You are on page 1of 3

This article was published in ASHRAE Journal, October 2009.

Copyright 2009 American Society of Heating, Refrigerating and Air-Conditioning


Engineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission
of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.

An Updated Look
Multiple-zone HVAC systems such
as VAV pose a greater challenge to
DCV systems. If a single zone has an
increase in carbon dioxide, and calls

At DCV Approaches
for an increase in ventilation, it is not
ideal to increase ventilation to the whole
building.
Meanwhile, varying the airflow to the
single zone may require some reheat-
ing of cooled air to maintain the zone
By Kurtis McKenney; John Dieckmann, Member ASHRAE; temperature, which also is not an ideal
and James Brodrick, Ph.D., Member ASHRAE solution. Nonetheless, these DCV ap-
proaches are likely to be more efficient

D
than ventilating at full design rates all
emand controlled ventilation (DCV) can meet ventilation requirements of the time. ASHRAE Research Project
1547 is addressing the issue of DCV in
without wasting energy in under-occupied buildings. About six years ago, multiple zone systems.

DCV was first discussed in this column.1 Updates to ASHRAE Standard 62.1- Other Methods
Energy recovery ventilation (ERV)3
20072 and continued development and research in the field make this a good and indoor air purification4 can be used
as alternatives to, or in combination with,
time to revisit the topic. DCV. An ERV exchanges sensible heat
When used properly, a DCV system minimum ventilation rates, as opposed and moisture from the incoming outdoor
modulates the level of ventilation to a to acceptable rates suggested in older air to the conditioned air exhausted from
building based on the current occupancy versions, further helping to establish the building, reducing the cooling or
of the building, saving energy while still baseline design specifications for DCV heating required. Air purification can be
maintaining proper IAQ. systems. used under the IAQP to reduce design
Carbon dioxide sensors are most com- The Indoor Air Quality Procedure ventilation requirements by removing
monly used to indicate outdoor airflow (IAQP) provides a framework for an gas and particle contaminants from in-
rate per person, providing a basis for engineered approach to providing ac- door air. However, Standard 62.1-2007
controlling outdoor airflow rates in DCV ceptable IAQ in a particular building. The does not expressly allow reduced intake
systems, but total volatile organic com- IAQP is needed when an air-purification airflow at part-load conditions without
pound (TVOC), PM, carbon monoxide, system is being considered in lieu of VRP dynamic sensing of the concentration of
formaldehyde, and relative humidity lev- minimum ventilation rates, but generally all contaminants of concern.
els, etc., can provide a multiple-parameter the IAQP is avoided by building designers
approach to IAQ control. and operators implementing DCV. Energy Savings Potential
The majority of buildings do not use
Standard 62.1-2007 and DCV DCV Approaches DCV systems (or alternate technologies
Standard 62.1-2007 offers two ap- DCV systems can range in complexity to reduce ventilation-related energy con-
proaches to deter mine adequate from simple CO2 sensor control to labo- sumption), so the energy savings poten-
ventilation. ratory systems that monitor the levels of tial remains similar to that presented in
The Ventilation Rate Procedure (VRP) a customizable set of contaminants and the previous column. The annual energy
is a prescriptive approach with a table of trigger responses ranging from alerts consumption in the U.S. associated with
minimum required outdoor airflow rates to lab purges. Buildings with multiple outdoor air ventilation in commercial
as a function of floor area and population conditioned zones can use an indi- buildings is on the order of 1.5 quadril-
for a variety of commercial, institutional, vidual sensor approach for each zone, lion Btus (quads), accounting for blower
and multifamily residential buildings. or a centralized control system with energy and the energy required to condi-
The contribution of the floor area to the multiplexed sensing. Furthermore, dif- tion the exchanged air.5
ventilation rate establishes a baseline ferent approaches exist to monitor CO2, As mentioned, building ventilation is
ventilation rate for DCV systems to deal including supply air, room or zone air, designed for maximum occupancy, but
with non-human generated contaminants. and outdoor/indoor differential-driven many buildings operate at well below
Standard 62.1-2007 also establishes methods. their design capacity. One study shows

82 ASHRAE Journal ashrae.org October 2009


www.info.hotims.com/25209-40
While Standard 62.1-2007 allows the use of DCV, it does not require it. ASHRAE
Standard 90.1-2007 requires DCV to be applied in some circumstances.
that office buildings typically operate at 10% to 40% below Californias Title 24 Building Code mandates that DCV be
designed capacity, restaurants operate at 30% to 60% below used in densely occupied spaces, but the baseline ventilation rate
design, and schools and meeting rooms operate at 10% to 70% per floor area is 2.5 times greater than the minimum specified
below capacity.6 by Standard 62.1-2007.
In aggregate, the national energy savings potential of DCV is While Standard 62.1-2007 allows the use of DCV, as dis-
estimated to be between 0.4 and 0.5 quads, with relatively high cussed earlier, it does not require it. ASHRAE Standard 90.1-
energy savings in buildings designed for dense occupancy that 200711 requires DCV to be applied to densely occupied areas
seldom operate at such levels.1 in some circumstances. Proposed ASHRAE Standard 189.1P12
Buildings in locations with high cooling and/or heating loads may include requirements for the use of DCV.
could realize more energy savings by using a DCV system. Given the anecdotal evidence that ventilation systems often
are disabled in buildings, DCV has not overcome the obstacles
Market Factors that lie between it and mass adoption. Issues with sensor
As mentioned, traditional DCV systems use carbon dioxide technology and maintenance and system operation need to be
sensors to indicate per-person outdoor airflow rates. To accu- addressed for its considerable energy savings potential to be
rately correlate CO2 levels to per-person outdoor airflow rates, realized.
sensors need to be installed, calibrated, and maintained properly.
Recent studies indicate that one or more of these steps gen- References
erally are not followed in buildings with DCV.7,8 One study 1. Roth, K., J. Dieckmann, and J. Brodrick. 2003. Demand con-
showed that 80% of CO2 sensors in buildings read high by an trolled ventilation. ASHRAE Journal 45(7):9192.
average of approximately 40%, resulting in higher-than-needed 2. ANSI/ASHRAE Standard 62.1-2007, Ventilation for Acceptable
ventilation rates.7 Indoor Air Quality.
3. Dieckmann, J., K. Roth, and J. Brodrick. 2003. Air-to-air
Anecdotal evidence also suggests that it is common for DCV
energy recovery heat exchangers. ASHRAE Journal 45(8):5758.
systems to be disabled when not working properly or complaints 4. Dieckmann, J., K. McKenney, and J. Brodrick. 2009 Air puri-
are received about IAQ.9 fication to reduce OA. ASHRAE Journal 51(4):6870.
The outdoor airflow turndown associated with DCV is 5. Orme, M. 1998. Energy Impact of Ventilation. Technical Note
limited by building pressure requirements. In the summer, 49, International Energy AgencyAir Infiltration and Ventilation
buildings must be at a positive pressure differential relative Centre, Coventry, UK.
to outdoors (a requirement in Standard 62.1-2007), which 6. Taylor, S. 2009. CO2 DCV Control Strategies. Seminar at the
means air exfiltrates locally, and building codes require spe- ASHRAE Winter Conference.
cific minimum local exhaust airflow rates. Therefore, intake 7. Fisk, W. 2009. Carbon Dioxide Sensors Used for Demand
airflow can never be less than the sum of local exfiltration and Controlled Ventilation: Accuracy in Real Installations. Seminar at
local exhaust. This limitation may discourage DCV use in the ASHRAE Winter Conference.
8. Shrestha, S. and G. Maxwell. 2009. Performance Evaluation
some buildings, particularly those with relatively low intake
of CO2 Sensors for Demand Controlled Ventilation. Seminar at the
rates (e.g., offices). ASHRAE Winter Conference.
However, when implemented properly, the simple payback 9. Sharp, G. 2009. Personal communication with Gordon Sharp,
of either traditional individual sensor systems or centralized Aircuity. August.
systems can be in the range of one to three years.9,10 Buildings 10. Clark, L. 2009. Multiparameter demand-controlled ventila-
in regions with relatively high utility costs and/or relatively high tion. HPAC Engineering 81(8). http://tinyurl.com/clark2009 (or
heating or cooling requirements will see higher returns on an http://hpac.com/ventilation-iaq/multiparameter-demand-controlled-
investment in DCV. ventilation-0809/index.html).
Another factor to consider in deciding whether to pur- 11. ANSI/ASHRAE/IESNA Standard 90.1-2007, Energy Standard
sue DCV is green building certification. LEED credits are for Buildings Except Low-Rise Residential Buildings.
awarded for commissioning a DCV system that reduces 12. BSR/ASHRAE/USGBC/IESNA Standard 189.1P, Standard for
the Design of High-Performance Green Buildings Except Low-Rise
energy use. However, credits are also awarded for increasing
Residential Buildings.
the breathing zone outdoor airflow by 30% above minimum
requirements. Kurtis McKenney is a senior technologist and John
Designers and building operators also will tend to err on Dieckmann is a director with TIAX, Cambridge, Mass.
the side of overventilation to avoid potential liability issues. James Brodrick, Ph.D., is a project manager with the
Codes and standards for DCV may help protect against liability Building Technologies Program, U.S. Department of Energy,
concerns. Washington, D.C.

84 ASHRAE Journal ashrae.org October 2009

You might also like