Professional Documents
Culture Documents
check whether its insulation can withstand the impulse over voltages
operation of the transformer, but also reduces the overall cost of it. The
Power frequency test by itself is not sufficient for the purpose. This may
be due to fast rate of rise of the impulse voltage and wave shape which
voltage.
251
ground and shunted by the parallel stray capacitance between the
the winding.
Detection of major faults has never been an issue since the waveforms,
which are being compared, show major difference for such fault. Hence,
the focus is on being able to detect accurately the smallest or minor type
of design and construction. They are oil insulated and OFAF cooled. They
are fitted with OLIC, bushings other usual accessories. They are most
252
Transformers are subjected to very unusual times of stresses due to
(rectification) or DC to AC (inversion)
minimized.
The short circuit levels are precisely controlled by means of the closely
phase of AC network.
253
By suitable combination of star-star, star-delta transformer
connections, the required phase shift and voltages are given at the
leads on the valve side. Thus the 12 pulse converter is possible with
High speed, reliable on load taps changer with 24 or more steps and
regulation of +17.5 and -12.5 % (or more). The tap changers operate
Specially built low loss, loss noise core. The magnetic circuit is
convertor operation.
High reliability.
254
4.1.3 MODELING OF A TRANSFORMER AND
REPRESENTATION OF EQUIVALENT ELECTRIC
NETWORK.
400 206
MVA 3 3 KV is divided into 60 sections. Figure 4.1 shows the
not required that the winding should be divided into such a large
number of sections can give accurate results. It also reduces the total
commutation time. For the purpose of the neutral current calculation the
impulse tests. The HVAC winding is divided into 8 sections and HVDC
inductance (M) with all other sections of the same winding as well as
with the other windings. The series and shunt capacitances are
calculated using standard formula [155] for parallel plate and cylindrical
network is derived.
255
Figure. 4.1 Sectional Distribution of HVDC converter Transformer.
A: Tapping winding, B: HV winding, C: HVDC Transformer winding
(star)
256
The transient voltage at any point in the winding for an impulse
windings.
winding for wide range of variations of the input impulse voltage wave
series/shunt capacitances.
and ground
258
4.1.4 SELF INDUCTANCE OF THE WINDING
P1 = P x f
M N1 N 2 f aA H (4.2)
259
'A' and 'a' are radii in cm.
(A - a) 2 d 2
K
1 2
where (A a) 2 d 2
(4.3)
Let
260
Ct = Capacitance between adjacent turns
If the voltage „v‟ is applied across the double disc, the energy stored
1
CS V 2
2
V
Voltage across each turn= Vt
2m
V V
Voltage across each disc m
2m 2
2 2
1 V 1 V
.Ct .2.(m - 1) .Ca 2
2 2 2 2 1 (4.4)
CS V 2
2
Or
Ct Ca
Cs
2 2 (4.5)
Further, it is generally true that Ca/2 is much smaller than the first
factor.
261
Figure 4.6 configuration of interleaved winding
a
Cs1 (Ca Ct' ) [ a coth a ]
1 a2 (4.6)
Where
Ct‟ = Ct /m
= Ca / Ct‟
262
4.1.7 GROUND / INTER WINDING CAPACITANCE
standard formula for parallel plate capacitor. The area of the plate is
263
4.1.8 INDUCTIVE CURRENT CALCULATIONS
through the inductive branch (n, n+1) is assumed to pass through the
branches due to mutual coupling between them. Since all node voltages
at any instant are known, the matrix equation defining the current and
di
[ L] [V ]
dt or
di 1
dt [ L] [V ]
(4.8)
inductances;
branch.
From the equation (4.8) the di/dt in the nth inductance is given by
din
Pn
dt or
264
in ( t1 ) t1
in t1 P0 t in (t0 )
or
in t 2 P1t in (t1 )
also
in tn Pn 1t in (t n 1 )
i.e (4.9)
265
4.1.9 CAPACITIVE CURRENT CALCULATIONS
Since Cg(n+) is very low, almost total current passing through the
1
Csn
Vn ( n 1) ic ( n ,n 1)
dvn ( n1)
Csn ic ( n,n1)
Or dt (4.10)
Vn ,n 1 (t1 ) Vn ,n 1 (t0 )
ic (t ) Csn
t (4.11)
following equation:
i (t ) in (t ) ic (t )
(4.12)
400 206
The parameters of a 315 MVA, 3 3KV three winding
transformer (Transformer ground capacitance, Inter turn capacitance,
and Inductance were calculated using the above method and are given in
annexure-IV.
266
able to with stand the voltage as per the relevant standard. In case of a
major problems are encountered when full winding failure does not occur
and a small fault in the form of turn to turn takes place during the
impulse test. Since the fault is major it does not reflect in considerable
system voltage is known as the BIL. The impulse voltage testing is the
most efficient quality control tool, which reveals the largest part of
flaws.
based on the comparison of the applied voltage and the neutral current
test, it is assumed that the winding impedance does not vary at the
voltages below the expected highest voltage range. The output signals
267
viz., neutral terminal current is expected to have the same shape
4.1
4.2
269
considered as acceptable, since the transformer does not have to be free
from the partial discharges at relatively higher impulse voltage test level.
view of the above, the neutral current has been calculated by simulating
lightning (including both direct and indirect stores). Full wave and
voltages [137].
270
4.3.2.1 GENERAL OBSERVATION
needs to be automatic for high volume testing and in any case all faults
and bubbles.
transformer windings. Thus, full wave and chopped wave impulse test
flowing through a resistive shunt between the neutral and ground point
271
is used for detecting the fault. The neutral current oscillogram consists of
reflections offered by the ground and of the windings for the fast rising
impulse currents. When fault occurs i.e. arcing between the turns or
from turn to ground take place, high frequency pulses similar to that of
between the low voltage windings and the ground is used for identifying
272
and reduced impulse test voltages. Differences between the transfer
voltage power transformers have so far been using the transfer function
and reduced test levels. This in turn will cause a difference between the
current and test voltage waveform changes considerably from one shot to
273
Figure. 4.8(a) Calculation process for the transfer function method
from the form of the observed deviation, but in practice this often results
of criterion.
the test voltage and neutral current records obtained respectively at full
274
and reduced test levels. Deconvolution yields the transfer function,
obtained at the BIL and reduced test voltages. Even minor shift in the
275
the pole height decreases, even though its frequency remains practically
unchanged.
and at the reduced test level fall into two categories i.e. a local
276
excitation and short circuit tests in positive as well as zero sequence
these matrices every turn to earth and turn to turn faults were modeled
these models are very accurate, there are still number of problems in
requirements.
of the finite element method and circuit simulation. The procedure was
model was exported and used in a circuit analysis package to study the
277
4.5 FREQUENCY RESPONSE ANALYSIS (FRA)
The method of system characterization by means of its frequency
T.N Vaessen et al. [151] proposed FRA method, which is easy to use in
the voltage independent defects like winding shorts are reflected in this
278
al. [152] presented a review of transformer model simulation for the
frequency range.
limitations:
279
It is necessary to avoid short circuiting of the other windings or
a transformer.
280
induced A.C. voltage. This D.C. potential (due to connection to high
design.
be analyzed using the neutral current obtained during the impulse test
model is used for the analysis. The neutral currents are to be analyzed
using the FFT, ANN and Wavelet Transform techniques. The neutral
winding to winding fault, winding to ground fault, turn to turn fault and
the signal is used to classify the faults in the converter transformer. The
techniques based on the wavelet transforms are proposed for the location
281
The standard impulse voltage waveform can be represented with
following equation:
Where α and β are constants and depends upon the rate of rise
and decay of the pulse. For a given value of α=0.7936 x 106 and
β=0.02335 x 106 impulse voltage generated has a rise time of 1.2µs and
tail time of 50µs. When a signal in the time domain is converted into the
healthy winding and the winding with simulated faults along the
domain.
282
Figure 4.9(a) Standard Impulse Voltage Applied in time domain
Rated voltage
283
HV side : 400 / 3 KV
Construction : Y/Y/∆
condition i.e. healthy and faulty conditions. FFT analysis is carried out
for the neutral currents obtained from transformer model for different
The current in the neutral has been measured at node no.25. Various
284
faults are simulated at different locations along the windings as follows.
current under no fault condition is 1.4e-3 amperes. The waveform for the
Figure 4.10(a).
wave form are given in table 4.1. It is also observed that the neutral
285
Figure. 4.10(b) FFT analysis of the neutral current signal during the
normal operating condition
frequency.
The wavelet transform can map any finite energy waveform from
the time of occurrence and the variation of transient current with time at
286
(4.14)
b = translation parameter
f = frequency
The Gabor mother wavelet has been used and is given by the
equation
(4.15)
identified.
(k). This factor converts the wavelet transform of the neutral current
287
Table 4.1 Value of k w.r.t 2 for a frequency of 50 kHz.
2 F (kHz) K f2/k
8 50 707.24 1.0004
16 50 500.25 0.5005
64 50 250.13 0.1251
scale parameter matches with the input or original waveform. Table 4.1
frequency equal to 50 kHz. Table 4.10 shows the value of f2/k for various
288
Table 4.2 Variation of k w.r.t. Frequency
F (kHz) K f2/k
107 37.383 0.0131
205 51.840 0.0113
293 57.670 0.0113
332 88.810 0.0113
381 65.617 0.0113
accuracy of the wavelet. All the wavelet signals have been added after
289
frequencies contained in the neutral currents. A typical FFT plot for
Table 4.3 List of dominant frequencies and corresponding K values w.r.t. 2 values
2
S.No Frequency K
1 48845 Hz 16 156.31
2 68342 Hz 256 46.23
3 106870 Hz 64 115.62
4 146088 Hz 512 47.80
5 204937 Hz 256 80.05
6 243853 Hz 512 61.763
7 293252 Hz 512 67.73
8 331741 Hz 512 72.04
9 380947 Hz 1024 54.62
10 410401 Hz 1024 56.69
11 430367 Hz 5120 26.32
12 458892 Hz 1024 59.94
13 488453 Hz 1024 61.84
14 527270 Hz 2048 45.87
15 547202 Hz 1024 65.46
16 566675 Hz 4096 34.11
17 585425 Hz 5120 30.70
The dominant frequencies are identified from the FFT analysis plot
for carrying out the wavelet analysis. The 2 is chosen in such a way that
290
the wavelet output is representing that particular frequency component.
Figure 4.11(a), 4.11(b) and 4.11(c) represents the FFT analysis applied to
Figure. 4.11(a) Magnitude Vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 1-7 listed in Table 4.3.
291
Figure. 4.11(b) Magnitude vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 8-14 listed in Table 4.3.
Figure. 4.11(c) Magnitude vs. Frequency plot for the FFT analysis of
the wavelet transformed signals 15-17 listed in Table 4.3.
292
Figure. 4.12(a) wavelet transform of the input signal for a corner
frequency of 9770 Hz, 2=0.25
293
Figure. 4.12(d) wavelet transform of the input signal for a corner
frequency of 106.870 kHz, 2=64
294
Figure. 4.12(g) wavelet transform of the input signal for a corner
frequency of 243.853 kHz, 2=512
295
Figure. 4.12(j) wavelet transform of the input signal for a corner
frequency of 380.95 kHz, 2=1020
296
Figure. 4.12(m) wavelet transform of the input signal for a corner
frequency of 458.89kHz, 2=1020
297
Figure. 4.12(p) wavelet transform of the input signal for a corner
frequency of 547.20Hz, 2=1020
298
Figure. 4.13 Reconstructed and Original Neutral current signals.
50μs is applied to one of the limb of the star winding of the HVDC
taking the absolute value of the signal. The neutral current signal is
sampled at 0.1 μs of time and 1024 samples taken for 102.4 micro
seconds of time. The neutral current signal for various fault conditions is
are divided into 16 sets. The normalized data is given as input to train
299
Figure 4.14(a): Recorded Neutral Current during normal operating
condition
300
Figure 4.14(d): Recorded Neutral Current during winding to winding
fault
301
Figure. 4.16: Normalized local maximum values as input patterns for
training neural network.
values and maximum for every 6.4μs of time. Out of the recorded neutral
current data of 102.4μs, the normalized local average data and the local
networks are trained till the error is reduced. The training data for all the
4.16. The error plot of neural network after training with the local
average values is given in Figure 4.17. The error plot of neural network
after training with the local maximum values is given in Figure 4.18.
From Figure 4.17 it can be stated that the neural network has
case when average data is taken as the input sets and from Figure 4.18
it has taken less than 130 iterations to reduce the error to 3.76898x10-16
when the local maximum values have been taken as the training and
302
testing patterns. A total number of 34 sets of data is prepared and out of
this 20 sets of data is used for training and 14 sets of data is used for
testing the Artificial Neural Network. Table 4.4 is shows various test
results with both average test patterns and Maximum test patterns.
From the test results as listed in Table 4.4 and Figure. 4.19 it can be
stated that the local maximum value based training patterns are
Figure 4.17: Mean square Error plot after training using local
average patterns as training sets.
Figure 4.18: Error plot after training using local maximum patterns
as training sets.
303
Table. 4.4 Test result for the network for both average and maximum data sets.
Diagnosis by
Fault Fault Location Local Average Local Maximum
value value
Normal Operation YES YES
12th Disk YES YES
14th Disk YES YES
15th Disk YES YES
Turn to 17th Disk YES YES
Turn
Faults 20th Disk YES YES
21st Disk YES YES
22nd Disk YES YES
24th Disk YES YES
17th to 4th YES YES
17th to 5th YES YES
18th to 4th YES YES
18th to 5th YES YES
19th to 4th YES YES
19th to 5th YES YES
Winding 20th to 4th YES YES
to
Winding 20th to 5th YES YES
20th to 6th YES YES
21st to 5th YES YES
21st to 6th YES YES
21st to 7th NO NO
22nd to 6th YES YES
22nd to 7th NO YES
17th Ground NO YES
18th Ground NO YES
Turn to 19th Ground YES YES
Ground 20th Ground YES NO
21st Ground YES YES
22nd Ground YES YES
304
Figure 4.19: Summary of the test results for the classification of
faults in convertor transformer.
The fault data generated for training the ANN is used for the
conditions are recorded and are used to generate the training data for
ANN. A set of model plots of the wavelet coefficients for various operating
4.20(a) to 4.20(d).
305
Figure. 4.20(a) Wavelet transform of the neutral current of the HVDC
converter transformer during No fault (Normal Operation)
306
Figure. 4.20(c) Wavelet transform of the neutral current of the HVDC
converter transformer during Winding to winding fault
307
The normalized absolute level 8 wavelet coefficients are used for
three layer neural network with 10 neurons in the input layer 4 neurons
sets of data is used for training and 14 sets of data is used for testing the
Artificial Neural Network. Figure 4.21 shows the mean square error
during the training of ANN for the classification of faults in the converter
transformer. The ANN has taken 347 epochs for the training to attain an
Figure. 4.21 Mean square error curve during the training of ANN for
the classification of faults in converter transformer
308
Table. 4.5 Test result of the neural network for the classification of
faults.
309
4.10 EXPERIMENTAL INVESTIGATION OF NEUTRAL
CURRENT
In an effort to characterize the behavior of the converter
the purpose of experiment, the leads from disc of high voltage winding
winding were brought out. The paper insulation of discs and turns at
creating the faults between different discs and between adjacent turns.
winding and tapping winding are physically shortened one after another
voltage impulse from a P-35 bench type impulse generator and voltage
signals are measured for healthy as well as winding with disc-to-disc and
transforms (WT) and plots are obtained for each case. Fast Fourier
310
the range of frequencies contained in the signal. From the results it has
recorded for healthy winding and for the disc-to-disc faults created at
various places along the winding. Subsequently, the recurrent surge was
also applied to one end of the tapping winding and currents were
recorded at other end of the winding. These currents were recorded for
healthy winding and winding with fault created in the disc and turn at
were repeated using suitable Metal Oxide Varistor (MOV) for shorting the
discs and turns at several places in the HV and tapping windings. The
neutral currents were also recorded for healthy winding and winding
311
with faults. The details of the transformer used and the method adopted
The Transformer and test setup used for study has the power
center entry type having a total of 112 discs. Each disc is of inter leaved
type having 22 turns per disc as shown in Figure 4.23. The tapping
generation. Due to symmetry, only one half of each winding is used for
312
Figure.4.22: Photographs of 61MVA, 11.5/230kV Generator
Transformer
313
Figure.4.25. Electrical Figure.4.26. Electrical
Connection without tapping Connection with HV and tapping
winding for 11.5kV/230kV GT. winding of GT.
U(t)
314
4.10.1.2 APPLICATION OF RECURRENT SURGE GENERATOR
(RSG)
Figure 4.28 shows a view of the experimental set up used for this
study. An impulse voltage of magnitude 100 Volts from RSG (Type 481)
was applied at the center entry lead of HV winding and the neutral
recorded for healthy winding as well as for winding with shorted discs.
disc of tap winding and the neutral currents were recorded at 1st disc of
the winding across the 20Ω shunt. In order to carry out the experiment,
the paper insulation from the outer end of a number of discs/turns along
access to the bare copper conductor of the discs and turns. The bare
315
Figure 4.29: Neutral Currents recorded on oscilloscope across 20
ohms shunt
316
B. TAPPING WINDING (Disc faults)
317
C. TAPPING WINDING (Turn faults)
Bench type Impulse generator (HAEFLY make, Model P-35) was applied
at the center entry of high voltage lead. The neutral currents were
1Ω shunt.
discs for high voltage and tapping windings. A 5 kV impulse voltage was
318
applied for turn-fault in the tapping winding. The bare portion of the
(ELPRO make, 440/20J) and neutral current have been recorded for
each fault.
formula, I = kVα, where 'α' denotes the "non linearity" exponent and in
At low applied voltages, the metal oxide type varistor looks like an
319
dissipation is typically a fraction of a milliwatt, as compared to the
operating voltage ratings for MOV-based series varistors range from 140
440l2OJ disc type MOV has been selected for experiment. Figure 4.30(a).
a fairly significant factor for the varistor's dynamic characteristic. The V-I
4.30(b) and Table 4.6. The V-I characteristic curve has been generated
when the MOV has been connected across the discs and turns at various
locations along the length of the high voltage and tapping windings. The
MOV. The main aim of using this device is to record the neutral currents
when actual shorting of disc or turn is taking place in the winding during
high voltage impulse test. The experimental setup for neutral current
320
Table 4.6: Voltage - Current characteristic of MOV (440/20J)
0.50 - -
321
Figure. 4.30(b) Voltage - Current characteristic of MOV
322
]
Figure.4.32: Photograph showing use of MOV during Neutral Current
measurement on HV winding using high impulse voltage
The neutral currents were recorded for healthy winding as well for
the winding with created faults along the length of HV and tapping
windings. The faults are created in the discs of HV winding and disc and
The neutral currents are also recorded for all the above cases by
Metal Oxide Varistor (MOV) was employed across the discs of HV winding
shown in Figure 4.33. Few typical neutral current waveforms using RSG
are shown in Figure 4.34 for HV winding and Figure 4.35 for tapping
winding.
323
Figure. 4.33 Applied impulse Figure. 4.34(c) Neutral Current
voltage waveform waveform with 2 – 6 disc fault
in HV winding
324
Figure. 4.34(f) Neutral Current Figure. 4.34(i) Neutral Current
waveform with 2 – 12 disc fault waveform with 4 – 6 disc fault
in HV winding in HV winding
325
Figure. 4.34(l) Neutral Current Figure. 4.35(a) Neutral Current
waveform with 10 – 12 disc waveform without disc fault in
fault in HV winding tapping winding
326
Figure. 4.35(d) Neutral Current Figure. 4.35(g) Neutral Current
waveform with 39 – 36 disc waveform with 39 – 32 disc
fault in tapping winding fault in tapping winding
327
Figure. 4.35(m) Neutral Current
Figure. 4.35(j) Neutral Current waveform with 39 – 37 disc
waveform with 39 – 27 disc fault in tapping winding
fault in tapping winding
328
Figure. 4.35(p) Neutral Current Figure. 4.35s) .Neutral Current
waveform with 33 – 31 disc waveform with 27 – 25 disc
fault in tapping winding fault in tapping winding
329
Figure. 4.35(v) Neutral Current Figure.4.35(y) Neutral Current
waveform with 21 – 19 disc waveform with 7 – 5 disc fault
fault in tapping winding in tapping winding
330
Figure. 4.35(ab) Neutral Figure. 4.35(ae) Neutral
Current waveform with 32 – 27 Current waveform with 13 – 8
disc fault in tapping winding disc fault in tapping winding
331
Figure. 4.36(a) Neutral Current Figure. 4.36(d) Neutral Current
waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 40th disc of tapping winding in 37th disc of tapping winding
332
Figure. 4.36(g) Neutral Current Figure. 4.36(j) Neutral Current
waveform with 1 – 2 turn fault waveform with 1 – 2 turn fault
in 25th disc of tapping winding in 13th disc of tapping winding
333
4.10.2 FFT ANALYSIS OF THE NEUTRAL CURRENTS:
The Fast Fourier analysis has been carried out for all the above
healthy winding and winding with disc fault in HV winding are given in
Figure 4.37. Similarly the FFT waveforms for healthy winding and
winding with disc and turn faults in tapping winding are shown in Figure
334
Figure. 4.37(e) FFT of Neutral Figure. 4.37(h) FFT of Neutral
Current waveform with 2 – 10 Current waveform with 2 – 16
disc fault in HV winding disc fault in HV winding
335
Figure. 4.37(k) FFT of Neutral Figure. 4.37(n) FFT of Neutral
Current waveform with 8 – 10 Current waveform with 14 – 16
disc fault in HV winding disc fault in HV winding
336
Figure. 4.38(c) FFT of Neutral Figure. 4.38(f) FFT of Neutral
Current waveform with 39 – 37 Current waveform with 39 – 33
disc fault in tapping winding disc fault in tapping winding
337
Figure. 4.38(i) FFT of Neutral Figure. 4.38(l) FFT of Neutral
Current waveform with 39 – 29 Current waveform with 39 – 25
disc fault in tapping winding disc fault in tapping winding
338
Figure. 4.38(o) FFT of Neutral Figure. 4.38(r) FFT of Neutral
Current waveform with 33 – 31 Current waveform with 27 – 25
disc fault in tapping winding disc fault in tapping winding
339
Figure. 4.38(u) FFT of Neutral Figure. 4.38(x) FFT of Neutral
Current waveform with 21 – 19 Current waveform with 7 – 5
disc fault in tapping winding disc fault in tapping winding
340
Figure. 4.38(aa) FFT of Neutral Figure. 4.38(ad) FFT of Neutral
Current waveform with 32 – 27 Current waveform with 13 – 8
disc fault in tapping winding disc fault in tapping winding
341
Figure. 4.39(b) FFT of Neutral Figure. 4.39(e) FFT of Neutral
Current waveform with 1 – 3 Current waveform with 1 – 2
turn fault in 40th disc of turn fault in 33rd disc of
tapping winding tapping winding
342
Figure. 4.39(h) FFT of Neutral Figure. 4.39(k) FFT of Neutral
Current waveform with 1 – 2 Current waveform with 1 – 2
turn fault in 21st disc of turn fault in 9th disc of tapping
tapping winding winding
343
4.10.3 WAVELET TRANSFORM OF THE NEUTRAL
CURRENTS
The individual neutral current data for all the cases mentioned
coefficients obtained form this analysis can be used for training of the
ANN and hence this technique can be adopted in the analysis and
winding with disc fault in HV winding are given in Figure 4.40. Similarly
the wavelet plots for the healthy winding and the winding with disc and
turn faults in tapping winding have been shown in Figure 4.41 and 4.42.
disc to disc fault in tapping winding using Daubechies Wavelet has been
given in Table.4.8 and Table.4.9 and the absolute maximum value of the
Wavelet coefficients for 2 turn Fault in the discs of tapping winding using
344
Figure. 4.40(a) Wavelet transform of Neutral Current waveform with
out disc fault in HV winding
345
Figure. 4.40(c) Wavelet transform of Neutral Current waveform with
2 – 6 disc fault in HV winding
346
Figure. 4.40(e) Wavelet transform of Neutral Current waveform with
2 – 10 disc fault in HV winding
347
Figure. 4.40(g) Wavelet transform of Neutral Current waveform with
2 – 14 disc fault in HV winding
348
Figure. 4.40(i) Wavelet transform of Neutral Current waveform with
4 – 6 disc fault in HV winding
349
Figure. 4.40(k) Wavelet transform of Neutral Current waveform with
8 – 10 disc fault in HV winding
350
Figure. 4.40(m) Wavelet transform of Neutral Current waveform
with 12 – 14 disc fault in HV winding
351
Figure. 4.41(a) Wavelet transform of Neutral Current waveform
without disc fault in tapping winding
352
Figure. 4.41(c) Wavelet transform of Neutral Current waveform with
39 – 37 disc fault in tapping winding
353
Figure. 4.41(e) Wavelet transform of Neutral Current waveform with
39 – 35 disc fault in tapping winding
354
Figure. 4.41(g) Wavelet transform of Neutral Current waveform with
39 – 32 disc fault in tapping winding
355
Figure. 4.41(i) Wavelet transform of Neutral Current waveform with
39 – 29 disc fault in tapping winding
356
Figure. 4.41(k) Wavelet transform of Neutral Current waveform with
39 – 26 disc fault in tapping winding
357
Figure. 4.41(m) Wavelet transform of Neutral Current waveform
with 39 – 37 disc fault in tapping winding
358
Figure. 4.41(o) Wavelet transform of Neutral Current waveform with
33 – 31 disc fault in tapping winding
359
Figure. 4.41(q) Wavelet transform of Neutral Current waveform with
29 – 27 disc fault in tapping winding
360
Figure. 4.41(s) Wavelet transform of Neutral Current waveform with
25 – 23 disc fault in tapping winding
361
Figure. 4.41(u) Wavelet transform of Neutral Current waveform with
21 – 19 disc fault in tapping winding
362
Figure. 4.41(w) Wavelet transform of Neutral Current waveform with
9 – 7 disc fault in tapping winding
363
Figure. 4.41(y) Wavelet transform of Neutral Current waveform with
5 – 3 disc fault in tapping winding
364
Figure. 4.41(aa) Wavelet transform of Neutral Current waveform
with 32 – 27 disc fault in tapping winding
365
Figure. 4.41(ac) Wavelet transform of Neutral Current waveform
with 21 – 16 disc fault in tapping winding
366
Figure. 4.41(ae) Wavelet transform of Neutral Current waveform
with 8 – 3 disc fault in tapping winding
367
Figure. 4.42(b) Wavelet transform of Neutral Current waveform with
1 – 3 turn fault in 40th disc of tapping winding
368
Figure. 4.42(d) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 37th disc of tapping winding
369
Figure. 4.42(f) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 29th disc of tapping winding
370
Figure. 4.42(h) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 21st disc of tapping winding
371
Figure. 4.42(j) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 13th disc of tapping winding
372
Figure. 4.42(l) Wavelet transform of Neutral Current waveform with
1 – 2 turn fault in 5th disc of tapping winding
A total of 14 sets of data have been generated to train and test the
data has been generated by normalizing the absolute 8th level wavelet
data are used for training the ANN and 4 sets of data have been used for
testing. The testing results are given in table 4.11. From the table it is
observed that more amounts of data for training the ANN is required to
373
Table.4.7 : Absolute maximum value of the Wavelet coefficients for
Disc to Disc Fault in HV winding using Daubechies Wavelet
374
Table.4.9 Absolute maximum value of the Wavelet coefficients for
Disc to Disc Fault in tapping winding using Daubechies Wavelet
375
Table.4.10: Absolute maximum value of the Wavelet coefficients for
2 turn Fault in the discs of tapping winding using Daubechies
Wavelet
2. 3 Turn 40th disc 1.3148 1.3603 3.4079 9.6011 6.9489 0.7668 0.8012 0.2836 2.3834
3. 4 Turn 40th disc 1.7509 1.2763 4.1910 8.0783 4.9634 1.7711 0.6912 0.5257 2.1089
4. 2 Turn 37th disc 1.8583 1.3427 3.9013 8.7042 5.8622 1.2704 0.5214 0.3969 2.4487
5. 2 Turn 33rd disc 1.7618 1.2602 4.1182 8.0708 4.7495 1.5443 0.6800 0.4311 2.1178
6. 2 Turn 29th disc 1.7899 1.3135 3.7721 8.4325 5.1805 1.3868 0.9107 0.2496 2.7943
7. 2 Turn 25th disc 1.0356 1.0069 3.0364 9.6602 4.7369 2.1822 0.9720 0.5610 3.0191
Local Average
Fault Fault Location
value
Normal Operation YES
Disc to 39 to 37 No
Disc
29 to 27 YES
faults
in
15 to 13 YES
tapping
winding 9 to 7 No
2 to 4 No
Disc to
Disc 6 to 8 YES
faults
in HV 10 to 12 YES
winding
14 to 16 YES
376
4.11 CONCLUSIONS
In this chapter the analytical modeling of the HVDC converter
considered for the analysis. The neutral currents were captured across
neutral current for these corner frequencies has been calculated. The
been analyzed and are classified using ANN and wavelet transform
technique. The neutral currents have been analyzed using the FFT, ANN
is proposed.
377
concluded from the results of the analysis of the converter transformer
that the combination of the techniques (Wavelet & ANN) can be adopted
core has been removed. The neutral currents are recorded using
are analyzed by using FFT and wavelet transform and different plots
obtained for each case have been presented. The absolute 8th level
wavelet coefficients have been normalized and are used to train and
test the ANN. The test results of the ANN have been presented. From
378