You are on page 1of 128

Chapter – 4

ANALYSIS OF HVDC CONVERTER TRANSFORMER

Converter transformer is very important and costly equipment in

the HVDC Transmission system. Thus great care has to be taken to

check whether its insulation can withstand the impulse over voltages

occurring in practice. Performance of the winding under impulse voltage

has a significant importance in the design of high voltage transformer

windings. Proper design of insulation not only provides trouble free

operation of the transformer, but also reduces the overall cost of it. The

purpose of impulse test is to ascertain the ability of the insulation of the

transformer to withstand the application of the standard test voltage.

Power frequency test by itself is not sufficient for the purpose. This may

be due to fast rate of rise of the impulse voltage and wave shape which

produces a non linear stress distribution through the transformer

winding and is characteristically different from that of power frequency

voltage.

4.1 ANALYTICAL MODELLING OF TRANSFORMER


The equivalent circuit of a transformer winding can be imagined in

the form of a string of inductors tapped by their parallel capacitance to

251
ground and shunted by the parallel stray capacitance between the

winding sections. The long duration power frequency voltage distribution

in the windings is almost uniform. However, impulse voltage distribution

is highly non uniform and is based on the inductance and capacitance of

the winding.

In the present context, the neutral current is visualized as a non

stationary signal whose properties changes in time, when there is fault.

Detection of major faults has never been an issue since the waveforms,

which are being compared, show major difference for such fault. Hence,

the focus is on being able to detect accurately the smallest or minor type

faults. In order to understand the above phenomena prototype

transformers were subjected to theoretical and experimental

investigations. In this chapter, mathematical modeling of a converter

transformer and calculation of neutral current has been discussed.

4.1.1 FUNCTION OF CONVERTOR TRANSFORMERS:

Convertor transformers are specially designed oil insulated power

transformers and are similar to AC power transformers in many respects

of design and construction. They are oil insulated and OFAF cooled. They

are fitted with OLIC, bushings other usual accessories. They are most

vital and costly equipment in the HVDC convertor station. Convertor

252
Transformers are subjected to very unusual times of stresses due to

combination of AC, DC voltages and harmonics.

Convertor transformers are used for transforming AC network

voltage to suitable voltages for feeding the 12 pulse convertor bridges.

The convertor transformer serves the following important functions

which are not performed by usual power transformers in AC substations.

 Convertor Transformer provides effective and natural barrier between

AC network and DC line. AC voltages/currents are not mixed with DC

voltages and currents, yet power is transferred from AC to DC

(rectification) or DC to AC (inversion)

 By tap changer fitted on the convertor transformer, the DC line

voltage DC power flow is effectively controlled.

 By means of tap changers reactive power requirement of converter is

minimized.

 The short circuit levels are precisely controlled by means of the closely

matched impedance of converter transformer. Impedance values are

selected for satisfactory operation of valves.

 DC load is distributed symmetrically by converter transformers over 3

phase of AC network.

253
 By suitable combination of star-star, star-delta transformer

connections, the required phase shift and voltages are given at the

leads on the valve side. Thus the 12 pulse converter is possible with

the use of converter transformer and quadruple valves

 The reactance of converter transformer help in minimizing non

characteristic current harmonics.

4.1.2 SPECIAL FEATURES OF A CONVERTOR


TRANSFORMER:

 High speed, reliable on load taps changer with 24 or more steps and

regulation of +17.5 and -12.5 % (or more). The tap changers operate

frequently and should need only modest maintenance.

 Specially built low loss, loss noise core. The magnetic circuit is

suitable for higher V/F ratios and higher harmonic content.

 Exceptionally long bushings to achieve desired creepage distances.

 Very special design of insulation system and windings.

 Higher percentage impedance to limit short circuit currents during

convertor operation.

 High reliability.

254
4.1.3 MODELING OF A TRANSFORMER AND
REPRESENTATION OF EQUIVALENT ELECTRIC
NETWORK.

A converter transformer can be modeled by sub-dividing the

windings into a large number of sections. The present transformer 315

400 206
MVA 3 3 KV is divided into 60 sections. Figure 4.1 shows the

constructional geometry of one limb of the converter transformer

comprising of tapping, HVAC and HVDC star windings. It has been

evaluated that for reasonably accurate neutral current calculation, it is

not required that the winding should be divided into such a large

number eight sections. Even formation of network with relatively smaller

number of sections can give accurate results. It also reduces the total

commutation time. For the purpose of the neutral current calculation the

tapping winding has been fully earthed as is done in a particular case of

impulse tests. The HVAC winding is divided into 8 sections and HVDC

winding is divided into 16 sections as shown in Figure 4.2. These

sections can be represented by self inductance (L) and mutual

inductance (M) with all other sections of the same winding as well as

with the other windings. The series and shunt capacitances are

calculated using standard formula [155] for parallel plate and cylindrical

geometry respectively. Using these above values an equivalent electric

network is derived.

255
Figure. 4.1 Sectional Distribution of HVDC converter Transformer.
A: Tapping winding, B: HV winding, C: HVDC Transformer winding
(star)

Figure. 4.2. Simulation model of the transformer

256
The transient voltage at any point in the winding for an impulse

excitation can be determined by solving the equivalent electric network.

An electrical equivalent network, made with the help of above parameters

has distribution given in Figure 4.3. The neutral current can be

calculated by applying impulse voltage at any point in the network. The

accuracy of the results obtained from equivalent circuit method depends

entirely on the number of sections introduced in the representation of

windings.

The equivalent circuit must describe the surge behavior of the

winding for wide range of variations of the input impulse voltage wave

shape and must be responsive to higher frequencies. This section

discusses the method of calculation of self / mutual inductance and

series/shunt capacitances.

Figure 4.3 Equivalent Circuit of a Single Winding of Transformer


257
Where

L1 , L2 ..... Ln represent the self inductance of the respective sections.

M 12 , M 13 ......... M 1n M 23 give the value of mutual inductance between


first and second sections and so on.

Cg1 , Cg 2 ,......... .Cgn corresponds to the capacitance between sections

and ground

Cs1 , Cs 2 ,......... .Csn corresponds to the series capacitance of the


sections

Rsh is the shunt resistance for computing the neutral current

Figure 4.4 Self inductance of a circular element

Where 2a = Mean diameter of the element

b = Axial height of the element

c = Radial dimension of the element

N = Number of turns in the element

258
4.1.4 SELF INDUCTANCE OF THE WINDING

The self inductance of a winding is given by

L = 0.001 N2 a P1µH (4.1)

Where 2a = Diameter of the winding in cm

N = Number of turns in the winding

P1 = P x f

Here P is a function of C/2a and f takes into account the


reduction of inductance due to separation of the turns in axial direction.
The values of P and f depend on the parameter c/2a and b/c.

Figure 4.5 Schematic diagram of two axially separated filaments if


different diameters

4.1.5 MUTUAL INDUCTANCE BETWEEN WINDINGS

The mutual inductance between the two coils, illustrated in


the above Figure 4.5 can be calculated by using the formula

M  N1 N 2 f aA  H (4.2)

Where, N1 and N2 are number of turns in each coil

259
'A' and 'a' are radii in cm.

f is evaluated as a function of the variable (K1)2

(A - a) 2  d 2
K 
1 2

where (A  a) 2  d 2
(4.3)

As a special case when A = a; M = N1N2f a.

4.1.6 SERIES CAPACITANCE OF TRANSFORMER


WINDING

The series capacitance of transformer winding depends on its

configuration. In the present study interleaved winding and plain disk

winding are considered.

4.1.6.1 SERIES CAPACITANCE OF INTERLEAVED WINDING

The series capacitance of an interleaved winding can be evaluated

by energy considerations. Let us consider an interleaved winding

comprising double discs with 2n turns / disc as shown in Figure 4.6

Let

CS = Equivalent series capacitance between two discs.

Ca = Capacitance between two discs based on geometric


factor.

2n = m (The number of turns in each disc)

260
Ct = Capacitance between adjacent turns

If the voltage „v‟ is applied across the double disc, the energy stored

across the two discs

1
 CS V 2
2

V
Voltage across each turn= Vt 
2m

V V
Voltage across each disc  m 
2m 2

Considering the energy balance in the disc winding we get

2 2
1 V  1 V 
  .Ct .2.(m - 1)    .Ca  2
2 2  2 2  1 (4.4)
 CS V 2
2

Or

Ct Ca
  Cs
2 2 (4.5)

From the above equation, it can be observed that higher the

number of turns higher is the total equivalent series capacitance.

Further, it is generally true that Ca/2 is much smaller than the first

factor.

261
Figure 4.6 configuration of interleaved winding

4.1.6.2 PLAIN DISC WINDING

Series capacitance of a plain disc winding is shown in


Figure 4.7(a) and is given by

a
Cs1  (Ca  Ct' )  [ a  coth  a ]
1   a2 (4.6)

Where

Cs1 = Total equivalent series capacitance of a disc

Ct = Capacitance between adjacent turns

Ca = Capacitance between two discs

Ct‟ = Ct /m

m = number of turns in a disc

= Ca / Ct‟

In general is much higher than unity hence approximately

Cs1 = Ca + Ct‟ (4.7)

262
4.1.7 GROUND / INTER WINDING CAPACITANCE

The capacitance between any two windings is calculated using the

standard formula for parallel plate capacitor. The area of the plate is

calculated on the basis of the mean diameter of the windings. The

distance between the plate/cylinder is considered based on the

composite oil/pressboard dimensions.

Figure 4.7(a) Configuration of Plain Disc Winding

263
4.1.8 INDUCTIVE CURRENT CALCULATIONS

In Figure 4.7(b) since a current shunt of a very small value of

Rsh is connected between node “n=1” and ground G, total current

through the inductive branch (n, n+1) is assumed to pass through the

shunt without being affected by the presence of capacitance Cg(n+1). The

current in the inductive branch is a function of the current in all other

branches due to mutual coupling between them. Since all node voltages

at any instant are known, the matrix equation defining the current and

voltage in all the branches can be described as:

 di 
[ L]   [V ]
 dt  or

 di  1
 dt   [ L] [V ]
  (4.8)

Where [L] is n x n matrix comprising of self and mutual

inductances;

[di/dt] is a column matrix representing rate of change of current in

all branches, [V] is column matrix, representing voltage drop across

branch.

From the equation (4.8) the di/dt in the nth inductance is given by

din
 Pn
dt or

264
in ( t1 ) t1

 din   P0dt  P0t


in ( t o ) t0

in t1  P0 t  in (t0 )
or

in t 2  P1t  in (t1 )
also

in tn  Pn 1t  in (t n 1 )
i.e (4.9)

where Pn assumed to be constant in any interval Δt

Figure: 4.7(b) Electrical equivalent network of the simulation model

265
4.1.9 CAPACITIVE CURRENT CALCULATIONS

Since Cg(n+) is very low, almost total current passing through the

series capacitance Csn is recorded by Rsh

1
Csn 
Vn ( n 1)  ic ( n ,n 1)

dvn ( n1)
Csn   ic ( n,n1)
Or dt (4.10)

From the above the capacitive current is given by

Vn ,n 1 (t1 )  Vn ,n 1 (t0 )
ic (t )  Csn
t (4.11)

Total neutral current at any instant is calculated using the

following equation:

i (t )  in (t )  ic (t )
(4.12)

400 206
The parameters of a 315 MVA, 3 3KV three winding
transformer (Transformer ground capacitance, Inter turn capacitance,
and Inductance were calculated using the above method and are given in
annexure-IV.

4.2 TRANSFORMER TESTING METHODS


The standard method of impulse testing for high voltage

transformer is carried out to determine whether a given transformer is

266
able to with stand the voltage as per the relevant standard. In case of a

major failure, the voltage collapses and current overshoots. However,

major problems are encountered when full winding failure does not occur

and a small fault in the form of turn to turn takes place during the

impulse test. Since the fault is major it does not reflect in considerable

change, either current or in voltage wave shape. The difference is to be

determined by eye estimation only. Since the transformer can be

declared to have passed the test if no detectable change is observed, it is

likely that sometime a faulty transformer can be declared to have passed

alternately a healthy transformer can be declared to have failed due to

small change is current caused by partial discharge at test voltage level.

The impulse test on converter transformer is intended to assess its

dielectric strength at basic impulse level (BIL). The minimum lightning

impulse withstands level of an apparatus for the specified nominal

system voltage is known as the BIL. The impulse voltage testing is the

most efficient quality control tool, which reveals the largest part of

internal insulation faults caused by the design or the manufacturing

flaws.

The conventional method of impulse testing of a transformer is

based on the comparison of the applied voltage and the neutral current

oscillogram taken at reduced and full voltages. In this non-destructive

test, it is assumed that the winding impedance does not vary at the

voltages below the expected highest voltage range. The output signals

267
viz., neutral terminal current is expected to have the same shape

provided the test object remains healthy.

4.1

4.2

4.2.1 IMPULSE TEST ON A TRANSFORMER

The shape of the voltages, their magnitude and sequence of

application that constitute proof tests are covered by standards such as

IEC-76, 1980 and IS 22026, 1977. The generally recommended order at

different impulse application is

 One reduced full impulse


268
 One 100% full impulse

 One or more reduced chopped impulse (S)

 Two 100% chopped impulse

 Two 100% full impulses

In addition to the record of the applied voltage, it is mandatory to

observe another performance related waveform during the test (IEC-722).

The transient waveform could be one of the following:

 The neutral current

 The winding current

 The current transferred to adjacent winding

 The tank current

 The voltage transferred to a non tested winding

4.3 METHOD OF DETECTING MINOR FAILURES


The standard method of impulse testing of a high voltage power

transformer is associated with the problems regarding identification of

minute failures particularly the inter turn faults. A minor difference

between the oscillogram of two cases can be indicative of inter turn

failure, which disqualifies a converter transformer. However, a strong

partial discharge can also result in a very similar difference which is

269
considered as acceptable, since the transformer does not have to be free

from the partial discharges at relatively higher impulse voltage test level.

Changes in the shape of the applied impulse voltage, due to

malfunctioning of the source, also affect the current oscillogram. In order

to establish the variations in current oscillograms with type of failure,

analytical modeling of the converter transformer is found to be useful. In

view of the above, the neutral current has been calculated by simulating

different types of failures.

4.3.1 IMPULSE TEST

The purpose of the impulse testing is to determine the ability of the

insulation of the transformer to withstand the transient voltage due to

lightning (including both direct and indirect stores). Full wave and

chopped wave impulse tests are methods to demonstrate the ability of

high voltage equipment to handle lightning strokes and switching over

voltages [137].

4.3.2 DETECTION AND LOCATION OF THE FAULT


DURING IMPULSE TESTING

The fault in the transformer insulation can be located during

impulse testing by means of any one of the following methods.

270
4.3.2.1 GENERAL OBSERVATION

Fault detection, which is the heart of routine impulse testing,

needs to be automatic for high volume testing and in any case all faults

should be clearly indicated. A major insulation fault, such as terminal to

ground or terminal to a low voltage winding is an easy fault to detect.

Typically this kind of fault can be detected by observing noise, smoke,

and bubbles.

4.3.3 VOLTAGE OSCILLOGRAM METHOD

Faults or failure appears as a partial or complete collapse of the

applied voltage wave. The sensitivity of the method is low, particularly if

turn to turn faults to be detected. The transient voltages generated

during lightning strokes are not distributed uniformly along the

transformer windings. Thus, full wave and chopped wave impulse test

oscillograms are recorded to demonstrate the ability of transformers to

handle the lightning strokes as defined in international standards like

IEC, IEEE etc.

4.3.4 NEUTRAL CURRENT METHOD

In the neutral current method, a record of the impulse current

flowing through a resistive shunt between the neutral and ground point

271
is used for detecting the fault. The neutral current oscillogram consists of

high frequency oscillations. These high frequency disturbances may be

super imposition of fault generated high frequency transients along with

reflections offered by the ground and of the windings for the fast rising

impulse currents. When fault occurs i.e. arcing between the turns or

from turn to ground take place, high frequency pulses similar to that of

the impulse current wave changes are caused.

4.3.4.1 TRANSFERRED SURGE CURRENT METHOD

In this method, the voltage across a resistive shunt connected

between the low voltage windings and the ground is used for identifying

the fault in the winding.

4.4 TRANSFER FUNCTION METHOD


It is an analytical model based diagnosis because the fault

detection is based on an identified model of the equipment. Ryszard

Malewski et al. [156] reported the transfer function of the transformer

winding, which is deconvoluted in the frequency domain from the

digitally recorded neutral current and impulse voltage applied during

impulse tests. The integrity of the winding insulation is determined by

comparing the transfer function obtained at Basic Insulation level (BIL)

272
and reduced impulse test voltages. Differences between the transfer

function plots reveal local breakdown in the winding that can be

dissociated from partial discharges. Some manufacturers of large high

voltage power transformers have so far been using the transfer function

method as a diagnostic technique. However, this basic philosophy may

be affected by a malfunction of the test voltage source i.e. the HV impulse

generator, which produces a slightly different impulse form at the full

and reduced test levels. This in turn will cause a difference between the

compared neutral current oscillogram, which according to the existing

standard may be interpreted as a transformer fault. Another drawback of

the present test technique is misinterpretation during evaluation of the

chopped impulse test. Neutral current comparison is not applicable here.

Since the time to chop cannot be controlled accurately, the neutral

current and test voltage waveform changes considerably from one shot to

another. Successive oscillograms of these parameters show a

considerable difference due to the scatter in the chopped impulse

duration and result in highly variable transfer function.

273
Figure. 4.8(a) Calculation process for the transfer function method

Figure. 4.8(b) Transfer function method

The third shortcoming of the existing test procedure is the

subjective way of interpreting the differences observed in the

oscillograms. An experienced inspector can tell the nature of the fault

from the form of the observed deviation, but in practice this often results

in controversy between the inspectors representing the buyer and seller.

This ambiguity is mainly due to non availability of recognized evaluation

of criterion.

The proposed transfer function method consists of comparing the

frequency domain graphs as shown in Figure 4.8(a) deconvoluted from

the test voltage and neutral current records obtained respectively at full

274
and reduced test levels. Deconvolution yields the transfer function,

which is characteristic of the test object and an ideal condition,

independent of the form of the applied impulse. The Converter

transformer can be seen as a black box, with fixed frequency behavior

between the four pole terminals as shown in Figure 4.8(b).

A simplistic conceptual winding model can be imagined in the form

of a string of inductors tapped by their parallel capacitances to ground

and shunted by parallel stray capacitance between the winding sections.

Such a model is quite adequate for explaining changes in the transfer

function caused by a fault in the winding insulation. In the lower

winding sections a fault would cause an oscillation at a proportionately

lower frequency. Experiments have demonstrated that a local

breakdown, in the winding occurring at the fault impulse test voltage

(BIL) results in a frequency shift of the transfer function poles.

This can be detected by superimposing the transfer function

obtained at the BIL and reduced test voltages. Even minor shift in the

pole frequency indicates a local breakdown. This evaluation may be

accurate, since no other mechanism could change the frequency of the

local winding resonance with increase in the applied test voltage. As

predictable, in nearly resistance free network of inductances and

capacitances a breakdown results in resistance damping. Consequently

275
the pole height decreases, even though its frequency remains practically

unchanged.

The differences between the transfer function recorded at the BIL

and at the reduced test level fall into two categories i.e. a local

breakdown and partial discharge.

A comprehensive analog model has been proposed by Syed

M.Isllam et al. [155], which can simulate leakage faults, partial

discharges as well as winding displacements, short circuits etc.

Sensitivity analyses of the parameters by sliding faults along the

distributed winding model results in distinct changes on the transfer

function. These results contribute to enrich the ability of the transfer

function approach as an excellent tool for condition monitoring by

locating faults in the high voltage power transformer.

Many researchers started modeling of transformers and generated

huge amount of data. It is important to note that, the transformer model

must be absolutely compatible with commercially available software

ensuring the simulation of the environment and the computation

management. Many authors [157,158] presented a method of modeling

internal faults in a power transformer which is entirely compatible with

Electromagnetic transient program (EMTP). The basic model is the one

supplied by the BCTRAN routine of the EMTP simulation software.

BCTRAN computes the elements of matrices [R] and [L] based on

276
excitation and short circuit tests in positive as well as zero sequence

elements of resistance, self inductance and mutual inductance. Using

these matrices every turn to earth and turn to turn faults were modeled

on the basis of leakage factors. These leakage factors can be determined

from geometrical data of the transformer and location of the fault.

A number of high frequency transformer models suitable for

transient simulation have been proposed in recent years. Even though

these models are very accurate, there are still number of problems in

terms of efficiency, numerical stability and data acquisition

requirements.

Some researchers attempt to present finite element analysis of

internal winding faults in a distribution transformer [159]. The

transformer with a turn to earth fault as well as turn to turn fault is

modeled using coupled electromagnetic and structural fine elements. The

terminal behavior of the transformer is studied by an induction coupling

of the finite element method and circuit simulation. The procedure was

realized using commercially available software. The equivalent circuit

model was exported and used in a circuit analysis package to study the

terminal behavior of the transformer compared with the previously

available experimental results. It is reiterated that with the help of Finite

Element model of transformer, an accurate estimation of the terminal

values of an internal winding fault is possible.

277
4.5 FREQUENCY RESPONSE ANALYSIS (FRA)
The method of system characterization by means of its frequency

behavior is called as frequency response analysis (FRA). The analysis is

recently introduced in the field of transformer testing and diagnosing.

T.N Vaessen et al. [151] proposed FRA method, which is easy to use in

field applications. The analysis gives reproducible results and high

resolution frequency spectra of both magnitude and phase without the

use of sophisticated equipment. The basic requirement for the analysis is

impulse source, a digitizer and a software implementation of a Fast

Fourier Transform (FFT) technique.

There are two ways of injecting the wide range of frequencies:

 By injecting an impulse into the winding or make a frequency

sweep into the winding using a sinusoidal signal. The former is

known as the low voltage impulse method

 Swept frequency method

The obtained frequency spectra can be used for diagnostics and

will be used as a finger print of a transformer. Mechanical changes and

the voltage independent defects like winding shorts are reflected in this

“finger print”. Results from FRA measurements can also be used as a

starting point for the development of a frequency dependent transform

model, which is required for transient calculations. Juan A. Martinez et

278
al. [152] presented a review of transformer model simulation for the

frequency content below 10 kHz.

Simon Ryder et al. [153] suggested that FRA is a powerful

diagnostic test technique. FRA consists of measuring the impedance of

transformer windings over a wide range of frequencies and comparing the

results of these measurements with a reference set. Differences may

indicate damage to the transformer, which can be investigated further by

combining with other techniques.

The low and medium frequency components in the frequency

response estimated by using the conventional Discrete Fourier Transform

(DFT) are insufficient [154]. To overcome this problem SSA (synthetic

spectral analysis) is proposed, which is based on CCM (cut and

concatenation method) for high quality frequency responses and the

„LOG‟ frequency interpolation for a balanced comparison over a whole

frequency range.

4.6 LIMITATIONS OF THE EXISTING METHODS


The testing of the transformer suffers from the following

limitations:

279
 It is necessary to avoid short circuiting of the other windings or

else the detection sensitivity decreased.

 This method is satisfactory for the small transformers. For the

transformers where there is considerable series capacitance, this

method may not give good result.

 Many times the allowable partial discharge that is tolerable is also

considered as a fault in the existing methods of testing.

 Comparison of neutral currents becomes more difficult during

chopped impulse tests and is also not acceptable as time of

chopping can not be more accurately controlled.

 The variation of resonant frequencies in the event of very minor

faults is often difficult to interpret from transfer function approach.

Hence it is not much effective in identifying the very minor faults in

a transformer.

4.7 PROBLEM FORMULATION


Converter transformers are essential y designed as special high

power transformers. However during the operation, the windings

connected to values have a D.C. potential to ground in addition to

280
induced A.C. voltage. This D.C. potential (due to connection to high

voltage D.C. values) requires different insulation design and winding

design.

The faults associated with the HVDC converter transformer are to

be analyzed using the neutral current obtained during the impulse test

on the HVDC converter transformer. A 315MVA converter transformer

model is used for the analysis. The neutral currents are to be analyzed

using the FFT, ANN and Wavelet Transform techniques. The neutral

currents obtained during the normal operating condition are decomposed

in to various frequency components and based on the wavelet transform

technique the reconstruction of the neutral current signal is to be done.

The HVDC converter transformer is subjected to various faults such as

winding to winding fault, winding to ground fault, turn to turn fault and

the signal is used to classify the faults in the converter transformer. The

techniques based on the wavelet transforms are proposed for the location

of faults in the converter transformer.

4.8 CLASSIFICATION OF FAULTS IN CONVERTER


TRANSFORMER

4.8.1 CALCULATION OF NEUTRAL CURRENTS

281
The standard impulse voltage waveform can be represented with

following equation:

V = V0(e-αt – e-βt) (4.13)

Where α and β are constants and depends upon the rate of rise

and decay of the pulse. For a given value of α=0.7936 x 106 and

β=0.02335 x 106 impulse voltage generated has a rise time of 1.2µs and

tail time of 50µs. When a signal in the time domain is converted into the

frequency domain, magnitude vs frequency plot is obtained. The

magnitude at first frequency step i.e. Δf is called DC level of the signal.

The neutral currents were calculated using computational method for

healthy winding and the winding with simulated faults along the

winding. The following converter transformer model has been considered

for neutral current calculation. Figure 4.9(a) represents a standard

impulse voltage applied to the transformer and Figure 4.9(b) represents a

standard impulse voltage applied to the transformer in frequency

domain.

282
Figure 4.9(a) Standard Impulse Voltage Applied in time domain

Figure 4.9(b) Standard Impulse Voltage Applied in frequency domain

4.8.2 ANALYSIS OF HVDC CONVERTER TRANSFORMER

In order to carry out the study a typical transformer has been

considered with the following rating.

KVA rating : 315MVA, Single phase 3 winding

Rated voltage

283
HV side : 400 / 3 KV

LV side : 206 / 3 KV both star and delta

Construction : Y/Y/∆

Tappings : 24 steps, on load – 12.5% to + 17.5%

Type of cooling : OFAF

This section describes the equivalent circuit of a transformer

model. Calculation of neutral current is carried out under various

condition i.e. healthy and faulty conditions. FFT analysis is carried out

for the neutral currents obtained from transformer model for different

conditions. The transformer is having 60 sections. The sectional

distribution of the windings is as follows:

 Tapping winding - 12 sections

 HV winding-32 sections and

 Star winding of the converter transformer - 16 sections

The details of the inter turn capacitances and inductances i.e.

equivalent circuit parameters is given in annexure-V for the convenience

the model has been simulated with 24 sections i.e. 8 sections of HV

winding and 16 sections of HVDC winding. The Tapping winding is

assumed to be short circuited and hence is eliminated in the simulation.

The current in the neutral has been measured at node no.25. Various

284
faults are simulated at different locations along the windings as follows.

The recorded neutral currents for various operating conditions of the

converter transformer have been given in annexure – IV.

4.8.3 NORMAL CONDITIONS

A standard impulse voltage of 1KV, 1.2µsec/50 µsec is applied at

node no.10 as shown in Figure 4.8. The highest magnitude of neutral

current under no fault condition is 1.4e-3 amperes. The waveform for the

neutral current during the normal operating conditions is shown in

Figure 4.10(a).

The neutral current is calculated for time duration of 102.4 µsec at

a sampling rate of 0.1 µsec. Dominant frequency corresponding to the

normal operating condition has been calculated using FFT analysis as

shown in Figure 4.10(b). The dominant frequencies in the neutral current

wave form are given in table 4.1. It is also observed that the neutral

current is consisting of the major part of the DC current.

Figure. 4.10(a) neutral current of the converter transformer during


normal operation

285
Figure. 4.10(b) FFT analysis of the neutral current signal during the
normal operating condition

4.9 RESULTS AND DISCUSSIONS

4.9.1 RECONSTRUCTION OF NEUTRAL CURRENTS USING


GABOR WAVELET

The aim of the present analysis is to segregate the neutral current

signal into the time varying current waveform at each dominant

frequency.

The wavelet transform can map any finite energy waveform from

the time domain to a finite energy two dimensional distribution in the

time- frequency domain. The transformation provides a way to predict

the time of occurrence and the variation of transient current with time at

a particular frequency. The wavelet transform W(a,b) of a function I(t)

with respect to a given mother wavelet (t), is defined as

286
(4.14)

Where a = scaling parameter

b = translation parameter

f = frequency

The Gabor mother wavelet has been used and is given by the

equation

(4.15)

Where 2 is a constant and control the band of frequencies to be

identified.

In order to evaluate the time varying current waveform at a

particular frequency, it is essential to determine the multiplication factor

(k). This factor converts the wavelet transform of the neutral current

signal at a particular scale parameter (a) into the transient current

waveform for corresponding frequency ( f  1/ 2  a ).

287
Table 4.1 Value of k w.r.t 2 for a frequency of 50 kHz.

2 F (kHz) K f2/k

8 50 707.24 1.0004

16 50 500.25 0.5005

64 50 250.13 0.1251

256 50 125.08 0.0313

512 50 88.42 0.0156

1024 50 62.56 0.0078

2048 50 44.27 0.0039

4096 50 31.36 0.0020

5120 50 28.10 0.0016

The selection of 2 value is based on the accuracy with which the

output waveform i.e. wavelet transformed input waveform at a particular

scale parameter matches with the input or original waveform. Table 4.1

gives the value of k corresponding to a 2 for a sinusoidal signal of

frequency equal to 50 kHz. Table 4.10 shows the value of f2/k for various

values of f and a constant 2=1024.

288
Table 4.2 Variation of k w.r.t. Frequency

F (kHz) K f2/k
107 37.383 0.0131
205 51.840 0.0113
293 57.670 0.0113
332 88.810 0.0113
381 65.617 0.0113

4.9.1.1 WAVELET CALCULATION

An algorithm is developed using Gabor Wavelet equation for

analysis of the neutral current. A suitable computer program has been

written using Gabor wavelet equation for the detection and

reconstruction of the neutral current signal of LV winding of the HVDC

converter Transformer. For the neutral current, the time frequency

characteristics were determined using wavelet transform. The wavelet

analyzed signal is again analyzed using FFT algorithm to find the

accuracy of the wavelet. All the wavelet signals have been added after

multiplying with the concerned k value. That signal is the reconstructed

signal of the original signal. Figure 4.10(a) shows a typical nature of

neutral current for healthy winding of the converter transformer. The

currents thus measured show a characteristic of neutral current pattern.

The current is analyzed by FFT to obtain the range of dominant

289
frequencies contained in the neutral currents. A typical FFT plot for

above is shown in Figure 4.10(b).

Table 4.3 List of dominant frequencies and corresponding K values w.r.t. 2 values

2
S.No Frequency  K
1 48845 Hz 16 156.31
2 68342 Hz 256 46.23
3 106870 Hz 64 115.62
4 146088 Hz 512 47.80
5 204937 Hz 256 80.05
6 243853 Hz 512 61.763
7 293252 Hz 512 67.73
8 331741 Hz 512 72.04
9 380947 Hz 1024 54.62
10 410401 Hz 1024 56.69
11 430367 Hz 5120 26.32
12 458892 Hz 1024 59.94
13 488453 Hz 1024 61.84
14 527270 Hz 2048 45.87
15 547202 Hz 1024 65.46
16 566675 Hz 4096 34.11
17 585425 Hz 5120 30.70

The dominant frequencies are identified from the FFT analysis plot

of the neutral current. Table 4.3 indicates a list of 17 predominant

frequencies. These frequencies are used to obtain the dilation coefficients

for carrying out the wavelet analysis. The 2 is chosen in such a way that

290
the wavelet output is representing that particular frequency component.

Figure 4.11(a), 4.11(b) and 4.11(c) represents the FFT analysis applied to

each wavelet transform output. Figure 4.12 shows wavelet transform

neutral current signals for the identified 17 predominant frequencies.

Reconstruction is done by adding the all the frequency components by

multiplying with the corresponding k values. Figure 4.13 shows the

reconstructed neutral current signal along with the original neutral

current signal. It is clear that the reconstructed signal is almost identical

to the original signal.

Figure. 4.11(a) Magnitude Vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 1-7 listed in Table 4.3.

291
Figure. 4.11(b) Magnitude vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 8-14 listed in Table 4.3.

Figure. 4.11(c) Magnitude vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 15-17 listed in Table 4.3.

292
Figure. 4.12(a) wavelet transform of the input signal for a corner
frequency of 9770 Hz, 2=0.25

Figure. 4.12(b) wavelet transform of the input signal for a corner


frequency of 48.845 kHz, 2=16

Figure. 4.12(c) wavelet transform of the input signal for a corner


frequency of 68.342 kHz, 2=256

293
Figure. 4.12(d) wavelet transform of the input signal for a corner
frequency of 106.870 kHz, 2=64

Figure. 4.12(e) wavelet transform of the input signal for a corner


frequency of 146.088 kHz, 2=512

Figure. 4.12(f) wavelet transform of the input signal for a corner


frequency of 204.937 kHz, 2=256

294
Figure. 4.12(g) wavelet transform of the input signal for a corner
frequency of 243.853 kHz, 2=512

Figure. 4.12(h) wavelet transform of the input signal for a corner


frequency of 293.252 kHz, 2=512

Figure. 4.12(i) wavelet transform of the input signal for a corner


frequency of 331.74 kHz, 2=512

295
Figure. 4.12(j) wavelet transform of the input signal for a corner
frequency of 380.95 kHz, 2=1020

Figure. 4.12(k) wavelet transform of the input signal for a corner


frequency of 410.40 kHz, 2=1020

Figure. 4.12(l) wavelet transform of the input signal for a corner


frequency of 430.37 kHz, 2=5120

296
Figure. 4.12(m) wavelet transform of the input signal for a corner
frequency of 458.89kHz, 2=1020

Figure. 4.12(n) wavelet transform of the input signal for a corner


frequency of 488.45 kHz, 2=1020

Figure. 4.12(o) wavelet transform of the input signal for a corner


frequency of 527.27 kHz, 2=2050

297
Figure. 4.12(p) wavelet transform of the input signal for a corner
frequency of 547.20Hz, 2=1020

Figure. 4.12(q) wavelet transform of the input signal for a corner


frequency of 566.68 kHz, 2=4100

Figure. 4.12(r) wavelet transform of the input signal for a corner


frequency of 585.43 kHz, 2=5120

298
Figure. 4.13 Reconstructed and Original Neutral current signals.

4.9.2 CLASSIFICATION OF INTERNAL FAULTS IN A


CONVERTER TRANSFORMER USING ANN

A standard impulse voltage with a raise time of 1.2μs and a tail of

50μs is applied to one of the limb of the star winding of the HVDC

converter transformer. The calculated neutral current is normalized after

taking the absolute value of the signal. The neutral current signal is

sampled at 0.1 μs of time and 1024 samples taken for 102.4 micro

seconds of time. The neutral current signal for various fault conditions is

plotted in Figure 4.14.

The neutral current samples of the HVDC converter transformer

are divided into 16 sets. The normalized data is given as input to train

the artificial neural networks using back propagation algorithm.

299
Figure 4.14(a): Recorded Neutral Current during normal operating
condition

Figure 4.14(b): Recorded Neutral Current during inter turn fault in


LV winding fault

Figure 4.14(c): Recorded Neutral Current during inter turn fault in


HV winding fault

300
Figure 4.14(d): Recorded Neutral Current during winding to winding
fault

Figure 4.14(e): Recorded Neutral Current during winding to ground


fault

Figure. 4.15: Normalized local average values as input patterns for


training neural network.

301
Figure. 4.16: Normalized local maximum values as input patterns for
training neural network.

A separate training data is prepared after taking the local average

values and maximum for every 6.4μs of time. Out of the recorded neutral

current data of 102.4μs, the normalized local average data and the local

maximum data is given as an inputs to the neural networks and the

networks are trained till the error is reduced. The training data for all the

fault conditions is given after normalization is given in Figure 4.15 and

4.16. The error plot of neural network after training with the local

average values is given in Figure 4.17. The error plot of neural network

after training with the local maximum values is given in Figure 4.18.

From Figure 4.17 it can be stated that the neural network has

taken more than 180 iterations to reduce the error to 4.64276x10-16 in

case when average data is taken as the input sets and from Figure 4.18

it has taken less than 130 iterations to reduce the error to 3.76898x10-16

when the local maximum values have been taken as the training and

302
testing patterns. A total number of 34 sets of data is prepared and out of

this 20 sets of data is used for training and 14 sets of data is used for

testing the Artificial Neural Network. Table 4.4 is shows various test

results with both average test patterns and Maximum test patterns.

From the test results as listed in Table 4.4 and Figure. 4.19 it can be

stated that the local maximum value based training patterns are

providing better diagnosis characteristics when compared to that of the

local average value based data sets.

Figure 4.17: Mean square Error plot after training using local
average patterns as training sets.

Figure 4.18: Error plot after training using local maximum patterns
as training sets.

303
Table. 4.4 Test result for the network for both average and maximum data sets.

Diagnosis by
Fault Fault Location Local Average Local Maximum
value value
Normal Operation YES YES
12th Disk YES YES
14th Disk YES YES
15th Disk YES YES
Turn to 17th Disk YES YES
Turn
Faults 20th Disk YES YES
21st Disk YES YES
22nd Disk YES YES
24th Disk YES YES
17th to 4th YES YES
17th to 5th YES YES
18th to 4th YES YES
18th to 5th YES YES
19th to 4th YES YES
19th to 5th YES YES
Winding 20th to 4th YES YES
to
Winding 20th to 5th YES YES
20th to 6th YES YES
21st to 5th YES YES
21st to 6th YES YES
21st to 7th NO NO
22nd to 6th YES YES
22nd to 7th NO YES
17th Ground NO YES
18th Ground NO YES
Turn to 19th Ground YES YES
Ground 20th Ground YES NO
21st Ground YES YES
22nd Ground YES YES

304
Figure 4.19: Summary of the test results for the classification of
faults in convertor transformer.

4.9.3 CLASSIFICATION OF INTERNAL FAULTS IN A


CONVERTER TRANSFORMER USING WAVELET
TRANSFORMS

The fault data generated for training the ANN is used for the

classification of faults by using wavelet transform technique also. For

this purpose daubechies4 (with 8 levels of decomposition) wavelet is used

as the mother wavelet. The wavelet coefficients for various operating

conditions are recorded and are used to generate the training data for

ANN. A set of model plots of the wavelet coefficients for various operating

conditions of the HVDC converter transformer are as shown in Figure

4.20(a) to 4.20(d).

305
Figure. 4.20(a) Wavelet transform of the neutral current of the HVDC
converter transformer during No fault (Normal Operation)

Figure. 4.20(b) Wavelet transform of the neutral current of the HVDC


converter transformer during Turn to Turn Fault

306
Figure. 4.20(c) Wavelet transform of the neutral current of the HVDC
converter transformer during Winding to winding fault

Figure. 4.20(d) Wavelet transform of the neutral current of the


HVDC converter transformer during Turn to Ground fault.

307
The normalized absolute level 8 wavelet coefficients are used for

training the Artificial Neural Networks. The feed forward back

propagation method is used for training the artificial neural networks. A

three layer neural network with 10 neurons in the input layer 4 neurons

in hidden layer is used for this classification problem.

A total number of 34 sets of data is prepared and out of this 20

sets of data is used for training and 14 sets of data is used for testing the

Artificial Neural Network. Figure 4.21 shows the mean square error

during the training of ANN for the classification of faults in the converter

transformer. The ANN has taken 347 epochs for the training to attain an

accuracy of 0.025. Table 4.5 is shows various test results for

classification of faults in the converter transformer.

Figure. 4.21 Mean square error curve during the training of ANN for
the classification of faults in converter transformer

308
Table. 4.5 Test result of the neural network for the classification of
faults.

Fault Fault Location Classification by ANN


Normal Operation YES
12th Disk YES
14th Disk YES
15th Disk YES
Turn to Turn 17th Disk YES
Faults 20th Disk YES
21st Disk YES
22nd Disk YES
24th Disk YES
17th to 4th YES
17th to 5th YES
18th to 4th YES
18th to 5th YES
19th to 4th YES
19th to 5th YES
Winding to 20th to 4th YES
Winding 20th to 5th YES
20th to 6th YES
21st to 5th YES
21st to 6th YES
21st to 7th YES
22nd to 6th YES
22nd to 7th YES
17th Ground YES
18th Ground YES
Turn to 19th Ground YES
Ground 20th Ground YES
21st Ground YES
22nd Ground YES

309
4.10 EXPERIMENTAL INVESTIGATION OF NEUTRAL
CURRENT
In an effort to characterize the behavior of the converter

transformer, internal short circuits and incipient faults were analyzed.

Experiments were performed on a custom built transformer winding. For

the purpose of experiment, the leads from disc of high voltage winding

and tapping winding, and also turns at various locations in tapping

winding were brought out. The paper insulation of discs and turns at

specific locations is removed such that bare copper is available for

creating the faults between different discs and between adjacent turns.

The exposed copper conductors of each discs and turns in the HV

winding and tapping winding are physically shortened one after another

to create disc as well turn faults, simulating the internal faults in

transformer. The experiment was conducted by applying a low voltage

standard impulse (1.2/50μs) from a Recurrent Surge Generator (RSG)

and recorded the voltage and neutral current signals on a digital

oscilloscope. The same experiment is repeated by using a standard high

voltage impulse from a P-35 bench type impulse generator and voltage

and current signals are recorded on a digital oscilloscope. The above

signals are measured for healthy as well as winding with disc-to-disc and

turn-to-turn faults. The recorded currents are analyzed by wavelet

transforms (WT) and plots are obtained for each case. Fast Fourier

Transform (FFT) is carried out for selected neutral current to determine

310
the range of frequencies contained in the signal. From the results it has

been inferred that wavelet technique can be applied for detection of

minor faults in a power transformer. The concept of the experimental

studies, application of recurrent surge, high voltage impulse and wavelet

calculations for analysis of neutral currents are described below.

4.10.1 EXPERIMENTAL STUDIES ON TRANSFORMER

The measurements were carried out on the HV winding and

tapping winding of a Transformer. A low voltage impulse was applied

from Recurrent Surge Generator (RSG) at the HV central lead of the

winding and currents was recorded by an oscilloscope at the neutral

terminal across a suitable shunt. The transient neutral currents were

recorded for healthy winding and for the disc-to-disc faults created at

various places along the winding. Subsequently, the recurrent surge was

also applied to one end of the tapping winding and currents were

recorded at other end of the winding. These currents were recorded for

healthy winding and winding with fault created in the disc and turn at

different locations along the length of the winding. These experiments

were repeated using suitable Metal Oxide Varistor (MOV) for shorting the

discs and turns at several places in the HV and tapping windings. The

neutral currents were also recorded for healthy winding and winding

311
with faults. The details of the transformer used and the method adopted

are given below.

4.10.1.1 DESCRIPTION OF TRANSFORMER

The Transformer and test setup used for study has the power

rating of 61 MVA and the voltage rating of 11.5/230 kV as shown in

Figure 4.22. The high voltage winding is of two-group construction with

center entry type having a total of 112 discs. Each disc is of inter leaved

type having 22 turns per disc as shown in Figure 4.23. The tapping

winding comprises 40 plain discs of 4 turns each shown in Figure 4.24.

Both HV and tapping windings are considered for experimental data

generation. Due to symmetry, only one half of each winding is used for

experimental studies. The schematic diagrams used for experimental

studies are shown in Figure 4.25 and in Figure 4.26. Equivalent

electrical circuit of Generator Transformer for minimum tap position is

shown in Figure 4.27.

312
Figure.4.22: Photographs of 61MVA, 11.5/230kV Generator
Transformer

Figure.4.23: Photograph of upper Figure.4.24: Photograph of


half HV Winding of Generator Tapping Winding of Generator
Transformer Transformer

313
Figure.4.25. Electrical Figure.4.26. Electrical
Connection without tapping Connection with HV and tapping
winding for 11.5kV/230kV GT. winding of GT.

U(t)

ELECTRICAL NETWORK OF A MULTI-WINDING TRANSFORMER

Figure. 4.27. Electrical equivalent circuit of generator transformer

314
4.10.1.2 APPLICATION OF RECURRENT SURGE GENERATOR
(RSG)

Figure 4.28 shows a view of the experimental set up used for this

study. An impulse voltage of magnitude 100 Volts from RSG (Type 481)

was applied at the center entry lead of HV winding and the neutral

currents were recorded on digital oscilloscope (Type Nicolet Power Pro

610) across a 20Ω shunt as shown in Figure 4.29. Currents were

recorded for healthy winding as well as for winding with shorted discs.

Similarly, an impulse voltage of magnitude 100 Volts was applied at 40th

disc of tap winding and the neutral currents were recorded at 1st disc of

the winding across the 20Ω shunt. In order to carry out the experiment,

the paper insulation from the outer end of a number of discs/turns along

the height of the HV and tapping windings were removed to have an

access to the bare copper conductor of the discs and turns. The bare

portions of the conductors were physically shorted to create short circuit

and neutral current was recorded for each fault.

Figure 4.28: Circuit diagram for experimental setup

315
Figure 4.29: Neutral Currents recorded on oscilloscope across 20
ohms shunt

The following recordings were carried out on healthy and shorted

disc/turns of HV and tapping windings:

A. High Voltage Winding (Disc faults)


1). Healthy winding (without fault)

2). 2 to 4 disc fault

3). 2 to 6 disc fault

4). 2 to 8 disc fault

5). 2 to 10 disc fault

6). 2 to 12 disc fault

7). 2 to 14 disc fault

8). 2 to 16 disc fault

9). 4 to 6 disc fault

10). 6 to 8 disc fault

11). 8 to 10 disc fault

12). 10 to 12 disc fault

13). 12 to 14 disc fault

14). 14 to 16 disc fault

316
B. TAPPING WINDING (Disc faults)

1). Healthy winding (without fault)

2). Outer turns of disc no 39 and disc no.38

3). Outer turns of disc no 39 and disc no37

4). Outer turns of disc no 39 and disc no.36

5). Outer turns of disc no 39 and disc no.35

6). Outer turns of disc no 39 and disc no.33

7). Outer turns of disc no. 39 and disc no.32

8). Outer turns of disc no. 39 and disc no.31

9). Outer turns of disc no. 39 and disc no. 29

10). Outer turns of disc no. 39 and disc no. 27

11). Outer turns of disc no. 39 and disc no. 26

12). Outer turns of disc no. 37 and disc no. 35

13). Outer turns of disc no. 35 and disc no. 33

14). Outer turns of disc no. 33 and disc no. 31

15). Outer turns of disc no. 29 and disc no. 27

16). Outer turns of disc no. 27 and disc no. 25

17). Outer turns of disc no. 25 and disc no. 23

18). Outer turns of disc no. 23 and disc no. 21

19). Outer turns of disc no. 21 and disc no. 19

20). Outer turns of disc no. 15 and disc no. 13

21). Outer turns of disc no. 9 and disc no. 7

22). Outer turns of disc no. 7 and disc no. 5

23). Outer turns of disc no. 5 and disc no. 3

317
C. TAPPING WINDING (Turn faults)

1). 1 to 2 turn fault in 40th disc

2). 1 to 3 turn fault in 40th disc

3). 1 to 4 turn fault in 40th disc

4). 1 to 2 turn fault in 37th disc

5). 1 to 2 turn fault in 33rd disc

6). 1 to 2 turn fault in 29th disc

7). 1 to 2 turn fault in 25th disc

8). 1 to 2 turn fault in 21st disc

9). 1 to 2 turn fault in 17th disc

10). 1 to 2 turn fault in 13th disc

11). 1 to 2 turn fault in 9th disc

12). 1 to 2 turn fault in 5th disc

4.10.1.3 APPLICATION OF VOLTAGE FROM AN IMPULSE


GENERATOR

An impulse voltage of magnitude 10 kV (positive polarity) from

Bench type Impulse generator (HAEFLY make, Model P-35) was applied

at the center entry of high voltage lead. The neutral currents were

recorded using digital oscilloscope (type CL 564A, Lecroy make) across a

1Ω shunt.

The currents were recorded for healthy winding as well as shorted

discs for high voltage and tapping windings. A 5 kV impulse voltage was

318
applied for turn-fault in the tapping winding. The bare portion of the

disc/turn conductors were shorted across the Metal Oxide Varistor

(ELPRO make, 440/20J) and neutral current have been recorded for

each fault.

4.10.1.4 APPLICATION OF METAL OXIDE VARISTOR (MOV)

Varistors (Variable Resistors) are Voltage-dependent resistors with

a symmetrical V - I characteristic curve whose resistance decreases with

increasing voltage. When connected in parallel with any circuit, it will

form a low-resistance shunt when voltage increases. The voltage

dependence of varistors may be approximately characterized by the

formula, I = kVα, where 'α' denotes the "non linearity" exponent and in

this way may be interpreted as a measure of the steepness of the V-I

characteristics. Like other varistor transient suppressors, the new

varistor has a nonlinear voltage-current characteristic that makes it

useful in voltage-regulation applications. Because of its non-linear V-I

curve, it has a very steep-slope as compared to the most other varistors.

It can pass currents over a narrow voltage range.

At low applied voltages, the metal oxide type varistor looks like an

open circuit because its unique low-pass material assumes the

properties of an insulator. When applied voltage exceeds rated clamping

voltage, the device effectively becomes a short circuit; steady-state power

319
dissipation is typically a fraction of a milliwatt, as compared to the

hundreds of watts dissipated by some other varistor devices. At present

operating voltage ratings for MOV-based series varistors range from 140

to 1400 Volts peak.

By keeping in view the above characteristic, ELPRO make RDN

440l2OJ disc type MOV has been selected for experiment. Figure 4.30(a).

shows the connection of varistor to the windings where the neutral

current is measured. Simplified equivalent electrical circuit for the metal-

oxide-type varistor is a combination of capacitance and resistances. The

capacitance can be attributed to the very thin dielectric, which becomes

a fairly significant factor for the varistor's dynamic characteristic. The V-I

characteristic of RDN 440/20J was studied by at different impulse

voltages and corresponding currents were measured and resistance

values have been calculated. The experimental data is shown in figure

4.30(b) and Table 4.6. The V-I characteristic curve has been generated

when the MOV has been connected across the discs and turns at various

locations along the length of the high voltage and tapping windings. The

neutral currents were recorded on oscilloscope. All the neutral current

recordings as mentioned in the previous section were repeated using

MOV. The main aim of using this device is to record the neutral currents

when actual shorting of disc or turn is taking place in the winding during

high voltage impulse test. The experimental setup for neutral current

measurement using MOV is shown in Figure 4.31.and in Figure 4.32.

320
Table 4.6: Voltage - Current characteristic of MOV (440/20J)

Voltage (kVp) Current (A) Resistance (Ω)

0.50 - -

1.00 0.781 1175.10

1.10 1.219 902.37

1.25 1.578 687.14

1.35 2.391 459.62

1.50 3.094 379.81

2.00 5.375 267.09

3.00 11.090 165.05

4.00 16.310 140.25

5.00 21.620 160.27

6.00 26.630 120.31

7.00 31.940 114.16

8.00 37.720 107.01

Figure. 4.30(a) Close up view of MOV / shunt Connection in HV


winding

321
Figure. 4.30(b) Voltage - Current characteristic of MOV

Figure. 4.31 Neutral Current Recording using Digital Oscilloscope

322
]
Figure.4.32: Photograph showing use of MOV during Neutral Current
measurement on HV winding using high impulse voltage

The neutral currents were recorded for healthy winding as well for

the winding with created faults along the length of HV and tapping

windings. The faults are created in the discs of HV winding and disc and

turn of tapping winding. A voltage surge of 10kV is applied and neutral

currents were recorded using oscilloscope. Different cases are considered

for neutral current recordings by creating faults at different locations.

The neutral currents are also recorded for all the above cases by

applying 10 kV standard impulse voltage to HV and tapping windings. A

Metal Oxide Varistor (MOV) was employed across the discs of HV winding

and discs/turns of tapping winding. The applied impulse voltage is

shown in Figure 4.33. Few typical neutral current waveforms using RSG

are shown in Figure 4.34 for HV winding and Figure 4.35 for tapping

winding.

323
Figure. 4.33 Applied impulse Figure. 4.34(c) Neutral Current
voltage waveform waveform with 2 – 6 disc fault
in HV winding

Figure. 4.34(a) Neutral Current Figure. 4.34(d) Neutral Current


waveform with out disc fault in waveform with 2 – 8 disc fault
HV winding in HV winding

Figure. 4.34(b) Neutral Current Figure. 4.34(e) Neutral Current


waveform with 2 – 4 disc fault waveform with 2 – 10 disc fault
in HV winding in HV winding

324
Figure. 4.34(f) Neutral Current Figure. 4.34(i) Neutral Current
waveform with 2 – 12 disc fault waveform with 4 – 6 disc fault
in HV winding in HV winding

Figure.4.34 (g) Neutral Current Figure. 4.34(j) Neutral Current


waveform with 2 – 14 disc fault waveform with 6 – 8 disc fault
in HV winding in HV winding

Figure. 4.34(h) Neutral Current Figure. 4.34(k) Neutral Current


waveform with 2 – 16 disc fault waveform with 8 – 10 disc fault
in HV winding in HV winding

325
Figure. 4.34(l) Neutral Current Figure. 4.35(a) Neutral Current
waveform with 10 – 12 disc waveform without disc fault in
fault in HV winding tapping winding

Figure.4.34 (m) Neutral Current Figure. 4.35(b) Neutral Current


waveform with 12 – 14 disc waveform with 39 – 38 disc
fault in HV winding fault in tapping winding

Figure. 4.34(n) Neutral Current Figure. 4.35(c) Neutral Current


waveform with 14 – 16 disc waveform with 39 – 37 disc
fault in HV winding fault in tapping winding

326
Figure. 4.35(d) Neutral Current Figure. 4.35(g) Neutral Current
waveform with 39 – 36 disc waveform with 39 – 32 disc
fault in tapping winding fault in tapping winding

Figure. 4.35(e) Neutral Current Figure. 4.35(h) Neutral Current


waveform with 39 – 35 disc waveform with 39 – 31 disc
fault in tapping winding fault in tapping winding

Figure. 4.35(f) Neutral Current Figure. 4.35(i) Neutral Current


waveform with 39 – 33 disc waveform with 39 – 29 disc
fault in tapping winding fault in tapping winding

327
Figure. 4.35(m) Neutral Current
Figure. 4.35(j) Neutral Current waveform with 39 – 37 disc
waveform with 39 – 27 disc fault in tapping winding
fault in tapping winding

Figure. 4.35(n) Neutral Current


Figure. 4.35(k) Neutral Current waveform with 37 – 35 disc
waveform with 39 – 26 disc fault in tapping winding
fault in tapping winding

Figure. 4.35(o) Neutral Current


Figure. 4.35(l) Neutral Current
waveform with 35 – 33 disc
waveform with 39 – 25 disc
fault in tapping winding
fault in tapping winding

328
Figure. 4.35(p) Neutral Current Figure. 4.35s) .Neutral Current
waveform with 33 – 31 disc waveform with 27 – 25 disc
fault in tapping winding fault in tapping winding

Figure. 4.35(q) Neutral Current Figure.4.35(t) Neutral Current


waveform with 31 – 29 disc waveform with 25 – 23 disc
fault in tapping winding fault in tapping winding

Figure. 4.35(r) Neutral Current Figure. 4.35(u) Neutral Current


waveform with 29 – 27 disc waveform with 23 – 21 disc
fault in tapping winding fault in tapping winding

329
Figure. 4.35(v) Neutral Current Figure.4.35(y) Neutral Current
waveform with 21 – 19 disc waveform with 7 – 5 disc fault
fault in tapping winding in tapping winding

Figure. 4.35(w) Neutral Current Figure. 4.35(z) Neutral Current


waveform with 15 – 13 disc waveform with 5 – 3 disc fault
fault in tapping winding in tapping winding

Figure. 4.35(x)Neutral Current Figure. 4.35(aa) Neutral


waveform with 9 – 7 disc fault Current waveform with 38 – 33
in tapping winding disc fault in tapping winding

330
Figure. 4.35(ab) Neutral Figure. 4.35(ae) Neutral
Current waveform with 32 – 27 Current waveform with 13 – 8
disc fault in tapping winding disc fault in tapping winding

Figure. 4.35(ac) Neutral Figure. 4.35(af) Neutral Current


Current waveform with 27 – 22 waveform with 8 – 3 disc fault
disc fault in tapping winding in tapping winding

Figure. 4.35(ad) Neutral Figure. 4.35(ag) Neutral


Current waveform with 21 – 16 Current waveform with 39 – 2
disc fault in tapping winding disc fault in tapping winding

331
Figure. 4.36(a) Neutral Current Figure. 4.36(d) Neutral Current
waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 40th disc of tapping winding in 37th disc of tapping winding

Figure. 4.36(b) Neutral Current Figure. 4.36(e) Neutral Current


waveform with 1 – 3 turn fault waveform with 1 – 2 turn fault
in 40th disc of tapping winding in 33rd disc of tapping winding

Figure. 4.36(f) Neutral Current


Figure. 4.36(c) Neutral Current
waveform with 1 – 2 turn fault
waveform with 1 – 4 turn fault
in 29th disc of tapping winding
in 40th disc of tapping winding

332
Figure. 4.36(g) Neutral Current Figure. 4.36(j) Neutral Current
waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 25th disc of tapping winding in 13th disc of tapping winding

Figure. 4.36(h) Neutral Current Figure. 4.36(k) Neutral Current


waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 21st disc of tapping winding in 9th disc of tapping winding

Figure. 4.36(i) Neutral Current Figure. 4.36(l) Neutral Current


waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 17th disc of tapping winding in 5th disc of tapping winding

333
4.10.2 FFT ANALYSIS OF THE NEUTRAL CURRENTS:

The Fast Fourier analysis has been carried out for all the above

cases to obtain the dominant frequencies. Typical FFT waveforms for

healthy winding and winding with disc fault in HV winding are given in

Figure 4.37. Similarly the FFT waveforms for healthy winding and

winding with disc and turn faults in tapping winding are shown in Figure

4.38 and 4.39.

Figure. 4.37(a) FFT of Neutral Figure. 4.37(c) FFT of Neutral


Current waveform with out Current waveform with 2 – 6
disc fault in HV winding disc fault in HV winding

Figure. 4.37(b) FFT of Neutral Figure. 4.37(d) FFT of Neutral


Current waveform with 2 – 4 Current waveform with 2 – 8
disc fault in HV winding disc fault in HV winding

334
Figure. 4.37(e) FFT of Neutral Figure. 4.37(h) FFT of Neutral
Current waveform with 2 – 10 Current waveform with 2 – 16
disc fault in HV winding disc fault in HV winding

Figure. 4.37(f) FFT of Neutral Figure. 4.37(i) FFT of Neutral


Current waveform with 2 – 12 Current waveform with 4 – 6
disc fault in HV winding disc fault in HV winding

Figure. 4.37(g) FFT of Neutral Figure. 4.37(j) FFT of Neutral


Current waveform with 2 – 14 Current waveform with 6 – 8
disc fault in HV winding disc fault in HV winding

335
Figure. 4.37(k) FFT of Neutral Figure. 4.37(n) FFT of Neutral
Current waveform with 8 – 10 Current waveform with 14 – 16
disc fault in HV winding disc fault in HV winding

Figure. 4.37(l) FFT of Neutral Figure. 4.38(a) FFT of Neutral


Current waveform with 10 – 12 Current waveform without disc
disc fault in HV winding fault in tapping winding

Figure. 4.37(m) FFT of Neutral Figure. 4.38(b) FFT of Neutral


Current waveform with 12 – 14 Current waveform with 39 – 38
disc fault in HV winding disc fault in tapping winding

336
Figure. 4.38(c) FFT of Neutral Figure. 4.38(f) FFT of Neutral
Current waveform with 39 – 37 Current waveform with 39 – 33
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(d) FFT of Neutral Figure. 4.38(g) FFT of Neutral


Current waveform with 39 – 36 Current waveform with 39 – 32
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(e) FFT of Neutral Figure. 4.38(h) FFT of Neutral


Current waveform with 39 – 35 Current waveform with 39 – 31
disc fault in tapping winding disc fault in tapping winding

337
Figure. 4.38(i) FFT of Neutral Figure. 4.38(l) FFT of Neutral
Current waveform with 39 – 29 Current waveform with 39 – 25
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(j) FFT of Neutral Figure. 4.38(m) FFT of Neutral


Current waveform with 39 – 27 Current waveform with 39 – 37
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(k) FFT of Neutral Figure. 4.38(n) FFT of Neutral


Current waveform with 39 – 26 Current waveform with 35 – 33
disc fault in tapping winding disc fault in tapping winding

338
Figure. 4.38(o) FFT of Neutral Figure. 4.38(r) FFT of Neutral
Current waveform with 33 – 31 Current waveform with 27 – 25
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(p) FFT of Neutral Figure. 4.38(s) FFT of Neutral


Current waveform with 31 – 29 Current waveform with 25 – 23
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(q) FFT of Neutral Figure. 4.38(t) Neutral Current


Current waveform with 29 – 27 waveform with 23 – 21 disc
disc fault in tapping winding fault in tapping winding

339
Figure. 4.38(u) FFT of Neutral Figure. 4.38(x) FFT of Neutral
Current waveform with 21 – 19 Current waveform with 7 – 5
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(v) FFT of Neutral Figure. 4.38(y) FFT of Neutral


Current waveform with 15 – 13 Current waveform with 5 – 3
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(w) FFT of Neutral Figure. 4.38(z) FFT of Neutral


Current waveform with 9 – 7 Current waveform with 38 – 33
disc fault in tapping winding disc fault in tapping winding

340
Figure. 4.38(aa) FFT of Neutral Figure. 4.38(ad) FFT of Neutral
Current waveform with 32 – 27 Current waveform with 13 – 8
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(ab) FFT of Neutral Figure. 4.38(ae) FFT of Neutral


Current waveform with 27 – 22 Current waveform with 8 – 3
disc fault in tapping winding disc fault in tapping winding

Figure. 4.38(ac) FFT of Neutral Figure. 4.39(a) FFT of Neutral


Current waveform with 21 – 16 Current waveform with 32 – 2
disc fault in tapping winding disc fault in tapping winding

341
Figure. 4.39(b) FFT of Neutral Figure. 4.39(e) FFT of Neutral
Current waveform with 1 – 3 Current waveform with 1 – 2
turn fault in 40th disc of turn fault in 33rd disc of
tapping winding tapping winding

Figure. 4.39(c) FFT of Neutral Figure. 4.39(f) FFT of Neutral


Current waveform with 1 – 4 Current waveform with 1 – 2
turn fault in 40th disc of turn fault in 29th disc of
tapping winding tapping winding

Figure. 4.39(d) FFT of Neutral Figure. 4.39(g) FFT of Neutral


Current waveform with 1 – 2 Current waveform with 1 – 2
turn fault in 37th disc of turn fault in 25th disc of
tapping winding tapping winding

342
Figure. 4.39(h) FFT of Neutral Figure. 4.39(k) FFT of Neutral
Current waveform with 1 – 2 Current waveform with 1 – 2
turn fault in 21st disc of turn fault in 9th disc of tapping
tapping winding winding

Figure. 4.39(i) FFT of Neutral Figure. 4.39(l) FFT of Neutral


Current waveform with 1 – 2 Current waveform with 1 – 2
turn fault in 17th disc of turn fault in 5th disc of tapping
tapping winding winding

Figure. 4.39(j) FFT of Neutral


Current waveform with 1 – 2
turn fault in 13th disc of
tapping winding

343
4.10.3 WAVELET TRANSFORM OF THE NEUTRAL
CURRENTS

The individual neutral current data for all the cases mentioned

above, were analyzed for their time – frequency characteristics using

Daubechies wavelet transform for detection of faults in time scale. Every

signal has been analyzed using wavelet transform technique as is done in

case of the theoretical analysis of the converter transformer. The wavelet

coefficients obtained form this analysis can be used for training of the

ANN and hence this technique can be adopted in the analysis and

identification of the faults of the transformer. Figure 4.40

Typical wavelet analysis waveforms for healthy winding and

winding with disc fault in HV winding are given in Figure 4.40. Similarly

the wavelet plots for the healthy winding and the winding with disc and

turn faults in tapping winding have been shown in Figure 4.41 and 4.42.

The absolute maximum value of the Wavelet coefficients for disc to

disc fault in HV winding using Daubechies Wavelet has been given in

Table.4.7. The absolute maximum value of the Wavelet coefficients for

disc to disc fault in tapping winding using Daubechies Wavelet has been

given in Table.4.8 and Table.4.9 and the absolute maximum value of the

Wavelet coefficients for 2 turn Fault in the discs of tapping winding using

Daubechies Wavelet has been given in Table.4.10. The level 8 coefficients

can be used to locate the faults in the windings.

344
Figure. 4.40(a) Wavelet transform of Neutral Current waveform with
out disc fault in HV winding

Figure. 4.40(b) Wavelet transform of Neutral Current waveform with


2 – 4 disc fault in HV winding

345
Figure. 4.40(c) Wavelet transform of Neutral Current waveform with
2 – 6 disc fault in HV winding

Figure. 4.40(d) Wavelet transform of Neutral Current waveform with


2 – 8 disc fault in HV winding

346
Figure. 4.40(e) Wavelet transform of Neutral Current waveform with
2 – 10 disc fault in HV winding

Figure. 4.40(f) Wavelet transform of Neutral Current waveform with


2 – 12 disc fault in HV winding

347
Figure. 4.40(g) Wavelet transform of Neutral Current waveform with
2 – 14 disc fault in HV winding

Figure. 4.40(h) Wavelet transform of Neutral Current waveform with


2 – 16 disc fault in HV winding

348
Figure. 4.40(i) Wavelet transform of Neutral Current waveform with
4 – 6 disc fault in HV winding

Figure. 4.40(j) Wavelet transform of Neutral Current waveform with


6 – 8 disc fault in HV winding

349
Figure. 4.40(k) Wavelet transform of Neutral Current waveform with
8 – 10 disc fault in HV winding

Figure. 4.40(l) Wavelet transform of Neutral Current waveform with


10 – 12 disc fault in HV winding

350
Figure. 4.40(m) Wavelet transform of Neutral Current waveform
with 12 – 14 disc fault in HV winding

Figure. 4.40(n) Wavelet transform of Neutral Current waveform with


14 – 16 disc fault in HV winding

351
Figure. 4.41(a) Wavelet transform of Neutral Current waveform
without disc fault in tapping winding

Figure. 4.41(b) Wavelet transform of Neutral Current waveform with


39 – 38 disc fault in tapping winding

352
Figure. 4.41(c) Wavelet transform of Neutral Current waveform with
39 – 37 disc fault in tapping winding

Figure. 4.41(d) Wavelet transform of Neutral Current waveform with


39 – 36 disc fault in tapping winding

353
Figure. 4.41(e) Wavelet transform of Neutral Current waveform with
39 – 35 disc fault in tapping winding

Figure. 4.41(f) Wavelet transform of Neutral Current waveform with


39 – 33 disc fault in tapping winding

354
Figure. 4.41(g) Wavelet transform of Neutral Current waveform with
39 – 32 disc fault in tapping winding

Figure. 4.41(h) Wavelet transform of Neutral Current waveform with


39 – 31 disc fault in tapping winding

355
Figure. 4.41(i) Wavelet transform of Neutral Current waveform with
39 – 29 disc fault in tapping winding

Figure. 4.41(j) Wavelet transform of Neutral Current waveform with


39 – 27 disc fault in tapping winding

356
Figure. 4.41(k) Wavelet transform of Neutral Current waveform with
39 – 26 disc fault in tapping winding

Figure. 4.41(l) Wavelet transform of Neutral Current waveform with


39 – 25 disc fault in tapping winding

357
Figure. 4.41(m) Wavelet transform of Neutral Current waveform
with 39 – 37 disc fault in tapping winding

Figure. 4.41(n) Wavelet transform of Neutral Current waveform with


35 – 33 disc fault in tapping winding

358
Figure. 4.41(o) Wavelet transform of Neutral Current waveform with
33 – 31 disc fault in tapping winding

Figure. 4.41(p) Wavelet transform of Neutral Current waveform with


31 – 29 disc fault in tapping winding

359
Figure. 4.41(q) Wavelet transform of Neutral Current waveform with
29 – 27 disc fault in tapping winding

Figure. 4.41(r) Wavelet transform of Neutral Current waveform with


27 – 25 disc fault in tapping winding

360
Figure. 4.41(s) Wavelet transform of Neutral Current waveform with
25 – 23 disc fault in tapping winding

Figure. 4.41(t) Neutral Current waveform with 23 – 21 disc fault in


tapping winding

361
Figure. 4.41(u) Wavelet transform of Neutral Current waveform with
21 – 19 disc fault in tapping winding

Figure. 4.41(v) Wavelet transform of Neutral Current waveform with


15 – 13 disc fault in tapping winding

362
Figure. 4.41(w) Wavelet transform of Neutral Current waveform with
9 – 7 disc fault in tapping winding

Figure. 4.41(x) Wavelet transform of Neutral Current waveform


with 7 – 5 disc fault in tapping winding

363
Figure. 4.41(y) Wavelet transform of Neutral Current waveform with
5 – 3 disc fault in tapping winding

Figure. 4.41(z) Wavelet transform of Neutral Current waveform with


38 – 33 disc fault in tapping winding

364
Figure. 4.41(aa) Wavelet transform of Neutral Current waveform
with 32 – 27 disc fault in tapping winding

Figure. 4.41(ab) Wavelet transform of Neutral Current waveform


with 27 – 22 disc fault in tapping winding

365
Figure. 4.41(ac) Wavelet transform of Neutral Current waveform
with 21 – 16 disc fault in tapping winding

Figure. 4.41(ad) Wavelet transform of Neutral Current waveform


with 13 – 8 disc fault in tapping winding

366
Figure. 4.41(ae) Wavelet transform of Neutral Current waveform
with 8 – 3 disc fault in tapping winding

Figure. 4.42(a) Wavelet transform of Neutral Current waveform with


32 – 2 disc fault in tapping winding

367
Figure. 4.42(b) Wavelet transform of Neutral Current waveform with
1 – 3 turn fault in 40th disc of tapping winding

Figure. 4.42(c) Wavelet transform of Neutral Current waveform with


1 – 4 turn fault in 40th disc of tapping winding

368
Figure. 4.42(d) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 37th disc of tapping winding

Figure. 4.42(e) Wavelet transform of Neutral Current waveform with


1 – 2 turn fault in 33rd disc of tapping winding

369
Figure. 4.42(f) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 29th disc of tapping winding

Figure. 4.42(g) Wavelet transform of Neutral Current waveform with


1 – 2 turn fault in 25th disc of tapping winding

370
Figure. 4.42(h) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 21st disc of tapping winding

Figure. 4.42(i) Wavelet transform of Neutral Current waveform with


1 – 2 turn fault in 17th disc of tapping winding

371
Figure. 4.42(j) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 13th disc of tapping winding

Figure. 4.42(k) Wavelet transform of Neutral Current waveform with


1 – 2 turn fault in 9th disc of tapping winding

372
Figure. 4.42(l) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 5th disc of tapping winding

A total of 14 sets of data have been generated to train and test the

artificial neural network using back propagation algorithm. The training

data has been generated by normalizing the absolute 8th level wavelet

coefficients. The following are the observations made during the

classification and location of faults in the transformer winding. 10 sets of

data are used for training the ANN and 4 sets of data have been used for

testing. The testing results are given in table 4.11. From the table it is

observed that more amounts of data for training the ANN is required to

improve the accuracy in locating the faults in the transformer windings.

373
Table.4.7 : Absolute maximum value of the Wavelet coefficients for
Disc to Disc Fault in HV winding using Daubechies Wavelet

Descripti Location of Absolute maximum value of the Wavelet coefficients


Sl.
on of Fault in
No. d1 d2 d3 d4 d5 d6 d7 d8 a8
Fault Winding
Without
1. - 12.610 13.935 4.327 8.752 3.932 0.763 0.608 0.343 0.842
fault
2. 2 Discs 2-4 Discs 13.169 13.370 5.092 9.297 2.138 1.429 0.552 0.325 1.017
3. 4 Discs 2-6 Discs 12.518 14.084 3.512 8.334 4.775 1.560 0.707 0.386 0.940
4. 6 Discs 2-8 Discs 12.502 14.671 3.653 8.581 4.509 0.955 0.660 0.474 1.188
5. 8 Discs 2-10 Discs 12.338 14.050 4.523 9.052 2.280 1.110 0.589 0.212 1.372
6. 10 Discs 2-12 Discs 12.683 13.688 4.331 8.801 3.991 0.835 0.515 0.302 1.022
7. 12 Discs 2-14 Discs 12.941 13.021 4.172 7.733 4.533 1.739 0.687 0.268 1.537
8. 14 Discs 2-16 Discs 13.240 12.816 3.850 7.747 4.608 1.334 0.682 0.289 1.631
9. 2 Discs 4-6 Discs 12.409 14.511 2.960 7.452 4.350 1.768 0.577 0.343 1.043
10. 2 Discs 6-8 Discs 12.498 14.116 3.582 8.536 4.583 1.168 0.558 0.434 1.177
11. 2 Discs 8-10 Discs 12.630 13.831 4.215 8.707 1.919 1.060 0.365 0.104 1.211
12. 2 Discs 10-12 Discs 12.508 14.103 3.374 8.376 4.677 1.406 0.628 0.309 1.165
13. 2 Discs 12-14 Discs 12.975 14.186 4.304 8.702 3.827 1.013 0.557 0.413 1.345
14. 2 Discs 14-16 Discs 13.143 13.694 4.486 8.782 1.530 0.843 0.482 0.294 1.460

Table.4.8 : Absolute maximum value of the Wavelet coefficients for


Disc to Disc Fault in tapping winding using Daubechies Wavelet

Descrip Location of Absolute maximum value of the Wavelet coefficients


Sl.
tion of Fault in
No. d1 d2 d3 d4 d5 d6 d7 d8 a8
Fault Winding
Without
1. -- 1.1759 1.3675 3.5728 9.5690 7.4753 1.2757 0.8727 0.4180 3.0670
fault
2. 2 Disc 39-38 Disc 1.1477 1.4166 3.3122 9.5338 7.2363 0.8399 0.6865 0.3845 2.4396
3. 3 Disc 39-37 Disc 0.9070 1.2819 3.6695 9.2097 6.3304 0.8504 0.5563 0.3096 2.8746
4. 4 Disc 39-36 Disc 0.9482 1.3136 3.6770 8.9336 6.3745 0.8481 0.4313 0.3172 2.6192
5. 5 Disc 39-35 Disc 0.9420 1.3301 3.4457 9.7129 6.9865 1.0450 0.6740 0.3616 2.4400
6. 7 Disc 39-33 Disc 1.1541 1.3159 3.6247 9.5258 6.9793 1.0204 0.8082 0.3021 2.8403
7. 8 Disc 39-32 Disc 1.1683 1.2676 3.7723 9.5797 7.0157 0.9743 0.8960 0.2518 2.3905
8. 9 Disc 39-31 Disc 1.3148 1.3603 3.4079 9.6011 6.9489 0.7668 0.8012 0.2836 2.3834
9. 11 Disc 39-29 Disc 1.7509 1.2763 4.1910 8.0783 4.9634 1.7711 0.6912 0.5257 2.1089
10. 13 Disc 39-27 Disc 1.8583 1.3427 3.9013 8.7042 5.8622 1.2704 0.5214 0.3969 2.4487
11. 14 Disc 39-26 Disc 1.7618 1.2602 4.1182 8.0708 4.7495 1.5443 0.6800 0.4311 2.1178
12. 15 Disc 39-25 Disc 1.7899 1.3135 3.7721 8.4325 5.1805 1.3868 0.9107 0.2496 2.7943

374
Table.4.9 Absolute maximum value of the Wavelet coefficients for
Disc to Disc Fault in tapping winding using Daubechies Wavelet

Descri Absolute maximum value of the Wavelet coefficients


Location of
Sl. ption
Fault in
No. of d1 d2 d3 d4 d5 d6 d7 d8 a8
Winding
Fault
1. Without fault 1.0356 1.0069 3.0364 9.6602 4.7369 2.1822 0.9720 0.5610 3.0191
2. 2 Disc 39 to 37 discs 12.6102 13.9351 4.3268 8.7524 3.9324 0.7633 0.6082 0.3432 0.8419
3. 2 Disc 37 to 35 discs 13.1688 13.3700 5.0917 9.2971 2.1379 1.4291 0.5525 0.3250 1.0167
4. 2 Disc 35 to 33 discs 12.5177 14.0845 3.5119 8.3342 4.7750 1.5601 0.7067 0.3862 0.9399
5. 2 Disc 33 to 31 discs 12.5023 14.6706 3.6526 8.5805 4.5088 0.9555 0.6601 0.4736 1.1875
6. 2 Disc 31 to 29 discs 12.3383 14.0496 4.5225 9.0518 2.2797 1.1105 0.5886 0.2119 1.3724
7. 2 Disc 29 to 27 discs 12.6831 13.6878 4.3314 8.8012 3.9912 0.8355 0.5147 0.3024 1.0220
8. 2 Disc 27 to 25 discs 12.9410 13.0208 4.1720 7.7334 4.5329 1.7390 0.6871 0.2677 1.5374
9. 2 Disc 25 to 23 discs 13.2399 12.8159 3.8496 7.7467 4.6080 1.3342 0.6820 0.2886 1.6312
10. 2 Disc 23 to 21 discs 12.4092 14.5115 2.9599 7.4517 4.3502 1.7683 0.5774 0.3430 1.0433
11. 2 Disc 21 to 19 discs 12.4976 14.1164 3.5824 8.5359 4.5833 1.1684 0.5577 0.4338 1.1773
12. 2 Disc 15 to 13 discs 12.6296 13.8308 4.2155 8.7069 1.9186 1.0604 0.3653 0.1037 1.2109
13. 2 Disc 9 to 7 discs 12.5083 14.1028 3.3736 8.3763 4.6774 1.4055 0.6276 0.3094 1.1651
14. 2 Disc 7 to 5 discs 12.9753 14.1865 4.3043 8.7018 3.8274 1.0126 0.5571 0.4135 1.3454
15. 2 Disc 5 to 3 discs 13.1430 13.6937 4.4862 8.7818 1.5302 0.8430 0.4824 0.2944 1.4603
16. 2 Disc 38 to 33 discs 1.1759 1.3675 3.5728 9.5690 7.4753 1.2757 0.8727 0.4180 3.0670
17. 2 Disc 32 to 27 discs 1.1477 1.4166 3.3122 9.5338 7.2363 0.8399 0.6865 0.3845 2.4396
18. 2 Disc 27 to 22 discs 0.9070 1.2819 3.6695 9.2097 6.3304 0.8504 0.5563 0.3096 2.8746
19. 2 Disc 21 to 16 discs 0.9482 1.3136 3.6770 8.9336 6.3745 0.8481 0.4313 0.3172 2.6192
20. 2 Disc 13 to 8 discs 0.9420 1.3301 3.4457 9.7129 6.9865 1.0450 0.6740 0.3616 2.4400
21. 2 Disc 8 to 3 discs 1.1541 1.3159 3.6247 9.5258 6.9793 1.0204 0.8082 0.3021 2.8403

375
Table.4.10: Absolute maximum value of the Wavelet coefficients for
2 turn Fault in the discs of tapping winding using Daubechies
Wavelet

Descr Locatio Absolute maximum value of the Wavelet coefficients


Sl. iption n of
No. of Fault in d1 d2 d3 d4 d5 d6 d7 d8 a8
Fault Winding
1. 2 Turn 40th disc 1.1683 1.2676 3.7723 9.5797 7.0157 0.9743 0.8960 0.2518 2.3905

2. 3 Turn 40th disc 1.3148 1.3603 3.4079 9.6011 6.9489 0.7668 0.8012 0.2836 2.3834

3. 4 Turn 40th disc 1.7509 1.2763 4.1910 8.0783 4.9634 1.7711 0.6912 0.5257 2.1089

4. 2 Turn 37th disc 1.8583 1.3427 3.9013 8.7042 5.8622 1.2704 0.5214 0.3969 2.4487

5. 2 Turn 33rd disc 1.7618 1.2602 4.1182 8.0708 4.7495 1.5443 0.6800 0.4311 2.1178

6. 2 Turn 29th disc 1.7899 1.3135 3.7721 8.4325 5.1805 1.3868 0.9107 0.2496 2.7943

7. 2 Turn 25th disc 1.0356 1.0069 3.0364 9.6602 4.7369 2.1822 0.9720 0.5610 3.0191

Table.4.11 Test results of ANN for the classification of faults

Local Average
Fault Fault Location
value
Normal Operation YES

Disc to 39 to 37 No
Disc
29 to 27 YES
faults
in
15 to 13 YES
tapping
winding 9 to 7 No

2 to 4 No
Disc to
Disc 6 to 8 YES
faults
in HV 10 to 12 YES
winding
14 to 16 YES

376
4.11 CONCLUSIONS
In this chapter the analytical modeling of the HVDC converter

transformer has been discussed. A typical 315MVA transformer has been

considered for the analysis. The neutral currents were captured across

the 16th node to ground connection. Various testing methods of the

converter transformer were discussed.

From the analysis of the neutral current using FFT analysis

various dominant frequencies are identified. The wavelet transform of the

neutral current for these corner frequencies has been calculated. The

reconstructed signal using these wavelet transformed signals is almost

identical to the original neutral current signal. This technique can be

adopted for the elimination of noise.

The faults associated with the HVDC converter transformer have

been analyzed and are classified using ANN and wavelet transform

technique. The neutral currents have been analyzed using the FFT, ANN

and Wavelet Transform techniques. A technique that can be adopted for

the location of minor faults in the windings of the transformer windings

is proposed.

The comparative studies in this dissertation have demonstrated

that significant improvements over the traditional methods can be

achieved. The flexibility of the proposed approaches enables them to use

in variety of feasible applications in power system analysis. It can be

377
concluded from the results of the analysis of the converter transformer

that the combination of the techniques (Wavelet & ANN) can be adopted

for better fault diagnosis classification and location.

The digital recording of neutral currents in the HV and taping

windings of a 61MVA, 11kV/220kV transformer has been carried out

by applying a Low voltage impulse at one of the terminal for various

test conditions of the winding. The changes in the neutral current

characteristics depend primarily on the extent of failure. However the

core has been removed. The neutral currents are recorded using

digital oscilloscope for healthy winding and also by shorting several

pairs of discs and turns in succession. The recorded neutral currents

are analyzed by using FFT and wavelet transform and different plots

obtained for each case have been presented. The absolute 8th level

wavelet coefficients have been normalized and are used to train and

test the ANN. The test results of the ANN have been presented. From

the experimental analysis it is observed that to obtain more accuracy

more amounts of data required for the training of ANN.

378

You might also like