You are on page 1of 1

ZEFO:Nda bcf:IOP; lista os alarmes externos criados na BTS.

Ex.:
ZEFO:43:IOP;

LOADING PROGRAM VERSION 21.8-0

BSC3i BSCPA01 2011-11-21 18:11:26

EXTERNAL INPUT AND OUTPUT DATA:


===============================

BCF-0043: EXTERNAL OUTPUTS


-------------------------
OUTPUT 1 ....................... OFF TEXT ID -
OUTPUT 2 ....................... OFF TEXT ID -
OUTPUT 3 ....................... OFF TEXT ID -
OUTPUT 4 ....................... OFF TEXT ID -
OUTPUT 5 ....................... OFF TEXT ID -
OUTPUT 6 ....................... OFF TEXT ID -

INPUT 1 ..............ROUTE: ACT


POLARITY: OPEN SEVERITY: ** TEXT ID 1
FALHA NO RETIFICADOR NAO URGENTE
INPUT 2 ..............ROUTE: ACT
POLARITY: OPEN SEVERITY: ** TEXT ID 2
FALHA NO RETIFICADOR URGENTE
INPUT 3 ..............ROUTE: ACT
POLARITY: OPEN SEVERITY: ** TEXT ID 3
BATERIA EM DESCARGA
INPUT 4 ..............ROUTE: ACT
POLARITY: OPEN SEVERITY: ** TEXT ID 4
ALTA TEMP GAB SERVICO
INPUT 5 ..............ROUTE: ACT
POLARITY: OPEN SEVERITY: ** TEXT ID 5
FALHA DISJUNTO/FUSIVEL
INPUT 6 ..............ROUTE: ACT
POLARITY: OPEN SEVERITY: ** TEXT ID 6
FALHA DE ENERGIA AC

ZEFX:n da bcf:INBR=input number:ROU=ACT,POL=OPEN OU CLOSED:SEV=(AL1, AL2 OU AL3),TID=(n do texto do


alarme).

ZEFX:331:INBR=10:ROU=ACT,POL=OPEN:SEV=AL2,TID=10:;