You are on page 1of 4

D R I V E S &

S W I T C H G E A R

The unfortunate culture of copper theft that has become prevalent in


South Africa has exascerbated problems related to the integrity of the
neutral in low voltage (LV) distribution systems in recent years.

Loss of neutral in LV distribution


systems: consequences and solutions
While this problem is not unique to by Viv Cohen, retired engineer
South Africa, it is largely unknown in
developed countries. Neutral integrity
problems are generally more common in
developing countries due a combination
of aggressive environmental conditions,
vandalism and, in some cases,
questionable workmanship.
The consequences of a lost neutral
conductor will vary depending mainly
on the load balance conditions in a
three phase system, but also on the type
of earthing system used and the position
of the break in the neutral relative to
the load. Worst case scenarios could
include damage to connected loads
due to overvoltages on single phase
circuits and the creation of hazardous
touch voltages on exposed conductive
parts.
Systems affected by Fig. 1: The TN-S system.
loss of neutral
Almost by definition, the systems and
installations most adversely affected by this theoretical zero value, depending 230 V x 3 which is equivalent to
a lost or broken neutral conductor are upon the load current that is carried 400 V (nominal). The majority of
single phase systems and single phase by the neutral and the consequential residential end-users in South Africa are
circuits that are derived from three phase voltage drop resulting from the neutral provided with single phase electricity
star connected supplies. Three phase current. In a single phase system that derived from a distributed three phase
systems that include single phase loads is derived from a single phase source, system. Provided the neutral conductor
may experience voltage shifts between a break in the neutral conductor will remains continuous, the voltages
the star point and the three phases, simply result in a loss of energy supply. between each phase and the neutral
depending on the balance of single However, in a three phase system with a are largely unaffected, except for voltage
phase loads across the three phases. distributed neutral, a break in the neutral drops in the circuit which are load
conductor may result in undesirable dependent.
System voltages variations of the three (phase to neutral) For the (unusual) case of equal load
By convention, a solidly earthed neutral voltages. distribution across the three phases,
conductor is at zero potential to earth. The standard phase to neutral voltage even in the event of loss of the neutral
The potential on a correctly installed in South Africa is 230 V. The resulting conductor, the individual voltages from
neutral conductor may rise slightly above voltages between phases are thus each of the three phases to the star point

Nov/Dec 2012 - Vector - Page 46


will remain at approximately the nominal
level of 230 V.
A break in the neutral conductor can,
however, result in wide excursions of
the voltages between each phase and
the star point if the three single phase
load currents deviate from the ideal
balanced condition. Depending on
the degree of imbalance between the
single phase loads, in the extreme,
the three single phase voltages (phase
to neutral) could vary from as low as
0 V to any voltage up to the phase
to phase voltage. Irrespective of load
balance, the voltages between phases
are not affected by a break in the neutral
conductor.
Neutral shift Fig. 2: TN-C-S system.

In both TN and TT electrical distribution


systems, the neutral conductor is solidly TN-C-S system: in which neutral phases, one neutral and one protective
connected to earth at the source of and protective functions are conductor). South Africa is no exception
the electricity supply (transformer or combined in a single conductor in this practice. The combined neutral
generator). For reasons of safety, this in a part of the system (see Fig. 2). and protective earth conductor is
creates a reference point for the neutral The TT power system in which one commonly referred to as the PEN
(at earth potential). It should be recalled point is directly earthed, the exposed- conductor.
that in a three phase electricity supply conductive-parts of the installation Effective and safe operation of TN-C-S
system, the three phases are generated being connected to earth electrodes
at an electrical angle of 120 to each distribution systems depends on the
electrically independent of the earth
other. When considered in a rotating ongoing integrity of this PEN conductor.
electrodes of the power system.
vector system this can be described as The TT system is not permitted for In a TN-C-S system, the separate
each phase leading the subsequent new installations in South Africa, protective earth conductor (PE) for each
phase by 120 electrical degrees. As but still exists in many of the older end-user is created by simply tapping
long as the star point of a three phase installations. off a second parallel conductor from
transformer remains solidly connected The IT power system which has all
the PEN conductor at a location close
to earth, the relationship between the live parts isolated from earth, or one to or at the point of supply to individual
voltage of each phase and neutral (or point connected to earth through an end-users. The parallel conductor in the
earth) remains fixed, irrespective of impedance, the exposed-conductive- installation then becomes the neutral
the balance of load between the three parts of the electrical installation conductor.
phases. However, in the absence of being earthed independently or
Broken or lost PEN conductors
this reference, the neutral point at the collectively or to the earthing of the
confluence of the three vectors will be system. The IT system is not used Electrical distribution utilities are very
caused to shift depending on the ratio for public distribution of electricity, aware of the importance of maintaining
of the load currents drawn on the three but is used in private installations, the integrity of the PEN conductor. Since
phases. It is this shift of the neutral mainly for reasons of continuity of the protective earth (PE) conductor
service. Three phase IT systems with has a direct electrical connection to
that results in the variations of phase
a distributed neutral can result in the PEN conductor, this can lead to
to neutral voltages between the three
hazardous conditions. This latter type the creation of potentially hazardous
phases. of IT system is to be deprecated. conditions in the event of a break in
Low voltage distribution The problems of voltage variations the PEN conductor. In the absence of
systems between phase and neutral that can a direct return connection to the source
The main types of earthing system result from a break in the neutral are other than through the load, a break
include: common to all types of LV distribution in the PEN will result in the neutral
systems. The increasing use of the conductor (downstream of the break
TN power systems which have one
TN-C-S system has however introduced in the PEN conductor) assuming the
point directly earthed, the exposed-
a further dimension to the consequences same potential as the phase conductor.
conductive-parts of the installation
being connected to that point by of a loss of the neutral conductor. Similarly, all exposed conductive
protective conductors. Two types parts connected to the PE conductor
The TN-C-S power system (earth) will also become live in such
of TN system are approved for
new installations in South Africa. This power system is becoming widely circumstances.
These are defined according to used for the distribution of LV electrical The main disadvantage of the TN-C-S
the arrangement of neutral and power. The concept of combining the distribution system is this unprotected
protective conductors, as follows: neutral and protective functions in a hazardous condition that could arise
TN-S system: in which a separate single conductor eliminated one of the in the event of a break in the PEN
protective conductor is used five distributed conductors required conductor. This hazard continues to
throughout the system (see Fig. 1). for a three phase TN-S system (three exist independent of the presence of

Nov/Dec 2012 - Vector - Page 47


any protection devices that may be parts of items such as water taps and that appliance manufacturers will
installed. In the event of a break in the fences was possible. The problem guarantee that their wares would
PEN conductor, all exposed conductive became further aggravated by the survive. Consequently, devices designed
parts will remain live irrespective of the growing use of non-metallic pipes and as overvoltage protection devices may
operating state of the main switching fittings in water supply and plumbing not necessarily be able to guarantee the
or isolating device whether it is on systems. survival of appliances or equipment in
(closed) or off (open). Another problem is electrolytic corrosion the event of overvoltage. These devices
One possible mitigating solution to this of cable armouring and other buried will however mitigate the conditions and
hazard would be the installation of a metalwork, should such a condition provide a reasonable high measure of
foundation earth at the service entrance remain undetected or uncorrected. protection to the entire circuit and to
of the electricity supply. This is standard It should be recalled that all intentional equipment connected to it.
practice under the requirements of the earth connections on the neutral were A new, cost effective solution
National Electric Code in the USA and made upstream of the earth leakage
is also used to a limited degree in some Earth leakage circuit breakers are
circuit breaker (if fitted). The provision
European countries such as Germany. of sensitive earth leakage was therefore manufactured using two distinct and
The effect of the foundation earth is not a solution to this problem as, even differing technologies. Modern devices
to hold the neutral and PE potentials though the load current returned via the that employ solid state electronic
closer to earth potential even under earth rod, the live and neutral currents sensing systems already include all the
fault conditions. through the earth leakage circuit breaker basic elements to provide additional
remained balanced. protection. It is a relatively simple matter
It is not a simple matter to retrofit to extend these functions to include
TN-C-S distribution systems with such a The proposed solution at that time was
overvoltage protection.
facility. This is true for TN-C-S systems to monitor the level of neutral current
(such as those in South Africa) that that found a return path via the provided South African-manufactured earth
do not require the installation of a earth electrode and to interrupt the leakage circuit breakers have recently
foundation earth at the service entrance. supply mains in the event of this current become available with two discrete
exceeding a predetermined level. An optional additional protection functions:
Where only one end-user has a
foundation earth, all the load currents immediate problem was that, in the Devices to detect and operate under

of all the users connected to that case of a very efficient earth rod and a phase to neutral voltage rises above
distribution system would try to flow very low earth return loop impedance, a critical level.
significant level of current would return Devices that detect and operate a
through the single foundation earth.
to the source via the earth circuit, even in rise in the potential of the neutral
The consequential overheating and
the absence of a fault. A crude solution conductor above critical level.
the danger of incendiary ignition are
was to decrease the sensitivity of the
obvious. In the event of a break in the neutral
monitoring device.
conductor upstream of the point of
Early solutions supply, the former type devices will
The over-voltage problem
During the mid to late 1980s and early operate and open the protected circuit
Overvoltages in single phase installations
1990s ageing electrical installations in the event of an increase in phase to
that result from a break in the neutral
with poor electrical connections spurred conductor will invariably result in neutral voltage. In the event of neutral
researchers to address the phenomenon damage to most appliances and other shift, a voltage increase could result
of lost neutral conductors. The more connected electrical equipment. As a due to a higher load drawn on one of
commonly used distribution systems at general rule, any protection system that the other phases in the network.
that time were the so-called protective is designed to detect such overvoltages A break in the upstream neutral
multiple earthing (PME) or multiple will be arranged to disconnect the conductor will also result in voltage
earthed neutral (MEN) systems. In affected part of the installation from between neutral and earth. This voltage
most cases these types of distribution the source of electricity. Furthermore, will also increase in the event of an
system also included an earth rod protection systems must be designed so increase in load on a phase other than
at or near to the point of supply to that they are not too sensitive, since this the one being monitored.
individual end-users. The main purpose would result in unacceptably high levels
of the local earth rod was to ensure of nuisance operation. Applicability of protection
that the neutral conductor would be systems
According to the Electricity Act, electricity
held at earth potential in the event supply utilities in South Africa are Overvoltage detection and protection
of a high impedance or break in the permitted to deliver electricity at the systems based on standard earth
neutral conductor. In the event of such nominal voltage up to 110% of the leakage circuit breakers are most suited
a break in the neutral conductor, the nominal voltage. For this reason, to customer-level protection. With the
load current would return via the earth devices designed to detect overvoltages installation of sensitive earth leakage
connection. on standard 230 V single phase systems protection mandatory in South Africa
It was however conceded that in typically are usually preset at an operating value over the last quarter century, this can be
dry South African conditions, the exceeding 253 V (230 V x 110%) plus achieved easily and cost effectively by
probability of obtaining low resistance some additional margin to cater for the simply replacing the existing earth leakage
earth connections was not particularly possibility of short-duration temporary circuit breaker with a device that includes
good. Any significant load current overvoltages. the chosen type of overvoltage protection.
could result in a rise of potential in the An unprotected window of overvoltage
local earth circuit. In extreme cases may remain for practical reasons. Protection sensitivity
the development of hazardous touch Even for temporary overvoltages of An alternative to monitoring the voltage
potentials on the exposed conductive very short duration, it is highly unlikely increase on the neutral conductor

Nov/Dec 2012 - Vector - Page 48


relative to earth would provide better the busbar. In a typical sub-station, it is Conclusions
protection than monitoring the voltage a reasonably simple matter to anticipate
Intensive investigations in several
increase between phase and neutral. which copper busbars or cables are
technical working groups of the IEC
Depending upon the neutral conductor most vulnerable to vandalism of this
have shown that, in developed countries,
impedance between the system earth kind.
the incidence of a break in the neutral
point and the end-user and the system With the operating sensitivity of the conductor of low voltage distribution
load current being drawn, it is quite sensing device set to a relatively low systems is so low that it does not even
common for the neutral to rise several value, the two pilot wires used with the deserve any consideration. In normal
volt above earth. This is particularly so in device need only be of relatively small law abiding societies, the justification
the case of single point neutral earthing cross sectional area. In addition, the
for the development of devices such as
or where the last neutral earthing point pilot wires are arranged in such a way
those described in this paper would, as
is relatively distant from the customer. In that they will be self protected through
a result, remain questionable.
general, this neutral voltage elevation is isolation once the sensing device has
operated. In practical applications, the It is regrettable that similar criteria do
usually only a few volt (rarely exceeding
pilot wires are connected discretely at not apply in the new South African
10 to 15 V).
convenient locations where vandalism democracy for various reasons. This
SABS 0142-1:2001 annex K requires and theft are accepted. paper attempts to identify the causes and
notification of potential danger should consequences of a break in the neutral
The sensor arrangement is connected
the elevation of voltage on a supply conductor in low voltage distribution
across the neutral busbar in the sub-
neutral exceed 25 V. From this it can systems. While it is recognised and
station and effectively monitors this
be concluded that for neutral elevation accepted that protection devices cannot
conductor for continuity. Any removal or
detection devices, an operating level of always guarantee the protection of all
interruption of the system neutral busbar
about 20 V might be appropriate. will result in a current flow in the sensor connected appliances, a significant
Computer simulations have shown that due to the potential difference between reduction in such damage has already
at a preset operating level of 20 V, any the earth and the supply neutral resulting been demonstrated in pilot test sites.
interruption of the neutral conductor will from removal or damage to the neutral In recognition of the widespread
almost immediately be detected. It can busbar. equipment damage implications
also be shown that even for the case of Since the pilot wires are connected in resulting from a broken neutral, together
a balanced load on all phases, a load parallel with the anticipated break in with the need for economically viable
imbalance as low as 20% in any one the neutral conductor, even in the event solutions, three different solutions are
phase would elevate the neutral by at of such a break an alternative ohmic proposed in this paper. Since copper
least 20 V. connection is provided to complete the theft occurs mainly in substations, the
Sub-station level protection neutral circuit. This has the additional relatively low cost zone monitoring
benefit of (to some extent) restricting solution is more appropriate to sub-
The problems of copper theft and the neutral shift and consequential station applications.
the consequential damage to single excursions in the phase to neutral
phase equipment connected to It is not inconceivable that insurance
potentials.
TN-C-S distribution systems precipitated companies may demand the installation
In the event of a neutral break, an of means to mitigate against the effects
the development of more devices for auxiliary switch included as part of the
application in utility and customer of overvoltage damage to appliances.
sensing device is arranged to activate The voltage sensing devices described
sub-stations. In most cases, the theft of the shunt tripping mechanism of a
copper neutral and/or earth connection here offer affordable solutions involving
circuit breaker connected to isolate the
busbars takes place on the low voltage only relatively minor modifications to
low voltage circuits from the supply
side of the sub-station transformer. standard freely-available earth leakage
transformer.
While it is recognised that no such circuit breakers.
In practice, the installation of the
protective device can always guarantee References
sub-station level lost neutral detection
protection of all connected appliances, [1] Code of practice: The wiring of premises,
device always requires the presence of
a significant reduction in such damage SABS 0142-1:2001.
a shunt trip operated circuit breaker.
has been demonstrated. [2] Electrical installation of buildings IEC
Should the substation already include 60364-1, Part 1: General principles.
One device comprises a sensor a main transformer LV circuit breaker, [3] National Electric Code, 2002 edition
arranged to monitor current between an it is necessary to add a shunt trip NFPA 70.
earth connection and a predetermined device to that circuit breaker and to [4] Effect of multiple earthing systems
location on a conductor of the neutral install the patented current sensing on consumers installations,
pole of the supply. It is designed to Viv Cohen, Vector August 1983.
device. With isolation of the low voltage
[5] The Silent Killer pamphlet by Circuit
generate an output when the current distribution circuits being a prerequisite Breaker Industries, October 1990.
exceeds a predetermined value. The for protection systems such as this, older [6] Provisional patent application PA131014/P:
device also includes a switch that is sub-stations that include fuse protection Method and apparatus for protecting an
responsive to this output and is arranged on the transformer secondary would electrical installation against loss of supply
neutral, July 2001.
to disconnect the live conductors from require the installation of a trippable
[7] Viv Cohen, Application guide for the
the respective loads in response to such protection device such as a shunt trip protection of LV distribution systems,
an event. equipped circuit breaker. published by CBi electic.
In the case of interference with the The performance of the device was fully [8] www.cbi-electric.co.za.
copper busbars in sub-stations, the studied in a SPICE simulation, the results Contact Viv Cohen, retired engineer
sensor is arranged to detect changes in of which were confirmed in a laboratory Tel 082 737-7321,
current due to removal or damage to test program. vivcohen@telkomsa.net

Nov/Dec 2012 - Vector - Page 50

You might also like