CALCULATION OF VERY FAST TRANSIENTS IN GAS INSULATED SUBSTATIONS Gis)
U.C-Trivedi and M.Ramamoorty
‘and Development Association
Makarpura Road, Baroda - 390 010.
ABSTRACT: During the switching operation of
disconnectors in GIS, a great number of prestrikes
and restrikes occur because of the low speed of
disconnector moving contact. These arcs are
quenched rapidly in the SF6 gas medium. Further
voltage collapse” takes place in a few nano-
seconds when the arc is initiated which leads to
travelling waves along the GIS causing very fast
transient overvoltages(VFTs)
In this paper 400 kV GIS is modelled using
well known Electromagnetic Transients Program
(EMTP). Different components in GIS are
represented using appropriate models. VFTs due to
different switching operations of disconnector and
the effect of lightning on GIS are studied,
1. INTRODUCTION}2,3)
For improved reliability and to conserve space,
the use of Gas Insulated Substations. (GIS) is on the
increase for HV and EHV 5) stems.
During
disconnector restriking and prestriking the voltage
over the disconnector gap collapse within 2 to 12 ns
depending on the disconnector design, the
instantaneous gap distance and gas pressure. Due to
subsequent travelling surges originated from the
disconnector and superimposed to reflected surges
fast transient overvoltages are generated,
Measurements indicate that Very Fast Transients
(VFTs) at their origin in a GIS are characterised by
4-7 ns rise time followed by a very high feequency
component up to tens of MHz: These overvoltages
may cause a failure of support insulation of the
conductor and also failure of associated equipment
in GIS. These overvoltages are the result of surge
reflections and superpositions that. t
discontinuities within the GIS like open ends, ‘T"
sections or bushings: Because of the traveling
wave nature of the phenomena the overvoltages are
@ function of position: within GIS. The main
oscillation frequency of the fast transients depends
on the GIS dimension, i. the section switched by
the isconnector. Thevshape. afd mainly the
Steepness of the surge ate influenced by those
Sectional components whose surge impedance
deviates distinctly from the main surge impedance
of the GIS bus,
the higher systei
the system volt:
VETS in GIS are of great concern at
'm voltages. The ratio of the BIL to
‘age is greater at the lower voltages
than it is at the higher voltage systems. The system
voltage break point at which VFTs become concern
is tot known precisely. However at and above
System voltages of 420 kV some equipment failures
and problems of arcing between grounded parts
have occurred and have been directly correlated
with disconnecting switch and circuit. breaker
operation,
Jn this paper VFTs generated in a 400 kV
substation due to
1. disconnector switching on to a fl
2. disconnector switching on to the trapped charge
with -03 p.u., -0.5 p.u. and -1.0 P.u. magnitudes.
3. single line-to-ground faults
are calculated.
Further the optimal location of the Surge arrester 10
reduce the overvoltages due to lightning is
Suggested. Transients enclosure voltages due to
disconnector operation are calculated,
loating section.
2.MODELLING OF VARIOUS GIS
COMPONENTS{[1}
Various components in the GIS are
Elbows, Disconnectors, Bus duct, Circuit breakers.
Surge aresters, Gas to air bushings. Power
Electromagnetic potential
ransformers. In the present
‘V GIS, Bus duct is modelled
(buted transmission line
tea. of switching
i travel time for ion is
*PProximately 2ns and can be eee
Models are available for
‘sed one and second for opemone. The simpler model for the closed breaker is
the same as that for a section of bus. The open
circuit breaker can be modelled as two equal
lengths of the bus with a value of the surge
impedance calculated from the dimensions of the
breaker. These two lengths are connected together
by a capacitor with a value equivalent to the series
combination of all of the grading capacitors. In this
closed position throughout the study. All of the
calculated and experimental data indicate that the
voltages produced by disconnector switching will
not produce overvoltages that are high enough to
cause the Metal Oxide Arrester to conduct, so
Surge Arrester is modelled by its capacitance to
ground.
The entire bushing can be modelled as a
single short section of distributed transmission line
whose characteristic impedance is determined from
the overall dimensions of the bushing. The
electrical length of the transmission line should be
‘such that the total capacitance is equal to the actual
bushing. Electromagentic potential transformers
and current transformers are represented by a total
capacitance to ground of the order of few hundred
pico-farads.
In this simulation the following values of
capacitance are assumed[6]
Table I: Capcitances of the various components
considered for the study.
a 8 Bic, Mb hesy
isteach Veto ie he. wo,
wile
FIC.TISINGLE PHASE REPRESENTATION OF THE
4OOKY GAS INSULATED SUB-STATION,
In the above figure surge impedance of the GIS bus
sections is 60 ohms and the travelling velocity is
2.88108 m/sec. Section between C and D
represents the bushing and it is represented by a
Surge impedance of 91 ohms and a’ travelling
velocity of 9.13x107 m/sec. Section between D and
E represents the transmission line of length 30 kin.
Disconnector is shown in the open position,
Capacitance of CTs and PTs is lumped at various
points,
In this simulation the disconnector is
modelled as an ideal switch, arc resistance has not
been modelled.
3. DISCONNECTOR SWITCHING ON TO A«
FLOATING SECTION|5]:
When the source side voltage is 1 pu,
disconnector is closed on to the floating section
The maximum overvoltage is observed at a location
aro. | — Compound 5 7Capeinne? just after the bushing followed by the voltage just
to before bushing. The magnitudes of the overvoltages
Ground(pF) at various locations of the substation are. given
1__| Earthing Switch 200] below.
3 Potential 350
“Trafeformat Table II: Transient magnitudes at various locations
a Current 680 when the disconnector is switced on to a floating
"| Transformer section.
Fo | Surge Arrester 00 Location Overvortage(pu)
5. Bushin; 600 A 145
ung } B 168
ic. 2AT
3.CONFIGURATION CONSIDERED: D 243
‘The. singlo- representation of the
considered 400 kV GIS is shown in fig.1. The waveform at ‘C’ is shown in fig2. It is
441
characterised by a rise time of 604 ns and a
frequency of 700 kHz.Fig 2 Transients at location C in fig.1 when
disconnector is closed on to a floating
section.
3.2. DISCONNECTOR SWITCHING ON TO THE
‘TRAPPED CHARGE:
3.2.1, TRAPPED CHARGE -0.3 P.U:
Disconnector is closed when the source
side is having a voltage of 1.p.u. and the bushing
side is having a trapped charge of -03 p.u, The
voltages observed at various locations are given in
table Il.
Table 111: Transient magnitudes at various
locations when the disconnector is switced on to a
trapped charge of -0:3 pu.
Location ‘Overvoltage(p.u)
158
1.89
The waveform at C’ is shown in fig3. It is
characterised by a rise time of 604 ns and a
frequency of 700 kHz.
ola} a} >|
Fig 3 Transients at location C in fig.1 when
disconnector is closed on to a trapped charge
of -03 pu.
3.2.2. TRAPPED CHARGE “0.5 p.U:
The voltages observed at various locations
are given in table 1V.,
Table” IV: Transient
magnitudes “at
locations when the discor
various
nnector is switced orf to a
‘rapped charge of -0.5 p.u:
Location Overvoltage(p.uy
A 167
B 2.02
c 2.76
D 314
The waveform at “C*
characterised by a rise
frequency of 700 kHz
is shown in fig.4, It is
time of 604 ns. and a
7)
Fig 4 Transients at location C inifig:t
‘when disconnector is closed on to.
Wwapped charge of -0.5 p.u
3.2.3. TRAPPED CHARGE -1,0 P,
The voltages observed at
Riven in table V_
Various locations are
pe Ma Transient magnitudes at Various locations
is switced on to a trapped
442Fig $ Transients at location C in fig. when
disconnector is closed on to.a trapped charge of =
10pu
3.3 TRANSIENTS DUE TO LINE TO GROUND FAULT:
When a line to ground fault is created at
location B and Bl in fig 1 the overvoltages
produced at location C are given in the table below.
‘The waveform at location C is shown in fig 6
TableVi: Transient magnitudes due to single line
to ground faults.
4. EFFECT OF LIGHTNING STROKE ON
SUBSTATION EQUIPMENT{(
In this simulation a lightning striking the
400 kV transmission line at a distance 1 km away
from the GIS bushing and the subsequent over
voltages generated inside the substation are studied.
It is assumed that the stroke has struck the phase
conductor directly. No back flashover of the
insulators is simulated. The effect of different
magnitudes of lightning currents and their wave
shapes on the overvoltage magnitudes is shown in
the table VII,
Table VII: The overvoltage magnitude at various
locations in p.u. for different lightning current
magnitudes and wave shapes,
Colt ]Col2 | A B c D
60kA | Casel [1-28 [180 | 212 [2.57
2/230 [Case2 [1.3 [193 [246 3.13
us.
Fault] Voltage(p.u) at location D
80KA | Casel [118 [1.58 [1.94 [239
Location 4/230
B a7 us| Casez | 19] 160 | 197 | aae
BI O64 40KA | Casel [138 | 205 | 231] 263
1/20
Even though the magnitudes are less the rise time ns | Case2 [1.63 [284 [3.63 [ast
observed in these cases are 154 ns and 135 ns at B
and B1 respectively.
60kA | Casel [1.13 [145] 1.73 | 208
a Case2 [1S [145 [173 | 208
100 | Casel [1.2 [164 [204 [ass
kA
eS hee Sear ae
Pe ca
Fig.6 Waveform at location C when the
single line-to-ground fault is created at
location B..
4/20 | Case2 | 1:24] 1.76 | 221 | 2.80
us
Coll —
shapes
Col.2 — Arrester status
Casel ~ With arrester at D
Case2 ~ Without arrester at D
ightning magnitudes and their wave
From this table it can be observed that
there is @ considerable reduction in overvoltages
when the arrester is placed at location D. A
Lightning current of 40 kA, 1/20 us wave shape'is
found to be. most. severe. Fig 7 shows ‘the
waveforms at location C for 40 kA current.Fig 7 Transients at location C due to lightning
Striking the transmission line at 1 Km away from
the station without surge arrester inside the
substation
Further studies are carried out by keeping
the arrester at D permanently and placing another
arrester inside the GIS to further reduce the
overvoltages. The optimal location for this arrester
is found to be at C. Table VIII gives the magnitude
of the voltages for this case,
Table VIII: Transient magnitudes at various
locations when the arresters are placed at C and D
Location ‘Overvoltage(p.u)
A 138
B 2.04
t 2.29
D 2.62
From the above table it ‘can be concluded that the
Placement of an arrester inside substation has litte
effect on the overvoltage magnitudes. Most of the
reduction in overvoltages is due tothe arrester at D
Fig 8 shows the waveform at location
The arrester at C is modelled by a non-linear
resistor in Parallel with the capacit e
Fig & Transients at location C due vo lighting
seating the transmission line at 1 Km away fom,
“the (suation with. surge. amesen “taste. te
‘Siomalion when it is located at ‘an optimal
position C.
5. TRANSIENT ENCLOSURE VOLTAGE:
‘Transient enclosure voltages are short
duration high voltage transients that appear on the
enclosure of the GIS through the coupling of
internal transients to enclosure at enclosure
discontinuities. The usual location’ for these
‘ansients is the transition GIS-overhead line at an
air bushing although they can also emerge at other
Points such as visual inspection ports, insulated
spacers for CTs or insulated flanges at GlS/cables
interfaces.
Modelling using EMTP:
For calculation of TEV in EMTP. apparatus
‘must be modelled as @ two phase system, which is
defined by the model parameters Zi and Zo
calculated from surge impedance as follows.
Z=60in(D/d) ohms
Z1=Z2 ohms
Zo=20000-Z1 ohms
Where D is the Outside diameter of the enclosure
and d is the outside diameter of the centre
conductor.Fig.9 shows the two phase transmission
line representation of the GIs,
aa
aa
Fig.9 Two
of the Gis,
transmission line representation‘The waveform shown in fig 10 is the TEV
at location C when the disconnector is closed on to
the floating section of the busbar. The maximum
voltage induced on the enclosure is -0.28 p.u.
Figip Waveform for the transient enclosure
voliage
6. CONCLUSIONS?
Various parameters in the’ substation are
Fepresented using appropriate models, It is
observed that the maximum voltage inside the
substation is 3.35 p.u when the disconnector is
switched on to. trapped charge of -1.0 p.u.. The
transients due to single phase-to-ground faults are
having fast rate of rise when compared to the
disconnector switching. The optimal location of
arrester inside this particular substation is found to
be *C’. The TEV calculated is with in the expected
range of 0.3 pi. for this particular substation.
REFERENCES:
1.Z,Haznadar,S.carsimamovic,R.Mahmut-cehajie’
More Accurate Modelling of Gas Insulated
Substation. Components in Digital Simulations of
Very Fast Electromagnetic Transients” IEEE
Transactions on Power Delivery, Vol.7, January
1992, pp.434-441.
2.J.Meppelink, K.Diederich, K.Feser(SM), W.Pfaff
“ Very Fast Transients in GIS", IEEE Transactions
on Power Delivery, Vol.4, No.1, January 1989, pp.
223-233.
3. W.Boeck, R.Witzmann “ Main influences on the
fast transient, development in. GIS”, Fifth
International . Symposium on» High Voltage
Engineering, 24-28 August 1987, Braunschweig,
Republic of Germany.
445,
5:$.A Boggs, F.Y.chu and N.Fujmoto “ Disconnect
switch Induced Transients and trapped charge in
Gas Insulated Substations”, [EEE Transactions on
Power Apparatus and Systems, Vol.PAS-101,
No.10, October 1982, pp.3593-3602.
6. Report prepared by the Fast Front Transients
Task Force of the IEEE Modelling and analysis of
system Transients Working Group.
“Modelling guidelines for fast transients” [EEE
Transactions on’ Power Delivery, Vol.11, No.1,
January 1996,pp.493-506.
7. E,P.Dick, N.Fujimoto, G.L.Ford and S.Harvey
“Transient ground potential rise in gas insulated
substations- Problem identification and Mitigation”
IEEE Transactions on Power Apparatus and
Systems, Vol.PAS-101, No.10, October 1982,
pp.3610-3619,