Professional Documents
Culture Documents
recloser
All Protn
A PH Fault Open OFF
B PH Fault
C PH Fault Inst
Close Protn OFF
Ground Fault
SGF Reclose
Lockout ON
Aux Power OK
Hot Line Tag
Recloser OK
ON
Ground Fault
Protn OFF
www.usa.siemens.com/reclosers
Training aid
7SR224 three-phase control relay
Type SDR 15.5 kV to 38 kV three-phase distribution recloser
2
2
SDR
1 recloser
F1/L9 F7/L15
All Protn
7 A PH Fault Open OFF
8 B PH Fault
F2/L10 F8/L16
9 C PH Fault Inst
Close Protn OFF
10 Ground Fault
3
Type 7SR224 protection and
control relay operation
exercises
Example 1: open recloser
4
Example 4: toggle hot line tag on and off
5
Example 8: toggle instantaneous (fast) protection on and off
To scroll up , press
To select, press
6
Recloser Name
ENTER to control
Press
Footnote:
1
T
his function only available with LOV relay DEMAND METERS
option.
BINARY INPUT METERS
VIRTUAL METERS
COMMUNICATION METERS
MISCELLANEOUS METERS
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
Press
8
AR: Trip & Reclose To trip and close the Press AR: Trip & Reclose Press
recloser. This screen will Confirm Action
ENTER to confirm
allow the user to trip the
Press recloser, then the recloser
will automatically reclose.
Recloser will trip, then reclose.
AR: Trip & Lockout To trip and lockout the Press AR: Trip & Lockout Press
recloser. This screen will Confirm Action
ENTER to confirm
allow the user to trip and
lockout the recloser.
Press
Recloser will trip and lockout.
Hotline Working: IN To toggle hot line tag On/ Press Hotline Working: IN Press
Off. This screen will read In|Out
to select
"Hotline Working: IN" or
"Hotline Working: OUT"
indicating hot line tag
being in/out of service. Hotline Working
Select "In" Press
Press or "Out"
Confirm Out
ENTER to confirm
9
Inst Protection: IN To toggle Inst (fast) Press Inst Protection: IN Press
In|Out
Protection On/Off, the LCD to select
screen will read "Inst
Protection: IN," or "Inst
Protection: OUT" indicating
Inst (fast) protection is in or Select "In" Inst Protection: IN Press
out of service. Confirm Out
or "Out" ENTER to confirm
Press
Set Local To set operational mode Press Set Local: mode Press
Confirm Local Mode
to local, the LCD screen ENTER to confirm
will read "Set Local: mode"
Press (where mode is local, L or
R, remote or out of
service.) Relay will be in local mode.
10
Set Remote To set operational mode Press Set Remote: mode Press
Confirm Remote Mode
to Remote, the LCD screen ENTER to confirm
will read "Set Remote:
Press mode" (where mode is
local, L or R, remote or out
of service.) Recloser will be in remote mode.
Note: The Out of Service mode will inhibit all local and remote control of relay. To regain local control, refer to
Changing the Operating Mode from the settings tree on page 23.
11
Settings mode tree
Recloser Name
enter to control
Press
CONTROL MODE Press SETTINGS MODE This is the second of four modes in the relay
tree, which bring you to multiple screens
Press that will allow you to control the recloser.
Press
12
SUPERVISION This menu allows the user to change
supervision settings, including battery and
capacitor tests, CT and VT supervision,
Press
broken conductor, etc..
CONTROL & LOGIC This menu allows the user to change control
and logic settings.
Press
13
Settings mode detailed tree structure
SETTINGS MODE
14
NPS Overvoltage
Neutral Overvoltage
U/O Frequency
CB Fail
VT Supervision
CT Supervision
Broken Conductor
Inrush Detector
CB Counters
I^2t CB Wear
Battery Test
Capacitor Test
LOV Automation1
Footnote:
1
T
his function only available
with LOV relay option.
27Sag & 59Swell
15
NPS OVERCURRENT 46IT
46DT
THERMAL 49
59NIT
59NDT
VT SUPERVISION 60VTS
CT SUPERVISION 60CTS
16
POWER QUALITY Voltage Input Mode
27SAG
59Swell
AUTORECLOSE CONFIG 79
Close CB Pulse
Reclaim Timer
Open CB Delay
Open CB Pulse
CB Controls Latched
E1 thru E16
GENERAL ALARMS
LED CONFIG
PICKUP CONFIG
17
DATA STORAGE DEMAND/DATA LOG
WAVEFORM STORAGE
FAULT STORAGE
EVENT STORAGE
ENERGY STORAGE
COM1-RS485 Protocol
COM1-RS485 Parity
COM1-RS485 Mode
COM2-USB Protocol
COM2-USB Mode
18
Settings change examples
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
Press Press
SETTINGS MODE
Active G1
Active Group
Press 1 Blinking
Press
Press ENTER button to accept changes.
Active G1
Language Setting Active G2 Notice the screen has updated from G1 to G2 indicating
English Active Group
2
the new active setting group.
Done
19
Example 2: changing the settings group that you are viewing/editing
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
SETTINGS MODE Active G1 Notice the screen has updated from G1 to G2 indicating
View/Edit Group
2
the new active setting group.
Press
When finished making changes, press CANCEL button three times
to return to initial ENTER to CONTROL screen.
SYSTEM CONFIG
to view
Done
Press
Active G1
Language Setting
English
Press
until the
following
appears
Active G1
View/Edit Group
1
Press
Active G1
View/Edit Group
1 Blinking
20
Example 3: changing a password
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
Press Active G1
Confirm Password
_ The relay will present a code. Retain this code in case of
a lost password. Refer to the instruction manual for the
SYSTEM CONFIG Siemens type 7SR224 recloser control relay (standard
Repeat previous step.
To view
control and protection relay option) http://www.usa.
Active G1 siemens.com/reclosers
Setting Password
Press Code = 1682678776
Active G1 When finished making changes, press CANCEL button three times
Language Setting to return to initial ENTER to CONTROL screen.
English
Press Press once You will now be prompted
more to
until the to enter the password once
change the
following control before you can make a
appears password. setting change. Follow the
Active G1 same process to change the Note: To deactivate the password feature,
Settings Password
password at the control change the password to "NONE."
Not Active
level.
Press
Done
Active G1
New Password
_ Blinking
21
Example 4: changing the pickup level of phase overcurrent element 51-1
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
Press up or down buttons to change desired pickup level to
desired current level.
Press
SETTINGS MODE
Press ENTER button to accept changes.
Press
until the
following Active G1 View G1
appears 51-1 Setting
_x In
CURRENT PROTN
to view
Done
CURRENT PROTN
PHASE OVERCURRENT
to view Note: "_xIn" refers to the value times the
nominal current that equals the trip
setting. In = 800 A for type SDR reclosers.
Press
Active G1 View G1
67 Char Angle
45 deg
Press
until the
following
appears
Active G1 View G1
51-1 Setting
_x In
Press
22
Example 5: changing the operating mode from the settings tree
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
SETTINGS MODE Active G1 Notice the screen has updated from Out Of Service to
Operating Mode
Local or Remote
Local or Remote, Remote or Local mode.
Press
When finished making changes, press CANCEL button three times
to return to initial ENTER to CONTROL screen.
SYSTEM CONFIG
to view
Done
Press
Active G1
Language Setting
English
Press
until the
following
appears
Active G1
Operating Mode
Out Of Service
Press
Active G1
Operating Mode
Out Of Service Blinking
23
Example 6: changing the baud rate on COM1
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
Press
Active G1
Station Address
0
Press
until the
following
appears
Active G1
COM1-RS485 Baud Rate
19200
Active G1
COM1-RS485 Baud Rate
19200 Blinking
24
Example 7: manually initiating the battery test
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
Press
CONTROL MODE
Press
until the
following
appears
Battery Test
Press
Battery Test
Confirm Start
Press
Battery Test
Active Note: Result will be displayed at end of test.
Done
25
Instrument mode tree
Recloser Name
enter to control
Press
Press
This menu will allow the user to view the favorite meters. FAVORITE METERS
Press
This menu will allow the user to view the current meters. CURRENT METERS
Press
This menu will allow the user to view the voltage meters. VOLTAGE METERS
Press
This menu will allow the user to view the frequency meters. FREQUENCY METERS
Press
This menu will allow the user to view the power meters. POWER METERS
Press
This menu will allow the user to view the energy meters - active energy, reactive ENERGY METERS
energy.
Press
Instrument mode tree continues on page 27.
26
This menu will allow the user to view the directional meters if directional current DIRECTIONAL METERS
elements are used.
Press
This menu will allow the user to view the thermal meters. THERMAL METERS
Press
This menu will allow the user to view the auto-reclose meters. AUTORECLOSE METERS
Press
This menu will allow the user to view the loss-of-volts meters if loss-of-volts function LOSS OF VOLTS METERS
is used. This is only available with the LOV relay option.
Press
This menu will allow the user to view the maintenance meters - counters. MAINTENANCE METERS
Press
This menu will allow the user to view the general alarm meters, which indicates GENERAL ALARM METERS
which alarms are present.
Press
This menu will allow the user to view the battery condition meters. BATTERY CONDITION
Press
This menu will allow the user to view the capacitor condition meters. CAPACITOR CONDITION
Press
This menu will allow the user to view the power quality meters: SIARFI, SMARFI, POWER QUALITY METERS
Interrupts, etc.
Press
This menu will allow the user to view the demand meters. DEMAND METERS
Press
27
This menu will allow the user to view the binary input meters - BINARY INPUT METERS
_ indicates status is low, 1 indicates status is high.
Press
This menu will allow the user to view the binary output meters - BINARY OUTPUT METERS
_ indicates status is low, 1 indicates status is high.
Press
This menu will allow the user to view the virtual meters - VIRTUAL METERS
_ indicates status is low, 1 indicates status is high.
Press
This menu will allow the user to view the communications meters. COMMUNICATION METERS
Press
This menu will allow the user to view the miscellaneous meters: MISCELLANEOUS METERS
date, time, waveform records, fault records, event records and data log records.
Press
This menu will allow the user to view the quick logic meters - QUICK LOGIC METERS
_ indicates status is low, 1 indicates status is high.
28
Viewing meter examples
Example 1: viewing the current meters and adding them to favorite meters
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
Confirm
Add to Favorites
Press YES Blinking
Primary Current
Any meter or meters in the instrument mode may be added to
1a 0.00kA favorite meters. The favorite meters may be displayed on the LCD
1b 0.00kA screen, in rotating order, after no buttons have been pressed for a
1c 0.00kA Done selectable period of time. To turn on and set the timer, select
Setting Mode System Config Favorite Meters Timer.
Displays primary current
levels.
29
Example 2: viewing the voltage meters and adding them to favorite meters
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
Confirm
Press Add to Favorites
until the
YES Blinking
following
appears Any meter or meters in the instrument mode may be added to
INSTRUMENTS MODE favorite meters. The favorite meters may be displayed on the LCD
Press screen, in rotating order, after no buttons have been pressed for a
Done selectable period of time. To turn on and set the timer, select
until the
following Setting Mode System Config Favorite Meters Timer.
appears
Voltage Meters
to view
Press
Displays
primary phase-
to-phase
voltage levels
Press the down button to view other voltage meters:
Press
Secondary phase-phase voltage
Nominal phase-phase voltage (for reclosers, Vn = 63.5 V)
Primary phase-neutral voltage
Secondary phase-neutral voltage
Nomimal phase-neutral voltage (for reclosers, Vn = 63.5 V)
V-sequence components
Calculated ground voltage
CS/NVD voltage (VX)
Last trip voltage.
30
Example 3: viewing the demand meters and adding them to favorite meters
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
CONTROL MODE
Confirm
Press Add to Favorites
until the
YES Blinking
following
appears Any meter or meters in the instrument mode may be added to
INSTRUMENTS MODE favorite meters. The favorite meters may be displayed on the LCD
screen, in rotating order, after no buttons have been pressed for a
Press Done selectable period of time. To turn on and set the timer, select
until the
Setting Mode System Config Favorite Meters Timer.
following
appears
Demand Meters
to view
Press
V Phase A Demand
Max 0.00kV
Min 0.00kV
Mean 0.00kV
Displays
phase A
voltage
demand
Press Press the down button to view other demand meters:
Phase demand voltage (A, B and C)
Phase-phase demand voltage (AB, BC and CA)
Phase demand current (A, B and C)
Ground demand current
Power (P three-phase demand MW)
Power (Q three-phase demand MVAR)
Power (S three-phase demand MVA)
Frequency demand.
31
Fault data mode tree
Recloser Name
enter to control
Press
To view the fault data for the fault selected, press to view the fault data Fault 1
Press
and then for more data..
Fault 2
Press
Fault 7 Fault 3
Press Press
Fault 8 Fault 4
Press Press
Fault 9 Fault 5
Press Press
Fault 10 Fault 6
Press
32
Viewing fault data example
If the LCD screen does not read ENTER to CONTROL, press until it does.
Recloser Name
This will not cause the recloser to operate.
enter to control
Done
33
Troubleshooting
Malfunction Remedy
1. Check miniature circuit breaker CB1 and switch on if necessary.
'AUX Power OK' LED not illuminated
2. Check the status of the auxiliary power supply.
Check the discharge switch on PCB2 circuit board and verify it is in the
'Recloser OK' LED not illuminated
operating position.
Travelling' indicated that no position indication signals are received from
the recloser or that both open and closed signals exist simultaneously.
Position indication shown as 'Travelling'
1. Check the recloser position.
34
Notes
35
The information provided in this
document contains merely general
descriptions or characteristics of
performance which in case of actual use
do not always apply as described or which
may change as a result of further
development of the products. An
obligation to provide the respective
characteristics shall only exist if expressly
agreed in the terms of contract.
Siemens Industry, Inc. For more information, contact: Subject to change without
7000 Siemens Road +1 (800) 347-6659 prior notice.
Wendell, NC 27591 Order No.:
www.usa.siemens.com/reclosers
E50001-F710-A410-X-4A00
All rights reserved.
Printed in USA
© 2012 Siemens Industry, Inc.