CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015
1
FIRERETARDANTTREATEDWOOD www.cwc.ca
and lower corrosivity to metal fasteners. These water FRTW is generally restricted to interior use because of
solublechemicalsareeffectiveinreducingflamespread, thepossibilitythattheprotectivesaltsinthetreatment
and through careful proportioning succeed in reducing chemicals will leach out of the materials if they are
smokedevelopmentandafterglow. exposedtotheweather.
To dispel any myths that may still exist, it should be FRTW products are used in many interior applications,
understood that the fireretardant treatment does not such as millwork and panelling, where the code
make the wood noncombustible. This idea stems from requirementsforflamespreadaremostrestrictive.The
certainearlierversionsofbuildingcodeswhichequated Canadian building codes also permit the use of fire
a 25 surface flamespread rating to noncombustibility. retardanttreatedlumberandplywoodforroofandfloor
The 2010 NBCC uses a different method to determine trusses,beams,interiorroofdecks,andforinteriorload
noncombustibility (CAN/ULCS135, Standard Method bearingandnonloadbearingpartitions.
ofTestforDeterminationofDegreesofCombustibilityof
FRTW is suitable for indoor applications where the
Building Materials Using an Oxygen Consumption
humidityisnotexpectedtoexceed60percentforlong
Calorimeter (Cone Calorimeter)), and FRTW does not
periods of time. FRTW should be protected from
meetthenoncombustibilitycriteriaunderthatmethod.
excessivemoistureandweatherduringtransit,storage,
Theuseofafireretardanttreatmentdoesnotprevent and erection. While some wetting might be expected
ignition or charring. The rate of burn through fire during installation, frequent wetting or ponding is
retardanttreated wood is approximately the same as unacceptable. In general, FRTW requires more care in
that for untreated wood, even though ignition is more installationthanwouldnormallybeconsideredsufficient
difficult and the rate at which flame travels across its goodpracticefornonFRTWproducts.
surface(FSR)hasbeenreduced.
EXTERIORUSE
When FRTW products are used in areas where the
materialisexposedtoweatherorhighhumidity,itmust
betreatedwithspecialnonleachingchemicalssimilarto
those used for fireretardant treated cedar shakes and
shingles.
Theserequirementsapplytoproductsused,forexample,
Figure1.Samplelabels/markingsfromoneindependent as exterior grade fireretardant treated plywood siding
certification organization for fireretardanttreated over wood studs in exterior walls of noncombustible
lumberandplywood. buildings and FRTW decorative cladding on exterior
marqueefasciasofnoncombustiblebuildings.
CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015
2
FIRERETARDANTTREATEDWOOD www.cwc.ca
CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015
3
FIRERETARDANTTREATEDWOOD www.cwc.ca
StandardMethodofTestforFireSpreadUnderRoofDeck FRTWornoncombustibleceilingsmaybeattachedtothe
Assemblies. underside of the system, with the resulting concealed
spacesappropriatelyfirestopped.
AroofdecksystemofFRTWmaybesupportedby:
metalandreinforcedconcretebeamsorjoists; FRTWroofassembliesarepermittedasanalternativeto
heavytimbersupports;and/or, roof assemblies of noncombustible construction or
FRTWjoistsortrusses. ordinary woodframe roof assemblies having a fire
resistance rating of 45 minutes. When used, however,
WhensupportinganFRTWroofsystem,unlessthewood
the NBCC requires that, except for mercantile or light
members are heavy timber, which has an inherent
industrial occupancies, the area of the building be half
capacity to withstand fire exposure, they must be fire
thatwhichwouldbepermittedifeitheroftheothertwo
retardant treated. Experience shows that both lumber
typesofroofassemblywereused.
and plywood decking must have a minimum actual
thickness of 19 mm and both should be tongue and As noted earlier, fireretardantcoated wood is not the
groove.Plywooddecking,ifnottongueandgroove,must sameasFRTW,andFRTWisspecificallycitedintheNBCC
alsohaveunsupportedjointssolidlybackedwithFRTW for this application; therefore, fireretardantcoated
orplywood. wood is not permitted to be used under this
requirement. However, its use may be accepted via
Figure2showsthattheconstructionofroofassemblies
approval of an alternative solution by the Authority
using FRTW is similar to that of other types of roof
HavingJurisdiction.
assemblies, using a metallic vapor barrier membrane
betweenthedeckingandtheinsulation.Usually0.05mm
aluminum sheeting is attached with an approved
Moredetailedinformationaboutfireretardanttreated
adhesive, although steel foil is also acceptable.
woodandtheNBCCprovisionsrelatedtoitcanbefound
Galvanized roof nails may be used to fasten the
inChapter6ofCWCsFireSafetyDesigninBuildings.2
insulationtothevaporbarrierwhichisthenstapledto
thedeck.
CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015
4
FIRERETARDANTTREATEDWOOD www.cwc.ca
Figure2.Fireretardanttreatedwoodroofsystem.
1
NationalBuildingCodeofCanada,NationalResearchCouncil,Ottawa,ON,2010.
2
Availableatwww.cwc.caasafreePDFfordownload.
CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015