurable parameters, all
of which can be referenced relative to a single ‘tag name’.
SCADA shall maintain the real time database that requires frequent high-speed
access as memory resident information and other less frequently accessed data as
disk resident data. Memory resident data is logged to data storage device every
specified time frame defined by the administrator to minimize the loss of data in
the event of loss of power.
• Hierarchical alarming
• Alarm/event reporting
• Alarm/communication/ message/downtime annunciator
• Alarm priority escalation
The standard Alarm Summary display shall allow operators to focus on the problem
at hand by supporting filters. Alarms may be filtered by:
Colors for the various priority levels of alarms can be configured by the user for
display purposes in the Alarm Summary and on custom graphics. The recommended
color codes are provided in Appendix 1. The software shall support configuration
of alarm priority colors and display on all process graphic displays to enables
operators immediately determine critically of the alarm.
The alarm shall annunciate in the status zone blinks with the color of the highest
priority for unacknowledged alarm. The alarms configuration shall consist but not
limited to the followings:
• SPV Hi
• SPV Lo
• Transmitter Hi
• Transmitter Lo
• Trip
• Time out
With each of the configured alarms assigns a priority ranging from "Attention" -
acknowledge of non-critical alarm that required maintenance attention, "Responsive"
- action required with predefined period, "Urgent" - action required immediately.
The Alarm/Event summary shall list but not limited to the followings:
• Alarms
• Alarm Acknowledgments
• Return to normal
• Operator Control Actions
• Operator Login & Security Level Changes
• On-line Database Modifications
• Communications Alarms
• System Restart Messages
C-9 Historian
Historical trend shall provide wide range of sampling frequencies in both data-
point and average formats. The history trend intervals are shall be able to but not
limited to the following displays:
• second data-point of pre-defined scale
• minute data-point of pre-defined scale
• hour data-point of pre-defined scale
• minute-average of pre-defined scale
• hour-average of pre-defined scale
• day-average of pre-defined scale
• Month-average of pre-defined scale
The software shall provide but not limited to the following report formats:
C-12 Security
The SCADA software shall provide configurable security levels, control levels
and area assignments. These may be configured for each individual operator or
alternatively for each operator station. The security levels shall be able to configure
the following security levels:
Level 1:
Sign-on for View mode only
Level 2:
View only mode with alarm acknowledge
Level 3:
Level 2 plus control of field parameters
Level 4:
Level 3 plus field parameters of level 4, configure standard system
infrastructure such as reports
Level 5: Level 4 plus user configured field parameters
Level 6: Unlimited access
Logon password shall not be less than 6 alphanumeric characters and shall be
encrypted. Operators may change own passwords; however, new password shall
not be the same as the last 10 passwords used in the previous 3 months. Three
unsuccessful attempts of logon shall lock the operator out for a lock-out period.
Once logged on, an operator can log off at any time or will be automatically signed
off after a defined period of inactivity.
Area assignments limit operator access to graphics, alarms and point data to assigned
areas, providing effective plant partitioning. Individual operator profiles, including
security levels, control levels and area assignments, are activated when operators
sign on to the system. In addition, area profiles can be created enabling plant areas
to be enabled or disabled for control, between certain time and date criteria.
C-13 Scripting
The software shall have the VB or VBA scripting language enable to allow user to
create script that will run when a display is active or scripts can also be attached
to server objects like point parameters, alarm events, report completion and other
events.
C-14 Interfaces
SCADA software provides Data Acquisition and Control facilities to communicate
with a wide range of controllers and Remote Terminal Units (RTUs). The controllers
connection type shall comply with the following communication protocol:
The software may have optional Digital Video Monitoring that integrates digital
video controls and storage with the software to assist in process monitoring. Some
of the features are:
The DVM shall base on open system hardware that digitizes video from standard
video cameras and transports the video to SCADA software clients anywhere on
the network for real-time viewing.
IMM enables the automated creation, assignment, tracking and closing of maintenance
work orders. If required, work orders can also be manually raised. This is all
managed from either your IMM SQL server database with full access available
through the open Web-based interface of IMM.
The SCADA software shall have the capability to produce but not limited to the
following reports:
• Batch Report
• Downtime analysis
• Schedule maintenance
• Statistical Process & Quality Control (SPQC)
• Event archiving
• Alarm messaging (SMS or pager)
Downtime Analysis –to detect, record and code any equipment breakdowns or process
delays to provide plant downtime analysis. A list of all current downtime events is
maintained as well as the history of previous downtime events, with each assigned
a category and a reason code. Downtime reports may be printed periodically or
on-demand, showing downtime duration sorted by categories and reasons.
Statistical Process & Quality Control (SPQC) - generates statistical report of average
(of specified time period) of the real-time data collected by the system.
Event Archiving –archiving events logged data by the system that based on sampling
frequency and storage capacity.
Alarm Messaging – reports the alarm messages sent designated supervisors. The report
shall incorporate summary of alarm messages by alarm type and supervisors.
SP Low Level Light Blue (Non- Alarm event of lower level than
Blinking) set point
Point Point
Monitoring
Qty
(For Each Equipment) (For Each
AO
DO
AI
DI
Equipment)
Instrumentation
Panel
Instrumentation Panel - Local Indicator 1 1
Instrumentation Panel - Remote Indicator 1 1
Instrumentation Panel - Battery
Indicator 1 1
Low
TNB Power (kWh meter) Data Record 1 1
PLC System
PLC (battery Low) Measure 1 1 Alarm Low (Fault Report)
Battery Charger Indicator 1 1 Alarm (Fault Report)
Penstock
Penstock Panel: Manual Switch Indicator 1 1
Penstock Panel: Auto Switch Indicator 1 1
IP open close RTU via RS-485 Serial Link
Penstock Position Actuator (%) 1
control Alarm - High torque
Penstock - Fully Open Indicator 1 1
Penstock - Fully Close Indicator 1 1
Remote
Penstock - To Open / To Close 1 1
Control
Penstock - UPS Low Indicator 1 1
UPS (battery Low) Inlet
Measure 1 1
Penstock
Primary Coarse Screen
Screen - Run Indicator 1 1 Counter - Number of start / stop
Screen - Trip Indicator 1 1 Alarm (Fault Report)
Screen - Auto Mode Indicator 1 1
Screen - Manual Mode Indicator 1 1
Remote
Screen - To Start / Stop 1 1
Control
Reset of Hour-
Screen - Run-hour record 0 Software counter running hours
Run meter
Control Start / Stop operation by
Differential Level : Upstream Indicator 1 1
diff. level
Differential Level :
Indicator 1 1 Ref level for upstream.
Downstream
RSP Pumps
Pump - Run Indicator 1 1 Record number of Start / stop
Pump - Trip Indicator 1 1 Alarm (Fault Report)
Pump - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start/
Pump - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-
Pump - Run-hour record 0 Software counter running hours
Run meter
Pump - Ampere Reading 1 1 Record when operation
Pump - Voltage Reading 1 1 Record when operation
Analog (A)/
Digital (D)
Description of
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Analog (A)/
Digital (D)
Description of
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Reset of Hour-Run
Screen - Run-hour record 0 Software counter running hours
meter
Mechanical Differential Level : Control Start / Stop operation
Indicator 1 1
Upstream by diff. level
Mechanical Differential Level :
Indicator 1 1 Ref level for upstream.
Downstream
Screenings Conveyor
Screen c/v - Run Indicator 1 1 Record number of Start / stop
Screen c/v - Trip Indicator 1 1 Alarm (Fault Report)
Screen c/v - Auto Mode Indicator 1 1
Screen c/v - Manual Mode Indicator 1 1
Screen c/v - To Start / Stop Remote Control 1 1
Software counter / Interlock
Reset of Hour-Run
Screen c/v - Run-hour record 0 with screen operation with delay
meter
off.
Screenings Wash Water Pumps
Wash-water Pump - Run Indicator 1 1 Record number of Start / stop
Wash-water Pump - Trip Indicator 1 1 Alarm (Fault Report)
Wash-water Pump - Auto Mode Indicator 1 1
Wash-water Pump - Manual
Indicator 1 1
Mode
Wash-water Pump - To Start /
Remote Control 1 1
Stop
Software counter / Interlock
Wash-water Pump - Run-hour Reset of Hour-Run
0 with screen operation with delay
record meter
off.
Grit / Grease System
Grit Blower - Run Indicator 1 1 Record number of Start / stop
Grit Blower - Trip Indicator 1 1 Alarm (Fault Report)
Grit Blower - Auto Mode Indicator 1 1
Grit Blower - Manual Mode Indicator 1 1
Grit Blower - To Start / Stop Remote Control 1 1
Software counter / software
Reset of Hour-Run
Grit Blower - Run-hour record 0 Timer control operation by
meter
rotation.
Grit Pump : On Indicator 1 1 Record number of Start / stop
Grit Pump : Trip Indicator 1 1 Alarm (Fault Report)
Grit Pump - To Start / Stop Remote Control 1 1
Software counter / software
Reset of Hour-Run
Grit Pump - Run-hour record 0 Timer control operation by
meter
rotation.
Grit Classifier : On Indicator 1 1 Record number of Start / stop
Grit Classifier : Trip Indicator 1 1 Alarm (Fault Report)
Grit Classifier - To Start / Stop Remote Control 1 1
Software counter / software
Reset of Hour-Run
Grit Classifier - Run-hour record 0 Timer control operation by
meter
rotation.
Grit Auger : On Indicator 1 1 Record number of Start / stop
Grit Auger : Trip Indicator 1 1 Alarm (Fault Report)
Analog (A)/
Digital (D)
Description of
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Analog (A)/
Description of Digital (D)
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Analog (A)/
Description of Digital (D)
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Qty
AO
DO
(For Each Equipment)
AI
DI
Equipment) Monitoring
Status & counter no. of start /
Pump - Run Indicator 1 1
stop
Pump - Trip Indicator 1 1 Alarm (Fault Report)
Pump - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Pump - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-Run
Pump - Run-hour record 0 Software counter
meter
Pump - Ampere Measure 1 1 Record when operation
Pump - Volt Measure 1 1 Record when operation
Sludge Flow Meter
RAS/WAS Flow Rate Meter Measure 1 1 Record
RAS/WAS Flow Rate Totalizer Measure 1 1 Record
Flow Meter System
Flow Meter
Measure 1 1 Record
(Data record of flow rate)
Flow Meter (Totalizer) Measure / Reset 1 1 SCADA Software Accumulator
Gravity Thickener
Status & counter no. of start /
G. Thickener - Run Indicator 1 1
stop
G. Thickener - Trip Indicator 1 1 Alarm (Fault Report)
G. Thickener - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
G. Thickener - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-Run Software record of running
G. Thickener - Run-hour record 0
meter hours
G. Thickener - Ampere Measure 1 1 Record when operation
G. Thickener - Voltage Measure 1 1 Record when operation
Thickened Sludge Digester Feed
Pump: Primary & Secondary
Status & counter no. of start /
Feed Pump - Run Indicator 1 1
stop
Feed Pump - Trip Indicator 1 1 Alarm (Fault Report)
Feed Pump - Off (MCCB) Indicator 1 1 Record non-operation hours
Remote Start /
Feed Pump - To Start / Stop 1 1 Software control / PLC
Stop
Reset of Hour-Run Software record of running
Feed Pump - Run-hour record 0
meter hours
Feed Pump - Ampere Measure 1 1 Record when operation
Feed Pump - Voltage Measure 1 1 Record when operation
Speed control : RTU via RS-485
Feed Pump - VSD Parameters Speed Control 1 1
Serial Link
Sludge Flow Meter
Sludge Feed Flow Rate Meter Measure 1 1 Record
Sludge Feed Flow Rate Totalizer Measure 1 1 Record
Gas Blower
Status & counter no. of start /
Gas Blower - Run Indicator 1 1
stop
Gas Blower - Trip Indicator 1 1 Alarm (Fault Report)
Gas Blower - Off (MCCB) Indicator 1 1 Record non-operation hours
Analog (A)/
Description of
Description of Monitoring Digital (D)
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Remote Start / Speed control : RTU via RS-485
Gas Blower - VSD Parameters 1 1
Stop Serial Link
Reset of Hour-Run Software record of running
Gas Blower - Run-hour record 0
meter hours
Gas Blower - Ampere Measure 1 1 Record when operation
Gas Blower - Voltage Measure 1 1 Record when operation
Temperature Sensor
Gas Blower - Temperature Measure 1 1 Record & Alarm (High)
Gas Flow Meter
Gas Flow Meter Measure 1 1 Record
Digester Gas Detector Meters
Record & Alarm (Detection &
H2S Meter at Dewatering House Measure 1 1
Fault)
Record & Alarm (Detection &
Methane Gas Meter Measure 1 1
Fault)
Record & Alarm (High-Low &
PVRV Sensor Meter Measure 1 1
Fault)
Internal Digester Gas Analyzer Measure 1 1 Record & Report
Floating Roof Gas Holder
Record & Alarm (High-Low &
Floating Roof Level Measure 1 1
Fault)
High Lever Alarm Indicator 1 1 Alarm (High)
Low Lever Alarm Indicator 1 1 Alarm (Low)
Record & Alarm (High-Low &
PVRV Sensor Meter Measure
Fault)
Gas Flare System
Gas Control Actuator Valve: Full
Indicator 1 1 Record & Timer
Open
Gas Control Actuator Valve: Full
Indicator 1 1 Record & Timer
Close
Gas Control Actuator Valve:
Indicator 1 1
Manual
Gas Control Actuator Valve:
Indicator 1 1 Program Control operation
Auto
Status & counter no. of start /
Gas Control Actuator Valve: ON Indicator 1 1
stop
Gas Control Actuator Valve:
Indicator 1 1 Alarm (Fault Report)
TRIP
Gas Control Actuator Valve: To Remote Start /
1 1 Software control / PLC
Turn Clockwise Stop
Gas Control Actuator Valve: To Remote Start /
1 1 Software control / PLC
Turn Counter-Clockwise Stop
Record & Alarm (flame
Pilot Light Igniter Indicator 1 1
distinguished)
Flare Igniter : Manual Indicator 1 1
Flare Igniter : Auto Indicator 1 1 Program Control operation
Flare Igniter : ON Indicator 1 1 Program Control operation
Record & Alarm (flame
Flare Indicator Indicator 1 1
distinguished)
Pressure Indicator: Inlet Measure 1 1 Record & Report Fault
Pressure Indicator: Discharge Measure 1 1 Record & Report Fault
Sludge Feed Pump to Belt Press
Belt Press Feed Pump - Manual Indicator 1 1
Analog (A)/
Digital (D)
Description of
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
Qty
AO
DO
(For Each Equipment)
AI
DI
Equipment) Monitoring
Analog (A)/
Digital (D)
Description of
Description of Monitoring
Control Point
Item
Point
(For Each SCADA Control /
(For Each Equipment)
Qty
AO
DO
AI
DI
Equipment) Monitoring
Notes:
AI = Analog Input AO = Analog Output DI = Digital Input DO = Digital Output
Qty = Quantity
PUMPS
(Centrifugal)
PUMPS
(Progressive Cavity)
BLOWER
SURFACE AREATOR
Valves
(General)
BUTTERFLY VALVE
AGITATOR
CONVEYORS
CONVEYORS SCREW
EQUIPMENT SYMBOLS
PLC CONTROLLER
WIRELESS COMMUNICATION
SCADA WORKSTATION
POWER TRANSMISSION
METER
COMPRESSOR
TANK