You are on page 1of 27

X High Performance (accuracy class 0,5S)

X Flexibility (open platform)


X Reliability (high quality of components)
X Connectivity (RS485, ExpBus, Ethernet, Wi-Fi, NFC)

X For continuous monitoring (E.g. ISO 50001)


X Energy efficiency (E.g. 2012-27 EU-Directive and EEC)

(Power Quality) Energy Analyzer & (Wi-Fi) Data Manager


Power Quality Energy Analyzer & (Wi-Fi) Web Data Manager
The Kilo RJ45 H (DIN rail or 96x96) is an Energy Analyzer The Kilo RJ45 PQ is a Power Quality Energy Analyzer &
& Data Manager microprocessor based (Dual Core Cortex- Data Manager which in addition to the functions of the del
M4) outstanding flexibility and accuracy designed to meet Kilo D6 H includes the management of the quality of the
the most demanding applications of monitoring of electrical energy through the Ethernet port (or Wi-Fi). It includes also
parameters and electrical energy management in industrial, functions related to the EN 50160 normative (peaks, dips,
tertiary, commercial and residential sectors. The high interruptions, harmonics) and EN 61000-4-30 for Class S
accuracy class 0.5 S, for Active Energy, according to EN with graphic detail of the event, table and timeline of the
62053-22 and measures of individual harmonics up to 51 events, measurement campaigns with selectable
order are obtained by continuously sampling the waveforms parameters and programmable sampling frequency.
of voltages and currents with a very high resolution, thus The Kilo net PQ is a Power Quality Energy Analyzer & Web
ensuring the maximum accuracy even in the presence of Data Manager, an open platform connected to the Ethernet /
rapidly varying loads in time (.eg. spot welding). The Kilo Internet via Rj45 (or Wi-Fi optional). it represents the
RJ45 H is equipped with a slave Rs485 and an Ethernet starting point for the continuous monitoring of the energy
(Wi-Fi option) port and, depending on the version, with an efficiency through the measurement and management of the
internal module for inputs/outputs or environmental sensors. energy parameters (electricity, gas, water, etc.),
The Kilo RJ45 H is equipped with a 128 MB high capacity environmental parameters (temperature, luminosity, CO2,
memory for implementing, through PUK codes, various etc.) and process parameters. Measures electrical
features. Its architecture allows the firmware upload & parameters and quality of energy, is a Web and FTP Server,
update even remotely. The Kilo RJ45 H is equipped as well and communicates with/manages the other Electrex devices
with an expansion bus, ExpBus, for the connection of digital via the RS485 master port and the ExpBus port.
and analog inputs/outputs, environmental sensors modules
and supports NFC(Near Field Communication). The Wi-Fi option permits to manage/display the data from
any device having a browser (PC, Smartphone, tablet, etc.).

Simplicity
Equipped with a FSTN dot matrix display with high contrast, indicates the functioning state. 2 additional LEDs positioned
back-lighted, white LEDs allowing the simultaneous under the white band report instead the activity on the RS485
displaying of 4 measurements and of their identification port. While for the Rj45 port the 2 built-in LEDs will indicate the
symbol with high visibility characters. Ethernet activity. In order to reduce the energy consumption it
is possible to configure the display's back-lighting, the state
LED and the ones related to the RS485 port.
Versatility
The Kilo D6 and Kilo 96 are suitable for virtually all type of
electrical grid systems, single phase, bi-phase, three phase
3- and 4-wire, symmetrical and asymmetrical, balanced or
unbalanced, LV/MV, with 1, 2 or 3 CTs as well as for 2 and
4 quadrant (import/export) measurement. A simple
configuration from the keyboard (or via our Energy Brain
software) allows to configure all the operating parameters
The 6 keys keypad Joystick positioned and menu list type like network type, CT and VT (if present) ratio, integration
on the display for configuration provide a simple and rational time (1-60m) and alarms (threshold, delay, hysteresis),
use of the instrument, while the default page displayed digital outputs and configuration parameters related to
when powering on is user definable. optional modules connected.
On the front panel 2 calibration and control LEDs pulse with a
frequency proportional to the imported Active and Reactive Conformity with EN 50470 normative
Energy for the on-field calibration with optical devices. The All the versions of the Kilo are compliant with EN 50470-1 +
red LED pulsing under the symbol by the Electrex logo 50470-3 as requested for obtaining the Energy Efficiency
Certificates (White Certificates).

page 1 of 12
Power quality energy analyzer & Wi-Fi web data manager

Measures Harmonics up to the 51-st order


Parameters Type ///Q P(8) Range The Kilo H displays also the single harmonics up to the 51-st
order for the 3 voltages and currents per each phase, 3 active
UL-N  
powers of each phase with the sign (+or-) that denotes the
UL-L   direction of the harmonic. FFT method calculation of the
Voltage UL-N MAX  harmonics, for amplitude and phase.
20,0V...400 kV
UL-L MAX 
Phase sequence
UL-N MIN 
The Kilo H permits the identification of the correct phase
UL-L MIN 
10 mA10,0 kA sequence.
I  
Electrex Flexible CT(7): Ethernet and/or serial via RS485 communication
I MAX 
Current 1A (5A - 500A)
IAVG THERM (1)  4A (20A - 2000A) The Kilo devices are equipped with a 10/100 Base-TX
IMD THERM (1)  8A (40A - 4000A) (RJ45) Auto-MDIX Ethernet port for the http
Power Factor PF   0,00ind..1,00..0,00cap communications (real-time measurements and memory logs)
Frequency F  45 65 Hz and Modbus over IP (real-time measurements). It is
THD-UL-N   equipped also with a serial RS485 port, protected against
Harmonic Distortion THD-UL-L   0199,9% overvoltage, using Modbus-RTU full compliant
THD-I   (instantaneous measurements). The data are read as
P   numerical registers composed by mantissa and exponent in
PAVG (2) 
the IEEE format. The communication speed of the RS485 port
Active Power 0,001999 MW is configurable, up to 115.200bps, with a max. 125 registers
PMD (2) 
requested (equivalent to 62 parameters) with no waiting time
PMAX (3) 
between two requests.
Q IND  
Q CAP   Versions of Kilo D6 and Kilo 96
QAVG IND (2)  0,001999 Mvar x 1DI 2DO Self-Powered: 1 self powered digital input and 2
Reactive Power
QAVG CAP (2)  digital outputs rated at 250V 100mA;
QMD IND (2)  x 2AO 4-20mA: 2 analog self-powered 4-20mA outputs for
QMD CAP (2)  loads up to 250 ohm, power supply needed for higher loads;
S   x 2DI 1RO Self-Powered: 2 self-powered digital inputs and 1
Apparent Power SAVG (2)  0,001999 MVA relay (24VDC);
SMD (2)  x 2RO24VDC: 2 relay outputs (24VDC);
Life Time h, h/100   0,0199.999,99 hours
x 4DI: 4 digital inputs;
Ea IMP (5)  
Active Energy 0,1 kWh100 GWh x 4DO: 4 digital outputs;
Ea EXP (5)  
Er IND IMP (5)   x 2DI 2DO: 2 digital inputs and 2 digital outputs;
Er CAP IMP (5)   x 4AI: 4 analog inputs 010V ( 420mA);
Reactive Energy 0,1 kvarh100 Gvarh
Er IND EXP (5)   x 4PT100 or 4PT1000 or 4NTC for the relative sensors
Er CAP EXP (5)  
x 4SI: for environmental sensors (T, H, L, P, etc);
Es IMP (5)  
Apparent Energy 0,1kVAh100 GVAh Digital Inputs
Es EXP (5)  
Pulse Counter CNT (6)  The versions .. 1DI or 2DI or 4DI are equipped with an
Analog Measure (6) 
optically insulated digital input with programmable filter for
input glitches. The digital input is set to operate for external
For all the "instantaneous measures": mean over 10 cycles - example: 200ms at 50Hz.
(1) Mean value (rolling average) over the integration time (1.. 60 min. program.) and peak pulse count of, example, water meters, gas meters
(MD). (insulation to meet the ATEX requirements), water meters,
(2) Average value (moving average) in both import and export over the integration time (1..60 quantity count, etc. For the 1DI or the 2DI 1RO the max
min programmable) and peak (MD) that is the maximum average value.
(3) Maximum Power values for both import and export.
sampling frequency is 100Hz (5ms), while for the 2DI 2DO
(4) Non resettable total lifetime counter. 4 partial lifetime counters. and the 4DO 500Hz (2ms). Other user selectable operative
(5) Import/Export energies displayed as 9 digits in floating-point readings; internal energy counters are modes are ON/OFF state input (example for reading the
logged with a 64 bit resolution which assures a minimum definition of 0,1 Wh and a max count of 100
GWh
ON/OFF state of machines and switches) and tariff change
(6) Only for versions with digital and analog inputs. input (example for day-night tariff changeover). The digital
(7) With Flexible Electrex CT, accuracy Class 1 for both the devices, within the current ranges input requires an external 10-30Vdc power supply.
denoted above with brackets.
The 1DI 2DO Self-Powered and 2DI 1RO Self-Powered
(8) Three partial counters for each measure marked
versions instead are provided with self powered digital
Kilo H : Single Harmonic
inputs.
Parameters /// Management
Analog Inputs and PT100 or PT1000 or NTC
Harmonics H Voltage  Value (H01), % (H02-H51)
analysis H Current  Value (H01), % (H02-H51) The .. 4AI version is equipped with 4 analog inputs rated at -
(9) FFT method calculation of the harmonics, amplitude and phase, up to the 51-st for the 3 voltages and
1010V (compatible with 010V, 05V, -55V, 420mA at 200
currents per each phase, 3 active powers of each phase with direction (accumulated in 10 periods). ohm). While the .. 4PT100 or 4PT1000 or 4NTC versions have
Kilo PQ: Events U and I, measurement campaign 4 independent inputs for the relative sensors.
Parameters (9) (10) (11) /// Management Environmental Sensors Inputs
Dips and peaks. .  The ..4SI version is equipped with a Sensor Bus I2C for
Events logged in the internal
Overvoltage and overcurrent  memory with time-stamp
connecting up to 4 sensors (up to 4 for the temperature or up
Sags and interruptions  to 1 for the temperature, 1 for the humidity, 1 for the
(10) Event logging with date and time, duration, max/min value. Programmable thresholds. EN 50160 and luminosity and 1 for the air pressure). The max total distance
EN 61000-4-30.
(11) Event's graphic detail: nr. of samples (programmable e.g. 1 second) retrieved previously and after the
of the Sensor Bus is 20 m.
event (dips, peaks and interruptions).
(12) Distribution table of the events based on the threshold exceeded and duration following UNIPEDE
(http://www.eurelectric.org/) and Timeline of the events.
(13) Programmable measurement campaigns (choice of parameters and of the sampling time). See
Memory Management section.

page 2 of 12
Power quality energy analyzer & Wi-Fi web data manager

Relay outputs FCTS 040-500 Flexible split CT, internal


diameter 4 cm
The .. 2DI 1RO Self-Powered and the .. 2RO 24Vdc versions
FCTS 100-1000 Flexible split CT, internal
are equipped with relay outputs with changeover contact rated at diameter 10 cm
max 30V max 2A (resistive load). FCTS 200-2000 Flexible split CT, internal
diameter 20 cm
FCTS 280-4000 Flexible split CT, internal
Digital outputs diameter 28 cm
The .. 2DO or 4DO versions are equipped with two optically
insulated transistor outputs rated 27 Vdc 27 mA according to Load curves and data of consumption / production
DIN 43864 standards. The outputs may be set for the The Kilo H continuously logs the data of consumption /
transmission of pulses or alternatively configured as outputs of production of energy and power by organizing them into
the internal alarms (see Alarms) or as remote output devices separate daily files, containing the data necessary for the
controlled via serial line and Modbus commands. reconstruction of the load profile and the analysis of the trend
The ..1DI 2DO Self-Powered version instead is equipped with of buying/selling of energy (files downloadable via RJ45 port /
two opto-mos outputs rated at max 250V 100mA AC/DC. Ethernet or Wi-Fi using Energy Brain or via Http).

Alarms Astronomical Clock Calendar


The .. 2DO or 4DO or 1RO or 2RO versions are equipped with The Kilo H is equipped with a clock / calendar with
outputs which can be related to the internal alarms. Each alarm astronomical real time management of the Coordinated
can be linked to any one of the parameters available, for Universal Time (UTC). It manages also the rules for the
example, either as a minimum and/or as a maximum. All the automatic switching from Standard Time at summer time
alarm outputs can be linked to the same parameter in order to (Daylight Saving Time) and vice versa. Automatic
have more alarm thresholds. It is possible to set a delay on the synchronization via NTP.
activation / deactivation of each alarm (from 1s to 99 min), the
hysteresis (% of the threshold value) and the polarity of the
output contact (NA, NC, except for the 1RO which is always
NC). The alarms state information is always available on serial
communication as Modbus coils. Due to the numerous
combinations available, only a part of them are programmable by
keyboard while are entirely programmable via serial port with the
Energy Brain software or via serial port using Modbus Holding
registers.

Analog 4-20mA outputs


The .. 2AO4-20mA version is equipped with 2 galvanic insulated
analogue outputs 4-20 mA or 0-20 mA providing an extremely
high accuracy and signal stability. The outputs are active for
resistor loads up to 250 ohm, for higher loads an external power
supply (12Vdc) will be needed (up to 750 ohm). In order to
transform the output in a 0-10V type must be connected in
parallel a 500Ohm resistance. The outputs ensure a response Operating time counter
time of max. 200mS. Each output can be associated to any of The Kilo H is equipped with partial time counters logging
the parameters. the operating time of a load or a machine. The counter can
be triggered from the exceeding of a threshold related to a
measurement or the status change of a digital input.
Wi-Fi, Wi-Fi EDA and NFC (Near Field Communication)
The Wi-Fi and Wi-Fi EDA versions (with a connector for an
external antenna) communicates using the Wi-Fi network
Tariffs TOU
without the need to be connected to an Ethernet cable while the Activating the Calendars and Energy Automation options
presence of NFC opens the possibility for the creation of and configuring the device in a proper way the Kilo H can
specific APPs for mobile devices on the energy management. manage energy tariffs based on a calendar or on the digital
inputs state.
The Kilo F version for Electrex Flexible CTs
The Kilo F H are equipped with current inputs exclusively for
the Electrex Flexible split core current transformers FCTS (mV
output and appropriate internal linearization in order to
maximize measurement accuracy).

WARNING: Do not connect to these current inputs of CT with


output in current (eg. ../1A or ../5A) because it may damage
both the Kilo F D6 and the CT.

Selectable Full Scale independent from the internal diameter of Example of a 3 Tariffs system
the Flex CT used: 500A or 2.000A or 4.000A (8.000A on
request), Class 1 accuracy (overall accuracy: flexible CT + Kilo Firmware and Special versions on request
F) between the full scale of current and its 1/100. Minimum The Kilo H can be provided also with other power supply or
measurable current equal to 1/500 of the full scale. hardware versions and the firmware is upgradeable, remotely,
at any time, in order to add and/or replace the existing
characteristics with new and different functions.

page 3 of 12
Power quality energy analyzer & Wi-Fi web data manager
Expansions via ExpBus
The Kilo H is an evolutionary instrument capable to be ExpBus
adapted to the needs of the customer, even after it has been
installed. The ExpBus, configurable via the Ethernet port from Web
The system architecture is designed to allow the pages:
implementation on the field of hardware expansions thanks x allows a multicast communication to 250kb/sec with
to the ExpBus, providing therefore to the customers the collision management
ability to modulate the investment and / or to respond to new x has a maximum length of 10 meters
needs. x manages up to 16 nodes (modules) but technically it
can manage up to 126
The connecting cable is a UTP where 4 wires are used:
2 for the power supply at 9 Vcc
2 for the bidirectional communication
The modules power the ExpBus
The cable must be connected in the in-out modality (multi-
drop) as for the RS485 Bus.
Each node must have an unique Modbus address
The Kilo D6 H manages up to 16 ExpBus Modules.

UTP cable for the ExpBus (max 10m)


VCC Blue
Exp L White & Blue
Exp H Brown
GND White & Brown

ExpBus Module suitable for the Kilo series


ExpBus Module D2 How to order ExpBus Module
The ExpBus Module D2 must be used with an external power Description Code
supply of 24Vdc (e.g. Switching Power Supply D1 24VDC
400mA code PFTP100-Q2) and can contain up to 2 modules ExpBus Module D2 versions (2 DIN rail modules):
similar to the one shown here at the (of which, however, only Possible hardware combinations with 1 or 2 different modules (of which,
however, only 1 can be a self-powered type, e.g. only one 1DI 2DO Self-
one of the two types can be self powered, Powered or 2AO4-20mA or 2DI 1RO Self Powered module). Requires external
therefore only one for 1DI 2DO Self- power supply 24Vdc:
Powered or 2AO4-20mA or 2DI 1RO Self Switching Power Supply D1 24VDC 400mA..PFTP100-Q2
Powered). Max. weight 45 gr. ExpBus Module D4 versions (4 DIN rail modules):
Configuration via Web interface. Possible hardware combinations with 1 or 2 different modules which can be also
self-powered type.
ExpBus Module D4 Internal power supply 230Vac or other power supplies on
The ExpBus Module D4 have a built-in request, see building code diagram below.
230Vac power supply (24Vdc power BUILDING CODE: .............................. PFAB 4 0 E N 2 P
supply version on request) and can PFAB = External modules
contain up to 2 modules, also self- Dimension in DIN modules: 4 = 4 modules
powered. Max. weight 100 gr. 2 = 2 modules
Configuration via Web interface. Bus Type: ........................... E = ExpBus
Internal modules:........................ Characters for code:
UTP cable for the I2C Sensor Bus (max 20m) No module..............................................................0
VCC Orange Module 1DI 2DO ...................................................1
SCL White Orange Module 2DI 1 RO Self Powered ............................2
SDA Green Module 2RO24VDC ..............................................5
GND White Green Module 2AO4-20mA ..............................................6
Module 2RO230V ..................................................8
Module 1DI 2DO Self Powered ............................. E
Module 4DI ........................................................... N
ExpBus Module catalog codes Module 4DO ......................................................... P
Type Code Module 2DI 2DO ..................................................Q
Module 4AI ........................................................... R
2
ExpBus Module D2 24VDC 4DI 4DO .................. PFAB20E-N5P Module 4SI (Sensor Bus I C) ................................ T
ExpBus Mod. D2 24VDC 2DI 2DO 2AO4-20mA.. PFAB20E-Q56 Module 4PT100..................................................... U
ExpBus Mod. D2 24VDC 4AI 2DI 2DO ................PFAB20E-R5Q Module 4PT1000................................................... X
ExpBus Mod. D2 24VDC 4SI 2DI 2DO ................ PFAB20E-T5Q Module 4NTC ........................................................ Y
ExpBus Mod. D4 230V 4DI 4DO ......................... PFAB40E-N2P Power Supply:
ExpBus Mod. D4 230V 2DI 2DO 2AO4-20mA..... PFAB40E-Q26 24Vdc +/- 10% only for Module D2 .......................5
230Vac +/- 10% only for Module D4 .....................2
ExpBus Mod. D4 230V 4AI 2DI 2DO ...................PFAB40E-R2Q
15y36Vac/18y60Vdc only for Module D4..............8
ExpBus Mod. D4 230V 4SI 2DI 2DO ................... PFAB40E-T2Q
9y24Vac/ 9y36Vdc only for Module D4................7

page 4 of 12
Power quality energy analyzer & Wi-Fi web data manager

Memory management (via Ethernet port or Wi-Fi)


The Kilo H family of devices manages the 128 MB flash memory in a flexible way for the storing of the different log services and
event logs. Each log service can contain a maximum of 255 files and is characterized by a predetermined sampling frequency;
The number of channels (e.g. instruments) that can be stored for each service depends on the activated PUKs and the amount of
free memory. In the same memory are hosted also the web pages for the configuration and display of measures (standard and
customized). It is possible to upgrade from the Kilo H to Kilo PQ purchasing the relative Upgrade (PUK) Code PFSU940-81. In
the Kilo PQ version the memory is also used for log of events and for the measurement campaigns The memory can be read
from Ethernet port or Wi-Fi network using the Energy Brain software and / or the HTTP protocol.
LOGGED PARAMETERS CHARTS EVENT'S GRAPHIC DETAIL (KILO NET WEB)
The Kilo RJ45 H continuously logs the data on the In the Kilo net PQ Web Charts in addition to the listo f PQ
consumption/production in daily files containing by default the events displayed in the web interface (available on the Kilo
96 quarters of hour. The data logged can be displayed using net PQ Web)
the software Energy Brain on a daily, weekly, monthly and
yearly basis.

it is included also the functionality named "event's graphic


detail" that allows to record and display the trends of the
beginning and end of the event with a time frame (for both
beginning and end) of a second (programmable).

POWER QUALITY (Class S - EN 61000-4-30): Events Log


The Kilo Rj45 PQ detects and logs various events with a
resolution of one cycle (with date / time * of each event, type of
event, phase involved, duration, min / max value reached
during the event and UNIPEDE classification) useful for
monitoring the quality of energy (functions related also to the
EN 50160 and EN 61000-4-30 standards for the S class). The
parameters for defining abnormal events are programmable.
Event types:
x Voltage Dip
x Voltage Swell
x Over current and its direction
x Interruption

(*) Date/hour expressed in hours, minutes, seconds and milliseconds


referring to the instruments' (local time).

page 5 of 12
Power quality energy analyzer & Wi-Fi web data manager

EVENTS TIMELINE AND THE UNIPEDE TABLE MEASUREMENT CAMPAIGN


The Kilo net PQ Web Charts can display a timeline of the In the Kilo PQ it is possible to configure the measurement
succession of events campaign in order to log, in the built-in memory, the various
parameters with a programmable sampling rate, for example
every 2 min. for 60 days (FIFO) in daily files. The data can be
displayed using Energy Brain software.
Example of a daily measurement campaign of the 3 currents:

With the Kilo net PQ Web Charts it is possible to display on


the web interface the measurement campaigns.
Example of a daily measurement campaign of the 3 voltages
every 15 seconds:

and maintains a diagram of distribution of events based on


the % of the parameter considered in relation to its reference
value and duration, according to the dictates of UNIPEDE
(International Union of Producers and Distributors of Energy -
http://www.eurelectric.org/).

Example: in the last column of the table here below , the S1


denotes a Voltage Swell with a duration between 10 and 500
mS (refer to the UNIPEDE table above),while the X2 denotes a
Voltage Dip lower than 5% of the nominal voltage value with a
duration between the 10 and 200 mS (refer to the UNIPEDE
table above).
FUNCTIONAL LOG
The instrument's memory is used also for other operative
functions such as:
x Functional log for the recording of all the operations that alter
the functioning of the instrument since the first use.
x Tariff Calendar file for the management of the tariffs and
other files for memory configuration.

Considering the quantity and the complexity of the data contained in


the memory, the memory management and the configuration of the
services can be made exclusively via Ethernet port or Wi-Fi using
FTP and HTTP commands, more simply by using Web pages and/or
the software Energy Brain.

page 6 of 12
Power quality energy analyzer & Wi-Fi web data manager

Power Quality Energy Analyzer & (Wi-Fi) Web Data Manager


Kilo net main features Additional functions activated via PUK code
The Kilo net PQ Web in addition to the features of the Kilo PQ It is possible to implement the following functions on the Kilo
already included, is also a: WEB Server used for the net ordering the Net upgrade options which are PUK codes to
configuration, via WEB Browser, of the Kilo Net and of the other be inserted in a Web page for the activation.
devices in the sub-network. The HTTP communication can be Enabled - Net upgrade WEB (PUK) PFSU940-05
used for the instantaneous readings and for accessing the Enables the display of measures on web pages for the Kilo Net
memory logs. It is also an FTP server for file transmissions; itself and each instrument connected to its RS485 port.
Modbus-TCP Server acting as a bridge between the Ethernet 2 x Enabled - Net upgrade Log 8 (PUK) PFSU940-01
network (Modbus-TCP protocol for the instantaneous Each Log 8 enables 1 logging service (e.g. log of 8
measures) and the RS485 port; Arbiter function between the instruments/Modbus registers, power / energy just in import).
Ethernet port (or Wi-Fi) and the expansion bus ExpBus (if other It is possible to activate up to 8 upgrade Log 8 (and then
interfaces are used); Synchronization of the internal clock is double those from Log 8 to Log 16 purchasing a PUK Log 16).
made via NTP server; Static or dynamic IP address (DHCP Net upgrade Log 16 (PUK) PFSU940-02
protocol). Doubles the capacity of the storage services from Log 8 to Log
The Kilo net PQ Web can record the trend over time of the 16. The Net upgrade Log 8 (PUK) code PFSU940-01 must
energy/environmental parameters retrieved by the Electrex have been installed previously.
devices (called also channels) connected in its RS485 port. The
1 x Enabled-Net upgrade Open Log(PUK) PFSU940-25
Kilo net has by default 2 active Log 8 storage services of which
a service for storing energy/environmental parameters typically Allows to modify the sampling frequency and the choice of
every quarter hour (with daily, weekly, monthly or yearly display parameters to be logged for an existing Log 8 service for e.g.
options) and one for the measurement campaigns (see Open when performing a measurement campaigns. The sampling
Log PUK). Each service is characterized by the same time duration will depend on the sampling frequency set (minimum
base (sampling rate). 5 or 10mS) and the number of parameters selected. The Log 8
services to be modified must already be active and if, for
example, it is needed to modify two Log 8 services, it is
necessary to activate two PUK Open Log. By default is
enabled one Open Log option for the measurement campaign,
logging every 2 minutes for 10 days of the 3 x voltages and
currents, both THD and the single Harmonics of the 1, 3, 5,
7 and 9 order.
Net upgrade Open WEB (PUK) PFSU940-10
Adds to the Kilo net the ability to upload and display custom
Web pages.
Net upgrade Charts (PUK) PFSU940-30
Allows to display on a web page charts, related to a
programmable period of time, of electricity, temperature,
humidity, luminosity, etc. obtained from the files stored in the
Kilo net with the possibility to export to CSV files.
Net upgrade Energy Automation (PUK) PFSU940-16
Adds the ability to manage Energy Automation tasks using the
Ladder programming language for implementing ON/OFF
switches, alarm and notifications and automations related to
events and/or calendars (the Calendars option must be active)
and/or the sending of e-mail/sms (E-Mail / SMS option must be
active).
Net upgrade Calendars (PUK) PFSU940-20
Allows to create calendars to be used for the time tariffs and /
or in combination with the Energy Automation option (if active).
Net upgrade eMail PFSU940-15 (& Sms PFSU940-17)
Adds the function of sending notification / alarm emails (and/or
SMS by adding a specific modem/router). It can also be used
in combination with the Energy Automation option (if active).
Net upgrade Sending Files PFSU940-50
Adds the function of sending / pushing and save into a remote
FTP server an Xml file (customizable on request.
Net Upgrade Kilo PQ to Kilo Net (PUK) PFSU940-82
Transforms the Kilo RJ45 PQ in Kilo net PQ Web. Net upgrade Net to Net Master (PUK)
Transforms the Kilo in Kilo net Master which is able to
Net upgrade New Features PFSU940-40 communicate with all the Electrex in the Ethernet network and
Upgrade to new versions of the firmware of the Kilo Net adding their relative sub-nodes.
new features.

page 7 of 12
Power quality energy analyzer & Wi-Fi web data manager

Production plant energy monitoring solution example


The diagram above represents a part of a monitoring solution in - Since the position of the Transformer 3 was distant from
a production plant powered by a main MV load and equipped the Ethernet nodes, for branch 3 has been used a Yocto
with 3 MV/LV transformers (one of them replaced recently). The net Web D6 (gateway datalogger). Connected to it via
3 MV transformers serve the 3 production lines, while the offices Rs485 has been installed the Exa F Rs485 with flexible
are powered by a LV system. The monitoring system consists of split CT (easier to be mounted) and an Exa D6 MID used to
branch 1, 2 and 3 for monitoring the transformers and part of the monitor the energy used in a galvanic process for tax
production lines while branch 4 and 5 controls the offices area. deduction purposes;
The branches are connected to the internal LAN Ethernet - In branch 4 has been inserted an Yocto net Coordinator E-
network via: Exa net D6 (branch 1), Yocto net D6 Web (branch Wi serving as a gateway and datalogger for a Deca Sensor
3), Yocto net Coordinator E-Wi EDA (branch 4) and via Wi-Fi E-Wi that monitors environmental parameters in the
Kilo net Wi-Fi 96 (branch 2) and Femto ECT net Wi-Fi EDA D6 laboratory.
(branch 5). The various instruments and sensors connected in - Branch 5 monitors both sides , DC load and AC load
the 5 branches monitor and control the principal loads. (Femto D4 and Atto D4 DC), of a PV system of 10 kWp
- In branch 1 the Exa net D6 (gateway and datalogger) and placed on the offices building roof.
the Exa RS485 96 connected to the RS485 port of Exa net In the same monitoring network has been installed also a Yocto
monitor two compressors while the Yocto I-O counts the Net Web D6 Master, branch 6, were are hosted customized web
gas, water and compressed air consumptions. The RS485 pages for the supervision of the system used from the plant
Module is connected to analog sensors previously installed. managers via PC, tablet, smart-phone. On the same device has
- In branch 2 for the monitoring of Power Quality and energy been activated also the Alert and Notification option which sends
consumption the Kilo net Wi-Fi EDA 96 (gateway and e-mails to the maintenance team in case of anomalies.
datalogger) has been placed under Transformer 1 while the While for monitoring the R&D building which is separated distant
X3M D6 H under Transformer 2. The ExpBus module from the production plant has been used a Libra (quick and
connected to the Kilo net is used for alarms and pulse easy installation via connectors), branch 7.
counting while the Exa TR connected to the RS485 port is The Energy Manager instead uses its laptop, for local or remote
one of the various transducers used for monitoring the connections via Ethernet / Internet, in order to control the
production machines. The Femto D4 70A ECT instead is effectiveness of the energy efficiency solutions analyzing the
used for the monitoring of an areas served by LED lighting data downloaded periodically from the software Energy Brain
systems. In the Kilo net has been activated the Energy PRO. Recently he has involved in the Energy Management
Automation option in order to automate the switching of System also his colleagues displaying energy related data on
various loads commanding the digital outputs built-in the the Energy Brain Cloud platform with specific dashboards per
Exa TR. each user / department.
page 8 of 12
Power quality energy analyzer & Wi-Fi web data manager

Examples of standard web pages PFSU940-05


The Net upgrade WEB option, enabled by default it is possible to view the
standard web pages displaying real-time measurements from the Kilo net D6
Web and the devices connected via Rs485. The images on the side show real-
time measurements, the average values and the energy counters related to a
laboratory building with offices.

Examples of custom web pages PFSU940-10


Enabling the Net upgrade WEB and the Net upgrade WEB open
functionalities it is possible to activate a memory part in the memory of
the Kilo Net Web where can be uploaded custom web pages. Alongside
are reported an example of real time monitoring of the electricity, gas and
water of a production plant with the possibility of setting thresholds and
alarms. The main page is linked to second level pages for more details
on each load/monitoring point. The pages residing on the web server of
the Kilo Net are easily accessible from any the browser of a PC,
Smartphone, etc., typing just the IP address.

Web charts examples PFSU940-30


Enabling the Net upgrade Charts option in the Yocto Net D6 it
is possible to display on a web page, charts obtained from the
files stored in the same Kilo Net log system with the possibility
to export to CSV files. In the example, the chart shows the load
profile every 15 min. of active energy produced and consumed
from PV system.

Measurement campaign example PFSU940-25


Enabling the Net upgrade Open Log option related to an existing Log 8
logging service of the Kilo net log it is possible to implement measurement
campaigns for any parameter retrieved from Electrex devices connect to it with
any sampling frequency. In the example it is shown the measures campaign
for the 3 phase-currents
and 3 phase-voltages
logged every 2 minutes.

Energy Automation PFSU940-16


Enabling the Net upgrade Energy Automation option it is possible to
automate even complex operations such as power on / off, alarms / alerts
and operations triggered by events. The programming of the logic is in
Ladder language. It is possible to combine the programming features also
with customized calendars (if implemented Upgrade Calendars option) and /
or with the sending of e-mail / SMS (if implemented Upgrade E-Mail / SMS
option).
Upgrade Calendars PFSU940-20
Enabling the Upgrade Calendars option it is possible to configure Calendars to be
used for e.g. for tariffs and/or combined with the Energy Automation option for
scheduled tasks of power ON/OFF. The astronomic type clock is synchronized via
NTP server (connection via Internet or to an internal LAN one).

E-mail alarms/notifications
examples (Sms PFSU940-17)
Enabling the Upgrade E-Mail / SMS it is possible to configure the Kilo net Web to
send email alarms and notifications for example related to the status of a digital
input. If connected to a suitable external router it is possible to send also SMS. The
example images show the e-mail alarm of a load in a bakery and the graphical
status display in the specific web page of Kilo net Web.

page 9 of 12
Power quality energy analyzer & Wi-Fi web data manager
Net upgrade Net to Master Version PFSU940-86
Implementing this option the Kilo net Web becomes a Master
device capable of communicating with all the Electrex gateways
and devices connected to the same Ethernet network (LAN or
WAN). The option is very useful in case of customized web pages
displaying measurements/alarm status from different nodes of the
network or when a single public IP address is given for a multitude of gateways present in the network.

Technical Specifications Kilo Front panel


Measurements Display ...........................LCD, FSTN dot-matrix 128 x 64 points
Voltage ...................U1-N, U2-N, U3-N, U1-2, U2-3, U3-1, U//, U/1 Visible area........................................................................22 x 44 mm
Max (ABSOLUTE VALUE): .. UL1-N, UL2-N, UL3-N, UL1-L2, UL2-L3, UL3-L1 Backlight ..................................................................White Led
Min (ABSOLUTE VALUE): UL1-N, UL2-N, UL3-N, UL1-L2, UL2-L3, UL3-L1 Keyboard ............................ 6 keys keypad Joystick positioned
Current .......................................................... I1, I2, I3, I, Ineutral On the front panel:
Max (ABSOLUTE VALUE):......................................... I1, I2, I3 Calibration LED ................................... 2 red for the Ea and Er
Therm: ............................................................ I1, I2, I3 Functioning / State LED ................. 1 red under the symbol
Power Factor ..............................................PF1, PF2, PF3, PF Communication RS485 LED1 green and 1 red under the white band
Frequency ...............................................................................f
Voltage THD .................... THD-U1, THD-U2, THD-U3, THD-U Functional characteristics
Current THD ........................ THD-I1, THD-I2, THD-I3, THD-I Measurement.....................True-RMS up to the 51st harmonic
Instantaneous Power ... P1,P2,P3,P - Q1,Q2,Q3,Q - S1,S2,S3,S Quadrants ................................ 2 or 4 quadrants (programmable)
Average Power ....... 3P4P LQG 4P FDS 6P LPSH[S  Accuracy: .......... Class 0.5S for Active Energy - EN 62053-22
3P4P LQG 4P FDS 6P LPSH[S Class C according to EN 50470-3
Powers peak .........3PG4PG LQG 4PG FDS 6PG LPSH[S Class 2 for Reactive Energy - EN 62053-23
Active Energy (also per each phase) ..........Ea (import/export) Sampling: Continuous sampling of voltage and current waveforms
Reactive Energy (also per each ph.) Er(ind/cap)(import/export) Compensation ........................... Automatic of the amplifiers' offsets
Apparent Energy (also per each phase) ..... Es (import/export)
Scale Change: ............................... Automatic on the current inputs
Life Time TOTAL and 3 PARTIALS: ......................................... h, h/100
Pulse counting (per each digital input): ..................CNT T, CNT Part. (highest resolution)
Analog measure(per each analog input): .............Instantaneous Insulation .......................Galvanic on all the inputs and outputs
Harmonics (FFT) ....... ....................HU1, HU2, HU3 (1-51 order) Standards: - Safety: ............... IEC EN 61010 class 2
H I1 , H I2 , H I3 (1-51 order) - E.M.C.: ..................... IEC EN 61326-1A
Harmonics power and direction (1-51 order) Mechanical characteristics
Load profile and consumption/production (via Ethernet port)
Tariff calendar Working temperature ...............................................-20/+60 C
Logged Events (Kilo Q - EN 50160 and EN 61000-4-30): Humidity.......................................... 95% R.H. non condensing
Voltage Dip (sags/dips) Enclosure.......Self-extinguishing plastic material class UL 94 V-0
Voltage swell and peaks Protection degree ....... Front panel IP40 IP20 (Terminals side)
Current peaks and direction Size.................................................................. 6 DIN modules
Interruptions Mounting ....................................................................... DIN rail
2
Overvoltage/Undervoltage Terminals: ...... screw connector cables max. section up to 4 mm
Overcurrent and direction Weight ...........................................................about 260 gr. net
Event classification
Functional logs - Harmonics measurement (Kilo PQ)
Electrical characteristics
Connection ...........3-phase, 1-phase and 2-phase, LV,MV,HV
balanced, unbalanced, 3- and 4-wires
Voltage inputs ........................from 20 to 500V phase-phase
(max. 1,7 crest factor)
With external VT (max. 400 kV primar.)
VT value: programmable
Overload ..... max, 900 Vrms peak per 1 sec.
Current Inputs .......................................... 1, 2 or 3 CT external
max. 10kA primary .../1A and ../5A secondary Size Kilo 96.................................................... 96 x 96 x 78 mm
CT value: programmable Panel cutout........................................................... 92 x 92 mm
Overload .... max, 100 Arms peak per 1 sec.. 2
Terminals: ....plug-in connector cables max. section up to 4 mm
Load on the CT ................................. < 0,5 VA Weight ........................................................... circa. 260 gr. net
For the Kilo F Net versions suitable with Electrex flexible CT:
max. 500/2000/8000A primary .../mV secondary
Power supply ...................................85y265 Vac/100y374 Vdc
or others on request e.g. 15y40 Vac/18y60 Vdc
or 9y24 Vac/ 9y36 Vdc
Power supply toward other modules, max:5 VA
Self consumption< 2 W
Frequency: 45-65 Hz

page 10 of 12
Power quality energy analyzer & Wi-Fi web data manager

The Energy Brain 6.x and PRO 6.x software (to be installed on a PC, optional)
The Energy Brain software is uesd for the Connections between PC and Kilo
management of instrument networks, also direct Ethernet Rj45 port, Wi-Fi, Ethernet network, Internet
very complex ones, both locally or remotely.
It is suitable for applications with Electrex
instruments equipped with a
communication port, and provides all the
necessary functions for monitoring and
accurate management of energy efficiency (consumption /
production of electricity, gas, water, etc..), environmental
parameters (temperature, humidity, luminosity, CO2, etc.)
and process parameters.
Main features
Configuration
x The available options allow for maximum flexibility in
adapting the software to the network instruments (even to
different types of networks connected simultaneously) and
the operator needs.
- Remote set-up of the devices (CT, alarms, etc.) Specific functions for Kilo PQ
- Network configuration (per each device, per each client,
per groups, per locations) with individual setting of the x Downloads, logs and displays the events recorded in the
local connection (direct RS485, E-Wi, Ethernet) or remote internal memory of the Kilo PQ in compliance with EN
(Internet, Wi-Fi) and of the communication parameters 50160 and EN 61000-4-30.
(speed, etc.). Graphical display of the instantaneous measures
- Configuration of scheduled downloading
x Manages the charts for the Kilo devices.
specific for each location and customer, on
a daily, weekly or monthly basis through a
programmable agenda. Wave form
Load chart and curves of consumption/production
x Charts of the daily, weekly, monthly, yearly power curves. Bar charts
x Charts of the daily, weekly, monthly, yearly
consumption curves.
x Charts of powers, power peaks and energy
per each tariff.
x Up to 4 simultaneous charts.
x Zoom and selection of measures functions.
x Numerical and graphical data print.
Parameters displaying
x Displays on-line all the measures provided
by each of the instruments on the field Vectorial charts

Data archive Harmonics measurement campaign and other parameters


x Automatic or manual download of the data
of power, energy and other variables from x It is possible to configure a measurement campaign, e.g.
the devices connected and automatic with a sampling frequency of 2 min. and date/time stamp
archiving in the internal database for different parameters, for a period of 10 days.
(Access,PostgresSQL or MySQL).
x Export data to other DB via ODBC module
or .txt or .xls format files.
Tariffs
x Management of the data per each tariff
x Configuration Editor for tariffs and calendars
Virtual and Multiple Channels
x Creating virtual channels, so of "groups" of
instruments (e.g. "summation" of various
departments) and display those, on
graphical form, in the same way of a physical channel
x Creation of multiple channels in order to view curves of
more instruments in the same chart for a quick comparison.
The software Energy Brain PRO 6.x
x Inclusion of variables and mathematical formulas, even
highly complex ones, particularly useful, for example, to x For more info on the additional functions found in the PRO
perform simulations. 6.x version please refer to the Energy Brain software
Other types of Energies / Measurements datasheet.
x Creating charts of data obtained from Electrex Deca Energy Brain software is expandable and it is available
Sensors and / or third party transducers with pulse output in different versions according to the functions and the
(e.g. luminosity, temperature, gas, calories, etc.). number of channels required. For more details about
the software: www.electrex.it/en

page 11 of 12
Power quality energy analyzer & Wi-Fi web data manager

How to order Kilo D6 and Kilo 96


Other versions of Kilo D6 and Kilo 96
Description Code
CODE P F N K -
Kilo RJ45 D6 H 85265V 2DI 2DO ...........PFNK6-1H7Q9-0M0
The Kilo RJ45 H or Kilo F RJ45 H can evolve in Kilo RJ45 PQ o Kilo F RJ45 Description Code
PQ by activating the following Upgrade (PUK):
BUILDING CODE ..................PFN K 6 - 1 Q 5 Q 9 - 1 2 1
Upgrade H to PQ version..................................... PFSU940-81
Kilo RJ45 D6 PQ 85265V 2DI 2DO .......PFNK6-1Q7Q9-0MM Family Kilo = K
The Kilo RJ45 PQ or Kilo F RJ45 PQ can evolve in Kilo Net PQ Web o Kilo Dimension 6 modules DIN = 6
F Net PQ Web by activating the following Upgrade (PUK): Flush mount 96x96 = 9
Upgrade RJ45 PQ to Net PQ Web version ......... PFSU940-82
Current Input ../5A & ../1A = 1
Kilo net D6 PQ Web Log 16 85265V 2DI 2DO ....................... Flexible Split Core CT = F
.................................................................. PFNK6-1Q5Q9-121
The Kilo Net PQ Web or Kilo F Net PQ Web can evolve in Kilo Net Master Displaying the single harmonics = H
PQ Web o Kilo F Net Master PQ Web by activating the following Net Upgrade Power Quality ................................ = Q
(PUK):
Communication ........................................................
Net Upgrade Net to Master version .................... PFSU940-86
RJ45 ................................................. 7
Kilo net D6 PQ Web Log 16 Charts 85265V 2DI 2DO ........... Net .................................................... 5
.................................................................. PFNK6-1Q5Q9-A21 Wi-Fi ................................................. W
Kilo net D6 PQ Web Log 16 Full 85265V 2DI 2DO ................ Wi-Fi EDA ..........................................A
................................................................. PFNK6-1Q5Q9-F21
Internal module .....................................................
Kilo net Wi-Fi EDA D6 PQ Web Log 16 85265V 2DI 2DO .....
Module 2DI 1 RO Self Powered ........ 2
.................................................................. PFNK6-1QAQ9-121
Module 2RO24VDC .......................... 5
Kilo net D6 PQ Web Log 16 1860VDC 2DI 2DO ................... Module 2AO4-20mA ......................... 6
................................................................. PFNK6-1Q5Q8-121 Module 1DI 2DO Self Powered.......... E
Kilo net D6 PQ Web Log 16 85265V 4DO PFNK6-1Q5P9-121 Module 4DI .......................................N
EB 8 6.x Kit Kilo Net D6 PQ Web Log 16 Charts 2DI 2DO ....... Module 4DO ...................................... P
........................................................................... PFAK614-116 Module 2DI 2DO ...............................Q
EB PRO 8 6.x Kit Kilo Net D6 PQ Web Log16 Charts 2DI 2DO Module 4AI ........................................R
Module 4SI (Sensor Bus I2C) ........... T
......................................................................... PFAKP614-116
Module 4PT100 ................................U
The sequence of codes listed above is repeated for the Kilo F D6 (F - the 7th
digit of the code), the Kilo 96 (9 - the 5th digit of the code) and the Kilo F 96 (9 Module 4PT1000 .............................. X
- the 5th digit of the code and F - the 7th digit of the code), the same for the EB Module 4NTC .................................... Y
8 6.X Kit while for the EB PRO 8 6.X Kit will change the 6th and the 8th digit.
For e.g.:
Power supply: .......................................................
Kilo F RJ45 96 H 85265V 2DI 2DO ....... PFNK9-FH7Q9-0M0
85265Vac/100374Vdc.................... 9
The Kilo Net and Kilo F Net can implement additional features in subsequent
times after the purchase by activating the following Net upgrade (PUK):
1540Vac/1860Vdc ......................... 8
Net Upgrade Log 8 (PUK) .................................................PFSU940-01 924Vac/936Vdc ............................. 7
Net Upgrade Log 16 (PUK) ...............................................PFSU940-02 NOT Master version ...............................................-
Net Upgrade Open Web (PUK) .........................................PFSU940-10 Master .................................................................. M
Net Upgrade Charts (PUK)................................................PFSU940-30 Additional functionality: ..................................................................
Net Upgrade Open Log (PUK) ..........................................PFSU940-25 No additional functionality ..................................... 0
Net Upgrade Energy Automation (PUK) ...........................PFSU940-16 Functionality Web ................................................. 1
Net Upgrade eMail (PUK) .................................................PFSU940-15 Functionality Web Charts...................................... A
Net Upgrade Sms (PUK) ..................................................PFSU940-15 Functionality Web Energy Automation................... 5
Net Upgrade Calendars (PUK) .........................................PFSU940-20 Functionality Web eMail......................................... 7
Net Up. Bundle En. Autom., Calendars, eMail (PUK) .......PFSU940-22 Functionality Web Calendars ................................. 8
Net Up.Bundle En.Autom., Calendars, eMail, Sms (PUK) PFSU940-23 Fun. Web Energy Automation eMail Calendars ..... 9
Net Upgrade Sending Files (PUK) ...................................PFSU940-20
Fun. Web Full (Charts Autom. eMail Calendars) ...F
Functionality Open Web ........................................ 2
Net Upgrade New Features (PUK)....................................PFSU940-50
Functionality Open Web Charts ............................ C
Upgrade H to PQ version (PUK) .......................................PFSU940-81
Fun. Open Web Automation eMail Calendars....... B
Upgrade RJ45 PQ to Net PQ Web version (PUK) ........... PFSU940-82 Functionality Open Web Full ................................ D
Net Upgrade Net to Master version (PUK) ...................... PFSU940-86
Log service for the internal analyzer ......... M
Flexible Current Transformers Codes Net: N. of active Log 8 services ............1 - 8
Log 8 services doubled to Log 16 ......9
FCTS 040-500 Flex Split Current Transformer .........PFCF005
FCTS 100-1000 Flex Split Current Transformer ...... PFCF002 Open Log for the internal analyzer............ M
Net: N. of active Open Log ....................1 - 8
FCTS 200-2000 Flex Split Current Transformer ...... PFCF003
FCTS 280-4000 Flex Split Current Transformer ...... PFCF004
Subject to modification without prior notice Datasheet Kilo D6 e Kilo 96 2016 10 18-ENG

Distributor

Electrex is a brand of Akse srl


Via Aldo Moro, 39 - 42124 Reggio Emilia (RE) - Italy
Tel : +39 0522 924244 - Fax : +39 0522 924245
www.electrex.it - email: info@electrex.it

page 12 of 12
SPLI T C T
SPLIT-CORE CURRENT TRANSFORMERS
WITH PATENTED FAST SNAP-ON SYSTEM

Description
The new SPLIT CT current transformers
feature an innovative fast snap-on system. Main features
The CT opens simply by pressing the release
button while a slight pressure ensures a robust
x Wide primary range (100 - 2500 A)
5 A secondary and compact size
and safe CT re-closing achieving a perfect
matching of the magnetic circuit. x 1% accuracy class
The SPLIT CTs are suitable for application on x Low-loss high-linearity magnetic core
power busbars (by means of the multipoint x Patented quick snap-on closing system
insulated fixing screws) as well as directly on (screw-free).
any power cable.
The current transformers of the SPLIT CT range drastically reduce the
x Multi-point insulated busbar fixing
installation costs, eliminating, at the same time, all the contracting x Built-in fixing lugs
complications. x Protected easy-access terminals
The use of the SPLIT CTs is easy, economical and competitive. x Competitive pricing
Models and ratings x Cost effective installation
Type Rating (Amp) Burden (VA) Weight (kg) Size (mm)
CTS 23-100 100 / 5 1,25 0,85
CTS 23-150 150 / 5 1,5 0,85
CTS 23-200 200 / 5 1,5 0,85
CTS 23-250 250 / 5 1,5 0,85
CTS 23-300 300 / 5 3,75 0,85
CTS 23-400 400 / 5 5 0,85
CTS 58-250 250 / 5 1,5 1,08
CTS 58-300 300 / 5 2,5 1,08
CTS 58-400 400 / 5 2.5 1,08
CTS 58-500 500 / 5 5 1,08
CTS 58-600 600 / 5 5 1,08
CTS 58-750 750 / 5 5 1,08
CTS 58-800 800 / 5 7,5 1,08
CTS 58-1000 1000 / 5 10 1,08
CTS 812-250 250 / 5 1,5 1,35
CTS 812-300 300 / 5 2,5 1,35 Type A B C C1 D E
CTS 812-400 400 / 5 2,5 1,35 CTS 23 93 106 34 58 20 30
CTS 812-500 500 / 5 5 1,35 CTS 58 125 158 34 58 50 80
CTS 812-600 600 / 5 5 1,35
CTS 812-750 750 / 5 5 1,35 CTS 812 155 198 34 58 80 120
CTS 812-800 800 / 5 7 1,35 CTS816 195 243 64 79 80 160
CTS 812-1000 1000 / 5 10 1,35
CTS 812-1200 1200 / 5 10 1,35
CTS 812-1250 1250 / 5 15 1,35 Technical specifications
CTS 812-1500 1500 / 5 15 1,35 Operating frequency ......................50 60 Hz
CTS 816-2000 2000 / 5 10 1,35 Max. system voltage ............................0.72kV
CTS 816-2500 2500 / 5 15 1,35 Rated insulation level.......3kV/1 min. @ 50 Hz
Insulation class ........................E (max 75 C)
Short-time
Subject to modification current
without rating............I
prior notice th = CT
Datasheet Split 60 2009-10-06
In / 1 s Eng

Distributor

Electrex is a brand of Akse srl


Via Aldo Moro, 39 - 42124 Reggio Emilia (RE) - Italy
Tel : +39 0522 924244 - Fax : +39 0522 924245
www.electrex.it - email: info@electrex.it
NG-9
New Generation analyzer, 9 lines measured by a single device
The world smallest analyzer featuring 9 channels within only 9 cm
Flexibility: Special probes from 1 to 2000 A offer the highest exibilty on the market.
Accuracy: 0,5 class on the entire measure chain.
Measurements: 160 parametres on LCD display and, on your own device, via Modbus-RTU.
Versatility: Possibility of using all range of Rogowski Coils or Split Current Sensors on each instrument
on either single, three or mixed phase mode.

It does not exist anything like our NG-9 to compare to.

NG9 is an innovative metering solution, unique on the market. It offers exibility and simplicity by
reducing product and installation costs compared to other devices on the market.

Reduced Size: The world smallest analyzer Settings: set manually or by software
` 9 channels within only 88x90x60 mm (5 DIN modules). ` Smart system 1 key joystick conguration.
` Easy to t in pre-existing panels. ` Set by NG software that permits simple and fast programming.
` New panels can be up to 67% smaller. ` Disaster Recovery Feature: every conguration is saved and shared
with Energy Team Assistance Service.
Installation: NG-9 reduces space, time and costs to increase
simplicity Efciency and High Performance: NG-9 the most efcient
` Set sizes and most suitable solutions to get extremely precise metering system on the market
measurements. ` Power consumption 12 times less than any other device on the market.
` Appropriate extensions allow a distance from the device up to 10 m. ` Modbus RTU communication speed 3 times faster than other
` Reduction of installation errors to allow a simple and correct start up. analyzers: 115200 baud rate
` Each current sensor can be connected to the device with a ` Auxiliary power supply 90 to 250 VAC or 24 to 1210 VDC
one-way electrical connector without using additional cables, ` Test voltage:3,7 kV, double than other analyzers
scissors and screwdrivers. Installation costs reduced by 85% and (less electrical disturbances and more safety).
no need for plants shutdown.
Graphics: NG-9 160 electrical parametres on the display
Flexibility: NG-9 the highest versatility on the market ` 160 parametres on LCD display and, on your own device,
` Only set sizes and most suitable solutions to get extremely precise via RTU-Modbus.
measurements: 1 to 2000A with 2m long cables and extensions ` Simple and immediate information: possibility to label each channel
up to 10m. by software.
` Possibility of using all range of Rogowski Coils or Split Current ` All measures displayed by using joystick
Sensors on each instrument on either single, three or mixed phase ` Graphic display with RGB led background.
mode.
Versatility: NG-9 anywhere its needed
Accuracy: NG-9 0,5 class on the entire measure chain ` Different elds of application: ofces, warehouses, retail centres,
` Device and sensors tested and calibrated to guarantee the stated small and large factories, data centres and many more.
accuracy. ` Different nal users: Energy Managers, Maintenance and
` Calibration certicate available for each instrument and related Production Managers, Energy Consulting Companies, ESCo,
sensor. Energy Certications (Diagnose, Audit).

NG-9 less time-consuming, reduces installation cost and avoids plant shutdowns
100 A

40 A

10 A
Connection sample: 2 three-phase, 3 mono-phase

200 A

ration:
y o u r congu
Choose s
ms
e syste phase
-p ha
2000 A 3 three se, 3 si
ngle-
ha se
2 three-p
, 6 single-pha
-phase
1 three se syste
ms
-p h a
* 9 single
*

* On demand: Internal Diameter


200 mm up to 8000A

Technical features General


Inputs The device allows AC or DC supply voltage
Auxiliary power supply in the limits specied below
Each voltage input can be matched with a AC supply voltage range 90 - 250 Vac 50/60 Hz
Voltage current channel to allow any type of three
or single phase measurement DC supply voltage range 24- 120 Vdc
Number of channels 3 Power consumption 1.5 VA max (ac) or 1.5 W max (dc)
Dimensions 5 DIN modules (approx. 88x90x60mm)
430 Vpeak phase - neutral Weight 95 grams without external sensors
Maximum working voltage 300 Vac phase - neutral
520 Vac phase - phase 128x64 pixels graphic display with multicol-
Display our RGB LED background
Current
Keyboard One 5 functions selector knob
9 - Choose among the combination of current
Number of channels sensors listed below; each channel is Isolated RS-485 with Modbus RTU protocol,
selectable individually Communication interface with selectable speed up to 115200 bps and
programmable parity
Accuracy Class 0,5
Sensor type 1 - Rogowski coil Electric withstand between
voltage inputs and 6 kV
Max. cable external diameter 100mm communication port
Selectable ranges by Joystick 2000- 1000 - 400 - 200 - 100 A between Voltmetric input and Rs 485
Insulation 6 Kv and between Aux Alim. and Rs 485
Sensor type 2 - Standard size current clamp Working temperature between -10 C and + 55 C
Max. cable external diameter 24mm Measurements
Dimensions (LxHxW) 44,5 x 65 x 33,5 mm Voltage L1-N, L2-N, L3-N, L1-2, L2-3, L3-1
Selectable ranges by Joystick 200 - 80 - 40 - 20 A Global Measures Frequency (measured on Voltage 1 channel)
Sensor type 3 - Miniature size current clamp Current, Peak current, Active power
Max. cable external diameter 16mm (bidirectional), Reactive power (bidirectional),
Dimensions (LxHxW) 30 x 43,5 x 30 mm Apparent power, Power factor, Working
For each one of the devices
Selectable ranges by Joystick 100 - 40 - 20 - 10 A quadrant, Imported Active energy, Exported
9 channels Active energy, Imported Inductive energy,
Sensor type 4 - Mini-transformer (TA) with output voltage Imported Capacitive energy, exported Inductive
Max. cable external diameter 6mm energy, Exported Capacitive energy.
Dimensions (LxHxW) 16 x 32 x 26,4 mm Equivalent line current, Three phase active
Selectable ranges by Joystick 1 - 2 - 5 - 10 A power (bidirectional), Three phase reactive
power (bidirectional), Three phase apparent
For 3 possible three phase power, Three phase power factor, Imported
clustering Active energy, Exported Active energy,
Imported Inductive energy, Imported
Capacitive energy, exported Inductive ener-
gy, Exported Capacitive energy.

Energy Team S.p.A. Via della Repubblica n.9 - 20090 Trezzano Sul Naviglio (Milan) Italy - Tel. +39 02.48405033 - Fax +39 02.48405035 - www.energyteam.it
Gamma TA

KBU
Trasformatori di corrente apribili

KBU 23/58
812/816

La gamma dei TA apribili KBU risulta essere la pi completa e af-


dabile disponibile oggi sul mercato.
> Corrente primaria 100 a 5000 A/Corrente secondaria 5A.
> Classe di precisione 1% (Classe 0,5 su richiesta).
> Area nestra interna da 6 cmq a 96. Type KBU 23 KBU 58 KBU 812 KBU 816
Un sistema di aggancio brevettato con un bloccaggio idoneo anche A 93 125 155 195
per la barra di corrente, consente di intervenire in tutte quelle situa- B 106 158 198 243
zioni in cui linserimento dei classici TA chiusi risulta essere pro- C/C1 34/58 34/58 34/58 64/79
blematico per cause tecniche, od onerose per motivi impiantistici,
rendendo le operazioni di installazione sicure, estremamente rapide D 20 50 80 80
e senza imprevisti. E 30 80 120 160

Gamma di TA apribili
Articolo Dim. Interne L x h (mm) Dim. esterne AxBxC (mm) Primario Secondario VA Classe
KBU 23 Sek.5A Kl.1
80241 20x30 93X106X58 100 5 1,25 1
80243 20x30 93X106X58 200 5 1,50 1
80045 20x30 93X106X58 300 5 3,75 1
80046 20x30 93X106X58 400 5 5 1
KBU 58 Sek.5A Kl.1
80064 50x80 125X158X58 500 5 5 1
80065 50x80 125X158X58 600 5 5 1
80066 50x80 125X158X58 750 5 5 1
80067 50x80 125X158X58 800 5 7,5 1
80068 50x80 125X158X58 1000 5 10 1
KBU 812 Sek.5A Kl.1
80094 80x120 155X198X58 500 5 5 1
80095 80x120 155X198X58 600 5 5 1
80096 80x120 155X198X58 750 5 5 1
80097 80x120 155X198X58 800 5 7,5 1
80098 80x120 155X198X58 1000 5 10 1
80099 80x120 155X198X58 1200 5 10 1
80101 80x120 155X198X58 1500 5 15 1
KBU 816 Sek.5A Kl.1
80140 80x160 195X243X79 1000 5 10 1
80142 80x160 195X243X79 1200 5 10 1
80144 80x160 195X243X79 1500 5 10 1
80146 80x160 195X243X79 1600 5 10 1
80148 80x160 195X243X79 2000 5 10 1
80150 80x160 195X243X79 2500 5 10 1
80152 80x160 195X243X79 3000 5 15 1
80154 80x160 195X243X79 4000 5 15 1
80157 80x160 195X243X79 5000 5 30 1

25
Nemo 96 HDLe
Network monitor
evolution
Nemo (Network monitor)
Famiglia di strumenti multifunzione, per misure su reti in cc e ca, che consentono di monitorare
i principali parametri della linea quali: tensione, corrente, frequenza, potenza attiva/reattiva/apparente,
fattore di potenza, energia attiva e reattiva, distorsione armonica, temperatura, sequenza fasi, contaore.
Possibilit di visualizzazione locale delle misure con display LCD o trasmissione a distanza
per centralizzazione ed analisi dei dati. Completa configurabilit in campo, che garantisce adattabilit
alle caratteristiche della rete (linea monofase o trifase 3/4 fili, carico equilibrato o squilibrato,
rapporti TA e TV) e permette di adeguarsi a sviluppi o modifiche future dellimpianto.

Multimisura Una panoramica completa ed affidabile delle misure di una rete elettrica
il primo passo indispensabile per poter realizzare unanalisi dettagliata
Misurano
e visualizzano dei consumi energetici e del loro variare nel tempo.
pi grandezze Lutilizzo del software IME MIDAs Evo, che acquisisce i dati dagli
contemporaneamente strumenti multifunzione Nemo, permette la centralizzazione delle
misure al fine di predisporre interventi mirati per migliorare lefficienza
energetica dellimpianto e il conseguente contenimento dei costi.
Conteggio
energia In particolare possibile:
Quantificano  visualizzare limmagine grafica degli strumenti ed accedere
i consumi energetici direttamente a tutte le misure effettuate
 realizzare grafici di una o pi grandezze misurate, per valutarne
il variare nel tempo
Comunicazione  abbinare allarmi software alle grandezze misurate, per evidenziare
eventuali punte di consumi
Comunicano le misure
effettuate a distanza  analizzare i consumi applicando 3 differenti calendari tariffari
Interfacciano differenti
modi di comunicazione Con MIDAs Evo possibile monitorare reti fino a 1020 dispositivi,
che possono essere oltre agli strumenti multifunzione Nemo,
anche contatori di energia della serie Conto oppure concentratori
Misura Conto-imp che accettano ingressi da dispositivi con uscita impulsi
e controllo quali contatori di energia elettrica, gas, acqua, calore.
Misurano Lanalisi energetica effettuata con MIDAs Evo permette di:
e intervengono
segnalando condizioni  suddividere i consumi per centri di costo
particolari  individuare punte di consumo, onde poterle eliminare agendo sui cicli
lavorativi (turni di lavoro, accensione macchine)
 verificare la suddivisione dei carichi sulle linee, individuare scompensi
e programmare interventi di riequilibrio
 valutare cambi di tariffe, effettuando simulazioni basate
sui consumi passati
 programmare interventi di manutenzione in periodi di minor
utilizzo energetico o al sorgere di consumi anomali
 quantificare redditivit investimenti effettuati in politiche
di risparmio energetico (fonti alternative, ammodernamento impianti
illuminazione, ridistribuzione cicli di lavoro)

3
I vantaggi dei Multifunzione

Conteggia Misura Comunica


energia attiva e reattiva, contemporaneamente tutti i parametri misurati e i dati
ore di funzionamento. i parametri di una linea di configurazione rendendoli
elettrica quali tensioni, disponibili ad un controllo
Calcola correnti, frequenza, fattore remoto tramite uscita impulsi,
corrente media massima di potenza, potenza attiva, comunicazione RS232,
e potenza media massima. reattiva e apparente. comunicazione RS485
interfacciabile con reti Modbus
Analizza RTU, Profibus, M-Bus,
la qualit dellenergia LonWorks, BACnet, Ethernet.
quantificando la componente
armonica di tensioni e correnti.

4
Unefficace diagnosi energetica, che rilevi i consumi ed individui
le possibilit di effettuare interventi di recupero di efficienza,
il fondamento essenziale per il risparmio energetico.
Gli strumenti multifunzione Nemo (che rilevano i consumi,
oltre a tutti i principali parametri della rete) e il software MIDAs Evo
(che raccoglie e analizza i dati) sono elementi essenziali per realizzarla.

Visualizza Si adatta Segnala


tutte le grandezze elettriche alle caratteristiche dellimpianto anomalie ed interviene
misurate, con display LCD con programmazione in campo con attivazione di rel allarmi
retroilluminato e men del tipo di inserzione (linea programmabili in campo.
accessibile da tastiera. monofase o trifase 3/4 fili)
e degli eventuali rapporti
TA e TV esterni.

5
negativi

Nemo D4-b Nemo D4-L Nemo D4-L+ Nemo D4-Dc Nemo 72-b Nemo 72-L Nemo 96 HDL Nemo 96 HDLe Nem
MF6G... MF6F... MF6H... MF6D... MF7G... MF7F... MF9610. MF964.. M
NT588 NT604 NT695 | NT782 NT753 NT651 NT652 NT706 NT854 N
BT BT BT / MT CC BT BT BT BT
      

equilibrato   

squilibrato       

si   

80...480Vca 80...480Vca 80...480Vca 10...300Vcc / 50...1.500Vcc 340...450Vca 80...480Vca 80...500Vca 80...500Vca 80..
1 5A 1 5A 1 + 5A 10A 1 5A 1 5A 1 + 5A 1 + 5A 1
da shunt 60-100-150mV
     

1...10 1...400 1...10 1...10 1...10


41(5...8.000A) 41(5...8.000A)
1...9.999 1...9.999 1...9.999 1...9.999 1...9.999 1..
99.990 100.000(5A) 99.990 99.990 99.990 9
400.000(1A)
1...9.999
/ IEC 61557-12 cl.1 cl.1 cl.1 cl.1 cl.]x c
rgia cc cl.1
e e parziale     

le  

/ IEC 61557-12 cl.2 cl.2 cl.2 cl.2 cl.2


e     

ale  

le  

atenata       

o (calcolata)       

urata) IF
assima (fase)       

      

 

a, apparente       

a massima        

va di fase       

  (corrente)  

      

       

 

IF9
  |     IF
  IF
IF9
IF
IF96002 IF96002 IF
  2
Esempi di applicazione

1. Connessione su rete RS485


Monitoraggio locale dispositivi su rete cablata.
Postazioni da monitorare: LINEA PRODUZIONE 1, LINEA PRODUZIONE 2, LINEA PRODUZIONE 3.
Strumenti: Nemo D4-L connessi tra loro in rete RS485.
PC supervisione: connesso agli strumenti tramite interfaccia RS485/Ethernet (IF2E011-IF2E111).

RETE LAN RS485

linea linea linea


produzione produzione produzione

1 2 3

RS485 RS485

2. Connessione su rete LAN aziendale


Monitoraggio locale dispositivi su rete cablata.
Postazioni da monitorare: PRODUZIONE, MAGAZZINO, UFFICIO.
Strumenti: Nemo 96 HD/HDLe connessi direttamente su rete Ethernet/LAN
tramite moduli IF96015 e Nemo D4-L tramite interfaccia (IF2E011-IF2E111).
PC supervisione: connesso agli strumenti tramite la rete Ethernet/LAN aziendale.

RETE LAN Switch Ethernet RETE LAN

RETE LAN
produzione magazzino ufficio

RS485

8
3. Connessione via radio
Monitoraggio locale dispositivi su rete non cablata.
Postazioni da monitorare: PRODUZIONE, MAGAZZINO, UFFICIO.
Strumenti: Nemo 96 HD+ con modulo radio 868MHz (IF96018).
PC supervisione: connesso agli strumenti tramite Gateway Radio/Ethernet.

Gateway
RETE LAN
Radio/Ethernet

produzione magazzino ufficio

4. Connessione attraverso internet


Monitoraggio remoto dispositivi attraverso collegamento internet.
Postazioni da monitorare: STABILIMENTO 1, STABILIMENTO 2, STABILIMENTO 3, CENTRO DIREZIONALE.
Strumenti: Nemo 96 HD/Nemo D4-L/Nemo 72-L connessi alle reti Ethernet/LAN locali tramite moduli/interfacce.
PC supervisione: connesso agli strumenti locali attraverso rete WAN (internet).

1 INTERNET

RETE LAN
2

CENTRO DIREZIONALE
3

9 9
Multifunzione 4 moduli per reti in ca
Nemo D4-b
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
MF6GT00073 5A 80480V (fase-fase) - 115Vca NT588
MF6GT00076 5A 80480V (fase-fase) - 230-240Vca NT588
MF6GT00079 5A 80480V (fase-fase) - 400Vca NT588
Altre esecuzioni

M F 6 G T 0 0 0 6 ... Ingresso corrente 1A

Nemo D4-L
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 6 F T0 0 0 23 5A 80480V (fase-fase) - 115Vca NT604
M F 6 F T0 0 0 26 5A 80480V (fase-fase) - 230-240Vca NT604
M F 6 F T0 0 0 2H 5A 80480V (fase-fase) - 20150Vcc+48Vca NT604
M F 6 F T4 0 0 23 5A 80480V (fase-fase) RS485 Modbus 115Vca NT604
M F 6 F T4 0 0 26 5A 80480V (fase-fase) RS485 Modbus 230-240Vca NT604
M F 6 F T4 0 0 2H 5A 80480V (fase-fase) RS485 Modbus 20150Vcc+48Vca NT604
M F 6 F TU 0 0 23 5A 80480V (fase-fase) Impulsi 115Vca NT604
M F 6 F TU 0 0 26 5A 80480V (fase-fase) Impulsi 230-240Vca NT604
M F 6 F TU 0 0 2H 5A 80480V (fase-fase) Impulsi 20150Vcc+48Vca NT604
Altre esecuzioni

M F 6 F T ... ... ... 1 ... Ingresso corrente 1A

Nemo D4-L+
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 6 H T 40 0 0 3 1-5A 80480V (fase-fase) RS485 Modbus+Impulsi 115Vca NT695
M F 6 H T 40 0 0 6 1-5A 80480V (fase-fase) RS485 Modbus+Impulsi 230-240Vca NT695
M F 6 H T 40 0 0 H 1-5A 80480V (fase-fase) RS485 Modbus+Impulsi 20150Vcc+48Vca NT695
M F 6 H T B0 0 0 3 1-5A 80480V (fase-fase) RS485 BACnet 115Vca NT782
M F 6 H T B0 0 0 6 1-5A 80480V (fase-fase) RS485 BACnet 230-240Vca NT782
M F 6 H T B0 0 0 H 1-5A 80480V (fase-fase) RS485 BACnet 20150Vcc+48Vca NT782
M F 6 H T U0 0 0 3 1-5A 80480V (fase-fase) Impulsi 115Vca NT695
M F 6 H T U0 0 0 6 1-5A 80480V (fase-fase) Impulsi 230-240Vca NT695
M F 6 H T U0 0 0 H 1-5A 80480V (fase-fase) Impulsi 20150Vcc+48Vca NT695

Multifunzione 4 moduli per reti in cc


Nemo D4-Dc
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 6 D C 4 2 0 0 6 da shunt 60-100-150mV-10A 10300V RS485 Modbus+2allarmi+Impulsi 230-240Vca NT753
M F 6 D C 4 2 0 0 H da shunt 60-100-150mV-10A 10300V RS485 Modbus+2allarmi+Impulsi 20150Vcc+48Vca NT753
M F 6 D C 4 2 0 6 6 da shunt 60-100-150mV-10A 501500V RS485 Modbus+2allarmi 230-240Vca NT753
M F 6 D C 4 2 0 6 H da shunt 60-100-150mV-10A 501500V RS485 Modbus+2allarmi 20150Vcc+48Vca NT753

Multifunzione da incasso 72x72mm per reti in ca


Nemo 72-b
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 7 GT0 0 0 9 A 5A 340450V (fase-fase) - Autoalimentato NT651
M F 7 GT2 0 0 9 A 5A 340450V (fase-fase) 2allarmi Autoalimentato NT651
M F 7 G M0 0 0 9 A 5A 195260V (fase-neutro) - Autoalimentato NT651
M F 7 G M2 0 0 9 A 5A 195260V (fase-neutro) 2allarmi Autoalimentato NT651
Altre esecuzioni

M F 7 G ... ... ... ... 8 ... Ingresso corrente 1A

Nemo 72-L
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 7 F T 40 0 4 3 5A 80480V (fase-fase) RS485 Modbus 115Vca NT652
M F 7 F T 40 0 4 6 5A 80480V (fase-fase) RS485 Modbus 230-240Vca NT652
M F 7 F T 40 0 4 H 5A 80480V (fase-fase) RS485 Modbus 20150Vcc+48Vca NT652
M F 7 F T U0 0 4 3 5A 80480V (fase-fase) Impulsi 115Vca NT652
M F 7 F T U0 0 4 6 5A 80480V (fase-fase) Impulsi 230-240Vca NT652
M F 7 F T U0 0 4 H 5A 80480V (fase-fase) Impulsi 20150Vcc+48Vca NT652
Altre esecuzioni

M F 7 F T ... ... ... 3 ... Ingresso corrente 1A

10
Multifunzione da incasso 96x96mm per reti in ca
Nemo 96 HDL
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
MF96101 1-5A 80500V (fase-fase) Impulsi+Nemo MD* 80265Vca+110300Vcc NT706
MF96102 1-5A 80500V (fase-fase) Impulsi+Nemo MD* 1160Vcc NT706

Nemo 96 HDLe
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
M F 9 6 4 1 1 1-5A 80500V (fase-fase) Impulsi+Nemo MD* 80265Vca+110300Vcc NT854
M F 9 6 4 1 2 1-5A 80500V (fase-fase) Impulsi+Nemo MD* 1160Vcc NT854
M F 9 6 4 2 1 1-5A 80500V (fase-fase) RS485 Modbus+impulsi + Nemo MD* 80265Vca+110300Vcc NT854
M F 9 6 4 2 2 1-5A 80500V (fase-fase) RS485 Modbus+impulsi + Nemo MD* 1160Vcc NT854

Nemo 96 HD
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
MF96001 1-5A 80500V (fase-fase) fino a 4 Nemo MD* 80265Vca+110300Vcc NT680
MF96002 1-5A 80500V (fase-fase) fino a 4 Nemo MD* 1160Vcc NT680

Nemo 96 HD+
Codice di ordinazione Ingressi in corrente e tensione Uscite Alim. ausiliaria Nota tecnica
MF96021 1-5A 80690V (fase-fase) fino a 4 Nemo MD* 80265Vca+110300Vcc NT681
MF96022 1-5A 80690V (fase-fase) fino a 4 Nemo MD* 1160Vcc NT681
* Moduli plug-in inseribili posteriormente per aumentare le funzioni del multifunzione

Moduli per Nemo 96 HD/ Nemo 96 HD+/ Nemo 96 HDL/ Nemo 96 HDLe
Nemo MD
Nemo 96
Codice di ordinazione Descrizione Nota tecnica
HD HD+ HDL HDLe
I F 9 6 0 0 1 comunicazione RS485 Modbus RTU     NT675
I F 9 6 0 0 2 comunicazione RS232 Modbus RTU     NT676
I F 9 6 0 0 7 comunicazione Profibus EN50170   NT682
I F 9 6 0 0 9 comunicazione LonWorks   NT684
I F 9 6 0 1 3 comunicazione M-Bus   NT707
I F 9 6 0 1 4 comunicazione RS485 BACnet    NT743
I F 9 6 0 1 5 comunicazione Ethernet con funzione web-server    NT785
I F 9 6 0 1 2 comunicazione RS485 Modbus+memoria   NT704
I F 9 6 0 1 8 comunicazione RS485 Modbus via radio 868MHz (ricetrasmittente)**  NT856
I F 9 6 0 0 3 2 uscite impulsi energia (SPST)   NT677
I F 9 6 0 0 4 2 uscite analogiche 020/420mA   NT678
I F 9 6 0 0 5 2 uscite rel allarmi (SPST)   NT679
I F 9 6 0 1 0 I/O 2 ingressi (SPST) + 2 uscite rel allarmi (SPST)   NT702
I F 9 6 0 1 1 I/O 2 ingressi (12/24Vcc) + 2 uscite rel allarmi (SPST)   NT703
I F 9 6 0 1 7 analisi armoniche ***  NT855
I F 9 6 0 0 6 misura corrente di neutro da TA esterno   NT683
I F 9 6 0 1 6 misura temperatura 2 ingressi da Pt100   NT810
I F 9 6 0 1 9 misura temperatura 2 ingressi da Pt500   NT849
** Il modulo di comunicazione ricetrasmittente via radio 868MHz fornito completo di alimentatore, antenna a stilo orientabile e cavo di prolunga 20cm.
Separatamente si dovr prevedere il gateway ricetrasmittente con uscita Ethernet ( I F M T R 0 1 ) fornito in kit completo di accessorio attacco canalina,
antenna a stilo orientabile e cavo di prolunga 20cm.
***Analisi fino al 50 grado, disponibile sulla comunicazione RS485 Modbus in abbinamento al modulo I F 9 6 0 0 1 .

Accessori Codice di ordinazione Nota tecnica


Interfaccia conversione RS485 Modbus-Ethernet Alim. ausiliaria 80270Vca+100300Vcc IF2E011 NT809
Interfaccia conversione RS485 Modbus-Ethernet Alim. ausiliaria 24Vca+2060Vcc IF2E111 NT809
Interfaccia conversione RS485-RS232 Alim. ausiliaria 80270Vca+100300Vcc IF2E002 NT693
Interfaccia conversione RS485-RS232 Alim. ausiliaria 24Vca+2060Vcc IF2E102 NT693
Interfaccia ripetitore RS485-RS485 Alim. ausiliaria 80270Vca+100300Vcc IF2E003 NT694
Interfaccia ripetitore RS485-RS485 Alim. ausiliaria 24Vca+2060Vcc IF2E103 NT694
Interfaccia conversione RS485 Modbus-Profibus DP
IFC4R NT592
per Nemo D4-L/L+/Nemo 72-L Alim. ausiliaria 1835Vca/cc
MIDAs Evo software di gestione e monitoraggio fino a 5 strumenti SWMF2 NT851
MIDAs Evo software di gestione e monitoraggio fino a 20 strumenti SWMF3 NT851
MIDAs Evo software di gestione e monitoraggio fino a 1020 strumenti SWMF4 NT851
Trasformatore per alim. ausiliaria a 230V dei Nemo su impianti
AVMF2 NT741
dove sono disponibili tensioni diverse 115-127-400-500-600V
Kit per montaggio ad incasso multifunzione Nemo D4-b/L/L+/Dc AVKIT4

11
Trasformatori di corrente - Misura
Apribili

TRA230 NT869
Finestra passaggio cavo/sbarra 20x30mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TA23050B600 s TA23010B600 60A 1
TA23050C100 s TA23010C100 100A 1,5
TA23050C150 s TA23010C150 150A 1,5 2,5
TA23050C200 s TA23010C200 200A 1 2,5
TA23050C250 s TA23010C250 250A 1,5 3
TA23050C300 s TA23010C300 300A 1,5 4
TA23050C400 s TA23010C400 400A 2,5 6

Accessori
ATACOP13 s coprimorsetto sigillabile

TRA580 NT841
Finestra passaggio cavo/sbarra 50x80mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TA58050C250 s TA58010C250 250A 1 2
TA58050C300 s TA58010C300 300A 1,5 3
TA58050C400 s TA58010C400 400A 1,5 3
TA58050C500 s TA58010C500 500A 2,5 5
TA58050C600 s TA58010C600 600A 2,5 5
TA58050C800 s TA58010C800 800A 3 7
TA58050D100 s TA58010D100 1000A 5 10

Accessori
ATACOP13 s coprimorsetto sigillabile

TRA812 NT842
Finestra passaggio cavo/sbarra 80x120mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TA81250C500 s TA81210C500 500A 4 12
TA81250C600 s TA81210C600 600A 5 14
TA81250C800 s TA81210C800 800A 3 7
TA81250D100 s TA81210D100 1000A 5 10
TA81250D120 s TA81210D120 1200A 6 11
TA81250D150 s TA81210D150 1500A 8 15

Accessori
ATACOP13 s coprimorsetto sigillabile

TRA816 NT863
Finestra passaggio cavo/sbarra 80x160mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TA81650D200 s TA81610D200 2000A 15 20
TA81650D250 s TA81610D250 2500A 15 20
TA81650D300 s TA81610D300 3000A 20 25
TA81650D400 s TA81610D400 4000A 20 25
TA81650D500 s TA81610D500 5000A 20 25

Accessori
ATACOP13 s coprimorsetto sigillabile

32
Trasformatori di corrente - Misura
Apribili

TRA11 NT721
Finestra passaggio cavo/sbarra 110mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TAAA50C100 100A 3
TAAA50C120 120A 3
TAAA50C150 150A 5
TAAA50C200 200A 5
TAAA50C250 250A 5
TAAA50C300 300A 5
TAAA50C400 400A 5
TAAA50C500 500A 8
TAAA50C600 600A 15
TAAA50C800 800A 15
TAAA50D100 1000A 15
TAAA50D120 1200A 20
TAAA50D150 1500A 20
TAAA50D200 2000A 25
coprimorsetto sigillabile di serie

TRA15 NT722
Finestra passaggio cavo/sbarra 150mm

Codice Isr 5A Euro Stock Codice Isr 1A Euro Stock Ipr VA/cl.0,5 VA/cl.1 VA/cl.3
TAAB50C100 100A 3
TAAB50C120 120A 3
TAAB50C150 150A 5
TAAB50C200 200A 5
TAAB50C250 250A 5
TAAB50C300 300A 5
TAAB50C400 400A 5
TAAB50C500 500A 8
TAAB50C600 600A 15
TAAB50C800 800A 15
TAAB50D100 1000A 15
TAAB50D120 1200A 20
TAAB50D150 1500A 20
TAAB50D200 2000A 25
TAAB50D250 2500A 25
TAAB50D300 3000A 25
TAAB50D400 4000A 30
TAAB50D500 5000A 30
coprimorsetto sigillabile di serie