Generator Performance Report DATE:1/12/2014

Page | 1 OF 1

Model : Olympian Client: Power House Report NO. GPR( 66-1)/2015


Maximum LOAD : 108 KW \ 50 HZ Machine Code: 74 Work order NO: NA
Date of Inspection: 8 / 4 / 2015 Fuel type: Diesel Run hours: 27662.9 Hrs. Lifting Certificate NO.
Engine serial number :U887679P Ambient temp : 24 ° C Sound proof: No CR code: N/A

Oil Water Exhaust Battery


Duration load Blowby Boost Exhaust
Min Press Temp. Temp. Volt. P.f A1 A2 A3 Hz V KW
% inch H 0 2 pressure color
bar °C °C V
10 3.81 64 190 13.8 1 0 0 0 50.1 407 0 0 0.114 N/A Normal
10 3.4 70 345 13.8 1 42 43 44 50.1 407 30 28 0.152 N/A Normal
10 3.2 75 430 13.8 1 75 66 72 50.1 407 50 46 0.152 N/A Normal
10 3.1 80 535 13.8 1 117 109 115 50.1 407 80 74 0.152 N/A Normal
10 2.9 85 605 13.8 1 152 147 150 50.1 406 105 97 0.152 N/A Normal

ENGINE INSTRUMENTS Available Check ALTERNATOR CONTROLS Available Check

High Coolant Temperature √ √ Emergency Stop √ √


Oil /Low Oil Pressure √ √ O/U Voltage Fault
Water /Low water Level O/U Frequency Fault
High Oil Temperature Reverse Power
Exhaust Temp. 3 Start attempts
Fuel Level Overload 110%
Audible Alarm Over speed

Compression Test Records


Cylinder NO: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Pressure (Bar) NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA

VIBRATION RECORDS (VELOCITY MM/S

POINT X Y Z
1 7.3 9.3 7.5
2 5.4 9.5 7.5
3 5.3 12.1 10.3
4 6.9 12 11.3
5 3.7 9 11
6 7 11 10.2
7 3.2 19.2 24
8 2 9.5 16.8

Evaluation:

1-Generator tested at 97 % from its full load & all paramters are in the acceptance
range .
2- Generator without spark arrestor .(cleared)

Note :

Result:
Accepted

Inspected By QC Rep. Reviewed By QC Manager Witnessed By


Name:Wagih Abd El Aziz , Said Mahmoud Name: Mohamed Wageh Name: Abd El Rahman
Signature:Wagih Abd El Aziz Signature: Mohamed Wageh Signature:
Date : 8 / 4 / 2015 Date : 8 / 4 / 2015 Date : 8 / 4 / 2015