INTRODUCTION During a fire, fireretardant chemicals begin to react


Fireretardanttreated when temperatures reach a point slightly below the
wood(FRTW),asdefined pointwherewoodwillignite.Nonflammablegasesand
by the National Building watervapourareformedandreleasedataslowsteady
Code of Canada (NBCC),1 rate thereby insulating the wood fibres from
is wood which has been temperaturesthatwouldcausethemtoburn.
impregnated with fire The fireretardant treatments used in FRTW do not
retardant chemicals in solution under high pressure in generallyinterferewiththeadhesionofdecorativepaint
accordancewiththeCAN/CSAO80SeriesofStandards, coatings unless the treated wood has an increased
WoodPreservation. moisturecontent.Thefinishcharacteristicsofparticular
This means that any wood product that has been only productsshouldbediscussedwiththemanufacturersof
coated on the surface (or has been impregnated using thetreatedwood.
some method other than pressureimpregnation in
accordancewiththeCAN/CSAO80SeriesofStandards) FLAMESPREADRATING
does not meet the NBCC definition of fireretardant FRTWasdefinedandspecifiedintheNBCCmusthavea
treated wood. As a result, in Canada, a more flamespread rating of not more than 25. It therefore
appropriatetermforwoodproductsusingfireretardant qualifiesasaninteriorfinishforanyapplicationsincethe
surfacecoatingsisfireretardantcoatedwood. mostrestrictiveflamespreadratingis25.FRTWmustbe
identified by a label (Figure 1) from an independent
The treatment used in FRTW (as defined by the NBCC) testing laboratory or certification organization which
reduces surface burning characteristics, such as flame indicates that the necessary tests were performed and
spread,rateoffuelcontributionandsmokecontribution. productioncontrolsmaintained.
FRTWcontainsdifferentchemicalsthanproductsknown For many wood species, and particularly plywood and
as preservative treated wood. However, the same lumber in sizes common to frame construction, FRTW
manufacturing process is used to apply the chemicals. treatmentresultsinchemicalretentionshighenoughto
The products are not interchangeable. FRTW products obtainaflamespreadratingof25orless.Itshouldbe
arehardertoignitethanuntreatedwoodproducts. notedthatthechemicalswillnotusuallypenetratethe
Fireretardant chemical treatments applied to FRTW entirewoodmember,asrefusalwillusuallyoccurwhen
retard the spread of flame and limit smoke production the chemicals have penetrated approximately 13 mm
fromwoodinfiresituations. fromtheoutersurfaceoftheproduct.

FireretardanttreatmentsappliedtoFRTWenhancethe The actual flamespread rating of treated lumber or


fireperformanceoftheproductsbyreducingtheamount plywood depends on the fireretardant chemicals used
of heat released during the initial stages of fire. The and the amount of chemicals retained in the wood,
treatments also reduced the amount of flammable which depends on several factors, including wood
volatilesreleasedduringfireexposure.Thisresultsina species.
reductionin therateofflamespread overthesurface. Commonly used chemicals are proprietary mixtures
Whentheflamesourceisremoved,treatedwoodceases which are free of halogens, sulphates, ammonium
tochar. phosphate and formaldehyde. These provide superior
performancecharacteristicsoverpreviousformulations

CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015

1
FIRERETARDANTTREATEDWOOD www.cwc.ca

and lower corrosivity to metal fasteners. These water FRTW is generally restricted to interior use because of
solublechemicalsareeffectiveinreducingflamespread, thepossibilitythattheprotectivesaltsinthetreatment
and through careful proportioning succeed in reducing chemicals will leach out of the materials if they are
smokedevelopmentandafterglow. exposedtotheweather.

To dispel any myths that may still exist, it should be FRTW products are used in many interior applications,
understood that the fireretardant treatment does not such as millwork and panelling, where the code
make the wood noncombustible. This idea stems from requirementsforflamespreadaremostrestrictive.The
certainearlierversionsofbuildingcodeswhichequated Canadian building codes also permit the use of fire
a 25 surface flamespread rating to noncombustibility. retardanttreatedlumberandplywoodforroofandfloor
The 2010 NBCC uses a different method to determine trusses,beams,interiorroofdecks,andforinteriorload
noncombustibility (CAN/ULCS135, Standard Method bearingandnonloadbearingpartitions.
ofTestforDeterminationofDegreesofCombustibilityof
FRTW is suitable for indoor applications where the
Building Materials Using an Oxygen Consumption
humidityisnotexpectedtoexceed60percentforlong
Calorimeter (Cone Calorimeter)), and FRTW does not
periods of time. FRTW should be protected from
meetthenoncombustibilitycriteriaunderthatmethod.
excessivemoistureandweatherduringtransit,storage,
Theuseofafireretardanttreatmentdoesnotprevent and erection. While some wetting might be expected
ignition or charring. The rate of burn through fire during installation, frequent wetting or ponding is
retardanttreated wood is approximately the same as unacceptable. In general, FRTW requires more care in
that for untreated wood, even though ignition is more installationthanwouldnormallybeconsideredsufficient
difficult and the rate at which flame travels across its goodpracticefornonFRTWproducts.
surface(FSR)hasbeenreduced.
EXTERIORUSE
When FRTW products are used in areas where the
materialisexposedtoweatherorhighhumidity,itmust
betreatedwithspecialnonleachingchemicalssimilarto
those used for fireretardant treated cedar shakes and
shingles.

An accelerated weathering test (ASTM D2898) exposes


FRTWtoregularwettinganddryingcyclestorepresent
actual longterm outdoor conditions. FRTW must still
achieveaflamespreadratingof25afterundergoingthis
acceleratedweatheringprocedureinordertoqualifyfor
exterioruse.

Theserequirementsapplytoproductsused,forexample,
Figure1.Samplelabels/markingsfromoneindependent as exterior grade fireretardant treated plywood siding
certification organization for fireretardanttreated over wood studs in exterior walls of noncombustible
lumberandplywood. buildings and FRTW decorative cladding on exterior
marqueefasciasofnoncombustiblebuildings.

CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015

2
FIRERETARDANTTREATEDWOOD www.cwc.ca

FIRERETARDANTCOATINGS Crust formation: the coating melts under the


As mentioned above, in addition to chemical actionofheat,coveringthetreatedmaterialwith
impregnationbypressuretreatingthatproducesFRTW, animpermeableinsulatingcrust.
therearealsofireretardantcoatingsthatcanbeapplied Heatabsorption:thecoatingabsorbstheheatand
to the surface of wood products (referred to as fire maintains the temperature of the protected
retardantcoatedwood(FRCW))toreducethesurface surfacebelowitsignitiontemperature.
flamespreadratingtolessthan75or25.Thesecoatings, Intumescent insulation: the coating swells when
are generally used for architectural woodwork heatedtoformathickinsulatinglayerthatdelays
applicationswhereappearanceisimportant. thespreadofflameandthetransmissionofheat
totheprotectedsurface.
Thesecoatedproductscanbeusedforinteriorfinishin
noncombustiblebuildingsundertheNBCCexceptwhere Like FRTW products, wood products protected by fire
theflamespreadratinglimitsapplynotonlytoexposed retardant coatings, because of their reduced flame
surfaces but also to surfaces that may be exposed by spread rating, canbe used in areas where untreated
cutting through the product in any direction. FRTW wood products cannot be used. However, many fire
products are excluded from these requirements, while retardant coatings are not suitable for use in high
products protected by fireretardant coatings are not. humidityorexteriorapplications.
This recognizes the permanency of the pressure Fireretardantcoatingsaremanufacturedasproprietary
impregnatedfireretardanttreatments. products. For specifications on rate of coverage and
Theimageshownhereisaphoto testedproperties,amanufacturershouldbeconsulted.
oftheatticofachurch.Trusses These products can be applied by brush, roller, or
in the attic spaces were fire sprayer.Becausefireretardantcoatingsareusuallyhigh
stoppedand coatedwith afire viscosity (thick) liquids, they should be maintained at
retardantpaint.Thisavoidedthe room temperature, especially when sprayapplied, to
cost of sprinklering the ease application. Where appearance is important, two
concealedspaces. lightcoats,toreducesagging,aresuperiortooneheavy
Fireretardant coatings are coat and usually provide the required flamespread
available in clear and white characteristics as long as total application thickness is
finishes.Whereasolidcolouris achieved.
required,oneortwocoatsofalkydpaintcanbeapplied
overtheclearorwhitefireretardantcoatingwithonlya FIRERETARDANTTREATEDWOODROOFSYSTEMS
small increase in the flamespread rating. Check with Incertainunsprinkleredonestoreybuildings,theNBCC
manufacturersofspecificproductsformoreinformation. permitstheuseofaroofdeckconstructionsystemusing
FRTW that meets the flamespread performance
The reaction of these coatings to fire and the actual standard originally developed for noncombustible roof
mechanism of protection varies according to the assemblies.
composition of the coating. Some of the basic
mechanismsofprotectionareasfollows: Therequiredfireresistanceratingoftheroofassembly
Insulation:thickcoatingsthatinsulatethetreated canbewaivedifthedeckisconstructedofFRTWandthe
materialagainsthightemperatures. assembly passes the requirements of CAN/ULC S126

CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015

3
FIRERETARDANTTREATEDWOOD www.cwc.ca

StandardMethodofTestforFireSpreadUnderRoofDeck FRTWornoncombustibleceilingsmaybeattachedtothe
Assemblies. underside of the system, with the resulting concealed
spacesappropriatelyfirestopped.
AroofdecksystemofFRTWmaybesupportedby:
metalandreinforcedconcretebeamsorjoists; FRTWroofassembliesarepermittedasanalternativeto
heavytimbersupports;and/or, roof assemblies of noncombustible construction or
FRTWjoistsortrusses. ordinary woodframe roof assemblies having a fire
resistance rating of 45 minutes. When used, however,
WhensupportinganFRTWroofsystem,unlessthewood
the NBCC requires that, except for mercantile or light
members are heavy timber, which has an inherent
industrial occupancies, the area of the building be half
capacity to withstand fire exposure, they must be fire
thatwhichwouldbepermittedifeitheroftheothertwo
retardant treated. Experience shows that both lumber
typesofroofassemblywereused.
and plywood decking must have a minimum actual
thickness of 19 mm and both should be tongue and As noted earlier, fireretardantcoated wood is not the
groove.Plywooddecking,ifnottongueandgroove,must sameasFRTW,andFRTWisspecificallycitedintheNBCC
alsohaveunsupportedjointssolidlybackedwithFRTW for this application; therefore, fireretardantcoated
orplywood. wood is not permitted to be used under this
requirement. However, its use may be accepted via
Figure2showsthattheconstructionofroofassemblies
approval of an alternative solution by the Authority
using FRTW is similar to that of other types of roof
HavingJurisdiction.
assemblies, using a metallic vapor barrier membrane
betweenthedeckingandtheinsulation.Usually0.05mm
aluminum sheeting is attached with an approved
Moredetailedinformationaboutfireretardanttreated
adhesive, although steel foil is also acceptable.
woodandtheNBCCprovisionsrelatedtoitcanbefound
Galvanized roof nails may be used to fasten the
inChapter6ofCWCsFireSafetyDesigninBuildings.2
insulationtothevaporbarrierwhichisthenstapledto
thedeck.

CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015

4
FIRERETARDANTTREATEDWOOD www.cwc.ca


Figure2.Fireretardanttreatedwoodroofsystem.

1
NationalBuildingCodeofCanada,NationalResearchCouncil,Ottawa,ON,2010.
2
Availableatwww.cwc.caasafreePDFfordownload.

CanadianWoodCouncil,40099BankStreet,OttawaK1P6B9 April2015