GETCO / E / 2S-172 / PP - 015 1A / R0 Dt.30.04.

2012

Control & Relay Protection Philosophy for 220 KV MANJUVAS Sub Station

A) Bus Bar Configuration

 220 KV System: - Two Bus (One Main and One Main cum Transfer bus)
 66 KV System: - Two Bus (Two Main bus)

 Isolator system

220 KV System: - Four isolator configuration (Three Bus isolators and a Line
isolator)
66 KV System: - Three isolator configuration (Two Bus isolators and a Line
isolator)
B) Control Voltage

 220V DC

C) Control & Relay panels

 Control & protection Panels to be mounted in Yard Kiosk

D) PLCC panels

 PLCC Panels to be mounted in Control Room


 PLCC BCU panel to be mounted in Control Room for interface between Control &
protection Panels and PLCC Panels, through GOOSE commands

E) Nos. of 220 KV Bays

 Feeder Bay 2 Nos.


 Transformer Bay (220/11KV) 2 Nos.
 Bus coupler Bay - 1 No
 Total No. of Bays planned in first phase 5 Nos.
 Future Feeder Bays 03 Nos.
 Future Transformer Bay (220/66KV) - 02 Nos.
 Total Bays Planned 10 Nos.
 Bays to be connected to Bus Bar Protection in first phase - 5 Nos.
 Bus Bar Protection
Control Unit (Central Unit) - 24 Bays
Bay Units (Peripheral Unit) - 5 Nos. + 1 No (to be kept as spare)

F) Nos. of 66 KV Bays (Future)


 Feeder Bay 4 Nos.
 220/66KV Transformer LV Bay 2 No
 Station Transformer Bay 1 No.
 Bus Coupler Bay 1 No.
 Total Nos of Bays planned 8 Nos.

Control Philosophy MANJUVAS Sub Station


System Controlling Device to be Adopted Type of Controlling Device

220 KV Bay Bay Control Unit BCU with IEC 61850 Protocol
66 KV Bay Bay Control & Protection Unit BCPU with IEC 61850 Protocol

Page 1 of 3
GETCO / E / 2S-172 / PP - 015 1A / R0 Dt.30.04.2012

Protection Philosophy MANJUVAS Sub Station


A) Feeder Protection
Feeder Protection to be Adopted Type of Relay
220 KV Feeders 1 Two Distance Protection Numerical Relay with IEC
[shall be of two different make 61850 Protocol
(i.e. from different
manufacturers) or of same
make with two different
platforms with same
specifications]
-Main-I Protection &
-Main II Protection
2 Two Stage Over Voltage Integrated in Main I &
Protection Main II Protection
- Stage I
- Stage II
3 Local Breaker Backup (LBB) Integrated in Main I
Protection. Protection and Bus Bar
protection
66 KV Feeders 1 Directional O/C & E/F Integrated in Bay Control &
Protection Protection Unit (BCPU) with
IEC 61850 Protocol
2 Local Breaker Backup (LBB) Integrated in BCPU
Protection.
B) Power Transformer Protection
Equipment Protection to be Adopted Type of Relay
220/11 KV Transformer 1 Differential Protection Numerical Relay with IEC
61850 Protocol
2 Restricted Earth Fault Numerical Relays with IEC
Protection 61850 Protocol
(For HV & LV winding, To be
provided in HV Panel)
3 Directional O/C & E/F Numerical Relays with IEC
Protection 61850 Protocol
(HV side)
4 Over Fluxing Protection Integrated in Differential
Protection
5 Local Breaker Backup (LBB) Integrated in Differential
Protn. Protection and Bus Bar
protection
6 Buchholz Relay Integrated in Transformer.
Auxiliary relay in protection
panel.
7 Pressure Relief Device Integrated in Transformer.
Auxiliary relay in protection
panel.
8 Oil & Wdg. Temp. Alarm & Integrated in Transformer.
Tripping Auxiliary relay in protection
panel.
9 OLTC Oil Surge Relay Integrated in Transformer.
Auxiliary relay in protection
panel.
10 Oil Level Low Alarm Integrated in Transformer.
Auxiliary relay in protection
panel.

Page 2 of 3
GETCO / E / 2S-172 / PP - 015 1A / R0 Dt.30.04.2012

11 Transformer Cooling Troubles Integrated in Transformer.


Auxiliary relay in protection
panel.
12 Fire Protection System Integrated in Transformer.
Auxiliary relay in protection
panel.
66/11 KV Transformer 1 Differential Protection Numerical Relay with IEC
61850 Protocol
2 Non Directional O/C & E/F Integrated in Bay Control &
Protection Protection Unit (BCPU) with
- 66 KV side IEC 61850 Protocol
3 Local Breaker Backup (LBB) Integrated in BCPU
Protection.
4 Buchholz Relay Integrated in Transformer.
Auxiliary relay in protection
panel.
5 Pressure Relief Device Integrated in Transformer.
Auxiliary relay in protection
panel.
6 Oil & Wdg Temp. Alarm & Integrated in Transformer.
Tripping Auxiliary relay in protection
panel.
7 OLTC Oil Surge Relay Integrated in Transformer.
Auxiliary relay in protection
panel.
8 Oil Level Low Alarm Integrated in Transformer.
Auxiliary relay in protection
panel.
C) Bus Coupler Protection
220 KV Bus coupler 1 Non Directional O/C & E/F Numerical Relay with IEC
Protection 61850 Protocol
2 Local Breaker Backup (LBB) Integrated in Non Dir. O/C &
Protection. E/F Protection and Bus Bar
protection.
66 KV Bus coupler 1 Non Directional O/C & E/F Integrated in Bay Control &
Protection Protection Unit (BCPU) with
IEC 61850 Protocol
2 Local Breaker Backup (LBB) Integrated in BCPU
Protection.
E) Bus Bar Protection
220 KV Bus bar 1 Bus Differential Protection Numerical Relay with IEC
(Single scheme) 61850 Protocol
5 Bays, Extendable up to 24
Bays (i. e. Control Unit - 24
Bays)
F) Disturbance Recorder & Event Loggers
Integrated feature of protective relays is used to provide the information about the Disturbance and to log
the events.
G) GPS based Time Synchronizing Equipment
220 KV Sub station is to be provided with IEC 61850 compatible Global Positioning System based Time
Synchronizing Equipment to synchronize all the protections.

Page 3 of 3